Legrand SAF User Manual

SAF21/2
Legrand/Wiremold electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Legrand/Wiremold electrical products may bear the mark of a Nationally Recognized Testing Laboratory (NRTL) and should be installed in conformance with current local and/or the National Electrical Code.
Raised Floor Box
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 002 430R3 – Updated January 2011
IMPORTANT: Please read all instructions
before beginning.
PRODUCTS COVERED: SAF21/2
NOTE: Products are suitable for use in air handling spaces in accordance with Sec. 300-22(C) of the National Electrical Code.
CAUTION: Flange is an integral part of the box assembly. DO NOT REMOVE.
Step 1 Cut or form an 8 1/16" x 10 1/8" [205mm x
257mm] (+ 1/16" - 0") opening in the raised floor panel and carpet. (See Fig. 1.)
FIG. 1
Step 2 Blank communication plates come standard in floor box.
If other communication plates are required, remove communication conduit plate. (See fig 2.) Remove only blank communication plates that need exchanged and attach new communication plates (sold separately) to the floor box using (2) #8-32 x 3/8" self-tapping screws provided. (See fig 3.) Reattach communication compartment cover. ( See fig 2.)
FIG. 2
NOTE: Communication conduit plate
required only if using conduit to supply communications cabling. (See Step 5.)
Communication
Conduit Plate
FIG. 3
Step 3 Place Walker Shallow Raised Floor Box in
opening created in step one. (See Fig. 4.)
CAUTION: Flange is an integral part of the box
assembly. DO NOT REMOVE. Separating the Flange from the Box may cause damage to the Flange and Box, prevent reattachment, and may also cause the Box to not sit properly in the opening.
Step 4 Using a Phillips screwdriver tighten the (2)
#10-24 X 2 1/4" locking tab screws on both sides of the floor box. (See Fig. 5.)
Step 5 Remove appropriate knockout(s) and feed
flexible conduit to the floor box. Pull wires into the box and connect conduit to the box with a conduit connector. Pull communication wires into box. (See Fig. 6.)
FIG. 4
FIG. 5
FIG. 6
Power Conduit, not supplied by
Walker Systems, Inc.
NOTE: The communication conduit plate does not need to be attached behind
a compartment used for low voltage. Where required by local codes, connect conduit to the communication conduit plate. Type CMP communications plenum cable is required in raised floor plenums when wiring methods as described in NEC Article 300-22 are not followed.
Communication Cables,
not provided by
Walker Systems, Inc.
Loading...
+ 2 hidden pages