19" LSC2 freestanding cabinets are intended for digital infrastructures.
19" LCS2 cabinets are metal and provide IP20 - IK08 protection. They
have a single or double screen-printed curved glass door and are
finished throughout in charcoal grey RAL 7016.
19" LSC2 cabinets can be joined together, either directly or via a
cabling unit, and can be equipped with a modular plinth.
Equipment and accessories for cable management, vertical extension,
thermal management, etc. complete the range.
The 4 structural uprights and the 2 end plates form a metal framework
that is screwed together. The cabinet can be dismantled completely if
access is difficult.
The end plates contain the cabinet's cable entries. Their configuration,
which is identical for the top and the bottom, is dependent on the
dimensions of the cabinet:
(mm)Width 600Width 800
1.1 Presentation
The main parts of 19" LCS2 freestanding cabinets are:
- A framework consisting of 4 uprights and 2 end plates
- A single or double screen-printed curved glass front door
- 2 side panels (excluding extension cabinets)
- A rear panel
- 4 x 19" uprights
Depth 600
Depth 800
Depth 1000
Technical data sheet: F01424EN/01
Each cable entry is pre-cut in 19" format in order to be equipped with
a cable entry plate (see section 7.1).
The whole structure stands on 4 levelling feet that can be adjusted
from the inside and the outside of the cabinet.
- Curved colourless transparent glass with "pixel" screen-printing on
the vertical edges
- A handle equipped with a 2433A key lock
- 2 metal hinges (3 for 47U height)
The double front door comprises:
- Two half-doors made of curved colourless transparent glass with
"pixel" screen-printing on the external vertical edges
- A locking bolt located at the top of each half-door
- Two metal hinges on each half-door
Doors are removable and single door is reversible.
Locks are compatible with key barrels (other key codes) and inserts
Cat. Nos. 0 368 13/16/17/18/19/20/22/23/24/25/26/27.
For a perfect finish, 2 fascia trims, clipped onto the end plates,
continue the "pixel" design from the door. The upper trim carries the
Legrand name.
The side and rear metal panels are equipped with:
- A 2433A locking bolt
- A stainless steel equipotential link clip
Each panel is removable for total accessibility:
1. GENERAL FEATURES (continued)
1.1 Presentation (continued)
The four 19" uprights have dual marking of the Us and assistance with
depth adjustment for easy installation.
The adjustment is continuous with markings at 12.5 mm intervals:
12.5 mm
The dual marking of the Us enables location in relation to the top or
the bottom of the cabinet:
A
A
B
B
The clip automatically provides continuity of the metal conductive parts
between the panels and the rest of the cabinet (no risk of this being
forgotten).
The lock is compatible with key barrels (other key codes) and inserts
Cat. Nos. 0 368 13/16/17/18/19/20/22/23/24/25/26/27.
In the above example, the marking indicates that this is U no. 14 from
the top and U no. 29 from the bottom of the cabinet.
The 19" uprights are perforated with 9.5 x 9.5 mm square holes.
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
19" LCS2 freestanding cabinets comply with the following standards:
IEC 60529
EN 60529
IEC 62262
EN 62262
IEC 60950-1
EN 60950-1
C 77-210-1
EIA-310-ECabinets, racks, panels and associated
IEC 60297-3-100
DIN 41414-7
19" LCS2 freestanding cabinets can be integrated in installations
complying with the following standards:
EN 50173-1Information technology -
EN 50174-1 & 2
C 90-480-1 & 2
ISO IEC 11801Information technology - Generic cabling for
NF C 15-100
Part 4-41
IEC 60364-4-41Low voltage electrical installations
(NF C 20-010) Degrees of protection provided by
enclosures (IP code)
(NF EN 50102, NF C 20-015) Degrees of
protection provided by enclosures for electrical
equipment against external mechanical impacts
(IK code)
Safety of information technology equipment
equipment (ANSI/EIA/310-E-2005)
(NF C 20-150, NF C 20-151) Dimensions of
mechanical structures of the 482.6 mm series
(19 in)
Generic cabling systems
Information technology - Cabling installation
customer premises
Low voltage electrical installations recommendations
- Protection for safety
- Protection against electric shock
2. RANGE
2.1 Cabinet with single front door
Catalogue
Number
CapacityWidth
(mm)
(1)
0 463 0024U600600
0 463 0629U600600
0 463 1233U600600
0 463 1842U600600
0 463 1942U600800
0 463 2142U800600
0 463 2242U800800
0 463 2342U8001 000
0 463 2847U800800
0 463 2947U8001 000
Two extension freestanding cabinets complete the range. These are
supplied without side panels and with a baying kit:
19" LCS2 extension cabinets
Catalogue
Number
CapacityWidth
(mm)
(1)
0 463 3042U600600
0 463 3342U800800
2.2 Cabinet with double front door
Door opening suitable for small spaces
Catalogue
Number
CapacityWidth
(mm)
(1)
0 463 4142U800600
0 463 4242U800800
0 463 4342U8001 000
Depth
(mm)
Depth
(mm)
Depth
(mm)
(1)
(1)
(1)
To meet specific requirements, the made-to-measure department
offers 40 sizes and various configurations: front and rear door
(microperforations, metal double door…), mounting of equipment,
other colours, etc.
(1)
Designated dimensions. See section 4.1 for overall dimensions.
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
- IP20 in accordance with IEC EN 60529
Protected against solid objects whose diameter is larger than 12.5 mm
- IK08 in accordance with IEC EN 62262
Protected against mechanical impact with an energy of 5 joules
3.2 Mechanical performance
- Permissible load: 420 kg
- Resistance to shock acceleration and vibration in accordance with
IEC 61587-1: level DL4
3.3 Design
- Structural uprights and upper end plate 1.5 mm thick
galvanised steel + paint finish
- Lower end plate 1.5 mm thick Z140 MB-C galvanised steel
- Curved front door made of 5 mm thick colourless transparent
safety glass.
Charcoal grey RAL 7016 internal screen-printing on the vertical
edges: 2 x 143 mm in 600 mm width, 2 x 243 mm in 800 mm width.
- Single door handle charcoal grey RAL 7016 polyamide
- Door hinges zamak + paint finish
- Fascia trims charcoal grey RAL 7016 ABS.
Legrand marked in relief + pad printed in aluminium grey RAL 9006.
- Panels 1.2 mm thick sheet steel + paint finish
- Single door and panels bolt charcoal grey RAL 7016 polyamide
- 19" uprights 1.5 mm thick galvanised steel.
Number of U marked using black inkjet marking.
- Levelling feet zinc-plated steel with black polypropylene fixed base
3. TECHNICAL FEATURES (continued)
3.6 Electrical continuity of the conductive parts
Continuity of the metal conductive parts of the cabinet is achieved
by construction. For the panels, a stainless steel clip automatically
provides the equipotential link by pressing against the lower end plate
with galvanised steel finish.
3.7 Weight
Net weight excluding packaging.
Cabinet catalogue numberWeight (kg)
0 463 0069
0 463 0677
0 463 1284
0 463 18 (extension 0 463 30)99 (72)
0 463 19110
0 463 21/41114
0 463 22/42 (extension 0 463 33)127 (90)
0 463 23/43151
0 463 28138
0 463 29163
Note: 19" LCS2 cabinets are delivered on a 125 mm high pallet.
3.4 Corrosion resistance
- Corrosion class of the environment:
C2 according to EN ISO 12944-2,
3K3 according to IEC EN 60721-3-3
- Salt spray test according to ISO 9227 (NSS test) and
IEC EN 60068-2-11 (test Ka) for 168 hours:
degree of rusting Ri1 according to ISO 4628-3,
propagation 1 mm according to ISO 4628-8
- Sulphur dioxide (SO2) test according to EN ISO 6988 for 48 hours:
degree of rusting Ri1 according to ISO 4628-3,
ISO 10289 annex A class 8 type image
3.5 Properties of the paint coating
- Thermosetting polyester paint applied by electrostatic dusting
- Charcoal grey RAL 7016
- Textured satin appearance
- 60 to 80 m thick
- Excellent impact and scratch resistance
- Excellent resistance to cleaning agents (excluding strong chlorinated,
fluorinated and ketone solvents).
Some products may change the appearance. It is therefore advisable
to carry out a test first.
- Light exposure test (xenon-arc lamp) according to
ISO 4892-2 method B for 500 hours: no visible fading
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
19" LCS2 freestanding cabinets can be joined laterally together using
a baying kit:
Cat. No.For cabinets depth (mm)
0 463 37600
0 463 38800
0 463 391000
Note: The LCS2 range includes extension cabinets (single door) for
the 42U x 600 x 600 and 42U x 800 x 800 sizes. These special
cabinets are supplied with the baying kit and without side
panels.
A baying kit comprises:
- 2 galvanised steel lugs
- 2 steel crosspieces + paint finish (same as cabinets)
- Fixing screws
5. BAYING (continued)
5.2 Baying via cabling unit
5.2.1 Presentation
The LCS2 cabling unit is used to join laterally two 42U 19" LCS2
freestanding cabinets together, and provides easier management of
cables and patch cords.
Joined to 2 x 600 mm wide cabinets, the cabling unit is an
alternative solution to an assembly of 2 x 800 mm wide cabinets
and has smaller dimensions.
The cabling unit is available in 2 depths:
Cat. No.For 42U cabinets depth (mm)
0 463 34600
0 463 35800
Note: The LCS2 range includes extension cabinets (single door) for
the 42U x 600 x 600 and 42U x 800 x 800 sizes. These special
cabinets are supplied without side panels.
A cabling unit principally comprises:
- 2 identical end plates
- 2 identical doors
The crosspieces provide protection against dust and maintain the IP20
protection of the cabinets.
1600 (1610 overall)
800800
VIEW OF A COMBINATION FROM ABOVE
The cabling unit can only be installed between 2 cabinets.
It cannot be mounted at the end.
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
- The correct plinth kit for the width of the cabinet (corner blocks +
solid front and rear traps)
- The correct set of 2 solid side traps for the depth of the cabinet
(2 sets for a 200 mm high plinth)
D
Plinth kit (mm)
H = 100 W = 600
W = 800
H = 200 W = 600
W = 800
Cat. No.
0 464 50
Cat. No.
0 464 51
Cat. No.
0 464 52
Cat. No.
0 464 53
H
Set of 2 solid side traps (mm)
H = 100 D = 600
D = 800
D = 1000
H = 200 D = 600
D = 800
D = 1000
Cat. No. 0 464 54
Cat. No. 0 464 56
Cat. No. 0 464 58
2 x Cat. No. 0 464 54
2 x Cat. No. 0 464 56
2 x Cat. No. 0 464 58
W
6. PLINTHS (continued)
6.1 Freestanding cabinet plinths (continued)
6.1.1 Presentation (continued)
If cabinets are joined together directly, their plinths can be joined
together mechanically (screws not supplied).
The solid traps can be replaced by:
- Either a ventilated trap for natural ventilation
- Or a trap with brushes for cable entry on one side of the plinth
These special traps, also 100 mm high, are supplied singly.
D
W/D = 600
W/D = 800
W
Ventilated trapTrap with brushes
Cat. No. 0 464 60 Cat. No. 0 464 62
Cat. No. 0 464 61 Cat. No. 0 464 63
The plinths can be equipped with cross bars. Fixed between 2 corner
blocks, they can be used for clamping cables and, in a 200 mm high
plinth, for fixing a U-shaped cable tray.
0 476 93/94/95
Cross bars
Cat. No.For depth (mm)
0 476 93
0 476 94
0 476 95
600
800
1000
U-shaped cable trays
Cat. No. Internal width x height (mm)
0 464 69
0 464 70
200 x 54
400 x 54
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
When joining 19" LCS2 freestanding cabinets via a cabling unit,
Cat. No. 0 464 64 is used to link the plinths of the joined cabinets (at
the front and/or rear).
Cat. No. 0 464 64 comprises a 100 mm high trap.
For a height of 200 mm, the number of traps must be doubled.
100
Cat. No. 0 464 64
6. PLINTHS (continued)
6.3 Linking interface (continued)
6.3.1 Presentation (continued)
The linking interface helps to maintain the bending radius of the
cables:
U-shaped cable tray, see section 6.1.
200
Cat. No.
0 464 64 x 2
The trap is made of 1.5 mm thick steel with paint finish (same as
cabinets) and supplied with its fixing screws.
6.3 Linking interface
6.3.1 Presentation
The linking interface Cat. No. 0 464 66 provides protection and a
finish for the link between freestanding cabinets and cable ducts. It is
positioned to the right or left of a 600 mm deep cabinet equipped with
a 200 mm high plinth.
It is mechanically joined to the cabinet plinth.
The interface comprises:
- 3 corner blocks
- A front panel trap
- A cover
Its reversible cover with cut-outs allows for different cable entry
configurations.
6.3.2 Features
- Corner blocks and cover 2 mm thick steel + paint finish
(same as cabinets)
- Trap 1.5 mm thick steel + paint finish (same as cabinets)
- Supplied with black cable entry brushes (polyamide fibres)
and complete set of screws (apart from those for fixing to the floor)
120
600
(1)
Usable feedthrough area with brush: 110 x 435 mm
75
435
435
(1)
120
600
(1)
160
200
Fixing to the floor
14
478
478
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
Adjustable height plinths are used in rooms equipped with a raised
floor composed of tiles. The plinth transfers the load of the cabinet
directly to the ground.
Adjustable height plinth
Cat. No.For cabinet width / depth (mm)
0 464 30600 x 600
0 464 31600 x 800
0 464 32600 x 1000
0 464 34800 x 600
0 464 35800 x 800
0 464 36800 x 1000
Each plinth is supplied with front and rear floor tile support brackets.
Side tile support brackets must be order separately for the end of the
cabinets:
Set of 2 side tile support brackets
Cat. No.For plinth depth (mm)
0 464 38600
0 464 39800
0 464 401000
6. PLINTHS (continued)
6.4 Adjustable height plinths (continued)
6.4.2 Features
- For floor tiles 30 or 38 mm thick
- Height adjustable from 200 to 350 mm in 25 mm steps + fine
adjustement by levelling feet
- Permissible load: 1 000 kg
- Direct fixing to the end plate of the cabinet by M12 screws
- Can be fixed to the floor (screws not supplied)
- Plinth 2 mm thick galvanised steel
- Tile support brackets 1.5 mm thick galvanised steel
- Levelling feet zinc-plated steel with block polypropylene fixed base
- Supplied with complete set of screws for the equipotential link with
the cabinet
Depth
14
C
25
support
Set of
2 lateral
tile support
brackets
Cat. Nos
0 464 38/
39/40
Width
B
Ø9
D
H
thickness)
30
or 38
(tile
A
15
31
(tile
area)
Cat. No. Width x
0 464 30
0 464 31
0 464 32
0 464 34
0 464 35
0 464 36
(1)
Ajustable in 25 mm steps + fine adjustement
Depth
600 x 600
600 x 800730635 478 x 678 520 x 720
600 x 1000930835 478 x 878 520 x 920
800 x 600
800 x 800730635 678 x 678 720 x 720
800 x 1000930835 678 x 878 720 x 920
(1)
H
Min. Max. ABCDWith
200 350
Usable areaDistance
530
730
530
530
(width x depth)
cabinet
435 478 x 478 520 x 520
435
435 678 x 478 720 x 520
635
To the
ground
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
19" LCS2 freestanding cabinets have pre-cut 19" format top and
bottom cable entries.
800
600
7. CABLE MANAGEMENT (continued)
7.1 Cable entry plates (continued)
7.1.1 Presentation (continued)
The metal plates are equipped with 2 quick fixings that do not require
any screws or tools.
At the top of LCS2 cabinets, the metal plates must be fixed
using screws and cage nuts with pins in order to provide
the equipotential link between the plate and the painted end
plate of the cabinet.
1
Cat. No. 0 364 54
2
After cutting out the cable entries, they can be equipped with
feedthroughs with brushes using the following 19" equipment:
Cat. No.Plate with brushes
0 465 28Plastic 1U
0 465 29Plastic 2U
0 465 30Metal 1U
0 465 31Metal 2U
The plastic plates Cat. Nos. 0 465 28/29 clip directly onto the cable
entries. They require a flat screwdriver for removal.
CLICK
The 3U cable entries also enable the installation of plates with fans
Cat. Nos. 0 464 87/88 for thermal management of the cabinet (see
section 9.1).
7.1.2 Features
7.1.2.1 Plastic plates
ABS plates equipped with a flexible brush (2 brushes for 2U height).
Black RAL 9005
1U plate Cat. No. 0 465 28 (above):
- 2 feedthroughs 125 x 25 mm
- 1 central feedthrough 113 x 25 mm
2U plate Cat. No. 0 465 29:
- 2 feedthroughs 125 x 45 mm
- 1 central feedthrough 113 x 45 mm
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
800 mm wide 42U 19" LCS2 freestanding cabinets can take the
vertical cable management grid Cat. No. 0 331 35, fixed onto the
outside of the 19" uprights.
The guide has articulated latches. As the latches are clipped on, their
direction of opening can be reversed.
7. CABLE MANAGEMENT (continued)
7.4 Vertical cable manager
7.4.1 Presentation
800 mm wide 42U 19" LCS2 42U freestanding cabinets can be fitted
with the set of 2 vertical cable manager panels Cat. No. 0 464 80.
The panels are mounted on the outside of the 19" uprights. The wiring
is organised using feedthroughs with brushes, cable management
rings and slots for cable ties.
42U 19" LCS2 cabinets can also be joined via a cabling unit,
providing a solution for easy management of cables and cords (see
section 5.2).
7.3.2 Features
- Supplied singly
- Overall dimensions: H 1562 x W 100 X D 155 mm
- Wire diameter: 5 mm
- Steel wire + paint, ABS-PC latches
- Supplied with screws
- Black RAL 9005
The management rings are plastic and radiate out to provide optimum
protection for cords (maintain the bending radius). Each ring clips on
horizontally or vertically:
CLICK
42U 19" LCS2 cabinets can also be joined via a cabling unit,
providing a solution for easy management of cables and cords (see
section 5.2).
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
- Supplied with 9 cable ties with tightening indicator:
3 x Cat. No. 0 331 94,
3 x Cat. No. 0 331 95 and 3 x Cat. No. 0 331 96
- Supplied with screws
- Overall panel dimensions: 1878 x 108 mm
- Panels 1.5 mm thick steel
- Polyamide rings
- Black RAL 9005
7.5 Cable ties
7.5.1 Cable ties with tightening indicator
Cable ties with tightening indicator are wide ties with a smooth inner
surface for optimum protection of cables. They incorporate a warning
system to prevent over-tightening: fusible crescent-shaped pins snap
one after the other and act as visual and audible indicators.
8. VERTICAL EXTENSION
The set of 2 vertical extension uprights Cat. No. 0 464 81 increases
the capacity of 42U 800 mm wide 19" LCS2 freestanding cabinets by
12 U, giving a total capacity of 54U.
0 464 81
42U
800
Hooks hold the excess strap in place.
The ties are released by pinching the head of the tie and can be reused.
Cat. No.Width (mm)Length (mm)
0 331 94151803515
0 331 95152255035
0 331 96153208050
- Tensile strength: > 100 N
- Fire resistance: UL 94 HB
- Black high impact PBT
7.5.2 Self-locking cable ties
Self-locking cable ties are repositionable textile ties that do not
damage cables.
Cat. No.ColourWidth (mm) Length (mm)
0 331 84Black1615035
0 331 85Red1615035
0 331 86Green1615035
0 331 87Black1630080
0 331 88Red1630080
0 331 89Green1630080
- Tensile strength: > 220 N
- Fire resistance: UL 94 V2
- Double-sided textile with "loops" on one side and "hooks" on the other
Tightening Ø (mm)
Max.Min.
Max. tighte-
ning Ø (mm)
x 2
The extension, mounted on either side of 19" uprights, has 6 x 2U
positions for mounting 19" equipment vertically (panels, 19" PDUs,
etc.).
The cable management rings are plastic and radiate out to provide
optimum protection for cords (maintain the bending radius). Each ring
clips on horizontally or vertically:
Features
- Set of 2 uprights
-
For fixing on 19" uprights and
- Ability to adjust the depth of the 19" uprights retained
- Positions for 19" equipment: usable area 450 x 90 mm, perforations
19" LCS2 freestanding cabinets can take plates with fans at the 3U
cable entries. Installed in the top of the cabinet, the plates provide a
high extraction rate.
Cat. No.No. of fansOutput (m3/h)
0 464 872180
0 464 883270
Features
- IP XXB - IK08
- 230 V~ - 50/60 Hz power supply
Cat. No.Current (A)Power (W)
0 464 870.2536
0 464 880.3754
- Equipped with 3 x 0.75 mm2 flexible power supply cable,
length 2.5 m
- Fixed using M6 screws and cage nuts with pins (supplied)
- Plate steel + paint finish (same as cabinets)
- Charcoal grey RAL 7016
133 (3U)
89
60
482
465 (19
200
)
"
9. THERMAL MANAGEMENT (continued)
9.2 1U ventilation drawers
The ventilation drawers are 19" equipment which provide circulation
of the internal air. They provide targeted heat removal and ensure
uniformity of the temperature in the cabinet.
Cat. No.No. of fansDepth (mm)
0 464 892150
0 464 904300
Each fan provides an output of 90 m3/h.
The arrows below indicate the ventilation direction in the operating
position:
Features
- IP XXB - IK08
- 230 V~ - 50/60 Hz power supply per IEC 60320 C14 socket
Cat. No.Current (A)Power (W)
0 464 890.2536
0 464 900.572
60
45
45
482
465 (19
324
133 (3U)
)
"
162
89
- Supplied with C13 cord - French/German standard plug, length 1.2 m
- Illuminated ON/OFF switch
- For fixing on 2 x 19" uprights using M6 captive screws and 9.5 mm
cage nuts with pins (supplied)
- Weight: 3 kg (Cat. No. 0 464 89)
5.3 kg (Cat. No. 0 464 90)
- Drawer steel
- Black RAL 9005
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
The mechanical thermostat Cat. No. 0 348 48 is used to control the
switching on/off of the fans in order to control the temperature inside
the cabinets.
1U
FansThermostat Cat. No. 0 348 48
19
"
300
(1)
150
75
"
19
10. ACCESSORIES
10.1 Anti-tilt kit
The anti-tilt kit Cat. No. 0 464 84 stabilises a 19" LCS2 freestanding
cabinet (which is not fixed to the floor) when heavy products installed
on telescopic equipment are removed.
The kit, which consists of 2 rails fixed under the lower end plate,
prevents the cabinet tilting forwards.
The kit can be mounted before or after installation of the cabinet.
The kit is suitable for all three cabinet depths:
P 600/800/1000
P 600
P 800
P 1000
Features
- IP20
- 230 V~ - 50/60 Hz
- Adjustment range +5°C to +60°C
- Switching range: 2°C
- NC contact: 5 A, 250 V~
- NO contact: 10 A, 250 V~
- Connection via 2.5 mm2 terminal block
- Class N interfercab. suppression according to VDE 0875
- Magnetic mounting
- Black
51
68
To limit the projection of the rails at the front of the cabinet, another
type of mounting is possible for cabinets depth 600/800 mm:
P 600/800
P 600
P 800
It is essential not to exceed the following dual limit:
- 100 kg total weight installed on runners
- 570 mm projection
570
++
+…=
100 Kg max.
37
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
C-section, length 1400 mm.
Steel + paint finish (same as cabinets)
Supplied with fixing screws
Charcoal grey RAL 7016
40
10.2 Floor fixing kit
Fixing kit Cat. No. 0 464 86 is used to fix a 19" LCS2 freestanding
cabinet to the floor permanently. The 4 lugs in the kit, when screwed
to the floor, lock the levelling feet of the cabinet.
1212
2.5
60
10. ACCESSORIES (continued)
10.2 Floor fixing kit (continued)
The kit is used for remote fixing outside the cabinet.
Features
Set of 4 galvanised steel lugs (without screws).
10030
Ø 11Ø 11
200
10.5
14
40
2.5
Ø 10 mm max
B
10.3 Casters
19" LCS2 freestanding cabinets can be equipped with a set of 4
pivoting casters Cat. No. 0 464 83.
The total load on the 4 casters must not exceed 380 kg.
Features
- Set of 4 casters with fixing screws
- Raise cabinet by 70 mm
- Wheels black polyamide
5435
1227
3230
70
A
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
The kit Cat. No. 0 464 85 consists of a 1U 19" panel equipped with a
fluorescent light.
Features
- Quick screw-free fixing on 2 x 19" uprights
- Class I
- IP20
- ON/OFF switch
- 230 V~ - 50Hz power supply
- Ferromagnetic ballast
- Rear connection on terminal block
- For Ø 16 mm fluorescent tube, length 288 mm, G13 cap
- Supplied with 8 W white tube
- Panel 1.5 mm thick steel + black RAL 9005 finish
11. 19" EQUIPMENT
11.1 19" management panels
For ease of mounting, the 19" LCS2 panels incorporate a quick fixing:
- The plastic panels clip on directly. The only tool required is a flat
screwdriver for their removal (see section 7.1).
- The metal panels are equipped with 2 ergonomic fixings that do not
require any screws or tools.
11. 19" EQUIPMENT (continued)
11.1 19" management panels (continued)
11.1.1 Management panels with 2 axes
- Metal panels with quick fixing
- Horizontal and front to back feedthrough
- Plastic cable management rings radiating out (to protect cords and
maintain the bending radius)
Cat. No.
0 465 22
0 465 23
- Excellent resistance to unclipping under the weight of cables and
cords
Panels
with
2 axes
Metal 1U9030 x 601890
Metal 2U9065 x 604070
Depth
(mm)
Dimensions of
feedthroughs
(mm)
Rings usable
cross-section
(mm2)
The quick fixing for metal panels is compatible with 1.4 to 2.75 mm
thick 19" uprights with 8.25 to 9.5 mm square perforations.
An automatic equipotential link is ensured with 19" LCS2 uprights.
Direct clipping on of plastic panels is compatible with 1.5 to 2 mm
thick 19" uprights with 9.5 mm square perforations.
10 kg
50 mm
- Panels 1.5 mm thick steel
- Polyamide rings
- Zamak quick fixing
- Black RAL 9005
11.1.2 Management panels with brushes
- Direct clip-on plastic panels
- Metal panels with quick fixing
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
- Easy adjustment to the depth position of the 19" uprights
- Shelf is perfored for a better internal ventilation, and possibility of
clamping using cable ties
- Locking in open position
Cat. No.For cab.
depth (mm)
0 465 08600425425320
0 465 09800625425420
0 465 101000625425420
- Height 1U
- Max. load: 50 kg
- Automatic earthing
- 50 x 7 mm oblong perforations
- Shelf 1.5 mm thick steel
- Black RAL 9005
- Ball-bearing runners
In case of the risk of tilting when heavy items are removed,
the cabinet must be fixed to the floor or stabilised using an
anti-tilt kit (see sections 10.1 and 10.2).
11.4 Fixed shelf for heavy items
- For mounting on 4 x 19" uprights
- Front fixing via screws
- Adjustment in 12.5 mm intervals
to the depth position of the 19" uprights
Cat. No.For cab. depth
(mm)
0 465 171000820425
- Height 1U
- Max. load: 100 kg
- Supplied with screws and cage nuts with pins
- 50 x 7 mm oblong perforations (possibility of clamping using cable ties)
- 2 mm thick steel
- Black RAL 9005
11.5 Keyboard shelf
Shelf for computer screen.
Depth
(mm)
Depth
(mm)
Width
(mm)
Travel
(mm)
Width
(mm)
11. 19" EQUIPMENT (continued)
11.5 Keyboard shelf (continued)
With sliding shelf for mouse, integrated mat and position for mouse
250
- For mounting on 4 x 19" uprights
- Front fixing via screws
- Min. fixing centre: 625 mm
Cat. No.For cab.
depth (mm)
0 465 19
800
1000
- Height 1U (5U with vertical keyboard support)
- Max. load: 50 kg
- Supplied with screws and cage nuts with pins
- 1.5 mm thick steel
- Black RAL 9005
11.6 Set of 2 fixed sliders
- For fixing on 4 x 19" uprights
Cat. No.For cab. depth
(mm)
0 465 11600337312382—
0 465 12800537512582465
0 465 131000737712782654
- Max. load: 50 kg
- Supplied with screws
- 1.5 mm thick galvanised steel
Cat. No. 0 465 11 and 0 465 12
Ø 6.5
Ø 7
Depth
(mm)
625420500
(mm)B (mm)
460 max.
Shelf for screen
A
A
B
D
Width
(mm)
Usable
depth (mm)
C
(mm)
12.5
23.5
D
(mm)
22.5
12.5
19.5
With retractable
keyboard support
5U
Ø 15
Ø 7 Ø 7 (Cat. No. 0 465 12)
C
Profile and dimensions when in position in 19" LCS2 freestanding cabinets:
465 (width between 19" uprights)
462
441
18.5
394
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
One circuit per phase composed of 8 C13 sockets + 1 C19 socket.
Cat. No.
0 465 85
2P+E sockets
NumberStandard
24C13 IEC 60320
3C19 IEC 60320
Connection
5x4 mm2 cord of 3 m lenght
with IEC 60309 3P+N+E
plug 32A
Features
Cat. No.
Power supply Use
VoltageMax. currentPower
(1)
Protection
16A circuit
breaker
Single pole
+ neutral
0 465 85
380V
50/60 Hz
32A3680 W
C type
(1)
Per circuit/phase
(1)
Legrand also has a range of 19" PDU and vertical PDU with
intensity measure ability. To know all the features of these metered
PDU, consult the specific data sheet.
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012
- Designed to provide 230 V~ power supply for active products
- For mounting on 19" fixing centre
- 180° reversible end pieces for 2 fixing options:
- 2P+E sockets
- Connection via 2.5 mm2 terminal block
- Overall dimensions: H 55 x W 483 x D 52 mm (Cat. No. 0 332 37,
88 mm overall depth at the circuit breaker slot)
- Provide a 2U space
- Supplied with screws and cage-nuts
- Black aluminium body, plastic end pieces for fixing
12.2.1 Socket PDU
Cat.
No.
0 465 5112
0 465 529
0 465 509
0 465 546—
0 332 886
0 332 376Circuit breaker
0 332 876
0 465 609
0 465 626—
0 332 386Circuit breaker
0 465 656
6 339 005
2P+E sockets
NumberStandard
C13 IEC
60320
C19 IEC
60320
French
-
Belgian
German
British
Additional
function
—
—
—
Switch with
indicator
Tamperproof for
uninterruptible
power supply
(UPS)
—
—Black
Colour
Black
Black
Alumin. grey
White sockets
Alumin. grey
Red sockets
Black
Alumin. grey
White sockets
Alumin. grey
White sockets
12. POWER DISTRIBUTION (continued)
12.2 19" PDUs (continued)
12.2.1 Socket PDU (continued)
Features
Cat. No.
0 465 51
0 465 52
0 465 50
0 465 54
0 332 88
0 332 37
0 332 87
0 465 62
0 332 38
0 465 65
6 339 00
12.2.2 PDU with surge protector
- Provides protection against mains overvoltages while keeping
sockets energised
- Replacement of protection with surge protector module
Cat. No. 0 775 41 (indication by red LED)
Cat.
No.
0 332 786
Power supply Use
VoltageMax. currentPowerProtection
10A2500 W
16A circuit
breaker
230V - 250V
50/60 Hz
2P+E sockets
NumberStandard
French
-
Belgian
16A3680 W
13A2990W—
Additional
function
Surge protector
Switch with
indicator
2 pole
C type
16A circuit
breaker
2 pole
C type
Colour
Alumin. grey
White
sockets
—
—0 465 60
Features
Power supply Use
VoltageMax. currentPowerProtection
230V - 250V
50/60 Hz
16A3680 W—
Legrand also has a range of 19" PDU and vertical PDU with
intensity measure ability. To know all the features of these metered
PDU, consult the specific data sheet.
Cat. No.
0 332 78
Technical data sheet: F01424EN/01Updated on: 24/10/2014Created on: 21/02/2012