LEGRAND Wattstopper LCAP, LCAP44ALO, LCAP44A, LCAP44AMLO, LCAP44AMCB Series Manual

Wattstoppe
r
®
Commercial Power Enclosure Solutions and Main Lug Options — LCAP MODEL: LCAP44A
LCAP WITH MAIN LUG MODELS: LCAP44ALO/MLO/MCB
Overview
The Wattstopper® LCAP Series Commercial Enclosures ship with pre-configured modular solutions. Load dimming and switching use the InFusion™ controllers and switching products. The pre-configured designs save time in the Design Center™ software and during the installation process.
The UL listed LCAP44A panels are adaptable to spaces that have mixed 0-10V, and PWM loads and HV relay loads via the LVOS-0-10-PWM station. LCAP44A connects to any controller over the local network for easy connection and scalability.
Solution 1 – Parent-level Enclosure Models
Main Enclosure Description
LCAP44 44” Architectural Enclosure with hinged cover door
LCAP44A Panel
Configurations (see KIT panel
part numbers
ordering key
last page)
Optional Parts Description
LCAP-OPT-SWITCH 8-Port (4 standard and 4 POE) Ethernet switch/power supply
VA-RRU-1-120V Emergency Shunt Relay - 120V VA-RRU-1-277V Emergency Shunt Relay - 277V
Additional Parts Ordered Separately Description
VA-EPC-DFS-120V Emergency lighting surface mount switch 120V VA-EPC-DFS-277V Emergency lighting surface mount switch 277V
Panel Upper Section:
1 to 2 LVOS-0-10-PWM stations
Panel Middle Section:
1 to 2 LVOS-0-10-PWM stations
Panel Lower Section:
1 to 2 LVOS-0-10-PWM stations
Panel Low-Voltage Section
Specifications
Cabinet Dimensions HWD 44.5” x 24” x 4.575” / 113cm x 61cm x 11.6cm Door Dimensions HWD 44.5” x 24” x 0.75” / 113cm x 61cm x 2cm Panel Insert HWD 42” x 21” x 4.175” / 106.7cm x 53.3cm x 10.6cm Weight Enclosure 41 lbs / 18.6 kg Weight Door 20.7 lbs / 9.39 kg Weight Panel Insert 23 lbs / 10.43 kg Number of LVOS-0-10-PWM* stations Up to 6 Analog, 0-10DC/LV — Max. Outputs Up to 24 PWM, LV — Max. Outputs Up to 24 HV Relay 120-277 VAC — Max. Outputs Up to 24 Line Feeds (breakers) required 1 and Up Enclosure Finish Galvanized Steel Door Finish Black - Powder Coated Cover vented, hinged HV Wire copper wire, min of 80°C/176°F insulation Ventilation maintained 36” front clearance Ambient Operating Temp. 0-40°C / 32-104°F Ambient Operating Humidity 5-95% non-condensing UL, CUL, and CE listed yes
LCAP44A Specifications
* See these install sheets for important information: Low Voltage Output Station Lighting_LVOS-0-10-PWM-1
LCAP Enclosure Designs
LCAP Series Enclosure Facts. Enclosures must be populated from left to right and top down.
o Blank positions cannot be left between lighting modules in Design
Enclosures are pre-configured and wired (to the extent possible) using
The enclosure uses built-in barriers to separate high and low voltage wiring.
LCAP44A Enclosures only contain LVOS-0-10-PWM stations.
Center setup.
specific combinations of the following components. Installed components are dependent on the enclosure design.
o Components using high voltage wiring.
Mixed high voltage wiring.
o Components using low voltage control signal wiring. o Components using low voltage communication wiring. o Components using high voltage and low voltage connections made
inside the enclosure.
o Some designs include the barrier while other designs require the
barrier be added by the designer.
o High voltage barriers may be installed between 120V/240V/277V load
modules.
Enclosure Features / Parts
1. Enclosure can (includes door), order LCAP44 for can only.
2. Panel Insert (upper section). a. Ground terminals, (notice terminals for all sections). b. Wiring terminal blocks for upper section LVOS stations, (notice wiring
blocks for all sections if populated with LVOS stations).
i. Internal side pre-wired (see Wiring Block pg. 2).
ii. External side wired in field (see Wiring Block pg. 2).
c. Up to 2 LVOS-0-10-PWM stations (upper section)
3. Panel Insert (middle section). a. Up to two additional LVOS-O-10-PWM stations.
4. Panel Insert (lower section). a. Up to two additional LVOS-O-10-PWM stations.
5. Panel Insert (low-voltage section).
6. Enclosure cover with hinged/vented door allowing easy access when
servicing and proper ventilation for convection cooling process.
LCAP44A Panel Optional Construction Parts See Ordering Key, last page.
Installation / Enclosure Mounting Instructions Installation of LCAP products should be performed or supervised by a Wattstopper factory representative. Installation and maintenance of high voltage devices should only be performed by qualified and licensed personnel having appropriate training and experience.
General Wiring
Drill proper size holes in can for running wires in and out of the enclosure. Separate high and low voltage wire run channels. All wire runs in and out of the enclosure should be secured using 2-screw connectors or equivalent as shown at
the right . Proper conduit or equivalent wire channels
LCAP-OPT-SWITCH
8-Port (4 standard and 4 POE)
EMR. SWITCH
VA-RRU-1-12OV (277V)
The VA-RUU-1 switch comes pre-installed in KIT. The VA-EPC-DFS-1 switch is installed on site.
NOTE: Please see install sheets for emergency switch applications.
EMR. SWITCH
VA-EPC-DFS-12OV(277V)
Order Separate
should be used according to local codes and regulations.
IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS
CAUTION: Turn Breakers OFF and check that no power is on at the AC
Terminal Boards when working in the enclosure or working on lighting fixtures connected to the module’s loads, etc. Do not allow trimmed wire cuttings to fall into enclosure components as they may cause damage when power is restored. Damage from this type of short will void the warranty.
Do not use outdoors . Do not mount near gas or electric heaters.
WWW.LEGRAND.US/WATTSTOPPER - IS-00709-D Commercial Enclosure Solutions — MODEL: LCAP44/A & LCAP44/A + Main Lug page 1 of 8
k
V
or
V
s
V
or VA-
V
3
3
k
s
V
or VA-
V
s
V
or VA-
V
5
5
k
s
V
or VA-
V
s
V
or VA-
V
Do not mount enclosures in attics, garages, or crawlspaces, unless room is
properly conditioned to conform to ambient room temperature and humidity requirements.
Mount enclosure a minimum of 18” from ceiling or floor. National Electrical Code requires a minimum frontal clearance of 36” for the
enclosure.
Use screws provided for mounting. If any emergency circuits are fed or controlled from this panel, it must be
located electrically where fed from a UPS, generator, or other guaranteed source of power during emergency and power outage situations.
LISTED AS EMERGENCY LIGHTING EQUIPMENT – using an appropriate
label.
CAUTION: To avoid electrical
overload, total external connected load should not exceed output rating.
SAVE THESE INSTRUCTIONS Wire Block Terminal Close Up
EMERGENCY CIRCUITS
Part Number Ordering Key
Design Center will generate part numbers automatically as the enclosures are built. This key is for help creating manual orders if needed
LCAP44A–
LCAP44A - Architectural Panel - Auxiliary
LVOS-0-10-PWM - select quantity: select -
(Leave blank for 0) 1, 2, 3, 4, 5, or 6
KIT PART NUMBERS: LCAP44A-KIT
LCAP44A-1-KIT
LCAP44A-2-KIT
LCAP44A-3-KIT
LCAP44A-4-KIT
LCAP44A-5-KIT
LCAP44A-6-KIT
included 1 LCAP44A panel
optional 1 COM-POE-SWITCH Ethernet sw
included 1 LCAP44A panel, & 1 LVOS-0-10-PWM-P-1 with 1 pre-wired bloc
optional 1 COM-POE-SWITCH Ethernet sw, 1 VA-RRU-1-120
included 1 LCAP44A panel, & 2 LVOS-0-10-PWM-P-1 with 2 pre-wired block
optional 1 COM-POE-SWITCH Ethernet sw, 1 or 2 VA-RRU-1-120
included 1 LCAP44A panel, &
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 3 VA-RRU-1-120
included 1 LCAP44A panel, & 4 LVOS-0-10-PWM-P-1 with 4 pre-wired block
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 4 VA-RRU-1-120
included 1 LCAP44A panel, &
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 5 VA-RRU-1-120
included 1 LCAP44A panel, & 6 LVOS-0-10-PWM-P-1 with 6 pre-wired block
optional 1 COM-POE-SWITCH Ethernet sw, 1 to 6 VA-RRU-1-120
LVOS-0-10-PWM-P-1 with
LVOS-0-10-PWM-P-1 with
VA-RRU-1-277
pre-wired bloc
pre-wired bloc
*
RRU-1-277
RRU-1-277
RRU-1-277
RRU-1-277
RRU-1-277
LCAP44A Enclosure Multi-View
MULTI-VIEW
PANEL
BACK VIEW
WWW.LEGRAND.US/WATTSTOPPER - IS-00709-D Commercial Enclosure Solutions — MODEL: LCAP44/A & LCAP44/A + Main Lug page 2 of 8
LCAP Panels with Main Lug Panel OPTION
LCAP44/A/LO/CB Panels with Main Lug Panel OPTION
Main Lug Circuit Breaker Option
The LCAPA and LCAPM series enclosures can be configured as a load feed through panel (LCAP PANEL only) or as main lug panels with the addition of load circuit breakers below the load control feed through compartment. Main lug options can also contain a main breaker. The Main Lug option is available for the LCAPALO and LCAPMLO/SLO series panels – see the LCAP32/44/M/S install sheet. The circuit breaker options are based on the panel configuration, number and type of loads, panel and circuit breaker options are selected the panel is built and prewired* in the factory and delivered to the project ready to be installed.
Applications
The LCAP44A is designed for medium to large spaces requiring control of up to 24 low voltage PWM lighting circuits, 24 low voltage 010V DC lighting circuits, and 24 120-277VAC relay lighting circuits. The built-in integration and networking capabilities of the LCAP44A easily meet requirements in spaces needing multiple types of lighting, and other automation integration systems using this panel. Adding an Equinox 41 or 73 touchscreen to the project allows the facility manager or end user to create, change, and manage scenes, schedules, and user profiles.
Features Modular LCAP load section; pre-configured solution from the factory. Just
connect line voltage and load wires.
Pre-configured Main Lug Panel solution options. System is expandable using other LCAP series primary or secondary panels
and LCAP Main Lug / Circuit Breaker options.
Can be configured with emergency circuits for emergency lighting. Connects to InFusion Controller system via Ethernet or Station Bus. Up to 24 dry contact inputs; 12 of the contacts may be used for, system
powered, light sensors or occupancy sensors.
Dimmers have programmable start/stop and dimming curve adjustment
features to customize dimming linearity.
Simple programming from a single software solution - Design Center. Adding one BACnet enabled controller to a system allows the entire system
to be controlled through BACnet.
LCAP44ALO/MLO/MCB Series Specifications
and circuit breaker rating requirements. Once the main lug
*NOTE: Panels with GFI breakers: GFI breakers are not installed or pre-wired and are shipped separately.
Main Lug Panel options range from 18 to 36 circuits, 208-480V, and 10kAIC
to 65kAIC and may be configured with a main breaker option.
Setup In Design Center Understanding LCAP and Main Lug panels: LCAP panels with the Main Lug option is a larger enclosure that holds the
traditional LCAP components in the upper section of the enclosure and includes a breaker section in the lower section of the enclosure.
LCAP panels with the Main Lug option are built in Design Center the same
way as standard LCAP panels. The only difference is the Main Lug option has been selected. Follow the steps below to create an LCAP panel with the Main Lug option selected.
1. In Design Center | Object Explorer select
Vantage Objects,Enclosures, Commercial,LCAP model,
2. Right click in the enclosure and select
3. It is possible to add additional breakers in
4. Select the Main Lug section of the
o LCAP44A-KIT (Main Lug),
Populate to automatically add LVOS-PWM stations in the enclosure or select LVOS­PWM stations and drag into the enclosure as wanted. (It is not possible to drag an LVOS-PWM station below a blank station position in an LCAP enclosure – fill enclosure from left to right / top to bottom. Notice that breakers are automatically added to the Main Lug enclosure as LVOS-PWM stations are added.
the Main Lug section by right clicking below existing breakers and selecting Add Breaker until the maximum number of breakers allowed is reached.
enclosure and change the type to MCB to add a Main Breaker option or leave as MLO for standard load breakers only.
section of the
Specifications LCAP44ALO/MLO LCAP44ALO/MCB
Cabinet / Panel Cover Dimensions HWD
68.0” x 24.0” x 4.75”
172.72cm x 60.96cm x 12.06cm
77.0” x 24.0” x 4.75”
195.58cm x 60.96cm x 12.06cm
Breakers Up to 18 Up to 36 Main Lug Panel Door Dimensions HWD
16” x 12.5” x 0.75”
40.64cm x 31.75cm x 1.9cm
23” x 19” x 0.75”
58.42cm x 48.26cm x 1.9cm Weight Enclosure with Cover 165 - 175 lbs / 74.84 – 79.38 kg 170 - 180 lbs / 77.11 – 81.65 kg LCAP Panel Door Dimensions HWD 40.5” x 16.0” x 0.75” / 102.87cm x 40.64cm x 1.9cm Panel Insert HWD 42” x 21” x 4.175” / 106.7cm x 53.3cm x 10.6cm Weight Panel Insert M-23 lbs. 10.43 kg Number of LVOS-0-10-PWM* stations Up to 6 Analog, 0-10DC/LV — Max. Outputs Up to 24 PWM, LV — Max. Outputs Up to 24 HV Relay 120-277 VAC — Max. Outputs Up to 24 Enclosure Finish Galvanized Steel Door Finish Black - Powder Coated Cover vented, hinged Wire copper wire, MIN. of 80°C / 176°F insulation Ventilation maintained 36” front clearance Ambient Operating Temp. 0-40°C / 32-104°F Ambient Oper. Humidity 5-95% non-condensing UL, CUL, and CE listed yes
WWW.LEGRAND.US/WATTSTOPPER - IS-00709-F Commercial Enclosure Solutions — MODEL: LCAP44A & LCAP44ALO + Main Lug page 3 of 8
O
T
S
T
STANDARD LCAPA SERIES ENCLOSURES MAY BE CONFIGURED WITH MAIN LUG ENCLOSURES
Example LCAP44A configured with LCAP44ALO/MLO or MCB:
ANDARD
LCAP44A PANEL
ADD THE MAIN
LUG MLO OPTION
MLO
OPTION
LCAP44ALO/ MLO
O CREATE AN
OR CREATE AN
LCAP44ALO/ MCB
12 3 4
OR ADD THE MAIN LUG
MCB OPTION
CB OPTION
ADDS MAIN BREAKER
LCAP44A
1. Start with the standard LCAP44A Panel.
2. Select the Main Lug option MLO or MCB. Both LCAP44A MLO and MCB options come with (up to) 18 or 36, 20A breaker configurations. The MCB option also comes with a 100A main breaker for 18 breaker model or 225A
MCB
OPTION
main breaker for 36 breaker model.
3. Finished LCAP44ALO/MLO enclosure – 68” H.
4. Finished LCAP44ALO/MCB enclosure – 77” H.
See additional specifications below
LCAP44ALO/MLO with Main Lug (up to 18 Breakers) Enclosure Multi-View
4 .5 ” ( 11. 4 3 c m )24.0” (60 .9 6cm)
LCAP44ALO/MLO
1. Enclosure upper section for
4 4 .75 ” ( 113 .6 6 5 c m ) 23.25” (59.055cm)
LCAP44ALO Panel.
2. Enclosure lower section for up to 18 breakers. Select the Main Lug option MLO option for (up to) 18, 20A
DIMMER
SECTION
breakers.
3. Breaker section may be configured for 4-wire or 3-wire power configurations.
(See last page for breaker/order options)
17 2 .72 c m
68”
LCAP44-18 PANEL
SURFACE TRIM
BOX 4 1/2 ” D EEP
WITH DOORS INSTALLED
WWW.LEGRAND.US/WATTSTOPPER - IS-00709-F Commercial Enclosure Solutions — MODEL: LCAP44A & LCAP44ALO + Main Lug page 4 of 8
BARRIER
COMMUNICATION CONDUIT
GROUND BAR
LCAP44-18 PANEL
MAIN LUGS
WITH DOORS &
DEADFRONT REM
CIRCUIT BREAKERS
NEUTRA L
BAR
VED
12
20
34
20
56
20
G N
78
20
D
910
20
B
11 12
20
U
13 14
20
S
15 16
20
17 18
20
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
480Y/ 277V 30 4W
(14KAIC)
20 20 20 20 20 20 20 20
15
NEUTRAL
BUS DIAGRAMS
10 0 A M A IN L U G S
12
20
34
20
56
20
G N
78
20
D
910
20
B
11 12
20
U
13 14
20
S
15 16
20
17 18
20
12 0 V/ 24 0 V 10 3 W
(10KAIC-22KAIC-65KAIC)
20 20 20 20 20 20 20 20
15
NEUTRAL
LCAP44ALO/MCB with Main Lug & Main Breaker Enclosure Multi-View
4 4 .7 5 ” ( 113 . 6 6 5 c m ) 32.25” (81.9 15cm)
LCAP44-18 PANEL SURFACE MOUNT
BOX 4-1/2” DEEP WITH
DOORS INSTALLED
LCAP44ALO/MLO with Main Lug (up to 36 breakers) Enclosure Multi-View
4 . 5 ” ( 11. 4 3 c m )24.0” (60.96cm)
19 5.58cm
77”
BARRIER
COMMUNICATION CONDUIT
GROUND BAR
LCAP44-18 PANEL
MAIN BREAKER WITH DOORS &
DEADFRONT REMOVED
4.5” (11.43cm)24.0” (60.9 6c m)
CIRCUIT BREAKERS
NEUTRA L
BAR
1. Enclosure upper section for
2. Enclosure lower section for up to 18
DIMMER
SECTION
3. Breaker section may be configured
(See last page for breaker/order options)
12
20
34
20
56
20
78
20
910
20
11 12
20
13 14
20
15 16
20 20
17 18
G N D
B
10 0 A
U
10 0 A
S
208Y/120V 30 4W
(10KAIC-22KAIC-65KAIC)
480Y/ 277V 30 4W
(14KAIC-*35KAIC-*65KAIC)
*SERIES RATED
3P
20 20 20 20 20 20 20 20
15
MAIN BKR.
NEUTRAL
BUS DIAGRAMS
10 0 A MAIN BREAKER
LCAP44ALO/MCB LCAP44ALO Panel. breakers. Select the Main Lug type
and change to MCB to add a Main Breaker option.
for 4-wire or 3-wire power configurations.
12
20
34
20
56
20
78
20
910
20
11 12
20
13 14
20
15 16
20
17 18
20
G N D
B
10 0 A
U
10 0 A
S
12 0 V/ 24 0 V 10 3 W
(10KAIC-22KAIC-65KAIC)
2P
20 20 20 20 20 20 20 20
15
MAIN BKR.
NEUTRAL
LCAP44-36 PANEL
SURFACE MOUNT BOX
4-1/2” DEEP
WITH DOORS INSTALLED
1. Enclosure upper section for LCAP44ALO Panel.
LCAP44ALO/MLO (36 Breakers)
2. Enclosure lower section for up to 36 breakers. Select the Main Lug option MLO option for (up to) 36, 20A
44.75” (113.665cm) 32.25” (81.915cm)
breakers.
3. Breaker section may be configured for 4-wire or 3-wire power configurations.
(See last page for breaker/order
DIMMER
SECTION
(14KAIC)
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
15
20 22 24 26
NEUTRAL
28 30 3231 34 36
BUS DIAGRAMS
225A MAINLUGS
20
12
20
34
20
56 78
195.58cm 77”
BARRIER
LCAP4 4-36 PANEL
WITH DOORS &
DEADFRONT REMOVED
CIRCUIT BREAKERS
NEUTRA L
COMMUNICATION CONDUIT
GROUND BAR
MAIN LUGS
BAR
BREAKER
SECTION
20
910
20
11 12
20
13 14
20
15 16
20
17 18
20
G
19
20
N
20
21
D
23
20
B U
25
20
S
27
20
29
20 20
33
20
35
20
208 Y/120 V 30 4W
(10 KAIC-22KAIC-65 KAIC)
480 Y/277V 30 4W
options)
20
12
20
34
20
56 78
20
910
20
11 12
20
13 14
20
15 16
20
17 18
20
G
19
20
N
20
21
D
23
20
B U
25
20
S
27
20
29
20 20
33
20
35
20
12 0 V/ 2 4 0 V 10 3 W
(10 KAIC-22KAIC-65 KAIC)
20 20 20 20 20 20 20 20 20 20
20
20
22 24
20
26
20 20 20 20 20
15
28 30
34 36
NEUTRAL
3231
WWW.LEGRAND.US/WATTSTOPPER - IS-00709-F Commercial Enclosure Solutions — MODEL: LCAP44A & LCAP44ALO + Main Lug page 5 of 8
A
A
A
A
A
A
LCAP44ALO/MCB with Main Lug (up to 36 breakers) & Main Breaker Enclosure Multi-View
4.5” (11.43cm)24.0” (60.96cm)
1. Enclosure upper section for LCAP44ALO Panel.
2. Enclosure lower section for up to 36 breakers. Select the Main Lug type and change to MCB to add a Main Breaker option.
3. Breaker section may be configured for 4-wire or 3-wire power configurations.
44.75” (113.665cm) 32.25” ( 81.915cm)
DIMMER
SECTION
19 5.58cm
77”
BARRIER
CIRCUIT BREAKERS
COMMUNICATION CONDUIT
NEUTRAL
BAR
BREAKER
SECTION
LCAP4 4- 36 PANEL
SURFACE MOUN T BOX
4-1/ 2” DEEP
WITH DOORS INSTALLED
GROUND BAR
LCAP44-36 PANEL
MAIN B REA KER WITH DOORS &
DEADFRONT REMOVED
LCAP with Optional Main Lug Part Number Ordering Key
Design Center will generate LCAP44ALO/MLO/MCB part numbers automatically as the enclosures are built. This key is for help in understanding and creating orders in the
LCAP Quote Tool online ordering tool.
Breaker Types for LCAPALO/MLO/MCB Enclosure Configurations
SIZE HEIGHT BASE PANEL CONFIGURATION 10kAIC 14kAIC 22kAIC 35kAIC 65kAIC
18
circuits
100A
Bussing
SIZE HEIGHT BASE PANEL CONFIGURATION 10kAIC 14kAIC 22kAIC 35kAIC 65kAIC
18
circuits
100A
Bussing
CONFIGURATION FOR LCAP32
56"
240V - MCB (Single Phase)(up to 100A, 65kAIC)
65"
CONFIGURATION FOR LCAP44
240V - MLO (Single Phase) BAB QBH
68"
208V - MLO BAB QBH 480V - MLO GHB 240V - MCB (Single Phase)(up to 100A, 65kAIC) 208V - MCB (up to 100A, 65kAIC)
77"
480V - MCB (up to 100A, 35kAIC) GHB* 480V - MCB (up to 100A, 65kAIC)
240V - MLO (Single Phase) BAB QHB
208V - MLO BAB QHB 480V - MLO GHB
208V - MCB (up to 100A, 65kAIC) 480V - MCB (up to 100A, 35kAIC) GHB* 480V - MCB (up to 100A, 65kAIC)
DDER - Branch Breakers Each, 1-Pole, 20
DDER - Branch Breakers Each, 1-Pole, 20
GHB GHB
BAB* BAB*
GHB*
GHB GHB
BAB* BAB*
GHB*
Breaker Types for LCAPALO/MLO/MCB Enclosure Configurations (cont.)
CONFIGURATION FOR LCAP44 -
SIZE HEIGHT
240V - MLO (Single Phase) 208V - MLO
36
circuits
225A
Bussing
480V - MLO 240V - MCB (Single Phase)(up to 225A, 65kAIC) 208V - MCB (up to 225A, 65kAIC)
77"
480V - MCB (up to 100A, 35kAIC) 480V - MCB (110A - 225A, 35kAIC) 480V - MCB (up to 100A, 65kAIC) 480V - MCB (100A - 225A, 65kAIC)
* Breaker series rating when a main breaker option is selected
MLO = Main Lug Option MCB = Main Lug with Main Circuit Breaker Type QBH 22kAIC
LCAP Panel with Main Lug - Ordering Key
LCAP44ALO/MCB (36 breaker)
(See last page for breaker/order
NEUTRAL
20
12
20
34
20
5
20
78
20
910
20
11 12
13 14
20 20
15 16
20
17 18
G
20
19
N D
20
21
B
20
23
U
20
25
S
20
27
20
29
20
12
20
34
20
5
20
78
20
910
20
11 12
20
13 14
20
15 16
20
17 18
G
20
19
N D
20
21
B
20
23
U
20
25
S
20
27
20
29
36 Breaker
SIZE
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
NEUTRAL
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
BUS DIAGRAMS
100A - 225A
MAIN B REA KER
HEIGHT SIZE HEIGHT SIZE HEIGHT
BREAKER RATING LEGEND (Single Phase)
Type BAB 10kAIC
Type GHB 65kAIC
options)
20
33
20
35
20
6
225A 225A
|
10 0 A
20 22
208Y/120V 30 4W
24
(10KAIC-22KAIC-65KAIC)
26 28
480Y/ 277V 30 4W
30
(14KAIC-*35KAIC-*65KAIC)
*SERIES RATED
20
33
20
35
20
6
225A 225A
|
10 0 A
20 22
12 0 V/ 24 0 V 10 3 W
24
(10KAIC-22KAIC-65KAIC)
26 28 30
DDER - Branch Breakers Each, 1-Pole, 20
BAB BAB
GHB
QBH QBH
3P
2P
20 20 15
MAIN BKR.
20 20 15
MAIN BKR.
GHB* GHB*
3231 34 36
3231 34 36
GHB GHB
BAB* BAB*
GHB* GHB*