LEGRAND KEOR T EVO Operation Manual

KEOR T EVO 10-15-20 KVA
Installation & Operation Manual
LE10507AA
LE10507AA
KEOR T EVO
1
Installation & Operation Manual
1. FOREWORD 3
1.1. Overview 3
1.2. Manual 3
2. WARRANTY 5
2.1. Terms of Warranty 5
2.2. Out of Warranty Terms and Conditions 5
3. SAFETY 6
3.1. Description of the Symbols Used on the Labels Applied to the UPS 6
3.2. Individual Protective Gear 6
3.3. Important Notice for UPS 7
3.4. Important Notice for Battery 8
3.5. Emergency interventions 8
4. OPERATION MODES 9
4.1. Online Mode 9
4.2. Battery Mode 10
4.3. Bypass Mode 11
4.4. Eco Mode 12
4.5. No Operation 12
4.6. Operation with Maintenance Bypass 12
4.7. Operation with External Maintenance Bypass (Optional) 12
5. REQUIREMENT 13
5.1. Transportation 13
5.2. Placement 13
5.3. Storage 15
5.4. Electrical Requisites 15
6. INSTALLATION 18
6.1. Models and Dimensions 18
6.2. Unpacking Procedure 19
6.3. Installation Procedures and Instructions 20
6.3.1. Power Connections of Single Systems 21
6.3.2. Power Connections of Parallel Systems 34
7. HUMAN MACHINE INTERFACE 36
7.1. Front Panel Segments 36
7.1.1. Colour Graphical Touchscreen 37
7.1.2. UPS Status LED Bar 39
7.2. Menu 40
7.2.1. Alarms Menu 40
7.2.2. Measurements Menu 41
7.2.3. Settings Menu 42
7.2.4. Diagnostics Menu 45
7.2.5. About Menu 47
7.2.6. Command Menu 47
8. COMMUNICATION 49
8.1. Serial Communication (RS232) 50
8.2. Emergency Switching Device and Generator Connections 51
8.3. Dry Contacts 52
8.4. RS485 53
2
9. OPERATING PROCEDURES FOR SINGLE SYSTEMS 54
9.1. Preparations 54
9.2. Commissioning 55
9.2.1. Start-Up UPS with Internal Battery 55
9.2.2. Start-Up UPS with External Battery 55
9.3. Decommissioning 56
9.4. Maintenance Bypass Commissioning Instructions 56 (Transfer Load Supply from UPS to Internal Maintenance Bypass)
9.5. Maintenance Bypass Decommissioning Instructions 57
10. OPERATING PROCEDURES FOR PARALLEL SYSTEMS 58
10.1. Introduction 58
10.1.1. Redundancy 58
10.1.2. Power Increase 58
10.2. Procedure for Commissioning and Start-Up 59
10.3. Procedure for Decommissioning 60
11. TROUBLESHOOTING 61
11.1. Bypass voltage failure Alarm 61
11.2. Bypass phase sequence wrong Alarm 61
11.3. Inverter not sync. with bypass Alarm 61
11.4. Input phase sequence wrong Alarm 61
11.5. Rectier not sync. with input Alarm 61
11.6. DC voltage failure Alarms 61
11.7. ESD active Alarm 61
11.8. Ambient temperature high Alarm 61
11.9. Overload Alarms 61
11.10. Maintenance bypass active Alarm 62
11.11. Battery test failure Alarm 62
11.12. Input voltage failure Alarms 62
11.13. Inverter temperature high/ Rectier temperature high Alarms 62
12. PREVENTIVE MAINTENANCE 63
12.1. Batteries 63
12.2. Battery Fuses 63
12.3. Fans 64
12.4. Capacitors 64
Appendix-1: Alarms List 65 Appendix-2: Diagnostics List 66 Appendix-3: Event List 67 Appendix-4: Technical Specications 69 Appendix-5: Modbus List 71 Appendix-6: Description of UPS and Block Diagram 73
3
Installation & Operation Manual
1. Foreword
1.1. Overview
Thank you for choosing LEGRAND UPS KEOR T EVO product.
KEOR T EVO has been designed with advanced technologies and the latest compo¬nents generation; realized to satisfy both users and instal¬lers in their operational needs of high availability and perfor¬mance.
This UPS aims to be ecient, functional, safe and very easy to install and use. LEGRAND has studied the best way to reconcile high-tech performance and ease of use, making “user friendly” technologi¬cally advanced products.
KEOR T EVO supplies maximum protection and power quality for any type of IT load, tertiary application, lighting or building.
Furthermore, standards deployed by Legrand for R&D, supplier selection and manufacturing comply with the highest quality standards. This product is manufactured in an ISO 9001 & ISO14001 certied factory in full compliance with the eco-design laws. The UPS KEOR T EVO system is made in compliance with the existing European Community directives and with the technical standards in force to comply with CE marking as certied by the Declaration of Conformity issued by the Manufacturer.
Technology & Architecture
A special feature of KEOR T EVO is Online Double Conversion Operation (VFI-SS-111 as dened by the reference standard EN 62040-3) based on the capacity to supply a voltage that is perfectly stabilized in frequency and amplitude, even in event of extreme alterations of mains power supply.
The 3-Level Switching Technology used in this product is the latest solution to provide high energy eciency even with low load conditions.
The energy eciency performance of KEOR T EVO surpasses the minimum requirements dened by the Code of Conduct on Energy eciency and Quality of European of AC UPS dened by EC.
KEOR T EVO represents the best solution combining high performance, low management costs and ease of operation and maintenance:
• Dual Input
• User friendly touch screen design
• UPS via LED bar (with trac light coding) gives an immediate diagnosis of the system under any conditions.
• Internal Battery option as well as wide range external battery cabinets.
• Integrated Maintenance Bypass
• Parallel connection to increase the power
• Availability of dierent communication types
1.2. Manual
• The purpose of this manual is to provide indications for using the equipment safely and to carry out rst level of troubleshooting.
• This manual is addressed to persons already educated on precautions to adopt in face of electrical hazard
• This manual is addressed to “User“, generic term to identify all persons that will have the need and / or obligation to provide instructions or operate directly this UPS equipment
• Adjustments, preventive and curative maintenance jobs are not dealt with in this manual as they are reserved exclusively to skilled and authorized Legrand UPS Technical Service Engineers.
4
• The intended use and congurations envisaged for the equipment are the only ones allowed by the Manufacturer; do not attempt to use the equipment in disagreement with the indications given. Any other use or conguration must be agreed and written by the Manufacturer, in such a case, will be an enclosure to the manual.
• For its use the user must also comply with the specic laws in force that exist in the country where the equipment is installed. Reference is also made in this manual to laws, directives, etc., that the user must know and consult in order to full the purposes established by the manual.
• If information is exchanged with the Manufacturer or assistance personnel authorized by the former, please refer to the equipment’s rating plate data and serial number.
• The manual must be kept for the equipment’s useful life cycle and, if necessary (e.g. damage which prevents it being consulted even partially) the user must ask the Manufacturer for a new copy, quoting the publishing code on the cover.
• The manual reects the state of the art at the moment the equipment was put on the market, of which it is an integral part. The publication complies with the directives in force at such a date. The manual cannot be considered inadequate if updates of standards or changes are made to the equipment.
• Any integration to the manual which the Manufacturer deems tting to send to the users must be kept with the manual, becoming an integral part of it.
• The Manufacturer is available to its clientele to provide additional information and will take into consideration any suggestions made to improve this manual to bring it even closer to the requirements for which it was drawn up.
• If the equipment is sold, which always includes handing over this operating manual, the primary user must notify the Manufacturer, giving him the address of the new user so the latter can be reached if there are any communications and/or updates deemed indispensable.
The manufacturer reserves the rights to change the technical specications and design without notice.
LEGRAND reserves the rights to change the information in this document without notice. Refer to http://ups.legrand.com/ web site to dowload last release and translations.
Units that are labelled with a CE mark comply with the Standard: EN 62040-1 and EN 62040-2.
Read the manual completely before working on this equipment!
Reproduction, adaptation, or translation of this manual is prohibited without prior written permission of LEGRAND Company, except as allowed under the copyright laws.
5
Installation & Operation Manual
2. Warranty
2.1. Terms of Warranty
• Warranty is dened by General Conditions of Sale and Delivery.
• The UPS including all the internal parts is under the warranty of LEGRAND.
• If the UPS malfunctions because of component, manufacturing or installation (if it’s done by authorized LEGRAND UPS Technical Service Personnel) problems during the warranty period, the UPS will be repaired (spares and labour) by the Manufacturer under warranty.
2.2. Out of Warranty Terms and Conditions
This Warranty does not apply if:
• UPS not commissioned or maintained by an authorized LEGRAND UPS Technical Service sta or an authorized LEGRAND distributor Technical Service sta
• UPS not used according the terms of operating and installation manual
• Product serial number label has been removed or lost
This Warranty does not cover any defects or damages caused by:
• Neglect, accident, misuse, misapplication
• Failure due to fortuitous circumstances or force majeure (lightning, oods…etc.),
• Unloading and transportation damage and failures after delivery,
• Damage or injuries caused by negligence, lack of inspection or maintenance, or improper use of the products,
• Faulty electrical wiring,
• Defects arising either from designs or parts imposed or supplied by the purchaser,
• Defects and damage by re and lightning,
• Failures due to modication in the products without LEGRAND approval,
• Improper installation, testing, operation, maintenance, repair, alteration, adjustment, or modication of any kind by unauthorized personnel,
The Manufacturer will repair the device in such cases for a fee and is not responsible for the shipment of the equipment.
The Battery warranty does not apply if the temperature in the room exceeds 25 °C.
Extended battery warranty does not apply if:
• UPS has not been commissioned
• A yearly preventive maintenance visit has not been performed
By an authorized LEGRAND UPS Technical Service sta or authorized LEGRAND distributor Technical Service sta.
The UPS may contain batteries that should be recharged 24Hours min after 6 month storage duration to avoid deep battery discharge. Warranty cannot apply on batteries that have suered of deep discharge.
6
3.2. Individual Protective Gear
There is a high risk of electrical shock with the equipment as well as a considerable short circuit current. When installing and servicing the equipment it is absolutely forbidden to work without the protective gear mentioned in this paragraph.
The personnel who are going to work with the equipment for installation or maintenance jobs must not wear clothes with baggy sleeves or laces, belts, bracelets or other metal items that could be a hazard source.
The following indications summarize the protective gear to wear.
3.1. Description of the Symbols Used on the Labels Applied to the UPS
3. Safety
Information related to safety of the UPS, battery, load and the user is summarized below. But the equipment should not be installed before reading the manual completely.
PE: PROTECTIVE EARTH
PB: PROTECTIVE BONDING
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
This symbol points out the instructions, which may result with injury of the operator or damage of the equipment if not obeyed.
Accident and spark proof footwear with rubber sole and reinforced toe
Use : always
Waterproof rubber gloves
Use : always
Protective gear
Use : always
Protective glasses
Use : always
7
Installation & Operation Manual
3.3. Important Notice for UPS
• The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical Service Personnel.
• This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before installing the equipment and save this manual for future reference.
• Not obeying the instructions written on this manual which may result with possible injury of the operator or damage of the equipment.
• The equipment shall be packed and xed properly during transportation to avoid fall down and proper equipment should be used for transportation. Never transport in horizontal position.
• The UPS must always stands in a vertical position. Make sure that the oor can support the weight of the system.
• Connect the PE ground connector before connecting any other cable.
• UPS is designed for indoor use. To reduce the risk of re or electric shock, install this UPS in a temperature and humidity controlled indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum without condensation).
• UPS requires 3Ph-N+PE input connection.
• Do not connect the output neutral to the protective ground or protective bonding. KEOR T EVO does not modify the neutral arrangements of the system; the use of an isolation transformer is required should it be necessary to modify the neutral arrangements downstream KEOR T EVO.
• KEOR T EVO must be protected from voltage surge with devices that are suited to the installation; the mains voltage surge must be limited to 2kV. These protective devices must be sized to take into account all the installation parameters (geographical position whether or not there is a lightning rod, whether or not there are other suppressors in the electrical installation, etc )
• Even when connections removed, residual voltages of capacitors and/or high temperature may exist on connection terminals and inside the UPS. Before working on terminals, check between all the terminals included PE that no hazardous voltages exist.
• The connections shall be made with cables of appropriate cross-section in order to prevent the risk of re. All cables shall be of insulated type and shall not be laid out on the walking path of the persons.
• According to IEC 62040-2; this is a product for commercial and industrial application. In the second environment installation restrictions or additional measures may be needed to prevent disturbances.
• Contact your local recycling or hazardous waste centre for information on proper disposal of the used battery or UPS.
• Make sure that the UPS is not overloaded to provide a higher quality supply to the loads.
• In case of an extraordinary situation (damaged body, cabinet or connections, penetration of foreign materials into the body or cabinet etc.) de-energize the UPS immediately and consult to the LEGRAND Technical Assistance Centre.
• When used for particular applications such as life support systems or any other application where product failure is likely to cause substantial harms to person, we would advise you to contact LEGRAND UPS to conrm the ability of these products to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and specications.
8
3.4. Important Notice for Battery
• The batteries may only be installed and commissioned by authorized LEGRAND UPS Technical Service Personnel.
• Make sure that the battery qty is proper for the unit and they are same type and capacity. Otherwise danger of explosion and re is within the bounds of possibility.
• Do not dispose of batteries in a re. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
• In case of electrolyte in contact with skin, immediately wash the contaminated skin with water.
• Replaced batteries must be disposed of at authorized battery waste disposal centres.
• A battery can present risk of electric shock and high short circuit currents.
The following precautions should be observed when working on batteries;
• Remove rings, watches, necklaces, bracelets and all metal objects.
• Only use tools with insulated handles.
• Wear rubbers gloves and a rubber apron when handling batteries.
• Do not lay tools or metal parts on top of batteries.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Before a maintenance or repair work on the UPS;
• Switch the input, output and battery circuit breakers (Q1, Q2 and F5) to “OFF” position.
• If UPS has internal batteries; Remove and isolate + battery (red) and N battery neutral (blue) cables.
• If UPS has external batteries; also switch the circuit breakers of the battery cabinet to “OFF” position.
• Determine if the battery is inadvertently grounded. If inadvertently grounded; remove source of ground. Contact with any part of a grounded battery can result in electrical shock.
• Battery fuses shall only be replaced with the same rating and type which came along with the UPS.
3.5. Emergency interventions
The following information is of a general nature. For specic interventions please consult the laws existing in the country where the equipment is installed.
First aid interventions
If any rst aid intervention is required, comply with company rules and traditional procedures.
Fire-prevention measures
Never use water to extinguish re but only the extinguishers designed specically for electronic equipment or battery res.
9
Installation & Operation Manual
4. Operation Modes
Uninterruptible Power Supplies (UPS) most important function is the protection of critical and sensitive loads from the irregular mains voltage conditions. They are used to supply uninterruptible energy to these loads in such irregular mains voltage conditions and provide regulated energy supply to the equipment present in the IT room, industrial workshop, hospitals and oces.
KEOR T EVO UPS during Online mode operation provides stable pure sine wave not aected by input voltage uctuations. This helps to extend the life time of your sensible loads. Power factor of the current consumed from mains is nearly one. This allows perfect adaptation to upstream generator or isolation transformer supply. The reactive power consumption decreases.
During mains voltage failure, the energy needed for the load is provided by the internal battery (or installed in external battery cabinet/s). These batteries are charged by an intelligent battery charging circuit when mains voltage is within the limits. Batteries are lead acid battery (VRLA) and do not require any maintenance until the end of their life time.
In case of long overload or inverter failure situation, UPS transfers the load supply to bypass line, and load is supplied by mains . When the condition turns back to normal, UPS will continue to supply the load through inverter.
UPS control and management is done by Digital Signal Processor (DSP) which is 200 times faster than standard microprocessors. This helps to make your UPS smarter. DSP uses all the sources on optimum conditions, observes the failure conditions, and communicates with your computer system.
UPS can be operated in one of the following operational modes depending on the condition of mains voltage, battery, load, UPS status or user preference.
You may see the block diagram of UPS in Appendix-6 Description of UPS and Block Diagram.
4.1. Online Mode
Energy is drawn from the mains voltage input. Loads are supplied through the rectier and the inverter. The AC voltage at the input is converted to a DC voltage by the rectier. The inverter converts this DC voltage to an AC voltage with a stable sinusoidal waveform, amplitude and frequency. Output voltage and frequency can be set via front panel. Output voltage is sinusoidal and has a regulated amplitude and frequency. It is independent from the input voltage. The loads are not aected by the disturbances of the mains voltage.
If the mains voltage and frequency are in an acceptable range, Online Operation is possible.
Check Appendix-4 Technical Specications for Online Operation mode mains voltage limits.
The upper limit of mains voltage is independent from the load percentage and it is Ph-N: 270V. UPS switches to Battery Operation mode when the mains voltage is over Ph-N: 270V. The mains voltage is required to decrease below Ph-N: 260V for UPS to return Online Operation.
Online Operation Conditions;
In case Online Operation is set as operation mode of UPS, the mains voltage is within the limits and/or if there
is no abnormal condition (overheat, overload, failure…etc.) UPS operates in Online Operation. Except for failures, as soon as the abnormal conditions are eliminated, UPS switches to Online Operation automatically.
In case Bypass Operation is set as operation mode of UPS and the voltage and frequency is out of the bypass
limits but within the rectier limits, UPS switches to Online Operation.
10
4.2. Battery Mode
In this operation, energy is drawn from the batteries. The loads are supplied via inverter. Output voltage is sinusoidal and has a regulated amplitude and frequency.
Battery voltage should be in acceptable limits and the inverter should be enabled for the UPS to operate in this mode.
UPS operates in Battery Operation in the following cases:
• While UPS is operating in Online Operation; if frequency/waveform/rms value of mains voltage go beyond the rectier limits,
• While UPS is operating in Bypass Operation, if frequency/waveform/rms value of mains voltage go beyond Bypass limits,
• If Inverter enabled: “YES”, Rectier enabled: “NO” are selected through the front panel (Authorisations Menu for authorized Service Sta).
KEOR T EVO UPS operates with one or several parallel strings of 1 x 60pcs 12VDC battery with common neutral.
You may see the battery string connection as below;
+
-
n x 12-18 pcs n x 12-18 pcs
POSITIVE STRING
NEUTRAL
POINT
N
NEGATIVE STRING
Two Serial Strings with Central Point – Neutral Potential –
KEOR T EVO UPS operates with one strings of 24 to 36 x pcs 12VDC battery with common neutral
Battery Management and Battery Back-Up Time
When UPS operates in Online or Bypass Operation; it continuously calculates and displays the remaining back-up time.
Autonomy time depends on battery type, quantity, capacity, situation and load level. UPS stops supplying the loads if the battery voltage decreases under a specic value.
Battery life depends on some parameters such as battery type, charge-discharge cycle, and depth of dis­charge, ambient temperature, conditions. Please check Technical Specications for the ideal environmental conditions for the batteries. Using the batteries outside this temperature range will decrease battery opera­tion time and battery life.
11
Installation & Operation Manual
4.3. Bypass Mode
UPS transfers the loads automatically to the mains voltage in order to protect them during abnormal condi­tions.
While UPS operates in Online Operation, UPS switches to bypass automatically (in case the mains voltage and frequency is within the limits of bypass) in the following conditions;
• During start-up
• Bypass Priority
• Inverter Fault
• Prolonged Overload, output short circuit
• High Heatsink Temperature
After these conditions are eliminated, the UPS automatically returns to inverter.
Bypass Operation Voltage Range
The mains voltage is required to be in certain range for Bypass Operation. Voltage tolerance is set 18% of the output voltage in the factory. For instance; if the output voltage is Ph-Ph: 400V, the tolerance range of bypass voltage would be Ph-Ph: 328V – 472V. In case the input voltage decreases below Ph-Ph: 328V or in­creases above Ph-Ph: 472V; if UPS runs in Bypass Mode UPS switches to Online Mode Operation; if UPS runs in Online Mode Operation it cannot switch to Bypass Mode Operation even if a fault occurs. If the batteries and the inverter are suitable to supply the loads, UPS switches to Battery Mode Operation.
Bypass Mode Operation voltage tolerance limit can be adjusted in certain ranges depends on the cus­tomer’s request on site by Legrand UPS Technical Service Personnel.
To return to Bypass Mode Operation; the mains voltage should turn back to +5V above of lower limit, -5V down of upper limit of bypass limits. Default settings are Ph-Ph: 333V – 465V for Ph-Ph: 400V UPS.
Prolonged overloads in Bypass Operation may cause the thermal/magnetic pro­tection act. In this case, all loads will be de energized.
12
4.4. Eco Mode
Eco Mode Operation can be chosen through the Commands Menu.
The purpose of using this mode is to increase the eciency up to 98% and to provide energy saving; since the loads are supplied by the mains voltage directly, the loads are unprotected against any possible future risks. (e.g. surge voltage, etc.). In devices with auxiliary mains supply; energy is drawn from the auxiliary mains supply.
As long as the mains voltage and frequency within the limits, the load is supplied by the auxiliary voltage in a controlled manner; double conversion chain is on standby while ensuring the recharge of the batteries.
Eco Mode Operation does not provide perfect stability in frequency/waveform/rms value of the output voltage as in Online Operation. Thus, the use of this mode should be carefully executed according to the level of protection required by the application.
This procedure may only be executed by trained Personnel.
During Maintenance Bypass operation; in case of any mains voltage interruption occurs, all loads on the output will be deenergized. Maintenance Bypass Operation should not be preferred for long time use.
4.7. Operation with External Maintenance Bypass (Optional)
The external manual maintenance bypass may be installed in the general distribution panel where KEOR T EVO is installed, or in an external bypass panel that is supplied on request.
This operating mode enables the user to isolate the electronic circuitry of the UPS from the mains voltage and the load without interrupting the load operation by connecting the loads directly to the bypass utility supply. This feature is useful while performing maintenance or service and should only be executed by trained Personnel.
Maintenance Bypass enables the user to isolate the electronic circuitry of the UPS from the mains voltage and the load without interrupting the load operation by connecting the loads directly to the bypass utility supply. This feature is useful while waiting service sta and should only be executed by trained Personnel.
UPS switches to another mode in case the mains voltage or frequency goes beyond the Bypass limits. UPS returns to Eco Mode Operation when the auxiliary voltage returns to the limits.
Eco Mode Operation does not provide electronic short circuit current limitation. If a short circuit occurs downstream distribution panel supplied by the UPS, the magnetic protection o the Bypass line MCCB may act if not selective with downstream protection and all loads will be de energized. Check discrimination applies between upstream and downstream switchboard.
4.5. No Operation
This mode is used to make settings through Front Panel or by Service Software. To start-up UPS in No Operation mode; all the circuit breakers must be at “0” position except Q1 Input circuit breaker and Q4 Bypass circuit breaker. In this mode UPS does not apply output voltage to supply the loads. After all settings done during No Operation Mode, UPS should be restarted for the new service settings to be saved and valid. It is not necessary to restart UPS for user settings to be valid.
4.6. Operation with Maintenance Bypass
13
Installation & Operation Manual
5. Requirement
5.2. Placement
This product meets the safety requirements for devices to be operated in restricted access locations according to EN 60950-1 safety standard, which states that the owner should guarantee the following:
• Access to the equipment can only be gained by service persons or by users who have been instructed about the reasons for the restrictions applied to the location and about any precautions that shall be taken and,
• Access is through the use of a tool or lock and key, or other means of security and is controlled by the authority responsible for the location.
• UPS is not designed for outdoor application.
• The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat source.
• Recommended operating temperature and humidity values are listed on the Appendix-1 Technical Specications.
• Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
• The connection and the circuit breakers are at the front of UPS. Leave access at the front of the UPS for maintenance. (Refer to Figure.4.2-4)
• Air outlets of the UPS are at the front, back sides. Leave access at the front side, back side and from both lateral sides for battery replacement. (Refer to Figure.5.2-1, 5.2-2, 5.2-3 and 5.2-4)
• Recommended environmental humidity condition is between 20-95% (non-condensing).
The UPS must be placed and stand in a vertical position throughout the transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is recommended to keep the original package for future need.
All packing material must be recycled in compliance with the laws in force in the country where the system is installed.
5.1. Transportation
Environment Requirement
Model (kVA) 10 15 20
Max. dissipation at no load
(W) 144 150 204
(BTU) 491 511 696
Max. dissipation at full load
(W) 578 798 1053
(BTU) 1971 2722 3592
Storage temperatures -25/+55 °C (-13/131 °F) (15-25 °C for maximum battery life)
Working temperature 0/40 °C (32/104 °F) (15-25 °C for maximum battery life)
Maximum relative humidity 95% max. without condensation
Maximum altitude without derating 1.000 m (3.300 ft)
Degree of protection IP 20 (other IP as option)
Colour cabinet RAL 7016@enclosure RAL 9005@front door metal
Table.1
14
Figure.5.2-1
Figure.5.2-4
120 mm900 500 250
A (mm) B (mm) D (mm)C (mm)
Figure.5.2-2 Figure.5.2-3
Air conditioning
ROOM LAYOUT RECOMMENDATION TABLE (for UPS with Internal Battery)
Ventilation
Direction of ventilation is front/sides to back.
The room should be equipped with ventilation system or air conditioning to collect warm air
from the top of the room and provide cool air at the bottom.
15
Installation & Operation Manual
The UPS should be mounted on a concrete surface and non-combustible surface.
Ensure the stability of UPS without internal battery and take necessary precautions.
In order to prot from optimal ventilation, the side panels must remain in place for UPS with internal battery.
Optimal battery life time is reached when battery ambient temperature is kept between 15°C and 25°C. Operating battery at 30°C ambient temperature compared to 20°C will divide by factor 2 battery life time. Room thermal management as specied above is then necessary to avoid battery life time reduction. The Battery warranty does not apply if the temperature in the room exceeds 25°C.
When dual inputs is used:
• Separate Neutral conductor is necessary to be supplied for each input: Common Mains Input and Auxiliary Mains Input
• The two inputs should be supplied by the same MV/LV transformer source. If this is not the case, an insulation transformer should be added in the auxiliary mains line upstream the UPS.
• Separate protection is necessary for each input line.
5.3. Storage
Please store the UPS in an environment where the temperature is between -25
0
C + 550C, no receipt of direct sunlight, far from the heating, in a dry place. Environmental humidity must be between 20-95% (non-condensing). Recommended storage temperature, humidity and altitude values are listed on the Appendix-1 Technical Specications section.
If the batteries will be stored for longer than 6 months, they shall be charged periodically. Charge period depends on the storage temperature, as shown below:
• Every 9 months if the temperature is below 20°C,
• Every 6 months if the temperature is between 20°C and 30°C,
• Every 3 months if the temperature is between 30°C and 40°C,
• Every 2 months if the temperature is over 40°C
For long storage duration; please follow up the instructions of installation described in Section 5, start-up UPS described in Section 6 and charge the batteries at least 10 hours.
5.4. Electrical Requisites
The installation must comply with national installation regulations. The electrical distribution panels for common mains supply voltage and auxiliary mains supply voltage inputs must have a protection and disconnection system. Disconnection devices used in these panels shall disconnect all line conductors simultaneously. The following table shows the recommended size of common mains supply voltage and auxiliary mains supply voltage input protection devices (thermal, magnetic and dierential) and the cable cross-sections for the loads.
16
Installation Parameters
Model (kVA) 10 15 20
Phase in/out 3Ph+N+PE / 3Ph+N+PB
Rated output apparent power (kVA) 10 15 20
Rated output active power (kW) 9 13,5 18
Rated input current (A) at 400V nominal input voltage 14 21 28
Maximum input current (A) at 358V input voltage + full load + battery charging 18 26 36
Rated bypass current (A) at 400V nominal input voltage 15 22 29
Maximum bypass current (A) at 400V, 125% overload 10 min 19 28 36
Inverter output current @ 400V (A) 15 22 29
Maximum Inverter output current (A) at 400V, 125% overload 10 min 18 27 36
Overload tolerated by the inverter (with mains power present) (kW)
10 min
12,5 18,75 -
8 min - - 25
1 min 15 22.5 30
Recommended Protection Devices - Rectier/Mains Supply -*
D curve circuit breaker (A) (3 or 4-pole according neutral system) 20 25 32
GG fuse (A) 20 25 32
Recommended Protection Devices – General Bypass/Auxiliary Mains Supply –*
D curve circuit breaker (A) (3 or 4 pole according neutral system) 20 25 32
Maximum I2t supported by the bypass (A2s) (10ms) 6700 11200 15000
Icc max (A) 1200 1500 1700
Protection Devices – Battery Fast Fuse –
Ferrule style high speed fuses and with indicating striker (High Speed FWP Bussmann Fuse 22x58mm 690VAC (IEC)) (A)
63 63 63
Recommended Protection Devices – Output –
C curve circuit breaker (A) (3 or 4 pole according neutral system) ≤3 ≤4
B curve circuit breaker (A) (3 or 4 pole according neutral system) ≤6 ≤8
Maximum inverter short circuit current for 50 ms: IK1=IK2=IK3 =IF 2.1xIn
Min-Max. Cable Cross-Section for Terminals**
Rectier (mm²) 2.5 – 10 4 – 10 6 – 10
General Bypass (mm²) 2.5 – 10 4 – 10 6 – 10
Battery (+/-/N) (mm²) 2.5 – 10 4 – 10 6 – 10
Output (mm²) 2.5 – 10 4 – 10 6 – 10
Neutral (mm²) 4 – 10 6 – 10 10
Protective Earth/Bonding
Recommended cross section for ground wire at least half of the section of cable phases AND shall comply with the standards of the country (for example NFC 15100 in France).
Leakage Current Protection ***
Minimum 300 mA delayed (Type-B). When used, the residual current earth leakage protection system must be common for the two AC inputs (common & auxiliary mains) and installed upstream.
Table.2
17
Installation & Operation Manual
*Rectier protection alone should only be considered in the event of separate inputs; if the bypass and rectier inputs are combined, the general input protection rating (bypass + rectier) must reect the recommended bypass or general protection rating.
*Recommended discrimination of UPS downstream distribution with inverter short-circuits current (battery mode).
**Cables must be selected 1.2 times larger than the recommended size for parallel topologies.
***Must be selective with residual current circuit breakers downstream of the UPS connected to the UPS output. If the bypass network is separate from the rectier circuit, or in the event of parallel UPS, use a single residual current circuit breaker upstream of the UPS.
If the loads generates high rate of third harmonic current ( THDI > 33% ), the current on the common mains supply voltage and auxiliary mains supply voltage input and output neutral conductors may have a value that is 1.5-2 times the phase value during operation. In this case, size the neutral cables and the input/ output protection adequately.
18
6. Installation
When the UPS is delivered, examine the packaging and product carefully to see if any damage occured during transport. If either possible or ascertained damage is found report it immediately to:
• The carrier;
• LEGRAND Technical Assistance Center. Make sure that the unit received corresponds to the material specied on the delivery document. The UPS KEOR T EVO packaging protects the equipment against mechanical and environmental damages. For greater protection it is also wrapped in a transparent lm. Check if the following are provided with the equipment:
• Battery fuses (three pieces)
Before the installation, please check if your UPS is customized following your special requirements (if any).
6.1. Models and Dimensions
UPS Type Dimension (HxWxD) (mm) Net Weight (Kg) Internal Batteries Type
UPS KEOR-T EVO 10 KVA 1020H 0
102x26.5x80
78 NO Battery
UPS KEOR-T EVO 10 KVA 1020H 1 145 24x9Ah
UPS KEOR-T EVO 10 KVA 1020H 2 168 32x9Ah
UPS KEOR-T EVO 15 KVA 1020H 0 79 NO Battery
UPS KEOR-T EVO 15 KVA 1020H 1 163 30x9Ah
UPS KEOR-T EVO 15 KVA 1020H 2 180 36x9Ah
UPS KEOR-T EVO 20 KVA 1020H 0 84 NO Battery
UPS KEOR-T EVO 20 KVA 1020H 1 185 36x9Ah
Table.3
19
Installation & Operation Manual
Remove the wrap.
Remove the package. Place UPS in the installation area.
Figure.6.2-1
6.2. Unpacking Procedure
Figure.6.2-3
Figure.6.2-2
20
Figure.6.2-5
Remove the side parts which xes the carrier wooden
bar to the pallet. Unload the UPS from the pallet.
Fix the UPS to the ground as shown in the picture.
It is recommended to store the original UPS packaging for future needs.
The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical Service Sta or authorized LEGRAND distributor Technical Service Sta.
When the UPS is brought from a cold place to a warmer place, humidity of the air may condensate in it. In this case, wait minimum for 2 (two) hours before powering the UPS.
KEOR T EVO must be protected from voltage surge with devices that are suited to the installation; the mains voltage surge must be limited to 2kV. These protective devices must be sized to take into account all the installation parameters (geographical position whether or not there is a lightning rod, whether or not there are other suppressors in the electrical installation, etc )
Do not connect the output neutral to the protective ground or protective bonding
Power cables and communication cables shall be installed on trays according to the standards of the country.
6.3. Installation Procedures and Instructions
Figure.6.2-4
21
Installation & Operation Manual
Make sure that all circuit breakers are “OFF” before starting with the installation.
Figure.6.3.1-1
Figure.6.3.1-2
The power terminals are located on the lower rear side of the UPS. Firstly unscrew the metal cover, afterwards remove the cover of terminals. After the covers are removed, the cables shall be passed through the cable glands and attached under the terminals. After all connections done, replace the cover.
6.3.1. Power Connections of Single Systems
Rear view of KEOR T EVO UPS
Remove the cover of terminals.
22
Figure.6.3.1-3
Figure.6.3.1-4
Power Cables Path
Communication Cables Path
23
Installation & Operation Manual
Figure.6.3.1-5
Q1: Common Mains Supply Circuit Breaker Q2: Output Circuit Breaker Q3: Maintenance Bypass Circuit Breaker
Q4: Auxiliary Mains Supply Circuit Breaker F5: Battery Fast Fuse Q6: Inrush Circuit Breaker
KEOR T EVO 10-15-20kVA (3Ph Input – 3Ph Output) Circuit Breakers
24
X5 EXTERNAL BATTERY
X2 OUTPUT
PB
-
N
+
PE
X2/L1
X2/L2
X2/L3
X2/N
KEOR T EVO 10-15-20kVA (3Ph Input – 3Ph Output)
Connection if the MAINS and AUX Supply are connected in COMMON
Figure.6.3.1-6
X1 MAINS SUPPLY
X4 AUX SUPPLY
PE X1/L1 X1/L2 X1/L3 X1/N
X4/L1 X4/L2 X4/L3 X4/N
Loading...
+ 58 hidden pages