LEGRAND KEOR S 3KVA 1, KEOR S 3KVA 2, KEOR S 3KVA T1, KEOR S 6KVA 2, KEOR S 6KVA TX Installation Manual

...
LE08008AB
KEOR S 3-10 kVA
Operating & Installation Manual
2
ENGLISH 5-6
EN
KEOR S 3-10 kVA
3
Important Notices!
Thank you for choosing LEGRAND UPS System to supply your Critical Application.
This manual contains important information about commissioning, usage and technical properties of the UPS. It also contains safety information for operator and instructions to secure your critical load. Applying the recommendation detailed in this manual is necessary to use UPS safely and correctly.
Read the manual completely before working on this equipment!
Keep this manual near UPS for easy consultation!
Reproduction, adaptation, or translation of this manual is prohibited without prior written permission of LEGRAND Company, except as allowed under the copyright laws.
The manufacturer reserves the rights to change the technical specications and design without notice.
LEGRAND reserves the rights to change the information in this document without notice. Refer to http://ups.legrand.com/ web site to dowload last release and translations
Units that are labelled with a CE mark comply with the Standard: EN 62040-1 and EN 62040-2.
KEOR S 3-10 kVA
4
Description of the Symbols Used in the Manual
This symbol points out the instructions which are especially important.
This symbol points out the risk of electric shock if the following instruction is not followed.
This symbol points out the instructions, which may be resulted with the injury of the operator or damage of the equipment if not followed.
All packing material must be recycled in compliance with the laws in force in the country where the system is installed.
Description of the Abbreviations Used in the Guide
UPS: Uninterruptible Power Systems ESD: Emergency Switching Device RS232: Serial Communication Protocol RS485: Serial Communication Protocol MODBUS: Modicon Communication Protocol SNMP: Simple Network Management Protocol V: Volt A: Ampere P: Power
For Mains Supply, Auxiliary Mains Supply, Output, Battery Circuit Breaker and Maintenance Bypass Circuit Breaker;
“ON”: Closing the Circuit “OFF”: Opening the Circuit
5
KEOR S 3-10 kVA
Index
1 Foreword 7
1.1. Overview 7
1.2 Manual 7
2 Warranty 8
2.1. Terms of Warranty 8
2.2 Out of Warranty Terms and Conditions 8
3 Safety 9
3.1 Description of the Symbols Used on the Labels Applied to the UPS 9
3.2 Individual Protective Gear 9
3.3 Important Notice for UPS 10
3.4 Important Notice for Battery 11
3.5 Emergency interventions 11
4 Requirement 12
4.1 Transportation 12
4.2 Placement 12
4.3 Storage 13
4.4 Electrical Requisites 13
5 Installation 14
5.1 Models and Dimensions 14
5.2 Unpacking Procedure 15
5.3 Installation Procedures and Instructions for Single Systems 16
5.4. Installation Procedures and Instructions for Parallel Systems (for 6-10kVA) 23
5.4.1. Important Safety Instructions 23
5.4.2. Parallel System Accessories and Installation Position 23
5.4.3. Installation Instruction 25
5.4.4. Parallel Setting 26
5.4.5. Start-up Operation Procedure 26
6 Communication 32
6.1. Serial Communication (RS232) 32
6.2. SNMP/WEB Card 33
6
7 Operation Modes 34
7.1. Online Mode (norl) 35
7.2. Eco Mode (Eco) 35
7.3. Bypass Mode 36
7.4. Battery Mode 37
7.5. Frequency Converter Operation (cF50 – cF60) 37
7.6. Maintenance Bypass Mode (for 6-10kVA) 38
8 Front Panel & Rear Panel 39
8.1. Front Panel Segments 39
8.1.1. Keypad 39
8.1.2. Liquid Crystal Display (LCD) 41
8.2. Rear Panel 44
9. Operating Procedures 46
9.1. UPS Default Data and Special Function Execution 46
9.2. UPS Default Settings and Their Alternatives 49
9.3 Commissioning 51
9.3.1. Start-Up with the Mains 51
9.3.2. Start-Up with the Battery (Cold Start) 53
9.4. Decommissioning 54
9.5. Maintenance Bypass Commissioning and Decommissioning Instructions (6-10kVA) 54
9.6. Emergency Switching Device (ESD) 55
10 Preventive Maintenance 56
10.1. Batterie 56
10.2. Fan 56
10.3. Capacitors 56
11 Troubleshooting 60
Appendix-1: Error List 60 Appendix-2: Status & Alarm Buzzer 61 Appendix-3: Technical Specications 62 Appendix-4: Description of UPS and Block Diagram 63
7
KEOR S 3-10 kVA
1. Foreword
1.1. Overview
Thank you for choosing LEGRAND UPS Keor S product.
KEOR S has been designed with advanced technologies and the latest compo¬nents generation; realized to satisfy both users and instal¬lers in their operational needs of high availability and perfor¬mance.
This UPS aims to be ecient, functional, safe and very easy to install and use. LEGRAND has studied the best way to reconcile high-tech performance and ease of use, making “user friendly” technologi¬cally advanced products.
This product is manufactured in an ISO 9001 & ISO14001 certied factory in full compliance with the eco-design laws. The UPS Keor S system is made in compliance with the existing European Community directives and with the technical standards in force to comply with CE marking as certied by the Declaration of Conformity issued by the Manufacturer.
1.2. Manual
• The purpose of this manual is to provide indications for using the equipment safely and to carry out rst level of
troubleshooting.
• This manual is addressed to persons already educated on precautions to adopt in face of electrical hazard
• This manual is addressed to “User“, generic term to identify all persons that will have the need and / or obligation
to provide instructions or operate directly this UPS equipment.
• Adjustments, preventive and curative maintenance jobs are not dealt with in this manual as they are reserved
exclusively to skilled and authorized Legrand UPS Technical Service Engineers.
• The intended use and congurations envisaged for the equipment are the only ones allowed by the Manufacturer;
do not attempt to use the equipment in disagreement with the indications given. Any other use or conguration must be agreed and written by the Manufacturer, in such a case, will be an enclosure to the manual.
• For its use the user must also comply with the specic laws in force that exist in the country where the equipment
is installed. Reference is also made in this manual to laws, directives, etc., that the user must know and consult in order to full the purposes established by the manual.
• If information is exchanged with the Manufacturer or assistance personnel authorized by the former, please refer
to the equipment’s rating plate data and serial number.
• The manual must be kept for the equipment’s useful life cycle and, if necessary (e.g. damage which prevents it
being consulted even partially) the user must ask the Manufacturer for a new copy, quoting the publishing code on the cover.
• The manual reects the state of the art at the moment the equipment was put on the market, of which it is an
integral part. The publication complies with the directives in force at such a date. The manual cannot be considered inadequate if updates of standards or changes are made to the equipment.
• Any integration to the manual which the Manufacturer deems tting to send to the users must be kept with the
manual, becoming an integral part of it.
• The Manufacturer is available to its clientele to provide additional information and will take into consideration
any suggestions made to improve this manual to bring it even closer to the requirements for which it was drawn up.
• If the equipment is sold, which always includes handing over this operating manual, the primary user must
notify the Manufacturer, giving him the address of the new user so the latter can be reached if there are any communications and/or updates deemed indispensable.
8
2. Warranty
2.1. Terms of Warranty
• Warranty period begins from the date of commissioning of the UPS by authorized LEGRAND UPS Technical
Service sta or authorized LEGRAND distributor Technical Service Sta.
• The UPS including all the internal parts is under the warranty of LEGRAND.
• If the UPS malfunctions because of component, manufacturing or installation (if it’s done by authorized
LEGRAND UPS Technical Service Personnel) problems during the warranty period, the UPS will be repaired (spares and labour) by the Manufacturer under warranty.
2.2. Out of Warranty Terms and Conditions
This Warranty does not apply if:
• UPS not commissioned or maintained by an authorized LEGRAND UPS Technical Service sta or an authorized
LEGRAND distributor Technical Service sta.
• UPS not used according the terms of operating and installation manual
• Product serial number label has been removed or lost
This Warranty does not cover any defects or damages caused by:
• Neglect, accident, misuse, misapplication
• Failure due to fortuitous circumstances or force majeure (lightning, oods…etc.),
• Unloading and transportation damage and failures after delivery,
• Damage or injuries caused by negligence, lack of inspection or maintenance, or improper use of the products,
• Faulty electrical wiring,
• Defects arising either from designs or parts imposed or supplied by the purchaser,
• Defects and damage by re and lightning,
• Failures due to modication in the products without LEGRAND approval,
• Improper installation, testing, operation, maintenance, repair, alteration, adjustment, or modication of any kind
by unauthorized personnel,
The Manufacturer will repair the device in such cases for a fee and is not responsible for the shipment of the equipment.
The Battery warranty does not apply if the temperature in the room exceeds 25 °C.
Extended battery warranty does not apply if:
• UPS has not been commissioned
• A yearly preventive maintenance visit has not been performed
By an authorized LEGRAND UPS Technical Service sta or authorized LEGRAND distributor Technical Service sta.
The UPS may contain batteries that should be recharged 24Hours min after 6 month storage duration to avoid deep battery discharge. Warranty cannot apply on batteries that have suered of deep discharge.
9
KEOR S 3-10 kVA
Information related to safety of the UPS, battery, load and the user is summarized below. But the equipment should not be installed before reading the manual completely.
3.2. Individual Protective Gear
There is a high risk of electrical shock with the equipment as well as a considerable short circuit current. When installing and servicing the equipment it is absolutely forbidden to work without the protective gear mentioned in this paragraph.
The personnel who are going to work with the equipment for installation or maintenance jobs must not wear clothes with baggy sleeves or laces, belts, bracelets or other metal items that could be a hazard source.
This symbol points out the instructions, which may result with injury of the operator or damage of the equipment if not obeyed.
PE: Protective Earth
PB: Protective Bonding
Danger! High Voltage (Black/Yellow)
3.1. Description of the Symbols Used on the Labels Applied to the UPS
3. Safety
10
3.3. Important Notice for UPS
• The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical Service Personnel.
• This manual contains important instructions that you should follow during installation and maintenance of the
UPS and batteries. Please read all instructions before installing the equipment and save this manual for future reference.
• Not obeying the instructions written on this manual which may result with possible injury of the operator or
damage of the equipment.
• The equipment shall be packed properly during transportation and proper equipment should be used for
transportation. Never transport in horizontal position.
• The UPS must always stands in a vertical position. Make sure that the oor can support the weight of the system.
• Connect the PE ground connector before connecting any other cable.
• Because of “LITTLE LEAKAGE CURRENTS” generated by EMI Filter of the UPS, it is necessary to double ensure if the
earth of the UPS is properly grounded before AC mains is connected with.
• UPS is designed for indoor use. To reduce the risk of re or electric shock, install this UPS in a temperature and
humidity controlled indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum without condensation).
• UPS requires 1Ph-N+PE input connection.
• Neutral system: refer to Section 5.3.1.5 Output Connection.
• Even when connections removed, residual voltages of capacitors and/or high temperature may exist on
connection terminals and inside the UPS. Before working on terminals, check between all the terminals included PE that no hazardous voltages exist.
• The connections shall be made with cables of appropriate cross-section in order to prevent the risk of re. All
cables shall be of insulated type and shall not be laid out on the walking path of the persons.
• According to IEC 62040-2; this is a category C2 UPS product. In a residential environment, this product may cause
radio interference, in which case the user may be required to take additional measures.
• Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or
UPS.
• Make sure that the UPS is not overloaded to provide a higher quality supply to the loads.
• In case of an extraordinary situation (damaged body, cabinet or connections, penetration of foreign materials
into the body or cabinet etc.) de-energize the UPS immediately and consult to the LEGRAND Technical Assistance Center.
• When used for particular applications such as life support systems or any other application where product failure
is likely to cause substantial harms to person, we would advise you to contact LEGRAND UPS to conrm the ability of these products to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and specications.
The following indications summarize the protective gear to wear.
Accident and spark proof footwear with rubber sole and reinforced toe
Use : always
Waterproof rubber gloves
Use : always
Protective gear
Use : always
Protective glasses
Use : always
11
KEOR S 3-10 kVA
3.4. Important Notice for Battery
• The batteries may only be installed and commissioned by authorized LEGRAND UPS Technical
Service Personnel.
• Make sure that the battery qty is proper for the unit and they are same type and capacity. Otherwise
danger of explosion and re is within the bounds of possibility.
• Do not dispose of batteries in a re. The batteries may explode.
• Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
• In case of electrolyte in contact with skin, immediately wash the contaminated skin with water.
• Replaced batteries must be disposed of at authorized battery waste disposal centers.
• A battery can present risk of electric shock and high short circuit currents.
The following precautions should be observed when working on batteries;
• Remove rings, watches, necklaces, bracelets and all metal objects.
• Only use tools with insulated handles.
• Wear rubbers gloves and a rubber apron when handling batteries.
• Do not lay tools or metal parts on top of batteries.
• Eye protection should be worn to prevent injury from accidental electrical arcs.
• Before a maintenance or repair work on the UPS;
• Switch the input and output circuit breakers (Q1 and Q2) to “OFF” position.
• Switch battery circuit breakers (Q3) to “OFF” position.
• If UPS has external batteries; switch the circuit breakers (F5) of the battery cabinet(s) to “OFF” position.
• Determine if the battery is inadvertently grounded. If inadvertently grounded; remove source of ground.
Contact with any part of a grounded battery can result in electrical shock.
3.5. Emergency interventions
The following information is of a general nature. For specic interventions please consult the laws existing in the country where the equipment is installed.
First aid interventions
If any rst aid intervention is required, comply with company rules and traditional procedures.
Fire-prevention measures
Never use water to extinguish re but only the extinguishers designed specically for electronic equipment or battery res.
12
4.2. Placement
• UPS is not designed for outdoor application.
• The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat source.
• Recommended operating temperature and humidity values are listed on the Appendix-3 Technical
Specications section. To provide the required environmental condition.
• Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
• The connection and the circuit breakers are at the back side of UPS. Leave at least 30 cm at the back side
of the UPS for maintenance.
• Air outlets of the UPS are present on the front and back sides. Leave at least 30 cm at the front and back
side of the UPS for ventilation.
• To eliminate any overheating of the UPS, keep all ventilation openings free from obstruction, and do not
store “things” on top of the UPS.
• Even though the operating temperature of the UPS and batteries are between 0-40 °C, It is suggested to
provide an environment temperature between 20-25°C to get maximum performance from the UPS and batteries.
• Advised environmental humidity condition is between 30%~90% (non-condensing).
The UPS must be placed and stand in a vertical position throughout the transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is recommended to keep the original package for future need.
Optimal battery life time is reached when battery ambient temperature is kept between 15°C and 25°C. Operating battery at 30°C ambient temperature compared to 20°C will divide by factor 2 battery life time. Room thermal management as specied above is then necessary to avoid battery life time reduction. The Battery warranty does not apply if the temperature in the room exceeds 25°C.
All packing material must be recycled in compliance with the laws in force in the country where the system is installed.
4.1. Transportation
4. Requirement
13
KEOR S 3-10 kVA
4.3. Storage
Please store the UPS in an environment where the temperature is between -25
0
C + 550C, no receipt of direct
sunlight, far from the heating, in a dry place. Environmental humidity must be between 20-95% (non-condensing). Recommended storage temperature, humidity and altitude values are listed on the Appendix-3 Technical
Specications section. If the batteries will be stored for longer than 6 months, they shall be charged periodically. Charge period
depends on the storage temperature, as shown below:
• Every 9 months if the temperature is below 20°C,
• Every 6 months if the temperature is between 20°C and 30°C,
• Every 3 months if the temperature is between 30°C and 40°C,
• Every 2 months if the temperature is over 40°C
For long storage duration; please follow up the instructions of installation described in Section 5, start-up UPS described in Section 9 and charge the batteries at least 10 hours.
4.4. Electrical Requisites
The installation must comply with national installation regulations. The following table shows the recommended size of circuit breakers used in distribution panel and input/
output cables for the linear loads.
The UPS should be mounted on a concrete surface and non-combustible surface.
Figure.4.2-1 Figure.4.2-2
PLACEMENT: Please leave 30cm distance (12inch) from the back side of UPS for ventilation
and humidity should be between 30-90% (non-condensing)
Power
Max.
Current
Input
Circuit
Breaker
Output
Circuit
Breaker
Battery
Max.
Current
Cable Cross Section
Input Output Battery Neutral Pe & Pb
3 K VA 17 A 20 A 20 A 11 A 2.5 mm² 2.5 mm² 2.5 mm² 2.5 mm² 4 mm²
6 K VA 33 A 32 A 32 A 25 A 6 mm² 6 mm² 6 mm² 6 mm² 6 mm²
10 KVA 54,3 A 63 A 50 A 41 A 10 mm² 10 mm² 6 mm² 10 mm² 10 mm²
Table 1
14
Before the installation, please check if your UPS is customized following your special requirements (if any).
5.1. Models and Dimensions
When the UPS is delivered, examine the packaging and product carefully to see if any damage occurred during transport.
If either possible or ascertained damage is found report it immediately to:
• the carrier;
• LEGRAND Technical Assistance Center
Make sure that the unit received corresponds to the material specied on the delivery document. The UPS Keor S packaging protects the equipment against mechanical and environmental damages. For greater protection it is also wrapped in a transparent lm.
Check if the following are provided with UPS
• Loading Ramp
• RS232 Cable
• 2xRJ45 Cable for Paralleling (for 6-10kVA)
5. Installation
Models
Dimension
(HxWxD) (mm)
Weight
(kg)
Internal Transformer Internal Batteries Type
UPS KEOR S 3KVA 1
716*275*776
53 No 6 blocks 12 AH
UPS KEOR S 3KVA 2 75 No 12 blocks 12 AH
UPS KEOR S 3KVA 3 97 No 18 blocks 12 AH
UPS KEOR S 3KVA T1 85 Yes 6 blocks 12 AH
UPS KEOR S 6KVA 2 106 No 20 blocks 12 AH
UPS KEOR S 6KVA TX 100 Yes No Battery
UPS KEOR S 10KVA 1 114 No 20 blocks 12 AH
UPS KEOR S 10KVA TX 126 Yes No Battery
Table 2
15
KEOR S 3-10 kVA
5.2. Unpacking Procedure
Figure.5.2-1
Figure.5.2-3
Figure.5.2-5
Figure.5.2-2
Figure.5.2-4
Figure.5.2-6
Remove the wrap and the package.
Screw o the stop plates placed at the front and back of UPS. Remove the stop plate
Unload the UPS via wheels over the ramp. Place UPS in the installation area.
16
It is recommended to store the original UPS packaging for future needs.
The equipment may only be installed and commissioned by authorized LEGRAND UPS Technical Service Sta or authorized LEGRAND distributor Technical Service Sta.
When the UPS is brought from a cold place to a warmer place, humidity of the air may condensate in it. In this case, wait minimum for 2 (two) hours before powering the UPS.
KEOR S must be protected from voltage surge with devices that are suited to the installation; the mains voltage surge must be limited to 2kV. These protective devices must be sized to take into account all the installation parameters (geographical position whether or not there is a lightning rod, whether or not there are other suppressors in the electrical installation, etc )
Make sure that all circuit breakers are “OFF” before starting with the installation.
5.3.1. Power Connections
Power cables and communication cables shall be installed on trays according to the standards of the country.
Connection terminals are in the rear side of the UPS. Please take out the terminal cover to make the connections. Standard UPS circuit breakers and terminal settlements are shown below;
5.3. Installation Procedures and Instructions for Single Systems
17
KEOR S 3-10 kVA
Figure.5.3.1-2
Figure.5.3.1-1
1 Battery Circuit Breaker 2 Terminal Cover 3 Cable Glands 4 Input Circuit Breaker 5 Output Circuit Breaker 6 Terminals 7 Cable Fixing Tools
1 Battery Circuit Breaker 2 Terminal Cover 3 Battery Cable Gland 4 Input Cable Gland 5 Output Cable Gland 6 Input Circuit Breaker 7 Manual Bypass Circuit Breaker 8 Output Circuit Breaker 9 Terminals 10 Cable Fixing Tools
Keor S 3kVA
Keor S 6-10kVA
Terminals and Circuit Breakers of UPS
18
Pass the cables through the glands
Power Connection of Charger and Batt
Figure.5.3.1-3
1 Battery Cable 2 Input Cable 3 Output Cable
Figure.5.3.1-4
19
KEOR S 3-10 kVA
Figure.5.3.1-5
Power Connection of Charger and Batt
Connections shall be made in the following order;
The device shall be earthed for a safe and reliable operation. Connect the PE/PB ground terminals before connecting any other cable.
Recommended ground wire cross section should be at least half of the section of cable phases AND should comply with the standards of the country (for example NFC 15100 in France).
PE cable should be min. 10cm longer than the other cables.
Input protective earth connection terminal “PE” of the UPS shall be connected to ground with a low impedance connection.
The load shall be grounded via output protective earth terminal “PB”. If there is an external battery cabinet present, it shall be grounded via battery protective earth terminal
“PB” of the UPS.
5.3.1.1. Earth Connection
20
The installation and adjustment of distribution panel should be done by specialized technician.
The installation and adjustment of distribution panel should be done by specialized technician.
Please add double-pole miniature circuit breaker (equivalent UPS input breaker) to distribution board where UPS is to be connected. Do not connect any other load to this circuit breaker and please do not forget to add leakage current relay.
Connect the phase cable to input “L” terminal, the neutral to input “N” terminal.
According to EN 62040-1, the user should place a warning label on the input distribution panel and the other primary power isolators, in order to prevent the risk of voltage backfeed.
This label is sent with the Installation Manual. It indicates:
RISK OF VOLTAGE BACKFEED
• Isolate Uninterruptable Power Supply before working on this circuit.
• Then check for Hazardous Voltage between all terminals including the protective earth (PE).
5.3.1.2. Input Connection