LEGRAND Keor MOD 25, Keor MOD 100, Keor MOD 150, Keor MOD 125, Keor MOD 175 Installation And Maintenance Manual

...
Page 1
Keor MOD
Installation and maintenance manual
Part. LE11406AB-04/19-01 GF
Page 2
Keor MOD
ENGLISH 3
EN
2
Page 3
Table of Contents
1 Introduction 5
1.1 Purpose of the manual 5
1.2 Symbols in the manual 5
1.3 Where and how to keep the manual 5
1.4 Update of the manual 6
1.5 Manufacturer’s liability and guarantee 6
1.5.1 Guarantee terms 6
1.5.2 Extension of the guarantee and maintenance contracts 7
1.6 Copyright 7
2. Regulatory and safety requirements 8
2.1 General notes 8
2.2 Denitions of “Skilled Technician” and “Operator” 8
2.2.1 Skilled Technician 8
2.2.2 Operator 8
2.3 Personal Protective Equipment 8
2.4 Hazard signs in the workplace 9
2.5 Signs on the equipment 9
2.6 General warnings 10
2.7 How to proceed in an emergency 11
2.7.1 First-aid procedures 11
2.7.2 Fire procedures 11
Installation and maintenance manual
3. Transportation and placement 12
3.1 Visual check 12
3.2 Equipment check 12
3.3 Transportation 13
3.4 Unpacking 14
3.5 Placement 15
4. Installation 17
4.1 Safety regulations 17
4.2 Electrical connections 17
4.2.1 Protective devices 18
4.2.2 Disassembly of the distribution panel 18
4.2.3 Earthing connection 23
4.2.4 Cable fastening 25
4.2.5 Backfeed protection 34
4.2.6 Input cables installation 35
4.2.7 Bypass cables installation 41
4.2.8 Output cables installation 45
4.2.9 Battery cables installation 49
4.3 Power modules installation 58
4.4 Battery drawers installation 60
4.5 SSS interface 66
4.5.1 Emergency Power O (EPO) 67
3
Page 4
Table of Contents
5. Configuration and start-up 68
5.1 Pre-start-up checks 68
5.2 Start-up procedure 68
5.3 Switching o the UPS 70
6. Maintenance 71
6.1 Preventive maintenance 71
6.2 Periodical checks 71
6.3 Ordinary maintenance 72
6.3.1 Hot-swap procedure for the replacement of power modules 72
6.3.2 Installation/replacement of power modules with the UPS in maintenance bypass mode 76
6.3.2.1 Setting the UPS in maintenance bypass mode 76
6.3.2.2 Installation/replacement of power modules 76
6.3.2.3 Exit the UPS from the maintenance bypass mode 78
6.3.3 Removal of the SSS drawer 79
6.4 Battery drawers replacement 80
6.4.1 Installation/replacement of battery drawers with UPS in on-line mode 80
6.4.2 Installation/replacement of battery drawers with UPS in maintenance manual bypass 81
6.5 Replacing the fuses and surge arrester (DIN rail) 82
6.6 Extraordinary maintenance 83
7. Warehousing 84
7.1 UPS 84
7.2 Batteries 84
8. Dismantling 85
8.1 Battery disposal 85
8.2 UPS dismantling 85
8.3 Electronic component dismantling 85
9. Mechanical characteristics 86
9.1 Cabinets 86
9.2 Power module PM25 91
9.3 Battery drawer 92
9.4 Battery block 93
10. Technical data 94
11. Tables 98
4
Page 5
1. Introduction
INDICATION
The instructions in this manual are intended for a SKILLED TECHNICIAN (paragraph 2.2.1)
1.1 Purpose of the manual
The purpose of this manual is to provide the skilled technician (see paragraph 2.2.1) with instructions for safely installing the Keor MOD UPS, also called “equipment” in the rest of the manual and carry out ordinary maintenance procedures.
Extraordinary maintenance operations are not dealt with because they are the sole preserve of the LEGRAND Technical Support Service.
The reading of this manual is essential but does not substitute the skill of technical personnel who must have received adequate preliminary training.
The intended use and configurations envisaged for the equipment as shown in this manual are the only ones allowed by the Manufacturer. Any other use or configuration must be previously agreed with the Manufacturer in writing and, in this case, the written agreement will be attached to the installation and user manuals.
This manual also refers to laws, directives and standards that the skilled technician is required to be aware of and consult.
The original text of this publication, drafted in English, is the only reference for the resolution of disputes of interpretation linked to translations into other languages.
1.2 Symbols in the manual
Some operations are shown in graphic symbols that draw the attention of the reader to the danger or the importance they imply:
DANGER
This indication shows a danger entailing a high degree of risk that, if not avoided, will lead to death or serious injury or considerable damage to the equipment and things around it.
Installation and maintenance manual
WARNING
This indication shows a danger entailing a medium degree of risk that, if not avoided, could lead to death or serious injury or considerable damage to the equipment and the things around it.
CAUTION
This indication shows a danger entailing a low level of risk that, if not avoided, could lead to minor or moderate injury or material damage to the equipment and the things around it.
INDICATION
This symbol indicates important information which should be read carefully.
1.3 Where and how to keep the manual
This manual must be kept in a safe, dry place and must always be available for consultation exclusively by the skilled technician. It is recommended to make a copy of it and file it away. If information is exchanged with the Manufacturer or the authorized assistance personnel, it is essential to refer to the equipment’s rating plate data and serial number.
INDICATION
The manuals provided with the equipment are an integral part of it and must therefore be kept for its entire lifetime. In case of need (for example in case of damage that even partially compromises its consultation) the skilled technician is required to get a new copy from the Manufacturer, quoting the publication code on the cover.
5
Page 6
1. Introduction
1.4 Update of the manual
The manual reflects the state of the art when the equipment was put onto the market. The publication conforms to the directives current on that date. The manual cannot be considered inadequate when new standards come into force or modifications are made to the equipment.
Any addition to the manual the Manufacturer considers appropriate to send to the users, must be kept together with the manual of which they will become an integral part. The version of the manual updated to its latest release is available on the Internet at http://www.ups.legrand.com
1.5 Manufacturer’s liability and guarantee
The skilled technician and the operator shall scrupulously comply with the precautions and installation instructions indi­cated in the manuals. They must:
- always work within the operating limits of the equipment;
- always carry out constant and careful maintenance through a skilled technician who complies with all the procedures indicated in the installation and maintenance manual.
The Manufacturer declines all indirect or direct responsibility arising from:
- assembly and cabling made by personnel not qualified and authorized by LEGRAND and not fully qualified according to national standards to work on equipment presenting electrical hazards;
- assembly and cabling made without using safety equipment and tools required by national safety standards;
- failure to observe the installation and maintenance instructions and use of the equipment which differs from the spec­ifications in the manuals;
- use by personnel who have not read and thoroughly understood the content of the user manual;
- use that does not comply with the specific standards used in the country where the equipment is installed;
- modifications made to the equipment, software, functioning logic unless they have been authorized by the Manufac­turer in writing;
- repairs that have not been authorized by the LEGRAND Technical Support Service;
- damage caused intentionally, through negligence, by acts of God, natural phenomena, fire or liquid infiltration;
- damage caused by the use of batteries and protections not specified in the manuals;
- damage caused by improper unloading and transportation after delivery of the equipment;
- accidents caused by a wrong assembly of the safety protections or due to the lack of application of the safety labels specified in the installation manual.
The transfer of the equipment to others also requires to hand over all the manuals. Failure to do it will automatically nullify any right of the buyer, including the terms of the guarantee where applicable. If the equipment is sold to a third party in a country where a different language is spoken, the original owner shall be respon­sible for providing a faithful translation of this manual in the language of the country where the equipment will be used.
1.5.1 Guarantee terms
The guarantee terms may vary depending on the country where the UPS is sold. Check the validity and duration with LEGRAND’s local sale representative.
If there should be a fault in the product, contact the LEGRAND Technical Support Service which will provide all the in­structions on what to do. Do not send anything back without LEGRAND’s prior authorization.
The guarantee becomes void if the UPS has not been brought into service by a properly trained skilled technician quali­fied and authorized by LEGRAND (see paragraph 2.2.1).
If during the guarantee period the UPS does not conform to the characteristics and performance laid down in this manu­al, LEGRAND at its discretion will repair or replace the UPS and relative parts. All the repaired or replaced parts will remain LEGRAND’s property.
LEGRAND is not responsible for costs such as:
- losses of profits or earnings;
- losses of equipment, data or software;
- claims by third parties;
- any damage to persons or things due to improper use, unauthorized technical alterations or modifications;
- any damage to persons or things due to installations where the full compliance with the standard regulating the specific usage applications have not been guaranteed.
6
Page 7
1.5.2 Extension of the guarantee and maintenance contracts
The standard guarantee can be consolidated in a single extension contract (maintenance contract). Once the guarantee period has passed, LEGRAND is available for giving a technical assistance service able to meet all requirements, maintenance agreements, 24/7 availability and monitoring. Please, contact the LEGRAND Technical Support Service for further information.
1.6 Copyright
The information contained in this manual cannot be disclosed to any third party. Any partial or total duplication of the manual by photocopying or other systems, including electronic scanning, which is not authorized in writing by the Man­ufacturer, violates copyright conditions and may lead to prosecution. LEGRAND reserves the copyright of this publication and prohibits its reproduction wholly or in part without previous written authorization.
Installation and maintenance manual
7
Page 8
2. Regulatory and safety requirements
DANGER Before carrying out any operation on the equipment, it is necessary to read the entire manual carefully, especially this chapter. Look after this manual carefully and consult it repeatedly during installation and maintenance by a skilled tech­nician.
2.1 General notes
The equipment has been made for the applications given in the manual. It may not be used for purposes other than those for which it has been designed, or differently from those specified in this manual. The various operations must be carried out according to the criteria and the chronology described in this manual.
2.2 Definitions of “Skilled Technician” and “Operator”
2.2.1 Skilled Technician
The figure that will carry out the installation, start up and ordinary maintenance is called “Skilled Technician”. This definition refers to people qualified by LEGRAND who have the specific technical qualification and are aware of the method of installing, assembling, repairing, bringing online and using the equipment safely. In addition to the requirements listed in the section below for a general operator, the Skilled Technician is qualified according to national safety standards to work under dangerous electrical voltage and uses the personal protective equipment required by national safety standards for all the operations indicated in this manual (see the examples listed in paragraph 2.3).
INDICATION
The safety manager is responsible for protection and company risks prevention according to what is indicated in Europe­an directives 2007/30/EC and 89/391/EEC regarding safety in the workplace. The safety manager must ensure that all the people working on the equipment have received all the instructions concern­ing them in the manual, especially those contained in this chapter.
2.2.2 Operator
The figure assigned to the equipment for normal use is called “Operator”. This definition refers to people who know how to operate the equipment defined in the user manual and have the fol­lowing requisites:
1. technical education, which enables them to operate according to safety standards in relation to the dangers linked to
the presence of electric current;
2. training on the use of personal protective equipment and basic first aid interventions.
The company safety manager, in choosing the person (operator) who uses the equipment, must consider
- the person’s work fitness according to the laws in force;
- the physical aspect (not disabled in any way);
- the psychological aspect (mental stability, sense of responsibility);
- the educational background, training and experience;
- the knowledge of the standards, regulations and measures for accident prevention. He shall also provide training in such a way as to provide thorough knowledge of the equipment and its component parts.
Some typical activities the operator is expected to carry out are:
- the use of the equipment in its normal functioning state and the restore of the functioning after it shuts down;
- the adoption of the necessary provisions for maintaining the quality performance of the UPS;
- the cleaning of the equipment;
- cooperation with personnel responsible for ordinary maintenance activities (Skilled Technicians).
2.3 Personal Protective Equipment
DANGER
The UPS poses a considerable risk of electric shocks and a high short circuit current. During installation, use and mainte­nance operations, the equipment mentioned in this section must be used.
People responsible for operating this equipment and/or passing close to it must not wear garments with flowing sleeves, nor may laces, belts, bracelets or other metal pieces that might cause a danger.
8
Page 9
The following list sum up the minimum Personal Protective Equipment to wear always. Additional requirements may be needed according to national safety standards.
Anti-accident and non-sparking shoes with rubber sole and reinforced toe
Protective gloves for handling operations
Isolated rubber gloves for operations of connection and work under hazardous voltage
Protective garments for electrical work
Protective face and head shield
Isolated tools
INDICATION
The skilled technician must work on electrical insulated carpet and he must not wear any kind of metal objects like watch­es, bracelets, etc.
2.4 Hazard signs in the workplace
The following signs must be exhibited at all points of access to the room where the equipment is installed:
Installation and maintenance manual
Electric current
This sign indicates the electrical live parts.
How to proceed in an emergency Do not use water to quench fires but just the extinguishers specially designed for putting out fires in electrical
equipment.
No smoking This sign indicates that smoking is not allowed.
2.5 Signs on the equipment
Displayed on the UPS are explanatory plates that can vary depending on the country the equipment is intended for and constructional standards applied. Make sure the instructions are adhered to. Removing these plates and working in a way that differs from what written there, is strictly prohibited. The plates must always be clearly read and they must be cleaned periodically. If a plate deteriorates and/or it is no longer legible, even partially, the Manufacturer must be contacted for another one.
CAUTION
The plates must not be removed or covered. Signs in different languages are provided along with the equipment to replace those in English. No other plates may be affixed to the equipment without the Manufacturer’s prior written au­thorisation
9
Page 10
2. Regulatory and safety requirements
WARNING
Potential risks can be drastically reduced by wearing the Personal Protective Equipment listed in this chapter, which are indispensable. Always operate with due care around dangerous areas marked by the appropriate warning notices on the equipment.
2.6 General warnings
DANGER
The UPS works with dangerous voltages. Only skilled technicians qualified and authorized by LEGRAND must perform the installation and ordinary maintenance operations. No part of the UPS can be repaired by the operator. Extraordinary maintenance operations must be carried out by LEGRAND Technical Support Service personnel.
DANGER
Before beginning any installation and/or maintenance operation, make sure that all the DC and AC power sources are disconnected. The UPS and the external battery cabinet, if present, must be installed with an earth connection to avoid high leakage currents. First connect the earthing cable. Check during each installation and/or maintenance operation the continuity of the earthing system.
DANGER
The UPS is powered by its own DC energy source (batteries). The output terminals may have a dangerous voltage even if the UPS is not connected to the AC power network. Disconnect all battery drawers and external battery cabinets before performing any installation and/or maintenance operation.
WARNING A battery can present a risk of electrical shock and burns by high short-circuit circuit current. Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces. The following precautions should be observed when working on batteries: a) remove watches, rings or other metal objects. b) use tools with insulated handles. c) wear rubber gloves and boots. d) do not lay tools or metal parts on top of batteries. e) disconnect the charging source prior to connecting or disconnecting battery terminals. f) determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced
if such grounds are removed during installation and maintenance (applicable to equipment and remote battery sup-
plies not having a grounded supply circuit). g) never leave live cable terminals without an insulated protection. h) When replacing batteries, replace with the same type and number of batteries or battery packs. There is the risk of
explosion if batteries are replaced by an incorrect type.
Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic. The batteries installed inside the cabinet must be disposed of correctly. For the disposal requirements refer to local laws and relevant standards.
INDICATION
The UPS functions with TT, IT, TN-C and TN-S systems. Input and output neutral are referenced to the same neutral poten­tial: the output neutral status is the same as the input neutral status. When the output load needs a different neutral status, it is necessary to place downstream of the UPS a suitably scaled isolation transformer that must be protected in compliance with the standards in force.
10
CAUTION
Do not open the battery fuse holders while the UPS is powering the loads in battery mode.
Page 11
WARNING
To reduce the risk of fire or electric shock, the UPS must work in closed, clean environments with controlled temperature and humidity. It must be kept away from inflammable liquids and corrosive substances. The room temperature must not be above +40°C (+104°F) and the relative humidity must be a maximum of 95% not condensing.
WARNING
Keor MOD is a category C3 UPS according to the standard EN62040-2. The UPS is a product for commercial and industrial application in the second environment – installation restrictions or additional measures may be needed to prevent disturbances.
INDICATION
When the UPS is used for special applications such as life support systems or any other application where a product failure is likely to cause substantial harm to people, it is mandatory to contact LEGRAND to confirm the possibility of the equip­ment to meet the requested level of safety, performance, reliability and compliance with applicable laws, regulations and specifications.
Installation and maintenance manual
CAUTION
- While maintenance operations are being carried out, “Maintenance work in progress” signs must be affixed in the de-
partment in such a way that they can be easily seen from any access area.
- The connection of the equipment (and of any accessory devices) signs must always be perfectly grounded to discharge
short-circuit currents and electrostatic voltages. The input voltage must correspond with the value shown on the rating plate. Current adapters must not be used under any circumstances. Pay attention to polarity when connecting.
- Any intervention on the equipment must be done only after it has been disconnected from the power supply network
by means of a switch disconnector and must be locked with an appropriate padlock.
- The UPS must not be turned on if liquid is leaking from the batteries.
- Depositing flammable material near the equipment is strictly forbidden. The equipment should always be locked, and
only specifically trained personnel are allowed access to it.
- Do not disable any safety, notification or warning device and do not ignore any alarm, warning message or notice, no
matter whether they are generated automatically or represented by plates fixed to the equipment.
- Do not run the equipment with fixed protections not installed (panels etc.).
- In case of breaking, buckling or malfunctioning of the equipment or parts of it, repair or replace immediately.
- When replacing fuses, only use ones of the same type.
- The replacement of the batteries is an operation intended to be carried out by a skilled technician.
- Keep a register in which to enter the date, time, type, performer’s name and any other useful information about each
and any routine and extraordinary maintenance operation.
- Do not use oils or chemical products for cleaning because they could scratch, corrode or damage certain parts of the
equipment.
- The equipment and workplace must be kept completely clean.
- Upon completion of the maintenance operations, before connecting the power supply, carefully check that no tools
and/or material of any kind have been left next to the equipment.
INDICATION
The skilled technician must not leave at the disposal of the operator:
- the keys for opening the UPS door;
- the installation and maintenance manual.
2.7 How to proceed in an emergency
The following information are general. For the specific interventions consult the regulations in force in the country where the equipment is installed.
2.7.1 First-aid procedures
When administering first aid, adhere to the company rules and the usual procedures.
2.7.2 Fire procedures
Do not use water to quench fires but just the extinguishers specially designed for putting out fires on electrical equipment.
11
Page 12
3. Transportation and placement
3.1 Visual check
On delivery of the UPS, carefully inspect the packaging and the equipment for any damage that might have occurred during transport. Check there is no damage to the indicator on the outer label reading “Shock Watch”. If there is possible or ascertained damage, immediately inform:
- the transporter;
- the LEGRAND Technical Support Service. Check that the equipment corresponds with the items indicated in the delivery documentation. If the UPS must be stored, follow the instructions of Chapter 7.
3.2 Equipment check
The equipment and the relative supplied accessories must be in perfect conditions. Check that:
- the shipping data (address of the recipient, no. of packages, order no, etc.) correspond to what is contained in the deliv-
ery documentation;
- the technical rating plate data on the label applied to the UPS correspond with the material described in the delivery
documentation;
- the documentation accompanying the equipment includes the installation and user manuals. In case of discrepancy, immediately inform the LEGRAND Technical Support Service before commissioning the equip­ment.
The content of the supply is subject to thorough checking before the shipment. Nonetheless it is always advisable to check that it is complete and in order on receiving the material. The following list is general:
- 1 UPS (empty cabinet) with keys to close the doors;
- 1 accessory box;
- user manual;
- installation and maintenance manual. In case of defects and/or missing items, immediately inform the LEGRAND Technical Support Service before commission­ing the equipment.
INDICATION
The installation manual must be used and consulted only by Skilled Technicians.
INDICATION
Power modules and battery drawers to be installed must be bought separately.
12
Page 13
3.3 Transportation
WARNING
The UPS must be placed and stand in a vertical position throughout the transportation. It shall also be packed properly. Move the UPS very carefully, lifting it as little as possible and avoiding dangerous swings or falls. Follow always the directions indicated in the symbols present on the packaging. The equipment must always be handled by trained and instructed personnel. Comply with the safety regulations in force in your country relative to the usage of lifting equipment and/or accessories.
For any lifting, use a forklift or a transpallet with an adequate carrying capacity, placing the forks in the specific spaces of the base and making sure they come out on the other side by at least twenty centimetres.
Installation and maintenance manual
Keor MOD UPS has four wheels at the bottom of the cabinet. Before installations and while it is still empty, it can be moved by hand by at least two people.
CAUTION
Do not move the UPS after the installation or following the insertion of the power modules.
13
Page 14
3. Unpacking and moving
3.4 Unpacking
To remove the packaging material, two people are required and they must comply comply with the following procedure:
- bring the UPS to the installation site using a forklift and/or a transpallet with suitable characteristics (see fig. 1);
- remove the plastic film and cardboards protecting the UPS;
- bring down the wooden chute attached to the pallet (see fig. 2)
- loose the screws of the brackets that fix the equipment on the pallet (see fig. 3);
- gently slide by hand the equipment along the chute using the wheels (see fig. 4).
1
3
2
4
14
Page 15
3.5 Placement
When the UPS is in the final position for the installation, unscrew counterclockwise the feet on the front and rear of the cabinet to position it. Make sure that all the wheels and feet adhere to the floor.
Installation and maintenance manual
(all the dimensions are in mm)
15
Page 16
3. Unpacking and moving
The UPS must be positioned respecting the following conditions:
- do not cover the cooling vents of the power modules and keep a clearance of 20 cm beyond the cabinets real panels;
- keep a clearance of 160 cm on the front to allow the opening of the door;
- temperature and humidity must be within permitted limits;
- fire regulations must be respected;
- the wiring must be simply made;
- front and rear accessibility must be available for assistance or periodic servicing;
- the cooling flow of air must be guaranteed;
- the air conditioning system must be adequately sized;
- dust, corrosive and explosive atmospheres must be absent;
- the installation site must be free of vibration;
- the support surface must be sized for the weight necessary to support the equipment:
- regulate the equipment feet to have perfect perpendicularity and level of the UPS compare with the floor.
16
POWER MODULE EXTRACTION
BATTERY DRAWERS EXTRACTION
POWER MODULE EXTRACTION
BATTERY DRAWERS EXTRACTION
To safeguard the batteries as well as possible it is necessary to bear in mind that their average lifetime is strongly influ­enced by the operating room temperature. Position the UPS in an environment with a temperature range between +20°C (+68°F) and +25°C (+77°F) to guarantee the optimum life of the batteries.
Before proceeding with the installation operations, make sure that there is enough lighting to clearly see every detail. Provide artificial lighting if the natural lighting does not satisfy this requirement. In case of maintenance operations in places that are not sufficiently well lit, portable lighting systems must be used, avoiding shadows that prevent or reduce visibility on the point where you intend to work or on the surrounding areas.
Page 17
4. Installation
DANGER All UPS installation operations must be carried out exclusively by a SKILLED TECHNICIAN qualified and authorized by LEGRAND (paragraph 2.2.1).
4.1 Safety regulations
DANGER
Before carrying out any installation operation you must read and apply the following:
- The UPS has a high leakage current. The earthing connection must be connected before cabling the UPS input. The
switchgear must have a safe connection with the earthing and an adequate protection as required by the installation standards.
- The UPS must only be installed in a fixed way with a thermal-magnetic circuit breaker placed upstream of it. Connection
to the mains via traditional type plug is not allowed.
- A circuit to protect from voltage backfeed made as in the diagrams shown in paragraph 4.2.5 must be provided outside
the UPS.
- The switchgear or the disconnector switch must be installed near the equipment and must be easily accessible.
- A warning label must be placed on all the mains disconnector switches installed away from the area of the UPS to remind the
assistance personnel of the fact that the circuit is connected to a UPS. The label must contain the following or equivalent text:
Installation and maintenance manual
Before working on this circuit
- Isolate Uninterruptible Power System (UPS)
- Then check for the presence of Hazardous Voltage
between all terminals including the protective earth
Risk of Voltage Backfeed
- Do not carry out the installation in presence of water or humidity.
- Open only the UPS panels necessary for the electrical connections. After that, close and fix them.
- Check there is no mains voltage on the equipment.
- Check that the loads are off and disconnected from the UPS.
- Check that the UPS is off and no voltage is present.
- Check that the fuse breakers on the external battery cabinets (if present) are open.
- Check that all battery drawers (if present) are not fully inserted in the UPS cabinet.
- Check that the mains input voltage and frequency correspond with the values indicated in the technical data on the
UPS rating plate.
- Check that the earthing has been carried out in compliance with IEC (International Electrotechnical Commission) stand-
ards or local regulations.
- Check that the electrical system has been fitted with the necessary differential and thermal-magnetic protections up-
stream of the UPS.
- The energy quality of the electrical network should comply with the individual voltage harmonics compatibility levels
defined by EN 61000-2-2. For more severe conditions, a power quality audit is required during the UPS commissioning by the LEGRAND Technical Support Service in orded to check the compatibility.
4.2 Electrical connections
The electrical hook-up of the UPS to the switchgear or to the external battery cabinets is part of the installation that is not normally performed by the UPS manufacturer. For this reason, the indications that follow are to be considered approxi­mate and it is recommended that the electrical connections are based on local installation standards. After removing the UPS from the packaging and positioning it in its definitive place, the Skilled Technician can begin to make the electrical connections.
WARNING
The choice of cables type and their cross sections depending on the rated current and their installations must be made as indicated by the local installation standards and it is a responsibility of the Skilled Technician. The input current and the output power of the UPS are indicated in chapter 10 and the battery current in table 4 of chapter 11.
INDICATION
Chapter 11 includes tables with the recommended cables, fuses, automatic and differential breakers.
17
Page 18
4. Installation
4.2.1 Protective devices
To ensure proper protection from overloads, output short-circuits or electrical shocks, it is necessary to install adequate automatic residual-current and thermal-magnetic breakers upstream of the UPS on the input line. In case there is a sepa­rate bypass line, the residual current earth leakage protection system must be common for the AC input and bypass lines and must be installed upstream. The protective devices must be selected according to the indications in the tables shown in chapter 11.
CAUTION
The equipment can cause a d.c. current in the PE conductor. Where a residual current-operated protective device (RCD) is used for protection against electrical shock, only an RCD of Type B is allowed on the supply side of this product.
4.2.2 Disassembly of the distribution panel
To carry out all the electrical connection operations, it is necessary to unscrew the screws that fix the distribution panel to the cabinet. The screws must be saved to close the distribution panel at the end of the installation (hex socket M6x20 screws along with M6 toothed washers). Unscrew also the screws that fix the plexiglass protection panel and save them to close the panel and the end of the installation (Phillips pan head M4x10 screws).
The following pictures show how to disassemble the panels:
KEOR MOD 125
KEOR MOD 250
18
Page 19
To insert the cables in the cabinet, it is necessary to remove the panels at the bottom of the cabinet according to the following sequence:
1
2
Installation and maintenance manual
19
Page 20
4. Installation
3
4
20
5
Page 21
Insert the cable and add the panels according to the following sequence:
6
Installation and maintenance manual
7
8
21
Page 22
4. Installation
9
10
22
Page 23
4.2.3 Earthing connection
Before carrying out any other installation operation, connect the earthing wiring coming from the low voltage switchgear to one of the earthing bars located on the left and right side of the busbars connection system. The minimum cross-sectional area of the earthing conductor must be chosen according to the following criteria:
• if the cross-sectional area S of the phase conductors is S ≤ 16 mm2, the minimum cross-sectional area of the earthing
conductor must be the same as the phase conductors;
• if the cross-sectional area S of the phase conductors is 16 mm2 < S ≤ 35 mm2, the minimum cross-sectional area of the
earthing conductor must be16 mm
• if the cross-sectional area S of the phase conductors is S > 35 mm2, the minimum cross-sectional area of the earthing
conductor must be S/2 mm
Each earthing cable must be crimped with M8 eyelets and fixed to the earthing metal bar using hex M8x20 screws along with M8 flat washers and M8 grower washer. The grower washer must be put on the top of the flat washer.
2
;
2
.
Installation and maintenance manual
KEOR MOD 125 – earthing bars
23
Page 24
4. Installation
24
KEOR MOD 250 – earthing bars
Page 25
4.2.4 Cable fastening
In the accessory box there are two metal bars for Keor MOD 125 and three metal bars for Keor MOD 250. They are used along with the plastic supports for cable ties to fasten the installation cables. Each bar must be fixed to the cabinet using two hex M8x14 screws. The plastic supports for the cable ties must be fixed on the bar using the M6 torx pan head screws.
Installation and maintenance manual
(all the dimensions are in mm)
KEOR MOD 125 – view of the two metal bars for cable fastening
25
Page 26
4. Installation
The fastening of the battery, input and output cables on Keor MOD 125 must be done according to the following steps:
1) Fix the first metal bar to the cabinet, behind the surge arrester and the fuse holders, using two hex M8x14 screws.
2) Fix the plastic supports for cable ties using M6 torx pan head screws.
26
Page 27
3) Fix the cables with cable ties.
Installation and maintenance manual
The fastening of the neutral and output cables on Keor MOD 125 must be done according to the following steps:
1) Fix the second metal bar to the cabinet, close to the maintenance manual bypass switch, using two hex M8x14 screws.
27
Page 28
4. Installation
2) Fix the plastic support for cable ties using M6 torx pan head screws.
28
3) Fix the cables with cable ties.
Page 29
Installation and maintenance manual
(all the dimensions are in mm)
KEOR MOD 250 – view of the three metal bars for cable fastening
29
Page 30
4. Installation
The fastening of the battery and output cables on Keor MOD 250 must be done according to the following steps:
1) Fix the first metal bar at the bottom of the cabinet using two hex M8x14 screws. Then fix the plastic support for the
cable ties using M6 torx pan head screws.
2) Fix the cable with cable ties.
30
Page 31
The fastening of the neutral and bypass cables on Keor MOD 250 must be done according to the following steps:
1) Fix the second metal bar above the first bar using two hex M8x14 screws. Then fix the plastic support for the cable ties
using M6 torx pan head screws.
Installation and maintenance manual
2) Fix the cable with cable ties.
31
Page 32
4. Installation
The fastening of the input cables on Keor MOD 250 must be done according to the following steps:
1) Fix the third metal bar above the second bar using two hex M8x14 screws. Then fix the plastic support for the cable
ties using M6 torx pan head screws.
2) Fix the cable with cable ties.
32
Page 33
The tightening torque values for the cables are the following:
- M8 screws: 24 Nm
- M6 nuts: 15 Nm
- M10 nuts: 35 Nm
Installation and maintenance manual
KEOR MOD 125
KEOR MOD 250
33
Page 34
4. Installation
4.2.5 Backfeed protection
An external protection against voltage backfeed must be provided according to the following diagrams:
34
Page 35
4.2.6 Input cables installation
The default configuration has the input line in common with the bypass line through a metal jumper.
Before the installation of the input cables, check the following:
- the mains line must be able to provide an input voltage of 400 V + 15% - 20%;
- the available mains power must be at least the same of the UPS nominal power;
- the cables to connect to the UPS must be isolated upstream and no voltage must be present;
- the earthing cable from the low voltage switchgear must be properly connected (see paragraph 4.2.3).
WARNING The neutral input cable must always be connected.
KEOR MOD 125
The default configuration has the input line in common with the bypass line through a metal jumper. If no change is required, follow these steps:
- unscrew the three hex M8x25 screws that fix the jumper to the bypass terminal of the busbar;
- crimp the input and neutral cables with M8 eyelets;
- connect the input cables L1, L2, L3 to the metal jumper of the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar
using the three screws removed previously along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
Installation and maintenance manual
35
Page 36
4. Installation
36
KEOR MOD 125 – input cables installation with input line in common with bypass line
In case the input line is separated from the bypass line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M8 eyelets;
- connect the input cables L1, L2, L3 to the terminals IN L1, IN L2, IN L3 of the input busbar using three hex M8x20 screws
along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
Page 37
Installation and maintenance manual
KEOR MOD 125 – input cables installation with input line separated from the bypass line
When the input line is separated from the bypass line, it is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable. For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M8 eyelets;
- connect the first three input cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex M8x20
screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three input cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M8x25 screws along with M8 flat washers and M8 grower washers. Through these screws, fix the accessories to the ter­minals IN L1, IN L2, IN L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first neutral cable to the hole at the bottom of the accessory for double cable using a hex M8x20 screw
along with a M8 flat washer and a M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second neutral cable to the hole at the top of the accessory for double cable using a hex M8x25 screw along
with M8 flat washer and M8 grower washer. Through this screw, fix the accessory to the terminal of the neutral busbar. The grower washer must always be put on top of the flat washer.
KEOR MOD 125 – input cables installation with accessories for double cable and input line separated from the bypass line
37
Page 38
4. Installation
KEOR MOD 250
The default configuration has the input line in common with the bypass line through a metal jumper. If no change is required, follow these steps:
- unscrew the three hex M10x35 screws that fix the jumper to the input terminal of the busbar;
- crimp the input and neutral cables with M10 eyelets;
- connect the input cables L1, L2, L3 to the metal jumper of the terminals IN L1, IN L2, IN L3 of the input busbar using the
three screws removed previously along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
38
KEOR MOD 250 – input cables installation with input line in common with bypass line
Page 39
In case the input line is separated from the bypass line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M10 eyelets;
- connect the input cables L1, L2, L3 to the terminals IN L1, IN L2, IN L3 of the input busbar using three hex M10x30 screws
along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the input neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
Installation and maintenance manual
KEOR MOD 250 – input cables installation with input line separated from the bypass line
39
Page 40
4. Installation
When the input line is separated from the bypass line, it is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable. For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the input and neutral cables with M10 eyelets;
- connect the first three input cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex
M10x30 screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three input cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M10x35 screws along with M10 flat washers and M10 grower washers. Through these screws, fix the accessories to the terminals IN L1, IN L2, IN L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first input neutral cable to the hole at the bottom of the accessory for double cable using a hex M10x30
screw along with a M10 flat washer and a M10 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second input neutral cable to the hole at the top of the accessory for double cable using a hex M10x35
screw along with M10 flat washer and M10 grower washer. Through this screw, fix the accessory to the terminal of the neutral busbar. The grower washer must always be put on top of the flat washer.
40
KEOR MOD 250 – input cables installation with accessories for double cable
and input line separated from the bypass line
Page 41
4.2.7 Bypass cables installation
The default configuration has the input line in common with the bypass line through a metal jumper. If no change is required, follow the steps indicated in the previous paragraph.
To perform a dual input installation with a separate bypass line, the following requirements must be met:
- the two lines must be supplied by the same MV/LV transformer source (same electrical potential). If this is not the case,
an insulation transformer should be added in the bypass line upstream the UPS;
- separate protective devices are required for each line. The UPS does not modify the neutral configuration of the system. The mains, bypass and output neutral are connected internally to each other.
Before the installation of the bypass cables, check the following:
- the bypass line must be able to provide a voltage of 400 V + 15% - 20%;
- the available bypass power must be at least the same of the UPS nominal power;
- the cables to connect to the UPS must be isolated upstream and no voltage must be present;
- the earthing cable from the low voltage switchgear must be properly connected (see paragraph 4.2.3).
WARNING The neutral bypass cable must always be connected.
KEOR MOD 125
In case the bypass line is separated from the input line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M8 eyelets;
- connect the bypass cables L1, L2, L3 to the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar using three hex M8x20
screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the bypass neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
Installation and maintenance manual
KEOR MOD 125 – bypass cables installation with input line separated from the bypass line
41
Page 42
4. Installation
When the input line is separated from the bypass line, it is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable. For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M8 eyelets;
- connect the first three bypass cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three
hex M8x20 screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three bypass cables L1, L2, L3 to the hole at the top of the accessory for double cable using three
hex M8x25 screws along with M8 flat washers and M8 grower washers. Through these screws, fix the accessories to the terminals BYP L1, BYP L2, BYP L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first bypass neutral cable to the hole at the bottom of the accessory for double cable using a hex M8x20
screw along with a M8 flat washer and a M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second bypass neutral cable to the hole at the top of the accessory for double cable using a hex M8x25
screw along with M8 flat washer and M8 grower washer. Through this screw, fix the accessory to the terminal of the neutral busbar. The grower washer must always be put on top of the flat washer.
42
KEOR MOD 125 – bypass cables installation with accessories for double cable
and input line separated from the bypass line
KEOR MOD 250
In case the bypass line is separate from the bypass line, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M10 eyelets;
- connect the bypass cables L1, L2, L3 to the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar using three hex M10x30
screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the bypass neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
Page 43
Installation and maintenance manual
KEOR MOD 250 – bypass cables installation with input line separated from the bypass line
43
Page 44
4. Installation
When the bypass line is separated from the input line, it is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable. For this installation, follow these steps:
- remove the metal jumper that connects the input line with the bypass line;
- crimp the bypass and neutral cables with M10 eyelets;
- connect the first three bypass cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three
hex M10x30 screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three bypass cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M10x35 screws along with M10 flat washers and M10 grower washers. Through these screws, fix the accessories to the terminals BYP L1, BYP L2, BYP L3 of the bypass busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first bypass neutral cable to the hole at the bottom of the accessory for double cable using a hex M10x30
screw along with a M10 flat washer and a M10 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second bypass neutral cable to the hole at the top of the accessory for double cable using a hex M10x35
screw along with M10 flat washer and M10 grower washer. Through this screw, fix the accessory to the terminal of the neutral busbar. The grower washer must always be put on top of the flat washer.
44
Page 45
Installation and maintenance manual
KEOR MOD 250 – bypass cables installation with accessories for double cable
and input line separated from the bypass line
4.2.8 Output cables installation
Before the installation of the output cables, check the following:
- the nominal power of the UPS must be at least the same of the nominal power of the load;
- the cables to connect to the UPS must be isolated upstream and no voltage must be present;
- the earthing cable from the low voltage switchgear must be properly connected (see paragraph 4.2.3).
INDICATION
Provide a separate switchgear for the load. The following information must be indicated on the system switchgear by means of stickers or similar:
- maximum nominal power of the load;
- maximum nominal power of the load at the load outlets;
- if a common switchgear is used (mains and UPS power outlets), make sure that there is an indication of the power source
on every power outlet (“Mains” or “UPS”).
WARNING The neutral output cable must always be connected.
KEOR MOD 125
Follow these steps:
- crimp the output and neutral cables with M8 eyelets;
- connect the output cables L1, L2, L3 to the terminals OUT L1, OUT L2, OUT L3 of the output busbar using three hex
M8x20 screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the output neutral cable to the neutral busbar with a hex M8x20 screw along with a M8 flat washer and a M8
grower washer. The grower washer must always be put on top of the flat washer.
45
Page 46
4. Installation
KEOR MOD 125 – output cables installation
It is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable. For this installation, follow these steps:
- crimp the output and neutral cables with M8 eyelets;
- connect the first three output cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex M8x20
screws along with M8 flat washers and M8 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three output cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M8x25 screws along with M8 flat washers and M8 grower washers. Through these screws, fix the accessories to the termi­nals OUT L1, OUT L2, OUT L3 of the input busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first output neutral cable to the hole at the bottom of the accessory for double cable using a hex M8x20 screw
along with a M8 flat washer and a M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second output neutral cable to the hole at the top of the accessory for double cable using a hex M8x25 screw
along with M8 flat washer and M8 grower washer. Through this screw, fix the accessory to the terminal of the neutral bu­sbar. The grower washer must always be put on top of the flat washer.
46
KEOR MOD 125 – output cables installation with accessories for double cable
Page 47
KEOR MOD 250
Follow these steps:
- crimp the output and neutral cables with M10 eyelets;
- connect the output cables L1, L2, L3 to the terminals OUT L1, OUT L2, OUT L3 of the output busbar using three hex M10x30
screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the output neutral cable to the neutral busbar with a hex M10x30 screw along with a M10 flat washer and a M10
grower washer. The grower washer must always be put on top of the flat washer.
Installation and maintenance manual
KEOR MOD 250 – output cables installation
47
Page 48
4. Installation
It is also possible to install an accessory for double cable. In this way it is possible for each terminal to use two cables with a smaller cross section than the one of a single cable. For this installation, follow these steps:
- crimp the output and neutral cables with M10 eyelets;
- connect the first three output cables L1, L2, L3 to the hole at the bottom of the accessory for double cable using three hex M10x30
screws along with M10 flat washers and M10 grower washers. The grower washer must always be put on top of the flat washer;
- connect the other three output cables L1, L2, L3 to the hole at the top of the accessory for double cable using three hex
M10x35 screws along with M10 flat washers and M10 grower washers. Through these screws, fix the accessories to the terminals OUT L1, OUT L2, OUT L3 of the output busbar. The grower washer must always be put on top of the flat washer;
- do not change the phase sequence (L1, L2, L3);
- connect the first output neutral cable to the hole at the bottom of the accessory for double cable using a hex M10x30 screw
along with a M10 flat washer and a M10 grower washer. The grower washer must always be put on top of the flat washer;
- connect the second output neutral cable to the hole at the top of the accessory for double cable using a hex M10x35
screw along with M10 flat washer and M10 grower washer. Through this screw, fix the accessory to the terminal of the neutral busbar. The grower washer must always be put on top of the flat washer.
48
Page 49
Installation and maintenance manual
KEOR MOD 250 – output cables installation with accessories for double cable
4.2.9 Battery cables installation
The default configuration has the strings of batteries in common.
Before the installation of the input cables, check the following:
- the fuse breakers of all the external battery cabinets must be open;
- the cables to connect to the UPS must be isolated upstream and no voltage must be present;
- the earthing cable from the low voltage switchgear must be properly connected (see paragraph 4.2.3).
WARNING The neutral battery cable must always be connected.
49
Page 50
4. Installation
KEOR MOD 125
The default configuration has the strings of batteries in common.
KEOR MOD 125 – battery terminals
If no change is required, follow these steps:
- crimp the positive, negative and neutral battery cables with M8 eyelets;
- connect the positive cable of the battery cabinet to the + BATT terminal using a hex M8x20 screw along with M8 flat
washer and M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the negative cable of the battery cabinet to the - BATT terminal using a hex M8x20 screw along with M8 flat
washer and M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the neutral cable of the battery cabinet to the neutral busbar using a hex M8x20 screw along with M8 flat wa-
sher and M8 grower washer. The grower washer must always be put on top of the flat washer.
50
KEOR MOD 125 – battery cables installation with strings of batteries in common
Page 51
In case there is the need to use a double cable for each terminal in order to use a smaller cross section for each cable, follow the previous procedure but install two cables for each terminal.
Installation and maintenance manual
KEOR MOD 125 – battery cables installation with strings of batteries in common (double cable)
It is also possible to install independent string of batteries. In this case, each power module is associated to a unique string. The following picture shows the association between the power modules and the relative battery strings:
51
Page 52
4. Installation
In case of installation of independent strings of batterie, follow these steps:
- remove the metal jumpers inserted in the positive and negative battery terminals.
- remove the supports for the metal jumpers.
52
- insert the positive battery cables of the battery cabinets in the positive battery terminal and the negative battery cables
of the battery cabinets in the negative battery terminal. The maximum cross section accepted by the terminals is 16 mm2. Connect the battery cables on the terminals according to the string: BATT1: +1 ; -1 BATT2: +2 ; -2 BATT3: +3 ; -3 BATT4: +4 ; -4 BATT5: +5 ; -5
Page 53
Installation and maintenance manual
- take from the accessory box the metal support for the neutral battery cables and install it in the relative position on the
neutral busbar.
53
Page 54
4. Installation
- crimp the neutral battery cables with M5 eyelets;
- connect the neutral cables of the battery cabinets to the metal support of the neutral busbar using hex M5 nuts along
with M5 flat washer and M5 grower washers present in the accessory box. The grower washer must always be put on
top of the flat washer.
54
Page 55
KEOR MOD 250
The default configuration has the strings of batteries in common.
Installation and maintenance manual
KEOR MOD 250 – battery terminals
If no change is required, follow these steps:
- crimp the positive, negative and neutral battery cables with M8 eyelets;
- connect the positive cable of the battery cabinet to the + BATT terminal using a hex M8x20 screw along with M8 flat
washer and M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the negative cable of the battery cabinet to the - BATT terminal using a hex M8x20 screw along with M8 flat
washer and M8 grower washer. The grower washer must always be put on top of the flat washer;
- connect the neutral cable of the battery cabinet to the N BATT terminal using a hex M8x20 screw along with M8 flat
washer and M8 grower washer. The grower washer must always be put on top of the flat washer.
KEOR MOD 250 – battery cables installation with strings of batteries in common
55
Page 56
4. Installation
In case there is the need to use a double cable for each terminal in order to use a smaller cross section for each cable, follow the previous procedure but install two cables for each terminal.
KEOR MOD 250 – battery cables installation with strings of batteries in common (double cable)
It is also possible to install independent string of batteries. In this case, each power module is associated to a unique string. The following picture shows the association between the power modules and the relative battery strings:
56
Page 57
In case of installation of independent strings of batterie, follow these steps:
- remove the metal jumpers inserted in the battery terminals.
Installation and maintenance manual
- insert the positive battery cables of the battery cabinets in the positive battery terminal, the negative battery cables of
the battery cabinets in the negative battery terminal and the neutral battery cables of the battery cabinets in the neutral
battery terminal. The maximum cross section accepted by the terminals is 35 mm2. Connect the battery cables on the terminals according to the string: BATT1: +1 ; -1 BATT2: +2 ; -2 BATT3: +3 ; -3 BATT4: +4 ; -4 BATT5: +5 ; -5
57
Page 58
4. Installation
4.3 Power modules installation
Once all the electrical connections have been made, close the distribution panels and fix them by screwing all the hex socket M6x16 screws along with M6 toothed washers. It is then possible to move onto the insertion of the power modules into the UPS. During the installation it is necessary to use the appropriate Personal Protective Equipment like protective gloves and anti-accident shoes (see paragraph 2.3).
INDICATION
To guarantee the stability of the Keor MOD 125 cabinet, first install the power modules and only later the battery drawers.
Insert the power modules one at a time starting from the top of the cabinet. Unscrew the four screws that fix the slot cover where the power module must be installed and save them.
58
Handle the power module from his sides and never from the front.
Page 59
Insert the power module in the free slot, making sure that its switch in the front is open.
Installation and maintenance manual
Make sure that the power module is abut and then close its front switch. Fix the module to the cabinet with the four screws that were previously saved.
59
Page 60
4. Installation
4.4 Battery drawers installation
The cabinet for Keor MOD 125 may include two to ten internal battery drawers. Each battery string is made up of two drawers, therefore it is necessary to install them two by two. The battery drawers have a specific order in the cabinet that must be kept, especially if the UPS has to work in a configu­ration with indipendent strings of batteries. During the installation it is necessary to use the appropriate Personal Protective Equipment (see paragraph 2.3).
60
Page 61
Starting from the top of the cabinet, unscrew the four screws that fix the slot cover where the battery drawers must be installed and save them.
Installation and maintenance manual
Insert the empty battery drawers in the free slots and push them till the ‘click’ of the safety block is heard. The battery blocks must be added to the drawers only after the activation of the safety block.
61
Page 62
4. Installation
Remove the terminal covers of the batteries at the extremes.
Add two battery blocks on a drawer and connect in series the two blocks using the cable provided and respecting the polarity (connect a positive terminal to a negative terminal).
62
Page 63
Once the connection is done, insert the terminal covers on the two batteries and push the blocks at the bottom of the drawer.
Installation and maintenance manual
Add other two battery blocks on the drawer
63
Page 64
4. Installation
Connect in series the two new blocks to the ones already in the drawer using the cable provided and respecting the po­larity (connect a positive terminal to a negative terminal). Connect the free terminals of the two batteries located close to the handle of the drawer to the cables that go to the back of the drawer. Check the correct polarity of the whole cabling.
Insert the remaining terminal covers on the batteries.
64
Page 65
Fill the second drawer in the same way. After the two drawers are ready, push them inside the UPS cabinet till they are abut and fix them with the four screws that were previously saved.
Installation and maintenance manual
65
Page 66
4. Installation
4.5 SSS interface
TERMINAL PINS FUNCTION
Analogic
floating
inputs
Digital
floating
inputs
Output
contacts
N16
N15
N14
N13
N12
N11
N10
N9
1-2 CONFIGURABLE CONTACT 3 Maximum input voltage: 15V
3-4 CONFIGURABLE CONTACT 4
1-2 CONFIGURABLE CONTACT 1
3-4 CONFIGURABLE CONTACT 2
1-2
3-4
1-2 EPO
3-4 EXTERNAL OUTPUT SWITCH
1-2
3-4 EXTERNAL BATTERY SWITCH
4-5-6 CONFIGURABLE CONTACT 3 NC/NO contacts
1-2-3 CONFIGURABLE CONTACT 2
4-5-6 CONFIGURABLE CONTACT 1
1-2-3 BYPASS STATUS
4-5-6 ALARM
1-2-3 OVERLOAD
EXTERNAL MAINTENANCE
BYPASS SWITCH
EXTERNAL TEMPERATURE
Maximum Input Voltage: 5V
(not available at the moment)
GENSET
It allows the UPS to know if
there is an external generator.
If the contact is closed, the
generator is present.
125 Vac - 0,5 A (resistive load).
15 kΩ pull-up
Maximum input voltage: 5V
1 kΩ pull-up
30 Vdc -1 A
66
N8
N6 1-2
CONNECTOR TERMINAL
N3B
4-5-6 BATTERY AUTONOMY RESERVE
1-2-3 MAINS/BATTERY STATUS
bypass mode through this NO contact
USB HOST
Port used for FW updates
AUXILIARY REMOTE BYPASS
CONTAC T
It is possible to enable the forced
Page 67
4.5.1 Emergency Power Off (EPO)
The UPS has a contact that can be used to activate the immediate stop of the equipment. It can be set as normally closed (NC) or normally open (NO) from the user interface. The default configuration is NC. The EPO terminal is found on pins 1 and 2 of contact N13 of the SSS interface. Use a voltage-free contact to connect the epo externally.
INDICATION
It is not possible to connect in parallel the EPO circuits of several UPS. If necessary, use contacts on the EPO emergency pushbutton isolated from each other.
The electric characteristics of the EPO interface are:
- voltage between terminals 1 and 2 of contact N13 with open circuit: 5 Vdc
- current between terminals 1and 2 of contact N13 with closed circuit: 5 mA
Installation and maintenance manual
67
Page 68
5. Conguration and start-up
DANGER All the configurations and start-up operations must be carried out exclusively by a SKILLED TECHNICIAN (para­graph 2.2.1).
5.1 Pre-start-up checks
Before powering the equipment, carry out the following checks:
1. Close all the distribution panels on the UPS cabinet.
2. Check that the external mains input disconnector is open (OFF position).
3. Check that the external bypass input disconnector (if present) is open (OFF position).
4. Check that the external output disconnector is open (OFF position).
5. Check that the battery disconnectors of the external battery cabinets (if present) are open.
6. Check that the maintenance bypass disconnector and the output disconnectors of the UPS are open (OFF position).
7. Check that the input and output wiring has been done and that all the connections have been tightened up properly.
8. Check the correct phase sequence of the input and bypass line (if separate).
9. Check that the parameters (voltage and frequency) of the mains input are compatible with those shown on the UPS
rating plate.
10. Check that all the power modules are inserted properly and that the fixing screws are screwed up to abut the relative
slots (use hex socket M6x16 screws along with M6 toothed washers).
11. Check that all the battery drawers (if present) are inserted properly and that the fixing screws are screwed up to abut
the relative slots (use hex socket M6x16 screws along with M6 toothed washers).
12. Check the presence of the EPO terminal according to the setting (see paragraph 4.5.1)
5.2 Start-up procedure
1. Insert the battery fuses into the appropriate fuse breakers of the external battery cabinets (if present).
2. Press for at least 5 seconds the COLD START button of the SSS interface. The display turns on and the UPS boot starts.
3. The UPS boot ends when the LEDs on the power modules turn to steady blue. Tap on the Setting icon of the menu bar
at the bottom of the display
4. Choose the desired language in the tab “General” by tapping on the pencil icon on the item “Language”.
5. Set the correct day/time in the tab “General” by tapping on the pencil icon on the item “Date and Time”.
68
Page 69
Installation and maintenance manual
6. Set the desired voltage and frequency output in the tab “System” by tapping on the pencil icon on the items “Voltage”
and “Frequency”.
7. Set the correct number of KB (Battery Kits) installed in the tab “System”
69
Page 70
5. Conguration and start-up
INDICATION
1 KB (Battery Kit) represents a string of 48 batteries in series. In case of models with internal battery drawers, 1 KB is made up of 2 drawers.
8. Set the correct battery capacity in Ah of the single KB in the tab “System”
INDICATION
The UPS calculates the total battery capacity as produced by the total KB * Capacity.
9. Provide the mains supply to the UPS by closing the external mains input/bypass input disconnectors (ON position).
10. Tap on the tab “System” and select ON on the item “System Power” to turn ON the UPS. Ensure that the EPO is connect-
ed to the SSS interface (the default setting is NC).
11. The LEDs on the power modules turn to steady yellow while they are powered from the batteries. When they are
powered from the mains and the UPS is on-line, the LEDs turn to steady green.
12. Check that the output voltage and frequency values set correspond with the requirements of the load. If not, turn off
the UPS and set the correct values (see step 6).
13. Provide the power supply to the load by closing the external output disconnector (ON position).
14. Close the UPS door and remove the key.
DANGER
Do not remove the power modules during the functioning of the UPS without activating the hot-swap procedure (de­scribed in paragraph 6.3.1). The removal of one or more power modules without the proper use of the hot-swap proce­dure could damage the equipment.
CAUTION
The keys to open the UPS door and the installation manual must not be left at the disposal of the operator.
5.3 Switching off the UPS
Follow this procedure in case there is the need to turn off the UPS:
1. Tap on the Setting icon of the menu bar at the bottom of the display.
2. Tap on the tab “System” and select OFF on the item “System Power” to turn OFF the UPS.
3. The LEDs on the power modules turn to steady blue when they are in stand-by mode and the UPS is no longer sup-
plying the load.
DANGER
In this stand-by condition there are still hazardous voltages on the UPS.
To disconnect the UPS from all sources of supply:
- open the external mains input/bypass input disconnectors (ON position);
- open all the fuse breakers of the external battery cabinets (if present);
- remove at least one battery drawer for every shelf present to interrupt the battery string.
70
Page 71
6. Maintenance
DANGER INSTALLATION and ORDINARY MAINTENANCE operations must be carried out only by SKILLED TECHNICIANS (par­agraph 2.2.1). EXTRAORDINARY MAINTENANCE operations must be carried out only by LEGRAND TECHNICAL SUPPORT SER­VICE.
LEGRAND declines all liability for any injury or damage caused by activities carried out differently from the instructions written in this manual.
6.1 Preventive maintenance
The UPS does not contain parts for preventative maintenance by the operator. The operator must regularly perform:
- a general external cleaning;
- a check to verify there is no alarm indication on the display;
- a check to verify the correct functioning of the ventilating fans on each power module.
6.2 Periodical checks
The correct functioning of the UPS must be guaranteed by periodical maintenance inspections. These are essential to safeguard the reliability of the equipment. These inspections should also be made to determine if components, wiring, and connections exhibit evidence of over­heating.
Installation and maintenance manual
During a maintenance inspection, the skilled technician must carry out the following checks:
- no alarm presence;
- list of the memorised events;
- correct function of the static and maintenance bypass;
- integrity of the electrical installation;
- flow of cold air;
- battery status;
- characteristics of the applied load;
- conditions of the installation location.
Contact the LEGRAND Technical Support Service in case of problems.
WARNING The periodical checks involve operations inside the UPS in presence of dangerous voltages. Only maintenance personnel trained by LEGRAND are authorized to intervene.
71
Page 72
6. Maintenance
6.3 Ordinary maintenance
After the removal of power from the UPS, the capacitors discharge time inside the power modules is 40 minutes. It is forbidden to operate inside the power modules before this time has elapsed.
6.3.1 Hot-swap procedure for the replacement of power modules
The hot-swap procedure makes it possible to replace a faulty power module while the load is powered by the UPS in on-line mode. In case of a black-out during the procedure, there is no risk to power off the load since it is supplied by the other power modules.
INDICATION
To use this function, the UPS must have at least two power modules and the output power required must not be above the one available during the hot-swap procedure. Always replace just one PM at a time. If the load power does not allow the hot-swap without overload, perform the manual bypass mode maintenance proce­dure.
Each power module (PM) is identified by a unique address inside the system, as shown below:
72
KEOR MOD 125 KEOR MOD 250
Page 73
During the hot-swap procedure the maximum active power available is indicated in the following table:
MAXIMUM ACTIVE POWER AVAILABLE
KEOR MOD 50 25 kW (50%)
KEOR MOD 75 50 kW (66%)
KEOR MOD 100 75 kW (75%)
KEOR MOD 125 100 kW (80%)
KEOR MOD 150 125 kW (84%)
KEOR MOD 175 150 kW (86%)
KEOR MOD 200 175 kW (88,5%)
KEOR MOD 225 200 kW (89%)
KEOR MOD 250 225 kW (90%)
The following is the how-swap procedure:
1. Check that the load connected to the UPS allows the power module replacement without causing an overload.
2. On the main screen, tap on the UPS which has the PM to replace.
Installation and maintenance manual
73
Page 74
6. Maintenance
3. Choose the PM to replace by tapping on it or scrolling it with the ARROWS UP and DOWN icons. Then, tap on the
SWITCH icon and confirm to turn off the module once the pop-up appears.
4. Initially, the LED on the PM turns blue. Wait until it turns white: the PM is ready to be replaced.
5. Open the frontal switch of the PM.
74
6. Unscrew the fixing screws of the PM and save them.
7. Extract the PM until the safety block prevents to continue the extraction.
Page 75
8. Push the safety hook located on the top right of the PM to unlock the block and pull the PM to finalize the extraction.
Installation and maintenance manual
9. Insert the new PM on the free slot making sure that the frontal switch is open and that the module is in abutment.
10. Fix the PM to the cabinet using the screws previously unscrewed.
11. Close the frontal switch of the PM.
12. The LED on the PM turns red. After the boot of the PM, the LED turns blue. Next, the PM starts in battery mode (yellow
LED). Finally, the LED turns green and the PM is powered by the mains.
INDICATION
If one or more screws are lost, use only hex socket M6x16 screws along with M6 toothed washers to fix the power modules.
INDICATION
In case of emergency, e.g. if the display does not work, it is possible to perform a hot-swap replacement by simply open­ing the frontal switch of the PM. Wait until the LED turns white to replace the PM. When the frontal switch of the PM is open, it is not possible to restart the PM by simply closing it. It is necessary to extract the module.
75
Page 76
6. Maintenance
6.3.2 Installation/replacement of power modules with the UPS in maintenance bypass mode
If the hot-swap procedure explained in the previous paragraph is not applicable, it is possible to replace or even to add PM with the UPS in maintenance bypass mode.
INDICATION
During this procedure, the load is not protected by the UPS because it is powered from the bypass input line.
6.3.2.1 Setting the UPS in maintenance bypass mode
1. Tap on the Setting icon of the menu bar at the bottom of the display
2. Check on the tab “System” that the item “Bypass Enable” is set to YES. If not, tap on the item and enable the bypass.
3. Tap on the item “Bypass Forced Mode” and set it to YES. The LEDs of the PM blink fast in orange.
4. Close the maintenance manual bypass switch by bringing it to the ON position. The load is powered directly from the
bypass line.
5. Shutdown the UPS by following the procedure described at paragraph 5.3.
6. If present, open the battery disconnectors of the external battery cabinets.
DANGER
If there are battery drawers installed in the cabinet, some internal parts of the UPS are still live with dangerous voltage. Remove at least one battery drawer for every shelf present to interrupt the battery string.
6.3.2.2 Installation/replacement of power modules
Check that the procedure for setting the maintenance bypass mode described in paragraph 6.3.2.1 has been applied.
To replace a PM:
1. Open the frontal switch of the PM to be replaced.
2. Unscrew the fixing screws of the PM and save them.
76
Page 77
3. Extract the PM until the safety block prevents to continue the extraction.
Installation and maintenance manual
4. Push the safety hook located on the top right of the PM to unlock the block and pull the PM to finalize the extraction.
5. Insert the new PM on the free slot making sure that the frontal switch is open and that the module is in abutment.
6. Fix the PM to the cabinet using the screws previously unscrewed.
77
Page 78
6. Maintenance
7. Close the frontal switch of the PM.
To add a PM:
1. Unscrew the screws of the protective cover of a free slot starting from the top of the cabinet.
2. Insert the new PM on the free slot making sure that the frontal switch is open and that the module is in abutment.
3. Fix the module using the screws previously unscrewed.
4. Close the frontal switch of the PM.
INDICATION
If one or more screws are lost, use only hex socket M6x16 screws along with M6 toothed washers to fix the power modules.
6.3.2.3 Exit the UPS from the maintenance bypass mode
1. If present, close the battery disconnectors of the external battery cabinets and insert all the internal battery drawers.
2. Tap on the “Setting” icon. Then tap on the tab “System” and select ON on the item “System Power” to turn ON the UPS.
3. Wait for the UPS boot until the LEDs of the PM blink fast in orange.
4. Open the maintenance manual bypass switch by bringing it to the OFF position
5. Tap on the item “Bypass Forced Mode” on the “System” tab. Set it to NO. The LEDs of the PM turn to steady green.
78
Page 79
6.3.3 Removal of the SSS drawer
1
2
Installation and maintenance manual
3
4
79
Page 80
6. Maintenance
6.4 Battery drawers replacement
WARNING
A battery can present a risk of electrical shock and high short circuit current. Read and apply the safety instructions in chapter 2 before operating on batteries
INDICATION
The battery drawers must always be added/removed in multiples of two (1 KB consists of two battery drawers). Always replace just one KB at a time. If one KB is added, start from the free slots at the top which are covered by protective covers. If a KB is completely removed, install the protective covers to block any access to live parts. If the installation/removal procedure changes the total number of KB installed in the UPS, it is necessary to update this setting from the control panel. After concluding the installation/replacement operations, perform a battery calibration to get precise information re­garding the total autonomy of the UPS.
6.4.1 Installation/replacement of battery drawers with UPS in on-line mode
To replace a battery drawer:
1. Check that the UPS has installed more than 1KB every 25kVA of power supplied to the output.
2. Check that the UPS is not working in battery mode and that the battery charger is in the “maintenance” or “standby”
state.
3. Extract the battery drawer until the safety block prevents to continue the extraction.
80
4. Remove all the battery blocks from the drawer.
Page 81
5. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
Installation and maintenance manual
6. Follow the procedure shown at paragraph 4.4 to insert a new battery drawer
INDICATION
If the UPS turns to battery mode during these operations, do not continue the installation/replacement. It is possible to resume the operations when the UPS turns to on-line mode. When there is a black-out during the replacement of battery drawers, the backup time is reduced. It is necessary to care­fully assess this event before starting with the installation/replacement procedure.
To add a battery drawer: Follow the procedure shown at paragraph 4.4 to add a new battery drawer
6.4.2 Installation/replacement of battery drawers with UPS in maintenance manual bypass
To replace a battery drawer:
1. Follow the procedure described in paragraph 6.3.2.1 for setting the UPS in maintenance bypass mode.
2. Extract the battery drawer until the safety block prevents to continue the extraction.
81
Page 82
6. Maintenance
3. Remove all the battery blocks from the drawer
4. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
82
5. Follow the procedure shown at paragraph 4.4 to insert a new battery drawer
6. Follow the procedure described in paragraph 6.3.2.3 to exit from the maintenance bypass mode.
To add a battery drawer:
1. Follow the procedure described in paragraph 6.3.2.1 for setting the UPS in maintenance bypass mode.
2. Follow the procedure shown at paragraph 4.4 to add a new battery drawer
3. Follow the procedure described in paragraph 6.3.2.3 to exit from the maintenance bypass mode.
INDICATION
During the installation/replacement operations, the load is not protected by the UPS because it is powered from the bypass input line.
6.5 Replacing the fuses and surge arrester (DIN rail)
A surge arrester and two fuse holders can be found in the DIN rail inside the cabinet. The first fuse holder contains a 16A GG 10x38mm fuse (LG-013316). It is in series to the surge arrester. The second fuse holder contains a 2A GG 10x38mm fuse (LG-013302). It is in series to the input bypass disconnector release coil. The surge arrester is a T2 40kA 1P SPD (LG-412230).
INDICATION
It is mandatory to verify monthly the indication on the surge arrester. The device works correctly if the indicator is green. If the device is damaged, the indicator is red and the surge arrester must be replaced.
Page 83
Installation and maintenance manual
KEOR MOD 125
KEOR MOD 250
6.6 Extraordinary maintenance
Contact the LEGRAND Technical Support Service if there are failures that require the access to internal parts of the UPS.
83
Page 84
7. Warehousing
DANGER All storage operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1)
DANGER A SKILLED TECHNICIAN must check that there is no voltage present before disconnecting the cables. All the bat­tery isolator switches on the UPS and on the EBC must be open. All the battery isolator switches on the UPS and on the external battery cabinets must be open. The battery draw­ers of the UPS and of the external battery cabinet (if present) must be removed.
7.1 UPS
The UPS must be stored in an environment with a room temperature between -20°C (-4°F) and +50°C (+122°F) and hu­midity less than 90% (not condensing).
7.2 Batteries
It is possible to store batteries without recharging them in the following conditions:
- up to 6 months if the temperature is between +20°C (+68°F) and +30°C (+86°F);
- up to 3 months if the temperature is between +30°C (+86°F) and +40°C (+104°F);
- up to 2 months if the temperature is over +40°C (+104°F).
CAUTION
Batteries must never be stored if partially or totally discharged. LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing of the batteries.
84
Page 85
8. Dismantling
DANGER Dismantling and disposal operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1). The instructions in this chapter are to be considered indicative: in every country there are different regulations regarding the disposal of electronic or hazardous waste such as batteries. It is necessary to strictly adhere to the standards in force in the country where the equipment is used. Do not throw any component of the equipment in the ordinary rubbish.
8.1 Battery disposal
Batteries must be disposed of in a site intended for the recovery of toxic waste. Disposal in the traditional rubbish is not allowed. Apply to the competent agencies in your countries for the proper procedure.
WARNING
A battery may constitute a risk of electric shock and high short-circuit current. When working on batteries, the prescriptions indicated in chapter 2 must be adhered to.
Installation and maintenance manual
8.2 UPS dismantling
The dismantling of the UPS must occur after the dismantling of the various parts it consists of. For the dismantling operations, it is necessary to wear the Personal Protective Equipment mentioned in paragraph 2.3. Sub-divide the components separating the metal from the plastic, from the copper and so on according to the type of selective waste disposal in the country where the equipment is dismantled. If the dismantled components must be stored before their disposal, be careful to keep them in a safe place protected from atmospheric agents to avoid soil and groundwater contamination.
8.3 Electronic component dismantling
For the disposal of electronic waste, it is necessary to refer to the relevant standards.
This symbol indicates that in order to prevent any negative effects on the environment and on people, this
product should be disposed of separately from other household waste, by taking it to authorised collection centres, in accordance with the EU countries local waste disposal legislations. Disposing of the product without following local regulations may be punished by law. It is recommended to check that this equipment subject to WEEE legislations in the country where it is used.
85
Page 86
9. Mechanical characteristics
The UPSs Keor MOD are sold as empty power cabinets. It is necessary to purchase the power modules separately.
9.1 Cabinets
(all the dimensions are in mm)
(all the dimensions are in mm)
86
3 104 80 KEOR MOD 25-125 kVA 3 104 81 KEOR MOD 25-250 kVA
Page 87
Installation and maintenance manual
87
Page 88
9. Mechanical characteristics
88
Page 89
Installation and maintenance manual
89
Page 90
9. Mechanical characteristics
90
Page 91
9.2 Power module PM25
(all the dimensions are in mm)
Installation and maintenance manual
91
Page 92
9. Mechanical characteristics
9.3 Battery drawer
(all the dimensions are in mm)
92
Page 93
9.4 Battery block
(all the dimensions are in mm)
Installation and maintenance manual
93
Page 94
10. Technical data
Main features
Keor
MOD
25
Nominal Power
(kVA)
Active Power
(kW)
Number of power
modules
Technology
IN/OUT conguration Three-phase / Three-phase
Dual Input Available
UPS system Modular, expandable and redundant
Neutral system Neutral passing straight from input to output (not isolated)
Bypass
Overvoltage category OVC II
25 50 75 100 125 150 175 200 225 250
25 50 75 100 125 150 175 200 225 250
Keor
MOD
50
1 2 3 4 5 6 7 8 9 10
Keor
MOD
75
Keor
MOD
100
Automatic (static and electromechanical)
Keor
MOD
125
online, double conversion
VFI-SS-111 (EN62040-3)
Manual (for maintenance)
Keor
MOD
150
Keor MOD
175
MOD
Keor
200
Keor
MOD
225
Keor
MOD
250
Input electrical characteristics
Keor
MOD
25
Rated input current (A)
(full load and 400V
input voltage)
Maximum input
current (A)
(full load and 320V
input voltage)
Input voltage
(V)
Input frequency
(Hz)
Input Power Factor > 0.99
Total harmonic distortion
of the input current
Icp
Prospective short-circuit
current (kA)
37.6 75 113 150 188 225.6 263.2 300 338 376
47 94 141 188 235 282 329 376 423 470
Keor
MOD
50
Keor
MOD
75
Keor
MOD
100
(autosensing and/or selectable by the user)
Keor
MOD
125
400 + 15% - 20%
50 / 60 ± 14 %
THDi < 3% (at full load)
Keor
MOD
150
(3F+N+PE)
50 / 60 ± 2%
10
Keor MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
94
Page 95
Output electrical characteristics (normal mode)
Keor
MOD
25
Maximum output
current (A)
Output voltage
(V)
Output frequency
(Hz)
Range of the output
frequency
Crest factor admitted on the output current
Total harmonic distortion
of the output voltage
Eciency in Normal
Mode
Eciency in Eco Mode 99%
Overload capacity
Output electrical characteristics (battery mode)
36 72 108 144 180 216 252 288 324 360
Keor
MOD
50
If synchronized with the bypass frequency: adjustable range from ±1% to ±14%
Keor
MOD
75
125% for 10 minutes without automatic bypass intervention 150% for 60 seconds without automatic bypass intervention
Keor
MOD
100
If not synchronized (free run): ± 0.1 Hz
THDv < 0.5% (at full linear load)
THDv < 1% (at full non-linear load)
Keor
MOD
125
380/400/415 ± 1%
(selectable by the user)
up to 96.5%
50 / 60
3:1
Keor
MOD
150
Keor MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
Installation and maintenance manual
Keor
MOD
25
Output voltage
(V)
Output frequency
(Hz)
Total harmonic distortion
of the output voltage
Overload capacity 115% for 10 minutes
Shortcircuit
Keor
MOD
50
Keor
MOD
75
Keor
MOD
100
THDv < 0.5% (at full linear load)
THDv < 2.5% (at full non-linear load)
Keor
MOD
125
380/400/415 ± 1%
50 / 60 Hz ± 1%
Icc = 3 In for 50 ms
Icc = 1.45 In for 1 sec
Keor
MOD
150
Keor MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
95
Page 96
10. Technical data
Batteries and battery charger characteristics
Keor
MOD
25
Nominal battery
voltage (V)
Battery voltage
range (V)
Internal batteries: string made up of 2 drawers
Battery wiring
Battery type VRLA -
Unitary capacity
Type of battery charger
Maximum recharge
current (A)
Independent battery
conguration
Features
Keor
MOD
50
(composed by 4 blocks of 6 batteries)
Keor
MOD
75
External batteries
12 Vdc - 9 Ah
12 Vdc - 11 Ah
High performance PWM, one for each power module
Smart charge technology (3-stage advanced cycle)
Keor
MOD
100
± 288 (48 blocks)
± 264 to ± 312 (44-52 blocks)
5 (for each power module installed)
maximum 5 sets of independent batteries
(congurable as common or separate units)
Keor
MOD
125
Keor
MOD
150
Keor MOD
175
Only external batteries
Keor
MOD
200
-
Keor
MOD
225
Keor
MOD
250
Keor
MOD
25
Display 10-inch rotating colour touchscreen
Communication ports
Protections
Remote management available
Keor
MOD
50
Electronic against overloads, short-circuit and excessive battery discharge
Keor
MOD
75
Internal battery circuit fuses (for internal battery drawers)
Keor
MOD
100
2 x RS485 ports (one for external accessories)
Backfeed protections (NC/NO auxiliary contact)
Block of functions due to the end of autonomy
Keor
MOD
125
10 input oating contacts 8 output oating contacts
1 interface slot
USB host port
Emergency Power O (EPO)
In-rush limiter on start up
Keor
MOD
150
Keor MOD
175
Keor
MOD
200
Keor
MOD
225
Keor
MOD
250
96
Page 97
Mechanical characteristics
Keor
MOD
25
Empty power cabinet 3 104 80 3 104 81
Net weight (kg) 205 190
Dimensions H x W x D (mm)
Installable Power
modules PM25 3 106 75
PM25 net weight (kg) 22,5
Installable battery drawers
Weight of one battery
block (kg)
Weight of one battery
drawer with 4 battery
blocks (kg)
Environmental conditions
Keor MOD
25
Operating
temperature (°C)
Relative humidity
during operation
Storage
temperature (°C)
Noise level at 1 metre
(dBA)
Ingress Protection
Marking
Pollution degree PD2
Environmental category
(EN 60721-3-3)
Operating height up to 1000 metres above sea level without derating
Heat dissipation with
full load (BTU/h)
3560 7120 10680 14240 17800 21360 24920 28480 32040 35600
Keor
MOD
50
Keor
MOD
50
Keor
MOD
75
up to 5 up to 10
up to 10 -
17 (9Ah batteries)
19,2 (11Ah batteries)
72 (9Ah batteries)
81 (11Ah batteries)
Keor MOD
75
Keor
MOD
100
Keor MOD
100
-20 ÷ +50 (excluding batteries)
Keor
MOD
125
1990 x 600 x 970
Keor
MOD
125
0% ÷ 95% non-condensing
Keor
MOD
150
Keor MOD
150
0 ÷ +40
50 ÷ 65
IP 20
class 3K2
Keor MOD
175
Keor
MOD
175
Keor
MOD
Keor MOD
200
-
-
200
Keor
MOD
225
Keor
MOD
225
Keor
MOD
250
Keor MOD
250
Installation and maintenance manual
Reference directives and standards
Marks CE
Safety
EMC
Performance and test requirements EN 62040-3
Directive 2014/35/EU
EN 62040-1
Directive 2014/30/EU
EN 62040-2
97
Page 98
11. Tables
CAUTION
The choice of the type and section of the power cables must be done according to the voltage and rated current as well as the local wiring standards and regulations. It is a responsibility of the installation engineer. The input current and the output power of the UPS are indicated in chapter 10 and the battery current in table 4 of this chapter.
The following tables give an indication of the wire cross sections to use if the wires are unipolar with simple PVC installa­tion and installation in tube in the air.
TABLE 1 Minimum wire cross sections recommended for Keor MOD UPS
BYPASS CABLE
POWER INPUT CABLE
Phase: 1 x 95 mm
or 2 x 50 mm2 per pole
125 kVA
Neutral: 1 x 120 mm2
or 2 x 70 mm
2
2
(in case of separate
bypass line)
Phase: 1 x 95 mm2
or 2 x 50 mm2 per pole
Neutral: 1 x 120 mm2
or 2 x 70 mm
2
OUTPUT CABLE
Phase: 1 x 95 mm2
or 2 x 50 mm2 per pole
Neutral: 1 x 120 mm2
or 2 x 70 mm
2
250 kVA
Phase: 1 x 185 mm2
or 2 x 95 mm2 per pole
Neutral: 1 x 240 mm
or 2 x 120 mm
2
2
Phase: 1 x 185 mm2
or 2 x 95 mm2 per pole
Neutral: 1 x 240 mm2
or 2 x 120 mm
TABLE 2 Automatic breaker recommended for input and bypass line
POWER AUTOMATIC CIRCUIT BREAKER
125 kVA In=250 A curve C Icp=10kA
250 kVA In=630 A curve C Icp=10kA
TABLE 3 Residual current breaker recommended for input and bypass line
POWER RESIDUAL CURRENT BREAKER (In)
125 kVA
≥ 300 mA type B
250 kVA
Phase: 1 x 150 mm2
or 2 x 70 mm2 per pole
2
Neutral: 1 x 240 mm2
or 2 x 120 mm
2
98
Page 99
TABLE 4 Maximum current absorbed by the batteries at full load and minimum wire cross sections recommended for con­necting the UPS to the external battery units
POWER MAXIMUM BATTERY CURRENT MINIMUM WIRE CROSS SECTION
125 kVA 5 x 65 A 5 x 16 mm
250 kVA 5 x 130 A 5 x 35 mm
TABLE 5 External battery cabinets
CABINET
ITEM CODE
DIMENSION
SWITCHES AND PROTECTION KIT
L X D X H mm
3 109 65 1200 x 900 x 1900 1x FUSE HOLDER 3P NH2 400A - 3x aR FUSE 315A 70-93
3 109 67 1200 x 900 x 1900 1x FUSE HOLDER 3P NH2 400A - 3x aR FUSE 350A 105
3 109 44 1200 x 900 x 1900 1x FUSE HOLDER 3P NH1 250A - 3x aR FUSE 250A 55
3 109 89
2 cabinets
810 x 840 x 1900
2x FUSE HOLDER 3P NH2 400A - 3x gR FUSE 315A
2 cabinets
Installation and maintenance manual
2
2
BATTERIES
(Ah)
80
99
Page 100
LEGRAND Pro and Consumer Service BP 30076 - 87002 LIMOGES CEDEX FRANCE www.legrand.com
Installer stamp
Legrand reserves at any time the right to modify the contents of this booklet and to communicate, in any form and modality, the changes brought to the same.
Loading...