IMPORTANT – PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING.
Products Covered: FIT, 200-H/BTC, 241-H/BTC Style Service Heads, FP, and FIFP Style Faceplates.
Step 1. Core drill hole. Step 2. Remove junction box.
CAUTION: Holes shall be spaced a minimum of 2' [610mm]
on center and not more than one hole per each
65 sq. ft. [6 sq. m] of floor area in each span.
Step 3. BX/MC Connector (if applicable). Step 4. Prewire fitting (if applicable).
Connect the BX/MC Connector Install the connector plate
being applied to your application using the orientation
to the BX/MC Connector Plate. as shown. Be sure to
slide into slots located
at top of junction box.
NOTE: Fitting is supplied with a junction box bracket, a BX/MC NOTE: Fitting is supplied with a junction box bracket, a BX/MC
Connector Plate, and a junction box sleeve. The above Connector Plate, and a junction box sleeve. The above
instructions are for use if prewiring the fitting. instructions are for use if prewiring the fitting.
FIT Fire-Rated
Poke-Thru Series
INSTALLATION INSTRUCTIONS
Walker® electrical systems conform to and should
be properly grounded in compliance with
requirements of the current National Electrical
Code or codes administered by local authorities.
All electrical products may present a possible
shock or fire hazard if improperly installed or
used. Walker electrical products may bear the
mark as UL Listed and/or Classified and should
be installed in conformance with current local
and/or the National Electrical Code.
24" [610mm] Min.
Center – Center
BX/MC Connector
Remove Two Bottom
Screws and Junction Box
2" [51mm] Dia. Core-Drilled Hole
2 1/32" [52mm] Actual Diameter