Wall Plate-Mounted Movement Sensor EM803PIR, EM803PIRS
• There are 2 models as follows (see “Operation” for more details):
EM803PIR Basic model with Auto Mode only.
EM803PIRS Advanced model with Auto and Manual
Override Modes and user-selectable LED indicator colour.
• To access the additional features on the EM803PIRS model, it should be installed together with an additional push button EM800SLAVE or EM770X (not included) as shown in the image below. Please see “Wiring” for the connections between the two modules
Technical characteristics
Incandescent
+ 50oC
o
+ 0
C
230 - 240V a.c.
50Hz
Max load
1 x 2.5 mm
2 x 1.5 mm
2
2
LOAD
ACTIVE
NEUTRAL
1200W 1200W 500VA 500VA
REMOTE
(EM803PIRS only)
Halogen
Fluorescent
tube
500VA 500VA 500VA 500VA
Wirewound
transformer
Electronic
transformer
EM803PIRS
EM800SLAVE or EM770X
ED770/2GPLWE SWITCH PLATE SHOWN
Compact
Fluorescent
LED Fan
motor
Wiring
EM803PIR
LOAD
ACTIVE
NEUTRAL
ACTIVE
NEUTRAL
EM803PIRS
ACTIVE
NEUTRAL
REMOTE
ACTIVE
REMOTE
EM800SLAVE
LOAD
LOOP
OR
ACTIVE
NEUTRA
1
C
2
EM770X
Operation
Auto Mode – The load will turn on when movement is detected, and will stay on for a certain period of time after the last detected movement. The load will only turn on if the ambient light level is below a level set by the user (see “Lux Setting”). The time-out period is also set by the user (see “Time Setting”).
Manual Override Mode (EM803PIRS only) – If the push button is pressed while the load is off, the load will turn on. If it is pressed while the load is on, the load will turn off. In both cases, the movement sensor will be disabled for 5 minutes. After the 5 minute period, the EM803PIRS will revert to Auto Mode.
LED Indicator
• When power is first applied, the LED indicator will flash red, blue and purple for 5 seconds during the warm-up period before normal operation commences.
• The LED indicator will turn on while the load is on, and off while the load is off. When the load is already on, the LED indicator will blink momentarily if additional movement is detected. During the last 30 seconds before the timer expires, the LED indicator will flash quickly. If the time setting is set to less than 30 seconds, the LED indicator will start flashing as soon as the load turns on.
• For EM803PIR, the LED indicator colour is always red.
• For EM803PIRS, the LED indicator colour is red by default, but it can be toggled between red and blue by pressing and holding the push button for 10 seconds.
Lux Setting
• In Auto Mode, the movement sensor will only operate when the ambient lux level is below the threshold level set by the user. This is to prevent the load from coming on unnecessarily when there is sufficient light in the room.
• To adjust the threshold level, turn the Lux Setting knob using a small flat-head screwdriver. For a lower threshold level turn anticlockwise, and for a higher threshold level turn clockwise. For example, for the movement sensor to operate all the time (in normal daylight levels), turn fully clockwise.
• The threshold level can be adjusted between 1 lux and 2000 lux (figures are approximate only).
LOW LIGHT
LEVEL
1 LUX 2000 LUX
HIGH LIGHT
LEVEL
Time Setting
• When the load turns on in Auto Mode, it will remain on for a set period of time after the last movement is detected.
• To change this time period, turn the Time Setting knob using a small flat-head screwdriver. For a shorter time turn anticlockwise, and for a longer time turn clockwise.
• The time period can be adjusted between 5 seconds and 30 minutes (figures are approximate only).
DECREASE
TIME
INCREASE
TIME
User Controls
LUX SENSOR
TIME SETTING MOVEMENT SENSOR
LUX SETTING
& LED INDICATOR
Movement Sensor Range
DETECTION
40°
• The above diagram applies to both horizontal and vertical planes
AREA
5 METRES
Warranty
Legrand will honour all statutory guarantees that you as a consumer are entitled to rely upon under the Australian and New Zealand Consumer Law against a manufacturer including a guarantee that any products Legrand has manufactured or imported are of acceptable quality.
To make a claim under any statutory guarantee (or other warranty) you should first contact the supplier, contractor or retailer from whom you purchased the products.
LE07378AA
5 SECONDS 30 MINUTES
Important Information
• This product must be installed and used as per these instructions.
• This product must be installed by a licensed electrician.
• This product must only be used with the loads specied.
Other load types should only be used when written
conrmation is given by Legrand.
• Severe electromagnetic interference from other products may cause malfunction of this product.
• This product should only be cleaned with a damp cloth. Cleaning agents and solvents should not be used.
• This product contains no serviceable parts and no attempt should be made to repair this product. If the product is faulty it should be discarded.
• Legrand reserves the right to modify the specications of
this product at any time.
WARNING – DO NOT MEGGER THIS PRODUCT