Swifts® cable ladder ancillary items
AB CDE F G
Cover clip
(two fasteners per clip)
Overlap joint on 600 wide
(two fasteners per joint)
HJ KH
L
M
N
(four fasteners per joint)
HJ K H
L
M
Overlap joint on 750 and 900 wide
covers for straight lengths
150125100
Medium duty (Topaz), heavy duty (Sapphire) and extra heavy duty
(Emerald) use the same covers and closed / ventilated clips
Covers can be installed either by resting directly on the ladder side
rails (closed covers) or raised above the side rails providing a gap for
air to circulate (ventilated covers)
Covers up to 450 mm wide have a flat top surface and are simply buttjointed together. Covers 600 mm wide and above are overlapped and
bolted together to increase their rigidity. Covers 750 and 900 mm wide
have a stiffener fitted along the joint for added rigidity
All covers are 3 m in length and supplied with six cover clips and
associated fasteners
For ordering information, see p. 23
■ Installation (typical)
Closed cover installations
Up to 450 wide
600 wide and above:
overlap joint for
rigidity
750 and 900 wide
Ventilated cover installations
Up to 450 wide
■ Installation (typical) (continued)
Lid in run-off position
■ Assembly
Cover clip positions
Clips are fitted to the inside of both cover side flanges as shown; the
end clips provide anchorage for the joined ends of adjacent covers
Note
Covers can not be used when hanger rod brackets are fitted to ladder
Fasteners (included)
A Cover
B Side rail
C Cover clip
D M8 nut
E M8 form A washer
F Spring washer
G M8 x 16 setscrew
H Cover
J ‘U’-shape retaining nut
K M6 x 16 setscrew
L M6 form A washer
M Spring washer
N Stiffener
750 and 900 wide
Key : Replace the letter shown in red with your choice from the
following options :
W = Width (mm) 150, 300, 450, 600, 750, 900
F = Finish : G (hot dip galvanised after manufacture)
D (deep galvanised)
S (stainless steel)
E (powder coated)
600 wide and above :
overlap joint for
rigidity
Fastener finishes
For ladders with G and D finishes, fasteners are galvanised or zinc
plated. For ladders with S finish, fasteners are corrosion resistant
stainless Grade A470
For ladders with E finish, the fasteners are Grade 8.8 hot dip
galvanised
An alternative material for fasteners may be required depending on the
installation environment, for details contact
All dimensions (mm) are nominal
us on +44 (0) 845 605 4333
95

Swifts® cable ladder ancillary items
Cover
width
35
600-900
Ladder width
150-450
Ladder width
Cover
width
3 000
35
Eight 13 x 9·5
obround slots
for cover clips
Two Ø 9·5
holes
Two 18 x 8
slots
Eight 13 x 9·5
obround slots
for cover clips
3 000
TOP
TOP
TOP
44
96
38
Two 13 x 9·5
obround
slots
50
24
25 mm
Clip
Side rail
Cover
'U'-shaped
retaining nut
First cover
Second cover
'U'-Shaped retaining nut
First cover
Second cover
Stiffener
covers for straight lengths (continued)
150125100
■ Assembly (continued)
Covers
General
Before fitting the covers ensure
a minimum clearance of 30 mm
between the ladder and the vertical
support face. For access to fit
cover clips a larger clearance is
required when the vertical support
is a solid face
Closed covers
Place each cover over the ladder
side rails and push the clip under
the side rail return flanges before
fitting and tightening the fasteners
Ventilated covers
Slide the clips over the top return
flange of the ladder side rails and
place the cover over the clips. Fit
and tighten the fasteners
■ Dimensions and weights – covers
Widths 750 and 900 have two additional 18 x 8 slots and Ø 9·5 holes to
accept stiffener for added rigidity
Ladder Cover Weight
width (w) width (kg)
150 232 11·0
300 382 16·6
450 532 22·2
600 682 28·0
750 832 33·6
900 982 39·3
Key : Replace the letter shown in red with your choice from the
W = Width (mm) 150, 300, 450, 600, 750, 900
F = Finish : G (hot dip galvanised after manufacture)
96
following options :
D (deep galvanised)
S (stainless steel)
E (powder coated)
Wide covers – 600 mm and above
For wider covers with overlapped
joints, fit the first cover as above.
Push the ‘U’ shaped retaining
nuts over the holes in the overlap
tongue. Fit the second cover with
its straight end overlapping the
tongue on the first cover. Insert
fasteners and secure
700 and 900mm wide covers
For covers fitted with a stiffener,
assemble the covers as described
above and place the stiffener on to
the top cover along the joint. Insert
fasteners and secure
■ Dimensions and weights – clips
Weight: 0.5 kg per 4 clips
Weights
All weights given are in kilograms (kg) and are for hot dip
galvanised G finish
To obtain the appropriate component weight in other
finishes, multiply the given weight by the following factors :
Deep galvanised (D) x 1·07
Stainless steel (S) x 0·94
Powder coated (E) x 0·97
All dimensions (mm) are nominal