Medium duty (Topaz), heavy duty (Sapphire) and extra heavy duty
(Emerald) use the same covers and closed / ventilated clips
Covers can be installed either by resting directly on the ladder side
rails (closed covers) or raised above the side rails providing a gap for
air to circulate (ventilated covers)
Covers up to 450 mm wide have a flat top surface and are simply buttjointed together. Covers 600 mm wide and above are overlapped and
bolted together to increase their rigidity. Covers 750 and 900 mm wide
have a stiffener fitted along the joint for added rigidity
All covers are 3 m in length and supplied with six cover clips and
associated fasteners
For ordering information, see p. 23
■ Installation (typical)
Closed cover installations
Up to 450 wide
600 wide and above:
overlap joint for
rigidity
750 and 900 wide
Ventilated cover installations
Up to 450 wide
■ Installation (typical) (continued)
Lid in run-off position
■ Assembly
Cover clip positions
Clips are fitted to the inside of both cover side flanges as shown; the
end clips provide anchorage for the joined ends of adjacent covers
Note
Covers can not be used when hanger rod brackets are fitted to ladder
Fasteners (included)
A Cover
B Side rail
C Cover clip
D M8 nut
E M8 form A washer
F Spring washer
G M8 x 16 setscrew
H Cover
J ‘U’-shape retaining nut
K M6 x 16 setscrew
L M6 form A washer
M Spring washer
N Stiffener
750 and 900 wide
Key : Replace the letter shown in red with your choice from the
following options :
W = Width (mm) 150, 300, 450, 600, 750, 900
F = Finish : G (hot dip galvanised after manufacture)
D (deep galvanised)
S (stainless steel)
E (powder coated)
600 wide and above :
overlap joint for
rigidity
Fastener finishes
For ladders with G and D finishes, fasteners are galvanised or zinc
plated. For ladders with S finish, fasteners are corrosion resistant
stainless Grade A470
For ladders with E finish, the fasteners are Grade 8.8 hot dip
galvanised
An alternative material for fasteners may be required depending on the
installation environment, for details contact
All dimensions (mm) are nominal
us on +44 (0) 845 605 4333
95
Page 2
Swifts® cable ladder ancillary items
Cover
width
35
600-900
Ladder width
150-450
Ladder width
Cover
width
3 000
35
Eight 13 x 9·5
obround slots
for cover clips
Two Ø 9·5
holes
Two 18 x 8
slots
Eight 13 x 9·5
obround slots
for cover clips
3 000
TOP
TOP
TOP
44
96
38
Two 13 x 9·5
obround
slots
50
24
30 mm (min)
Cover
Clip
Side rail
25 mm
Clip
Side rail
Cover
'U'-shaped
retaining nut
First cover
Second cover
'U'-Shaped retaining nut
First cover
Second cover
Stiffener
covers for straight lengths (continued)
150125100
■ Assembly (continued)
Covers
General
Before fitting the covers ensure
a minimum clearance of 30 mm
between the ladder and the vertical
support face. For access to fit
cover clips a larger clearance is
required when the vertical support
is a solid face
Closed covers
Place each cover over the ladder
side rails and push the clip under
the side rail return flanges before
fitting and tightening the fasteners
Ventilated covers
Slide the clips over the top return
flange of the ladder side rails and
place the cover over the clips. Fit
and tighten the fasteners
■ Dimensions and weights – covers
Widths 750 and 900 have two additional 18 x 8 slots and Ø 9·5 holes to
accept stiffener for added rigidity
Key : Replace the letter shown in red with your choice from the
W = Width (mm) 150, 300, 450, 600, 750, 900
F = Finish : G (hot dip galvanised after manufacture)
96
following options :
D (deep galvanised)
S (stainless steel)
E (powder coated)
Wide covers – 600 mm and above
For wider covers with overlapped
joints, fit the first cover as above.
Push the ‘U’ shaped retaining
nuts over the holes in the overlap
tongue. Fit the second cover with
its straight end overlapping the
tongue on the first cover. Insert
fasteners and secure
700 and 900mm wide covers
For covers fitted with a stiffener,
assemble the covers as described
above and place the stiffener on to
the top cover along the joint. Insert
fasteners and secure
■ Dimensions and weights – clips
Weight: 0.5 kg per 4 clips
Weights
All weights given are in kilograms (kg) and are for hot dip
galvanised G finish
To obtain the appropriate component weight in other
finishes, multiply the given weight by the following factors :
Deep galvanised (D) x 1·07
Stainless steel (S) x 0·94
Powder coated (E) x 0·97
All dimensions (mm) are nominal
Page 3
Swifts® cable ladder ancillary items
Flat bend
cover
Tee
cover
4-way crosspeice
cover
Cover clips
Reducer
cover
Riser
cover
ABCDE F G
(two fasteners per clip)
Overlap joint on 600 wide
(two fasteners per joint)
HJ KH
L
M
N
HJ K H
L
M
Cover clip
Overlap joint on 750 and 900 wide
(two fasteners per joint)
covers for fittings
150125100
Covers are supplied to fit all fittings in the medium duty (Topaz), heavy
duty (Sapphire) and extra heavy duty (Emerald) cable ladder ranges
Covers can be installed either by resting directly on the fitting side rails
(closed covers) or raised above the side rails providing a gap for air to
circulate (ventilated covers)
Covers for fittings up to 450 mm wide are simply butt-jointed together
Covers 600 mm wide and above are overlapped and bolted together
to increase their rigidity. Covers 750 and 900 mm wide have a stiffener
fitted along the joint for added rigidity
All covers are supplied with the appropriate number of fasteners
■ Installation (typical)
Closed cover installation
600 wide and above:
interlock joint for rigidity.
750 and 900 wide
Ventilated cover installation
Up to 450 wide
■ Assembly
Cover clip positions
Clips are fitted to the inside of cover side flanges as shown ; the end
clips provide anchorage for the joined ends of adjacent covers
Note
Covers can not be used when hanger rod brackets are fitted to ladder
Fasteners (included)
A Cover
B Side rail
C Cover clip
D M8 nut
E M8 form A washer
F Spring washer
G M8 x 16 setscrew
H Cover
J ‘U’-shape retaining nut
K M6 x 16 setscrew
L M6 form A washer
M Spring washer
N Stiffener
To order a cover for a fitting, (except risers) remove first letter of fitting
product code (Z, P or E) and add CV before your chosen dimensions
Example :Product code = PFB 300 90 600 G
Cover code = FB CV 300 90 600 G
Riser covers are specific for Z, P or E
Key : selecting for ancillary items and covers. Replace the letters
shown in red with your choice from the following options :
W = Widths : 150, 300, 450, 600, 750, 900
Y = Ladder width reduction A = Angle (°) : 90 or 45
F = Finish :
r = Radius (mm) : 300, 600
G (hot dip galvanised after manufacture),
D (deep galvanised) S (stainless steel), E (powder coated)
Fastener finishes
For ladders with G and D finishes, fasteners are galvanised or zinc
plated. For ladders with S finish, fasteners are corrosion resistant
stainless Grade A470
For ladders with E finish, the fasteners are Grade 8.8 hot dip
galvanised
An alternative material for fasteners may be required depending on the
installation environment - contact
All dimensions (mm) are nominal
us on +44 (0) 845 605 4333
97
Page 4
Swifts® cable ladder ancillary items
Cover
Clip
Siderail
25 mm
Clip
Side rail
Cover
'U'-shaped retaining nut
First cover
Second cover
Stiffener
covers for fittings (continued)
■ Assembly
Closed covers
To fit covers as closed, fit the cover over the fitting side rails and place
the cover clips in position under the side rail return flanges. Fit and
tighten the fasteners
Ventilated covers
To fit the covers as ventilated, slide the clips over the top return flanges
of the side rails and place the cover over the clips. Fit and tighten the
fasteners.
150125100
Joining covers
When wide (600 mm or over) covers are fitted, the fitting cover may join
to either end of a straight length cover
If the straight cover has an overlap tongue, push ‘U’-shaped retaining
nuts over the holes in the tongue. Fit the fitting cover in position
overlapping the tongue. Insert fasteners through both covers and the
retaining nuts and tighten the fasteners
For 750 and 900 mm wide covers place the stiffener on to the top cover
along the joint before inserting the fasteners
If the straight cover has not got an overlap tongue, fit four ‘U’-shaped
retaining nuts over the holes in a joint strip and position the strip under
the butt-join between covers. Insert fasteners through each cover and
the two aligning holes in the joint strip and tighten the fasteners
For fitting a stiffener (covers 750 and 900 mm wide) refer to paragraph
above
Note
It may be necessary to drill holes in the straight cover if it has been cut
to length
Second cover
'U'-shaped
retaining
nut
First cover
■ Dimensions and weights – covers
For information on dimensions and weights for specific fitting covers,
contact us on +44 (0) 845 605 4333
Refer to p. 96 for cover clip dimensions and weights
98
Key : selecting for ancillary items and covers. Replace the letters
shown in red with your choice from the following options :
W = Widths : 150, 300, 450, 600, 750, 900
Y = Ladder width reduction A = Angle (°) : 90 or 45
F = Finish :
r = Radius (mm) : 300, 600
G (hot dip galvanised after manufacture),
D (deep galvanised) S (stainless steel), E (powder coated)
All dimensions (mm) are nominal
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.