Legrand EFBFF User Manual

Evolution Series
Legrand/Wiremold electrical systems conform to and should be properly grounded in compliance with requirements of the current National Electrical Code or codes administered by local authorities.
All electrical products may present a possible shock or fire hazard if improperly installed or used. Legrand/Wiremold electrical products may bear the mark of a Nationally Recognized Testing Laboratory (NRTL) and should be installed in conformance with current local and/or the National Electrical Code.
Furniture Feed Floor Box
I N S T A L L A T I O N I N S T R U C T I O N S
Installation Instruction No.: 1 009 727R1 – Updated October 2011
PRODUCTS COVERED: EFBFF, EFBFF-OG
CAUTION: Box is intended for use on carpet, tile or wood covered concrete floors.
CONCRETE POUR INSTALLATION (EFBFF, EFBFF-OG):
1. Position box in accordance with job site floor plan and/or engineering blue print. Use the dimensions give in the following table as a reference for positioning.
5 15/16" [151mm] 7 1/4" [184mm] 4" [101.6mm]
7 7/8"
[200mm]
Not designed for use on bare concrete or terrazzo floors
BOX DIMENSIONS
WIDTH LENGTH BOX HEIGHT
9 15/32"
[241mm]
Mudcap
7 3/8" [187mm]
Mudcap 6 11/16"
[170mm]
IMPORTANT: Please read all instructions
2. remove protective cover (Mudcap) from box.
before beginning.
3. Attach leveling skis to bottom of box using the nuts in the included sub-pack.
4. Remove required KOs from box and attach conduit fittings (not included) to box. Attach conduit to fittings.
CAUTION: Not designed for use on bare
concrete or terrazzo floors
5. Level box as required and anchor box to decking. To level, use 3/8-16 threaded rod (not included) cut to length as needed and secured with hex nuts (not included). Holes for threaded rod are provided in each end of the leveling bars. Be sure to set height of the top of the box to be flush with the finish level of the
oncrete pour.
c
NOTE: There is no provision for post pour
height adjustment.
6. Pour concrete flush with the top of the floor box protective cover.
WARNING: Pour concrete to within no more than 1/16"
[1.6mm] above box protective cover. Pours of 1/4" [6.4mm] or more over box cover will make it difficult to break out the cover and cause excessive concrete spalling around the edges of the box.
7. After concrete has cured, locate box and clear away
CAUTION: Not designed for use on bare
8. Pull wires as specified.
concrete or terrazzo floors
any concrete from cover as needed. Remove cover from box and clean out any debris from inside if box.
NOTE: Make sure that each compartment is properly
grounded in accordance with the National Electric Code and any local code that may apply.
9. Complete installation by attaching a Wiremold furniture feed cover (Sold separately), following the installation instructions supplied with the cover. Prior to installing the cover, it will be necessary to attach the divider top (provided with box) to the underside of the cover flange, using the two (2) flat head screws included in the divider top kit. Also make sure to attach the cover ground wire to the box ground.
NOTE: Evolution Series furniture feed floor
boxes and FloorPort™Series covers are cULus Listed for use with raised floors, wood floors, tile, carpet or wood-covered concrete.
NOTE: FPCTC and FPBTC Series
covers will work with EFBFF and EFBFF-OG Floor Boxes.
Loading...
+ 2 hidden pages