Legrand DSBEA User Manual

Solar panels supported by Delta Strut
on Metal Raised Seam Roof
C
A
Legrand Delta Strut Solar Systems have passed electrical/bonding testing per UL 2703. The following paragraph states the scope of the UL standards:
These requirements cover rack mounting systems and clamping devices for flat-plate photovoltaic modules and panels that comply with the standard for Flat-Plate Photovoltaic Modules and Panels, UL 1703, intended for installation on or integral with buildings, or to be freestanding (i.e., not attached to buildings), in accordance with the National Electrical Code, ANSI/NFPA 70 and Model Building Codes.
Installation Instructions:
1. Snap chalk lines for each DS (Delta Strut) stringer row. Rows should be located at even intervals allowing roughly 1/4 of the total PV length to overhang the top and bottom stringer (Allow 1/8” minimum between panel rows for expansion).
2. Install DS-S5 clamps to roof seams as required. Install on roof seams (not exceeding maximum span of 60” or roof loading requirements).
3. Attach DSBRSW washer to DS-S5 seam clamps using bolt provided. Then attach DS stringers to DSBRSW/DS-S5 assembly using DSPCC clamp and self-threading screws (sold separately). [Figure A]
4. Splice sections of DS together using a DSSA splice kit (install splices on both inside corners of DS for a single splice). Torque nuts to 6-8 ft/lbs. [Figure B]
FIGURE A
DSPCC
DSBRSW
DS-S5
For optimal holding strength, screw tension should be 160 to 180 inch pounds on 22 ga. steel and 130 to 150 inch pounds for all other metals and thinner gauges of steel.
FIGURE B
DSSA
Use two DSSA to splice any two sections of Delta Strut tray.
5. Pull string cabling into DS stringer row.
6. Position first PV panel at the beginning of first run, checking for position and square, then attach to DS using DSEHDC (End Bolt/Clamp). Torque nuts to 6-8 ft/lbs.
7. Connect PV cables to stringer cables and secure cabling to DS. Be aware that cabling is live at this point.
8. Add next PV panel in run. Use DSMHDC (Middle Bolt/Clamp ­Patent Pending) in areas where two panels adjoin, ending each row by utilizing a DSEHDC (End Bolt/Clamp). Torque nuts to 6-8 ft/lbs. [Figure C]
9. Each solar row to be connected to Earth as specified in NEC using proper sized ground conductor and UL Listed Split-bolt lug connected to Delta Strut. [Figure D]
FIGURE C
DSMHDC is spring-loaded and stays in position while panels are positioned.
FIGURE D
Use GNDSB split-bolt lug grounding connector to properly ground each solar support row.
DSMHDC
GNDSB
Solar panels mounted to Delta Strut
on Membrane Roof with Stanchions
D
E
C
A
Legrand Delta Strut Solar Systems have passed electrical/bonding testing per UL 2703. The following paragraph states the scope of the UL standards:
These requirements cover rack mounting systems and clamping devices for flat-plate photovoltaic modules and panels that comply with the standard for Flat-Plate Photovoltaic Modules and Panels, UL 1703, intended for installation on or integral with buildings, or to be freestanding (i.e., not attached to buildings), in accordance with the National Electrical Code, ANSI/NFPA 70 and Model Building Codes.
Installation Instructions:
1. Snap chalk lines for each DS (Delta Strut) support row. Rows should be located at even intervals (not exceeding maximum span of 60” or roof loading requirements).
2. Snap a second set of chalk lines at a right angle to position angle support legs. Actual spacing should be in accordance with the drawings provided with each DS shipment.
3. Install stanchions along support row according to manufacturer’s recommendations and roofing requirements. Install at even intervals with (not exceeding maximum span of 60” or roof loading requirements).
4. Attach DS to stanchions with DSPEBK (Pedestal Extension Bracket Kit). [Figure A]
5. Splice sections of DS together using a DSSA splice (install splices on both inside corners of DS for a single splice). Torque nuts to 6-8 ft/lbs. [Figure B]
6. Install and splice all DS rows before beginning next steps.
7. Install DSBEA (Angle Support Assemblies). Attach rear support to DS support first by pivoting leg forward then secure to DS using clamp and self­threading screw. Attach front clamp in the same manner. [Figure C]
FIGURE A
DSPEBK
Bolt is tightened using socket wrench or power drill thru access hole.
FIGURE B
DSSA
Use two DSSA to splice any two sections of Delta Strut tray.
FIGURE C
DSPCC
DSBEA
DSBPW
Self-threading screw is tightened using socket wrench or power drill thru access hole.
8. Install DS stringers to angle supports. Position DS in angle bracket saddle, then secure with a DSPCC (Connection Clamp and self-threading screw). [Figure D]
9. Splice sections of DS stringers together using a DSSA splice kit (install splices on both inside corners of DS for a single splice).
10. Position first PV panel at the beginning of first run, check for position and square, then attach to DS using DSEHDC (End Bolt/ Clamp). Torque nuts to 6-8 ft/lbs.
11. Add next PV panel in run. Use DSMHDC (Middle Bolt/Clamp ­Patent Pending) in areas where two panels adjoin. Torque nuts to 6-8 ft/lbs. [Figure E]
12. Pull feeder cabling into DS stringer row. Connect PV cables to feeder cables and secure cabling to DS. Be aware that cabling is live at this point.
13. Each solar row to be connected to Earth as specified in NEC using proper sized ground conductor and UL Listed Split-bolt lug connected to Delta Strut. [Figure F]
FIGURE D
Use punched pilot hole on either side of bracket to allow connection clamp clearance from cross wire.
FIGURE E
DSMHDC is spring-loaded and stays in position while panels are positioned.
FIGURE F
Use GNDSB split-bolt lug grounding connector to properly ground each solar support row.
DSPCC
DSMHDC
GNDSB
Solar panels mounted to Delta Strut
on Membrane Roof with Cablo-Port supports and hold down stanchions
E
B
D
A
Legrand Delta Strut Solar Systems have passed electrical/bonding testing per UL 2703. The following paragraph states the scope of the UL standards:
These requirements cover rack mounting systems and clamping devices for flat-plate photovoltaic modules and panels that comply with the standard for Flat-Plate Photovoltaic Modules and Panels, UL 1703, intended for installation on or integral with buildings, or to be freestanding (i.e., not attached to buildings), in accordance with the National Electrical Code, ANSI/NFPA 70 and Model Building Codes.
Installation Instructions:
1. Snap chalk lines for each DS support row. Rows should be located at even intervals with a maximum distance of 60”. Actual spans should be based upon roof loading requirements.
2. Snap a second set of chalk lines at a right angle to position angle support legs. Actual spacing should be in accordance with the drawings provided with each DS shipment.
3. Position each Cablo-Port support along support row at even intervals with a maximum distance of 60”. Always follow roof load requirements provided by a certified engineer. No gluing is necessary.
4. Install hold down stanchions along support row according to manufacturer’s recommendations and roofing requirements.
5. Lay-in sections of DS and insert into metal brackets on top of the Cablo-Port. Secure with fold down tabs. [Figure A]
6. Attach DS to hold down stanchions with DSBRSW washer and bolt. Torque nuts to 6-8 ft/lbs. [Figure B]
7. Splice sections of DS together using a DSSA splice kit splice (install splices on both inside corners of DS for a single splice). Install and splice all DS support rows before beginning next steps. [Figure C]
FIGURE A
Secure each Cablo-Port using only a screwdriver.
FIGURE B
DSBRSW
Use DSBRSW washer and bolt to secure array from wind lift.
FIGURE C
DSSA
Use two DSSA to splice any two sections of Delta Strut tray.
8. Install DSBEA (Angle Support Assemblies). Attach rear support to DS support first by pivoting leg forward then secure to DS using clamp and self­threading screw. Attach front clamp in the same manner. [Figure D]
9. Install DS stringers to angle supports. Position DS in angle bracket saddle, then secure with a DSPCC (Connection Clamp) and self-threading screw. [Figure D]
10. Splice sections of DS stringers together using a DSSA splice (install splices on both inside corners of DS for a single splice).
11. Position first PV panel at the beginning of first run, check for position and square, then attach to Delta Strut using DSEHDC (End Bolt/Clamp). Torque nuts to 6-8 ft/lbs.
12. Add next PV panel in run. Use DSMHDC (Middle Bolt/Clamp ­Patent Pending) in areas where two panels adjoin. Torque nuts to 6-8 ft/lbs. [Figure E]
13. Pull feeder cabling into DS stringer row. Connect PV cables to feeder cables and secure cabling to DS. Be aware that cabling is live at this point.
14. Each solar row to be connected to Earth as specified in NEC using proper sized ground conductor and UL Listed Split­bolt lug connected to Delta Strut. [Figure F]
FIGURE D
DSPCC
DSBEA
DSBPW
Self-threading screw is tightened using socket wrench or power drill thru access hole.
FIGURE E
DSMHDC is spring-loaded and stays in position while panels are positioned.
FIGURE F
Use GNDSB split-bolt lug grounding connector to properly ground each solar support row.
DSMHDC
GNDSB
Solar panels mounted to Delta Strut
on Membrane Roof with Pan Ballast
D
A
C
Legrand Delta Strut Solar Systems
E
have passed electrical/bonding testing per UL 2703. The following paragraph states the scope of the UL standards:
These requirements cover rack mounting systems and clamping devices for flat-plate photovoltaic modules and panels that comply with the standard for Flat-Plate Photovoltaic Modules and Panels, UL 1703, intended for installation on or integral with buildings, or to be freestanding (i.e., not attached to buildings), in accordance with the National Electrical Code, ANSI/NFPA 70 and Model Building Codes.
Installation Instructions:
1. Snap chalk lines for each DS support row. Rows should be located at even intervals with a maximum distance of 60”. Actual spans should be based upon roof loading requirements.
2. Snap a second set of chalk lines at a right angle to position angle support legs. Actual spacing should be in accordance with the drawings provided with each DS shipment.
3. Center each pan at the intersection of each chalk line to position it at the base of each angle support leg. Attach DS to proper sized DSXXX ballast pan with a DSPCC (clip) and bolt. [Figure A]
4. Splice sections of DS together using a DSSA splice (install splices on both inside corners of DS for a single splice). Torque nuts to 6-8 ft/lbs (see image above). [Figure B]
5. Load DSXXX ballast pans with concrete ballast on both sides of DS support row.
6. Install DSBEA (Angle Support Assemblies). Attach rear support to DS support first by pivoting leg forward then secure to DS using clamp and self­threading screw. Attach front clamp in the same manner. [Figure C]
FIGURE A
Load DSXXX ballast pans with standard 4” x 8” x 16” concrete blocks.
FIGURE B
DSSA
Use two DSSA to splice any two sections of Delta Strut tray.
FIGURE C
DSPCC
DSBEA
DSBPW
7. Install DS stringers to angle supports. Position DS in angle bracket saddle, then secure with a DSPCC (Connection Clamp) and self-threading screw. [Figure D]
8. Splice sections of DS stringers together using a DSSA splice install splices on both inside corners of DS for a single splice).
9. Position first PV panel at the beginning of first run, check for position and square, then attach to Delta Strut using DSEHDC (End Bolt/Clamp). Torque nuts to 6-8 ft/lbs.
10. Add next PV panel in run. Use DSMHDC (Middle Bolt/Clamp ­Patent Pending) in areas where two panels adjoin. Torque nuts to 6-8 ft/lbs. [Figure E]
11. Pull feeder cabling into DS stringer row. Connect PV cables to feeder cables and secure cabling to DS. Be aware that cabling is live at this point.
12. Each solar row to be connected to Earth as specified in NEC using proper sized ground conductor and UL Listed Split­bolt lug connected to Delta Strut. [Figure F]
FIGURE D
Use punched pilot hole on either side of bracket to allow connection clamp clearance from cross wire.
FIGURE E
DSMHDC is spring-loaded and stays in position while panels are positioned.
FIGURE F
DSPCC
DSMHDC
GNDSB
Self-threading screw is tightened using socket wrench or power drill thru access hole.
Use GNDSB split-bolt lug grounding connector to properly ground each solar support row.
Solar panels mounted Delta Strut
on Gravel Roof with Concrete Pier Ballast
C
A
Legrand Delta Strut Solar Systems have passed electrical/bonding testing per UL 2703. The following paragraph states the scope of the UL standards:
These requirements cover rack mounting systems and clamping devices for flat-plate photovoltaic modules and panels that comply with the standard for Flat-Plate Photovoltaic Modules and Panels, UL 1703, intended for installation on or integral with buildings, or to be freestanding (i.e., not attached to buildings), in accordance with the National Electrical Code, ANSI/NFPA 70 and Model Building Codes.
Installation Instructions:
1. Snap chalk lines for each DS support row. Rows should be located at even intervals with a maximum distance of 60”. Actual spans should be based upon roof loading requirements.
2. Snap a second set of chalk lines at a right angle to position DSCBP10-160 (concrete pier ballast). Actual spacing should be in accordance with the drawings provided with each DS shipment.
3. Place DSCBP10-160 (concrete pier ballast) using a dolly (or transfer bar).
4. Install DS stringers to DSCBP10-160 concrete pier ballast. Position DS stringer over poured-in metal mounting bracket and secure with a DSPCC (Connection Clamp) and self-threading screw. [Figure A]
5. Splice sections of DS together using a DSSA splice (install splices on both inside corners of DS for a single splice). Torque nuts to 6-8 ft/lbs. [Figure B]
FIGURE A
Concrete pier ballasts are weather resistant and keep array in place during high wind events.
FIGURE B
DSSA
Use two DSSA to splice any two sections of Delta Strut tray.
6. Position first PV panel at the beginning of first run, check for position and square, then attach to DS using DSEHDC (End Bolt/ Clamp). Torque nuts to 6-8 ft/lbs.
7. Add next PV panel in run. Use DSMHDC (Middle Bolt/Clamp ­Patent Pending) in areas where two panels adjoin. Torque nuts to 6-8 ft/lbs. [Figure C]
8. Pull feeder cabling into DS stringer row. Connect PV cables to feeder cables and secure cabling to DS. Be aware that cabling is live at this point.
9. Each solar row to be connected to Earth as specified in NEC using proper sized ground conductor and UL Listed Split­bolt lug connected to Delta Strut. [Figure D]
FIGURE C
DSMHDC is spring-loaded and stays in position while panels are positioned.
FIGURE D
Use GNDSB split-bolt lug grounding connector to properly ground each solar support row.
DSMHDC
GNDSB
Roof mounted solar panels supported by
Delta Strut and USS Angle Support
E
A
B/C
Legrand Delta Strut Solar Systems have passed electrical/bonding testing per UL 2703. The following paragraph states the scope of the UL standards:
These requirements cover rack mounting systems and clamping devices for flat-plate photovoltaic modules and panels that comply with the standard for Flat-Plate Photovoltaic Modules and Panels, UL 1703, intended for installation on or integral with buildings, or to be freestanding (i.e., not attached to buildings), in accordance with the National Electrical Code, ANSI/NFPA 70 and Model Building Codes.
Installation Instructions:
1. Snap chalk lines for each Universal Solar Support (USS) row. Rows should be located at even intervals with a maximum distance of 60”. Actual spans should be based upon roof loading requirements.
2. Snap a second set of chalk lines at a right angle to correctly position the Delta Strut stringers. Actual spacing will vary based upon PV panes size, angle and shading requirements.
3. Place USS according to chalk lines.
4. Load USS with concrete ballast blocks in each of the three cavities. Additional ballast can be added to each USS base by stacking ballast blocks on both sides of the base. This should be done within the loading requirements of the roof and the wind requirements of the array. [Figure A]
5. Install Delta Strut stringers to angle supports. Position Delta Strut using the built-in position tabs, then secure with a DSPCC Connection Clamp and self­threading screw. [Figures B, C]
FIGURE A
Load Universal Solar Support (USS) with standard 4” x 8” x 16” concrete blocks. Ballast blocks can be stacked for greater wind load requirements.
FIGURE B
Position Delta Strut stringers using built in positioning tabs on USS.
FIGURE C
DSPCC
6. Splice sections of Delta Strut together using a DSSA splice kit. Use both splices in the kit for a single splice. Torque nuts to 6-8 ft/lbs. [Figure D]
7. If you are using an Adjustable Universal Solar Support (USSA), you can adjust the support height to make allowances for low areas in the roof.
8. Attach cable bracing onto rear and front of USS supports using Cable Bracing Kit.
9. Place feeder cables into Delta Strut stringer row(s).
10. Position first PV panel at the beginning of first run, check for position and square, then attach to Delta Strut using DSEHDC End Bolt/Clamp. Torque nuts to 6-8 ft/lbs.
11. Add next PV panel in run. Use DSMHDC (Middle Bolt/Clamp ­Patent Pending) in areas where two panels adjoin. Torque nuts to 6-8 ft/lbs. [Figure E]
12. Connect PV cables and secure cabling to Delta Strut. Be aware that cabling is live at this point.
13. Each solar row to be connected to Earth as specified in NEC using proper sized ground conductor and UL Listed Split­bolt lug connected to Delta Strut. [Figure F]
FIGURE D
DSSA
Use two DSSA to splice any two sections of Delta Strut tray.
FIGURE E
DSMHDC is spring-loaded and stays in position while panels are positioned.
FIGURE F
DSMHDC
GNDSB
Use punched pilot hole in USS to allow connection clamp clearance from cross wire.
Use GNDSB split-bolt lug grounding connector to properly ground each solar support row.
Loading...