Legrand CSU User Manual

Syracuse, NY 13221-4822
800.223.4185 www.passandseymour.com
Installation Instructions
CSU Series
32kHz
Ultrasonic Occupancy Sensors
UNIT DESCRIPTION
COVERAGE PATTERNS
Visit our web site at www.passandseymour.com
UNIT PLACEMENT
tcerrocnItcerroC
FixturesFixtures
'01x'01'01x'01
Placement of ultrasonic sensors is critical for proper operation. It is best to place the sensor so that it has a clear view of all desktops and work surfaces within the coverage area. Orientation of the sensor is also important. The CSU600 offers 360° one-sided coverage while the CSU1100 and CSU2200 provide 360° two-sided coverage.
Transducers (the two or four small round openings on the cover of the sensor) operate in pairs (see the Coverage Patterns graphic, previous page), and the centerline of the pair must be oriented correctly for proper coverage.
Note:
• The transducer pairs orientation determines the coverage pattern.
• Sensors should not be mounted so that transducers point toward a wall that is within 4 feet of the sensor.
• Ultrasonic sensors may false trigger when exposed to high volumes of air flow. Sensors should be installed at least 4 feet from supply ducts and a minimum of 6 feet from horizontal discharge ducts.
• Do not mount sensors within 6 inches of a power pack.
• Always mount the sensor on a rigid vibration free surface.
• When mounting multiple sensors in a large room, do not mount the sensors within 10 feet of each other.
Open Office Sensor Placement
A typical layout for an open office space is to place the ultrasonic sensors so they control the office area in zones that overlap. A 20% coverage overlap is recommended.
Enclosed Office Sensor Placement
For smaller enclosed spaces, a CSU600 is recommended. Sensors should be placed so that they will not detect motion through an open door.
Transducers must face into the room and not be directed toward the closest walls or doors.
Call 800.223.4185 for Technical Support
Coverage
Overlap
(CSU2200
shown)
INSTALLATION
Note: Always try to attach the sensor to a vibration free surface.
Acoustic Tile Mounting
Install the Threaded Insert, flange side, into the hole on the back of the sensor and turn clockwise until it locks.
Keyhole Mounting
Positioning of keyhole mounting screws is important so that the transducer pairs point in the desired direction.
1. Use the template below to mark the location of mounting screws.
2. Install the provided screws—leaving approximately 3mm (1/8") space from the bottom of the screw head to the ceiling (see diagram).
3. Place the sensor’s mounting keyholes over screw heads and rotate sensor clockwise until secured.
Visit our web site at www.passandseymour.com
7/8" (22mm)
hole
Screws: 103mm (4.1") apart
Ceiling
Rotate clockwise
Space:
3mm/(1/8")
Nut
Washer
Threaded Insert
Ceiling Tile