LEGRAND 0 672 25, 0 784 85, 5 740 46, 5 740 96 User Manual

1/5
Catalogue number(s): 0 672 25 - 0 784 85 - 5 740 46/96
Switch sensor - PIR SCS
Technical data sheet: S000077071EN-2 Updated: 11/06/2014 Created on: 17/12/2012
1. USE
2. TECHNICAL FEATURES
Voltage: 27 V= No-load power consumption: 12 mA Connection between the sensor and the controller: BUS/SCS cable Wiring: 2 x 0.35 mm
2
Flush-mount box: 40 mm min. Weight: 60 g Impact resistance: IK04 Penetration by solid and liquid matter: - IP20 mechanism alone
- IP41 installed product with finger plate
Usage temperature: - 5°C to + 45°C Storage temperature: - 20°C to + 70°C Type of terminals: screw
CONTENTS Page
1. Use.....................................1
2. Technical characteristics . . . . . . . . . . . . . . . .1
3. Dimensions.............................1
4. Connection ............................1
5. Installation .............................2
6. Operation ..............................2
7. Settings ................................2
8. Configuration...........................3
9. Performance............................4
10. Maintenance............................5
11. Standards and approvals ................5
12. Troubleshooting ........................5
0 672 25 0 784 85 5 740 46
5 740 96
3. DIMENSIONS
35
45
45
51
4. CONNECTION
Pressing the auxiliary control enables the load to be switched on or off manually. If the control is not pressed, the sensor will cut off the load at the end of the time delay or when the light level threshold has been reached.
BUS/SCS
LEARN button
LED
Sensor / PIR Sensor
Light level cell
Detection LED
2/5
CONTENTS
Catalogue number(s): 0 672 25 - 0 784 85 - 5 740 46/96
Switch sensor - PIR SCS
Technical data sheet: S000077071EN-2 Updated: 11/06/2014 Created: 17/12/2012
5. INSTALLATION
5.1 Sensor positioning
5.2 Recommendation for measuring the light
5.3 Positioning
2.5 m
1 m
2.5 m
(*)
(
*
)
(
*) Not supplied
1
2
6. OPERATION
Auto ON/OFF mode:
The load will be switched on and off automatically.
Option: It is possible to control the sensor by infrared remote control
using: Cat. Nos. 0 882 20/31.
7. SETTINGS
7.1 Detection parameters
Time delay: Length of time the load is on after detection.
Sensitivity: Detection range setting.
Modes:
Auto on/Auto off mode:
Automatic switch-on:
- On detection of presence if the natural light level is insufficient. Automatic switch-off:
- If no presence is detected and at the end of the set time delay.
- Or if the natural light level is sufficient (regulation activated) Another detection causes automatic switch-on if there is insufficient light.
Walk-through mode:
- If no presence is detected in the 20 seconds following an initial detection, the product will cut off the load after 3 minutes.
- If another presence is detected in the 3 minutes following initial detection, the device will cut supply to the load at the end of the set time delay.
Manual on/Auto off mode:
Manual switch-on, automatic switch-off:
- When no presence is detected and at the end of the set time delay.
After switch-off, any new detection within a 30 second period triggers an automatic switch-on. The Restart function must be activated. After 30 seconds the device is switched on via a manual switch.
Sensor parameters Default
value
Modifiable parameters
Configuration
tools
0 882 30 0 882 35
Time delay 15 min
3, 5, 10, 15, 20 min
30 sec - 255 hr 59 min 59 sec
Sensitivity
PIR
(very high)
Low, medium, high, very high
Modes
Auto on/Auto off Inactive
Activate/ Deactivate
Walk-through mode
Active
Activate/ Deactivate
Manual on/Auto off
Inactive
Activate/ Deactivate
Partial on/ Group off
Inactive
Activate/ Deactivate
Detection
system
Initial PIR Not modifiable
Maintain PIR Not modifiable
Restart
PIR PIR, Deactivate
Alarm Inactive
Activate/ Deactivate