Wiremold Electrical Systems conform to and should be installed and properly grounded in compliance with requirements of the current National Electrical Code, Canadian Electrical Code or codes administered by local authorities.
All electrical products may represent possible shock or fire hazard if improperly installed or used. Wiremold electrical products are UL Listed to U.S. and Canadian safety standards, made for interior use only, and should be installed in conformance with current local and/or the National Electrical Code.
CABLE/WIRE SIZE O.D. 4015DFO
Inches [mm] 40% Fill
POWER WIRING
2 Awg 0.388 [9.86] 6
THHN/THWN 4 Awg 0.328 [8.33] 9
6 Awg 0.257 [6.53] 14 8 Awg 0.218 [5.54] 20 10 Awg 0.153 [3.89] 40 12 Awg 0.122 [3.10] 63 14 Awg 0.105 [2.67] 85
UNSHIELDED Cat. 5 UTP 0.220 [5.59] 19 TWISTED PAIR Cat. 3 UTP 0.190 [4.83] 26
2 Pair 0.140 [3.56] 28
Telephone 3 Pair 0.150 [3.81] 42
4 Pair 0.190 [4.83] 26 25 Pair 0.410 [10.41] 6
RG58/U 0.195 [4.95] 25
COAXIAL RG59/U 0.242 [6.15] 16
RG60/U 0.242 [6.15] 16 RG6/U 0.270 [6.86] 13
TWINAXIAL 100 Ohm 0.330 [8.38] 9
SHIELDED Type 1 STP 0.390 [9.91] 6 TWISTED PAIR Type 2 STP 0.465 [11.81] 4
Type 3 STP 0.245 [6.22] 16
FIBER OPTIC Fiber ZipCord 0.110 [2.79] 78
Round Fiber 2 Strand 0.180 [4.57] 29 Round Fiber 4 Strand 0.190 [4.83] 26 Round Fiber 6 Strand 0.210 [5.33] 21
4011FO
4015FO / 4015DFO
Use #8 (5/16" [7.9mm] head size) flat head fasteners or equivalent to mount base to surface.
RACEWAY WIRE AND FILL CAPACITY WHEN USING 4015DFO
4011FO/4015FO/4015DFO/ 4017FO/4018FO
INSTALLATION INSTRUCTIONS
Installation Instruction No.: 41398R1 – Updated July 2004
4017FO
4018FO
The Wiremold Company
U.S. and International: 60 Woodlawn Street • West Hartford, CT 06110 1-800-621-0049 • FAX 860-232-2062 • Outside U.S.: 860-233-6251 Canada: 850 Gartshore Street • Fergus, Ontario N1M 2W8 1-800-741-7957 • FAX 519-843-5980
41398R1 – Updated July 2004 – For latest specs visit www.wiremold.com
© Copyright 2004 The Wiremold Company All Rights Reserved