Legendfires Ethos 3S Installation And User Instructions Manual

Ethos 3S
- Live Fuel Effect Radiant Convector Stove
Installation and Users Instructions
These instructions should be read by the installer before installation and then should be handed to the end user when the installation is complete.
Having installed the appliance, the installer should take the necessary steps to ensure that the user fully understands how to operate the appliance and is also made aware of the fire’s basic cleaning and maintenance requirements.
CONTENTS
SECTION PAGE
Notes for the Installer and End User 3
Installation Requirements 6
Installation Procedure 7
Installation Procedure for Class One Closure Plate 8
Commissioning 9
Technical Data 11
Replacement Parts 11
Trouble Shooting (GAS SAFE Engineer Only) 11
User Instructions 14
Cleaning and Maintenance (GAS SAFE Engineer Only) 19
Log Layout Instructions 20
Trouble Shooting (User) 24
Guarantee 24
2
NOTES FOR THE INSTALLER AND END USER
This appliance has been designed, tested and manufactured to EN613 with references to British Standard BS 7977-1:2009 Class 1 & 2 relating to Radiant Convector Gas Appliances and must be installed by a qualified Gas Safe Registered Installer in accordance with the Gas Safety (Installation and use) regulations 1994 and all other relevant standards. This appliance is intended for use on a gas installation with a governed meter.
This appliance must be connected in accordance with the National Regulations. The appliance must be sealed into a non-combustible fireplace whose only opening must be through a Class I (7” or 175mm diameter) or Class II (5” or 125mm diameter) chimney / flue of at least three metres in height.
Before installation, ensure that the local conditions, (identification of gas type and pressure) and the adjustment of the appliance are compatible. Base temperatures of this appliance are quite low so it can be placed directly onto timber or laminate flooring. However, due consideration should be taken if installing directly onto materials such as deep pile carpets or similar combustible materials, in these circumstances a non-combustible hearth of 12mm minimum thickness should be used. This hearth should extend by 50mm minimum in all directions from the stove base.
Dimensions
580mm
Minimum Clearances Closure Plate Installation
225mm*
138mm
138mm
341mm500mm
Fig. 1
70mm minimum
50mm
minimum
Fig. 2
NOTE: Builders opening to be constructed of non-combustible materials.
* If using a wooden lintel, a minimum clearance of 225mm is required from the top of the stove to the underside of the lintel.
3
NOTES FOR THE INSTALLER AND END USER
This fire is a very effective heating appliance and must be fitted against a wall of non-combustible material as classified in BS 476-4:1970 (2007).
All parts of the appliance become hot while running and should therefore be considered to be working surfaces.
An air vent is not required for this application. The appliances have been tested without the need for additional air requirements.
We recommend that if the chimney/flue has been used for solid fuel, it is swept prior to installation of this appliance and that any flue restrictor or damper plate should be removed.
The chimney/flue must always generate a positive up draught to ensure safe operation.
The installer must then establish that all the products of combustion are entering the flue within ten minutes of lighting from cold. This can be verified by inserting a lit smoke match into the central duct immediately below the stove top panel. It should NOT be inserted into the left and right convector ducts. (see ‘Spillage Test’ page 6).
An isolation valve must be fitted adjacent to the appliance. When closed, this will allow the complete burner and control assembly to be disconnected for maintenance or repair in accordance with national regulations.
The gas supply should be provided by a semi rigid pipe with an 8mm diameter and should be no longer than 1.5 metres in length.
NOTE: When the gas supply pipe is passed through masonry or other brickwork always ensure that the end of the pipe is covered to avoid any debris passing through into the appliance controls.
The appliance is fitted with an Oxygen Depletion Sensor (ODS) that monitors the room for products of combustion. If products are detected, the ODS will automatically shut down the appliance. If this situation arises, re-light the appliance, referring to the user instructions (page 14).
If shut down re-occurs, a qualified person must be called to thoroughly check the appliance. The spillage monitoring system (ODS pilot) must not be put out of operation or be tampered with or adjusted by either the installer or the user. If the unit is found to be at fault it should be replaced with the manufacturers original replacement parts.
Fig. 3
4
Class one closure plate Class two copex offset spigot Class two copex top outlet
NOTES FOR THE INSTALLER AND END USER
Debris collection space for class one chimneys using closure plate
A debris collection space should be provided at the base of a flue unless it is lined or constructed of flue blocks, or is a factory made metal chimney with a flue box. This can be achieved by providing a space having a volume of not less than 12 litres and a depth of at least 150mm below the point where flue gases discharge into the chimney. The space should be readily accessible for clearance of debris, for example by removal of the appliance.
Deflector Panel (LEG-DDP01) shown fitted to larger plate LEG-DDP02
150mm
Fig. 3a
If the Debris Deflector Panel LEG-DDP01 is to be used, this must be installed into Class 1 brick constructed chimneys only and having a cross sectional area of not less than 52,258mm sq (9”x9”). The deflector panel should be fixed to a register plate of a minimum size of 776mm wide x 440mm deep. The height from the register plate up to the intersection with the flue should be not less than 150mm. The cut-out size in register plate to accommodate the Debris Deflector Panel should be 360mm long x 215mm wide.
Deflector Panel Catchment Space
150mm
Fig. 3b
The installer shall confirm that the chimney is in good condition and has passed a flue performance test before the appliance can be installed with the flue kit. The following warning attached to the deflector panel should also be observed:
WARNING: This appliance is installed to an unlined chimney. For examination of the debris void and condition of the chimney, refer to the appliance manufacturer’s instructions or remove the whole firebox.
5
INSTALLATION REQUIREMENTS
This appliance must only be installed in Great Britain or Ireland.
1. This fire is a natural gas appliance and has been designed for use with the following applications: a) Class I - Conventional brick or stone chimney as used for a solid fuel fire with a cross sectional dimension of
225mm x 225mm (9” x 9”) or a lined flue with a minimum diameter of 125mm (5”), with the fireplace components conforming to BS1251, or a standard builders opening a minimum of: 560mm (22”) high and 406mm (16”) wide with a minimum depth of 100mm (4”) to allow sufficient volume for debris collection (unlined chimney 12 dm lined 2 dm
3
). Any permanent flue restrictions or variable dampers are to be removed or locked in the fully open
position. The chimney should also be swept prior to installation.
b) Class II - An insulated flue (twin wall) having a minimum diameter of 125mm (5”) and a minimum effective overall height of 3 metres (10’).
NOTE: If the fire is to be used with an existing brick or stone chimney, a 125mm (5”) minimum diameter flue liner conforming to BS715 may be used.
2. Care should be taken to prevent any damage being caused to surrounding soft furnishings or decoration, e.g. many embossed vinyl wall coverings may become discoloured if placed too close to the appliance.
3. A suitable proprietary fire surround with 100°C rating may be used with a minimum clearance from the top of the stove to the underside of shelf of 225mm, providing that the depth of shelf is 150mm or less. It is recommended that combustible materials are not placed adjacent to this appliance unless shielded with a fire resistant surface 25mm minimum thickness.
FLUE FLOW TEST
A flue flow test (smoke test) is carried out to check the effectiveness of the flue and to ensure that there is no leakage into another part of the premises (including any loft), or as appropriate other adjoining premises (this is particularly important where a number of chimneys combine into a multiple stack).
The flue flow test should be carried out using a suitable smoke pellet which the pellet manufacturer claims to generate 5m
3
of smoke in 30 seconds burn time.
These gas fires should have the flue flow test carried out with the appliance in position but not connected to the gas supply so that the smoke test can be carried out with representative flue flow conditions.
A warm flue will be more effective than a cold flue. If the flue is reluctant to draw, which can be initially assessed by lighting a smoke match at the intended position of the appliance flue connection, introduce some heat into the flue for a minimum of 10 minutes using a blow torch or other means.
Other factors, such as weather conditions and a combination of materials used to construct the flue can all influence the flue draught. The pre-heating process may require as much as half an hour before the flue behaves satisfactory as a blow torch does not represent the volume of heat consistent with the normal appliance operation.
3
and
A Flue Flow Test should be checked as follows:
1. Carry out those visual checks as indicated previously, and continue only if satisfactory.
2. Establish that an adequate air supply is available for the combustion of the appliance
3. Close all doors and windows in the room that the appliance is to be installed.
4. Light a smoke pellet at the intended position for the appliance. Place the inset fire case into position.
5. The test is satisfactory if:
- there is no significant escape of smoke from the appliance position.
- there is no seepage of smoke over the length of the flue.
- smoke is discharged only from the correct terminal.
VENTILATION
No special ventilation bricks or vents are required in the room containing the appliance, providing that normal adventitious room ventilation exists. The installer must determine this by carrying out a spillage test.
SPILLAGE TEST
To check for satisfactory clearance of products of combustion, close all doors and windows and leave the fire burning on high setting for a minimum of ten minutes. The left and right hand ducts are for convection only. The central duct above the glass door has a visible hexagonal post in the middle, this post indicates the approximate depth to place a lit smoke match. All the smoke must be drawn into the flue. If spillage occurs, allow a further ten minutes and repeat the test. Should spillage still occur turn the appliance off and seek expert advice. To continue the test: If an extractor fan is situated in the room the test should be repeated with the fan running. If there is a connecting room with an extractor fan the test should be repeated with all the doors to that room open and the extractor fan running.
6
INSTALLATION PROCEDURE
Fig. 4
Top Cover
Fig. 5
Frame
Bottom Cover
1. Slide forward and remove the top and bottom covers from the front of the stove (Fig. 4).
2. Remove the six screws from the clamp securing the top of the glass panels and slide frame out forwards. (Fig. 5).
3. Remove the two side panels by lifting up and swinging out from the bottom, then slacken the six screws (3 on each side) releasing the glass (Fig. 6).
4. Carefully slide the glass out forwards (Fig. 7).
5. Withdraw the black internal top panel (Fig. 8).
6. Lift off the black burner grille. Note - pilot tab to be at the front on re-assembly (Fig. 9).
7. If necessary remove fire box liners to avoid damage during the installation process (Fig. 8).
8. Slide forward the lower controls heat shield and gas connection cover panel (Fig. 9).
9. Position and level the stove using the adjustable feet.
Securing Screws
Fig. 6
Side Panels
3 x Clamping Screws
Fig. 9
Black Internal Top Panel
Fire Box Liners
Fig. 8
Tab
Fig. 7
Glass
Black Burner Grille
Gas Connection Cover Panel
Lower Controls Heat Shield
7
INSTALLATION PROCEDURE FOR CLASS ONE CLOSURE PLATE
1. Fit the neoprene seal around the outer edge of the closure plate.
110mm
min
188mm
Centre Line
160mm
max
Drill Holes for 4 eye bolts
on 188mm centre lines
between max and min height.
188mm
407mm
min
457mm
Fig. 10
max
2. Mark off the rear of the builders opening, then drill the four holes for the wall plugs (Fig.10).
3. Fit the eye bolts.
4. Bring the 8mm gas supply in at the relevant position (rear or base).
5. Remove the left and right glass clamps to reveal the cable fixing holes (Fig.11).
6. Feed the two cables through the two 2mmØ holes in the stove back and then through the two 2mmØ holes in the closure plate (Fig.12).
7. Route the cables through the eye bolts and back through the closure plate and into the lower holes (6mmØ) in the stove back (Fig.12).
8. Push the stove and closure plate back to seal tightly against the fireplace back panel/wall (Fig.12).
Fig. 11
Eye Bolts
Closure Plate
Glass Clamp
Tension Nut
Cable Clamping Screw
Hearth
8
Fig. 12
COMMISSIONING
Fig. 13
M5 Machine Screws
Burner Assembly
Inlet Pressure
Test Point
1. Remove the burner assembly (2 x wing nuts) and chosen gas inlet plate in the base or the rear. (Fig. 13).
2. Relocate the burner assembly and mark/cut gas pipe to length, then secure burner assembly with the M5 machine screws and connect the gas pipe and purge. (Fig. 13).
3. Connect manometer to pressure test point on the brass Pressure Test elbow and ignite the burner to check working pressure and gas rate see (page 11). Note: the gas rate is factory set and is not adjustable without specialised Legend equipment.
Gas Connection Cover Panel
Lower Controls Heat Shield
Fig. 14
4. Refit heat shield, gas connection cover panel must be always fitted (Fig. 14).
9
COMMISSIONING
Black Internal Top Panel
Fire Box Liners
Tab
Fig. 15
5. Refit all the back-side liner components and slide black top panel back into position (Fig. 15).
6. At this stage locate the burner top grille on the tabs provided before slotting the remaining liner blocks into position (Fig. 16).
Note: The pilot tab should be positioned at the front (Fig. 16).
Fig. 16
Fig. 17
Black Burner Grille
7. Follow log layout guide (pages 20-22) fitting rear log and bark chippings around the black grille and not on top of the burner skin.
8. Replace the glass and frame and secure with six 6mm machine screws (Figs. 7,6,5).
9. Switch on the appliance and carry out smoke testing as laid out on page 6.
10
Glass
TECHNICAL DATA
Model Ethos 3S Stove
Gas Type Natural Gas Gas Category I Gas Type G20 Inlet Pressure (mbar) 20 Countries of Destination See table below Gas Valve TESC-01 RF 868-30 Injector Size Bray 82/360 Oxypilot ERTA PG-82-650 Gas Rate Full Reduced Nominal Heat Input (Gross, kW) 5.5 1.9 Nominal Gas Flow Rate (m Efficiency (net) 84 Efficiency Class 1 NOx Class 4 Weight (kg) 51.25 kg Countries of Destination AT, BG, CH, CZ, DK, EE, ES, FI, GB, GR, HR, IE, IT, LT, LV, NO, PT, RO, SE, SI, SK, TR
REPLACEMENT PARTS
2H
3
/h) 0.524 0.181
1. Log Set - The ceramic logs supplied with this appliance can be replaced at service intervals depending on their condition. If the logs do require replacement, the consumer can do so provided that the Ceramic Component Layout Instructions (pages 20-22) are adhered to. Under no circumstances should additional/extra logs be added. Only genuine Legend replacement parts should be used. Order Ref: ETHLOG3S
2. Oxygen Depletion Sensing Pilot - In the unlikely event of a pilot failure, the pilot assembly should only be replaced by a Gas Safe Registered Engineer. The user must not carry out this work. Order Ref: ETH01
3. TESC Valve - In the unlikely event of control valve failure, the assembly should only be replaced by a Gas Safe Registered Engineer. The user must not carry out this work. Order Ref: ETH02
4. Glass Panel - Should the glass become cracked or broken, the fire should not be used under any circumstance. Order Ref: ETHGLAS3S
5. Glass Rope Seal - The integrity of the glass rope seal should be checked on service and replaced if necessary by a Gas Safe Registered Engineer. Order Ref: ETHSEA3S
6. Remote Control Display Handset - Order Ref: ETH04
TROUBLE SHOOTING (GAS SAFE ENGINEER ONLY)
NOTE: The purpose of the Error code is to give some information as to the potential reason for the fire not
starting rather than just no flame. The appearance of an error code does not mean there is necessary a fault with the control or the appliance, it could be external factors outside the control that could cause error codes to appear from time to time and they could just be a one off event , so please check and work through the suggested service actions below before considering changing the control box. These codes are there to help with a more certain and efficient servicing of the appliance. Changing the box without working through the guide could lead to an unnecessary and expensive service and probably a repeat visit to fix the real fault.
SERVICING MUST ONLY BE CARRIED OUT BY COMPETENT PERSONAL WHO HAVE CURRENT QUALIFICATIONS AND ACCREDITATION (I.E. GAS SAFE)
NOTE: After correcting fault, perform a restart to reset error display to normal standby mode. Also depending
upon the repair, air will need to be bled out of the system and it may take several start attempts to do so. E00 may appear and need to be reset a few times during the purging process, depending upon the length of supply pipe. Bleeding the supply pipe via the isolation valve pressure test point will help speed up this process.
NOTE: Before undertaking any actions on the servicing as detailed below , replace the batteries in the control and handset (if applicable) with new and know to be good batteries. Faulty batteries will cause error codes. There is a difference between old and faulty batteries and they may give false errors if the batteries are faulty.
ALWAYS CHANGE ALL THE BATTERIES TOGETHER AND NOT JUST ONE OR TWO AND ALWAYS OF THE SAME MAKE AND TYPE (I.E MANUFACTURER AND MODEL TYPE).
Generally : After replacing the batteries, to clear the error code perform a start cycle by pressing the start button as normal. Then press again in the same way to attempt a new start cycle. The error code must be cleared this way after every error code is displayed to start again.
11
TROUBLE SHOOTING (GAS SAFE ENGINEER ONLY)
Reset control by pressing start button for 1 second and releasing. Then press again the same way to attempt a normal start command. Repeat up to 10 times as necessary to see if this overcomes the issue as it may resolve itself eventually.
Check to see if gas is present at gas appliance inlet. (Check gas supply is on, the gas line purged of air and the supply pipework is free of blockages or contamination)
Rectify and perform start cycle to clear the Error code. Try to light the fire as normal.
No gas on appliance inlet
Clean the pilot free of any dirt, dust carbon granules or lint, especially around the brass body of the bunsen burner and its gas and electrical connection and the area around the flame ports and the spark plug and electrode tip. Check the electrode gap is 3- 4 mm.
Rectify and perform start cycle to clear the Error code. Try to light the fire as normal. Replace pilot if necessary
Pilot contaminated with lint or other materials
Check ignition cable for damage and listen and watch for tracking out of spark to see if it is present but not making it to the electrode tip on the pilot burner.
If cable damaged, replace cable. Reset error by performing a normal start cycle and try to start again. Replace pilot if necessary.
Reset and try again
Reset and try again
No Spark at Electrode (fire not igniting pilot burner)
Clear pipe and consider changing pilotPilot pipe or pilot injector
could be blocked)
E00
Code Comment Apperance Possible Cause Action
TESC locked due to failed ignition
Red Led is permanently on TESC unit ( and E00 on handset, if used)
Temporary air disturbance around pilot burner
Check pilot pipe, check flame appearance of pilot flamesE01 Low current from thermocouple but flame: possibly CO alarm
Flashing Red LED on TESC C ontrol
Pilot pipe blocked - no gas reaching pilot burner
Occurs if started ok then subsequently loss of thermocouple current. Check for flue problems. Fire
cuts out to prevent over heating
E02 Too high ambient
temperature ( >73 °C) around control
Negative flue pull or blocked flue or similar
Reset and try againCheck if connected correctly and terminations are soundE03 No, defective, or bad connected thermocouple
Bad connection
Reset and try againSensing flame on pilot when no flame should be there. Investigate.E04 False flame signal Occurs during stopping
fire
Reset and try againReplace batteriesE06 Too low voltage on power supply to start the burner
Weak or old or defective batteries
Reset and try againReplace batteries / power adaptorE07 Power supply breakdown during peak current consumption
Check/change all the batteries or check power adaptor. : Note always change all batteries together never only 1 or 2
Reset and try againReplace if necessaryE08 Error caused by external pressure switch
Check the pressure switch
Reset and try againCheck pressure switch connections, check to see if jumpers are in place on back of TESC.E09 Error caused by external pressure switch
Pressures switch action connection or jumpers missing or not connected properly
Reset and try againCheck pressure switch connections, check to see if jumpers are in place on back of TESC.E10 Error caused by external pressure switch
Pressure switch action connection or jumpers missing or not connected properly
Reset and try againCheck switch for damage, contamination across terminals or damaged wiring. Disconnect wired
thermostat if fitted and try a start, if it works replace thermostat
E11 Short circuit on wired
thermostat (if used)
Check switch
Reset and try againCheck switch for damage, contamination across terminals or damaged wiring. Disconnect wired
thermostat if fitted and try a start, if it works replace thermostat
E12 Open circuit on wired
thermostat (if used)
Check wiring and thermostat
Reset and try againCheck switch for damage, contamination across terminals or damaged wiring. Disconnect wired
thermostat if fitted and try a start, if it works replace thermostat
E13 Wired thermostat is
out of tolerance
Check wiring and thermostat
Reset and try againClean as necessary. Replace switch panel as necessary if damaged or too contaminated.
disconnect wired control panel and try again – if it works replace wired control panel
E14 Button (-) sticks
either on TESC or on wired control panel (if used)
Check for contamination around buttons
Reset and try againClean as necessary. Replace switch panel as necessary if damaged or too contaminated.
disconnect wired control panel and try again – if it works replace wired control panel
E15 Button (+) is shorted
to other buttons either on TESC or on wired control panel (if used)
Check for contamination/ damage
Reset and try againClean as necessary. Replace switch panel as necessary if damaged or too contaminated.
disconnect wired control panel and try again – if it works replace wired control panel
E16 Button (ON/OFF) is
shorted to other buttons either on TESC or on wired control panel (if used)
Check for contamination / damage and replace wired switch panel if necessary
Reset and try againJumpers on back of valve missing
Check to see if jumpers are in 10 way connector
Reset and try againCheck and clean around the area of the pilot for lint and other contamination. Check where the
thermocouple connects to the TESC control for the same contamination. Clean these areas.
E05 False flame signal Flame sensing on pilot
before start of ignition sequence or after valve has shut off. Contamination of electrode to ground
Reset and try againReplace PilotDefective thermocouple
Check and clearBlocked flue
Reset and try again
Check manual for correct placementPoor position of
Ceramic parts
Check flueChimney blocked causing Co / Co2 to build up in the room build
Change pilot or thermocouplePilot thermocouple defective / old
Clear error and restart to check ignition okPossible temporary air disturbance on pilot flame
12
TROUBLE SHOOTING (GAS SAFE ENGINEER ONLY)
Reset and try againClean as necessary. Replace switch panel as necessary if damaged or too contaminated.
disconnect wired control panel and try again – if it works replace wired control panel
E17 Button (-) is shorted
to other buttons either on TESC or on wired control panel (if used)
Check for contamination / damage and replace wired switch panel if necessary
Reset and try againClean as necessary. Replace switch panel as necessary if damaged or too contaminated.E18 Button (AUX) is shorted to other buttons on switch panel
Check for contamination / damage and replace wired switch panel if necessary
Reset and try againCheck if wired correctly and replace IR eye if necessaryE19 Infrared receiver defective (if used)
Check connection of IR or damage - replace if necessary IR eye
Reset and try againCheck if wired correctly and replace IR eye if necessaryE20 Illegal setup parameters
Check connection of IR or damage - replace if necessary IR eye
Reset and try againUsually only a factory assembly error. Could happen if done in error in servicing.E21 Tried to config a TESC as Clusterslave while a wired thermostat is connected
Factory assembly warning on setup configuration not a maintenance error
Reset and try againDisconnect thermostat before attempting using Easy test unit.E22 Tried to calibrate TESC with TESC easy test while a wired thermostat is connected
Not field error
Reset and try againIndicated that control has performed a high number of operations and so fire should be serviced and
control replacement should be considered as preventative maintenance. (should not really occur before 10 years from new).
E23 Warning: end of life is
near, should be replaced soon
Not field error
Reset and try againCheck and correct Thermocouple wiring. Replace thermocouple if necessaryE24 Thermocouple doesn't reach final current - damaged or aged
Replace Pilot
Reset and try againCheck pilot thermocouple connections and connections to TESCE25 Poor thermocouple signal
Tired or bad connection of thermocouple or bad or unstable flame on pilot or poor grounding return
Reset and try againReplace with new USB power supply of the correct type.E26 Defective or wrong wired USB-power supply
Try again and if repeatedly fails replace
Reset and try againCheck and correct Thermocouple wiring. Replace thermocouple if necessaryE48 Short circuit on thermocouple, or thermocouple reversed polarity
Wrongly wired
Reset and try againCheck if and clean around the area of the pilot for lint and other contamination and clean. Check
where the thermocouple connect to the TSC control for the same contamination. Clean these areas.
E49 False flame signal Flame detected during
operation of fire when it should not be detected ­contamination of electrode circuit to ground
Reset and try againCheck if and clean around the area of the pilot for lint and other contamination and clean. Check
where the thermocouple connect to the TSC control for the same contamination. Clean these areas.
E50 Internal error
Reset and try againCheck pressure switch connections , check to see if jumpers are in place on back of TESC.E51 Error caused by external pressure switch
Reset and try againE52 Error
Reset and try againE27 Error
Reset and try againE28 Error
Reset and try againE29 Error
Reset and try againE30 Error
Reset and try againE31 Error
Reset and try againE32 Error
Reset and try againE33 Error
Reset and try againE34 Error
Reset and try againE35 Error
Reset and try againE36 Error
Reset and try againE37 Error
Reset and try againE38 Error
Reset and try againE39 Error
Reset and try againE40 Error
Reset and try againE41 Error
Reset and try againE42 Error
Reset and try againE43 Error
Reset and try againE44 Error
Reset and try againE45 Error
Reset and try againE46 Error
Reset and try againE47 Error
Reset and try againE53 Error
Reset and try againE54 Error
Reset and try againE55 Error
Reset and try againE56 Error Reset and try againE57 Error
Reset and try againE58 Error Reset and try againE59 Error Reset and try againE60 Error Reset and try againE61 Error Reset and try againE62 Error Reset and try againE63 Error
Flame detected during operation of fire when it should not be detected ­contamination of electrode circuit to ground
Reset and try againCheck and correct Thermocouple wiring. Replace thermocouple if necessaryCheck pilot connections
Reset and try againClear pipe, replace pilot as necessaryPilot pipe may be
blocked completely
Code Comment Apperance Possible Cause Action
13
USERS INSTRUCTIONS
Warnings
All parts of the appliance become hot while running and should therefore be considered to be working surfaces.
A suitable guard may be required to take account of special hazards that exist in nurseries and other places where there are young children, aged or infirm persons.
Curtains are not to be placed directly above the appliance.
It is recommended that combustible materials are not placed directly above this appliance.
This appliance should not be used if the glass door has been removed, broken or is open.
Fire Control
This control is situated on your fire. The drawing shows the main features of the control.
White power isolator switch (sliding)
Indicator light
Fig. 18
Decrease flame
Power button
Check the power isolator switch is in the On position (I).
Increase flame
Battery compartment cover opening lever
Battery compartment cover
To start the fire, press the power button and hold for 1 second then release. The burner will light within around 1 to 10 seconds, adjust to the maximum power setting.
The power of the burner can be adjusted up and down by pressing the – and + buttons.
To stop the fire, simply press the power button again and the burner will stop.
If for any reason the fire should be switched off, either intentionally or unintentionally, no attempt should be made to re-light the gas until at least 3 minutes have elapsed.
If you are not intending to use the fire for a long period (i.e. over summer time months), the battery life can be extended even more by sliding the white isolator switch to the left (away from the On position to (O)).
14
USERS INSTRUCTIONS
Handset
Ensure the Power Isolator Switch on the front corner of Fire Control is in the on position (I). Note: For safety reasons a button must be pressed and released for the command to be recognised. Keeping hold of the button when pressing (unless otherwise instructed) will not be recognised as a command press.
Grasp around the handset to unlock its functions. The green unlock light will illuminate to show when the handset is unlocked and ready to accept commands. (N.B. Keep a grip of handset to keep it unlocked, to continue to operate the command buttons.)
Mode - MAN (Manual), Zzz (Snooze), thermostat or timed.
Time (12 hour or 24 hour display
Day of the week
Gas fire burner status
Battery condition RC handset, FC fire control
Light sensor (for display backlight)
To change mode (see handbook)
Press to decrease flame
In range of fire (missing if not in range or if fire controlled turned off)
Room temperature can be set to fahrenheit/celsius
Handset unlocked when illuminated
To change handset settings (see handbook)
Press to increase flame
Fig. 19
Power button – To start the fire, (after ensuring the fire control is turned on as described above), with one hand grasp around the rear of both sides of the button area control. The green unlock light will illuminate. Keep the handset held to keep the control unlocked, to enable operation of the buttons. Then with the other hand touch and hold a finger on the power button for about 3 seconds. A short beep and a flash of the unlock light will happen upon touching. When the word “pilot” appears at the bottom left hand corner of the display, immediately release the power button. The Fire should be lit within a few seconds.
(N.B. If power button is held for more than a few seconds after second flash/beep/word pilot appears, the command is ignored for safety reasons. Similarly if it is released too soon before the word “pilot” appears, the command would also be ignored.
15
USERS INSTRUCTIONS
Operating instruction (Detailed)
THE HANDSET AND CONTROLS SHOULD ALREADY BE PAIRED AND THE DAY AND TIME SET CORRECTLY.
SHOULD ANY ADJUSTMENTS BE NECESSARY SEE INSTRUCTIONS BELOW:
Setting the time
Following pressing “SET” at paring above, the display will be as shown, as the time is not set yet and will progress automatically to the next screen shown below. Note: the legend at the bottom shows the battery condition of both the batteries in the hand set and in the fire control alternately. RC = Remote Control handset and FC = Fire control. The control is designed to get the most out of the batteries but when eventually the display shows they are spent(when the battery legend is a empty area, we recommend you change the batteries in the handset before they are flat, to avoid having to re-program the time of day in again. N.B. Pairing is not lost, even if the batteries are removed or flat.
Setting the display for 12 or 24 Hour display
As always when pressing the remote control buttons keep the control held to keep the green light on and therefore handset safety feature, unlocked. The H indicates that it is time to set the timer to either 24 hour display or 12 Hour (AM or PM ) display. Press the + or – button on the handset to toggle between the two settings. When you are ready to confirm the setting you want press the “SET” button to progress to setting the day of the week.
Fig. 20
Setting the day of the week
Press and release the + and – buttons until the correct day of the week is shown on the display. (Mo = Monday, Tu= Tuesday, We=Wednesday, Th=Thursday, Fr=Friday, Sa= Saturday and Su=Sunday). Press “SET” to accept the day of the week and to progress to setting the Hour of the day. Note: Whilst doing this setup pressing “SET” advances to the next display and pressing “MODE” will return you to the previous display setting.
Setting the Hour
Press and release the + or – button to change the hour to the correct hour and press set to store and to move to setting the minute. Repeat this for setting the minutes.
Setting the temperature display to Celsius or Fahrenheit.
Fig. 21
Fig. 22
Fig. 23
Press and release the + or - button to toggle between C and F. When the display shows the desired symbol, press and release the “SET” button to store.
As the important settings above have now been done. Press and hold (not releasing straight away) the “SET” button for a few seconds and this will exit the setup menu.
The control is now ready for use with the Fire Control.
16
Fig. 24
USERS INSTRUCTIONS
Paging the handset
If you have misplaced the handset you can page it by pressing the + button only on the fire control for around 5 seconds. The handset will flash and make a noise to help you to locate it. Once you pick up the TESC it knows you hold it and so the sound stops. The flashing and sound will last for 60 seconds each time the handset is paged as described. If not found in 60 seconds, page again and so on.
NOTE: Press “+” button ONLY, NOT “+” and “-” together. This will break the handset pairing and have to reset handset to factory state and pair again.
Advanced settings Menu
In the event that you may want to change the other preset settings of the control features. Do not do a long press and hold above but a normal short press and release will take you into the advanced settings area.
Advanced settings options are:-
• Back light –
• A = Automatic (default setting). The back light comes on in the dark but not in the light.
• 0 = Light never comes on.
• 1 = Light comes on when ever handset is unlocked.
• Display contrast – 8 levels from 0 to 7 (default level 4) .
• P = pairing with other devices other than the fire control. The hand set can pair with other modules to:-
• L= Operate an electric light – which is the dimmable in 9 steps
• F= operate an electric fan –which can have 9 speed levels
• A= operate an auxiliary contact to operate another device.
Other Modes than Manual Mode
Depending upon the model of Fire your handset maybe enabled to have some automatic features, namely, Thermostat mode, timed thermostat mode and snooze mode. Snooze mode can be selected to work with in conjunction with either manual or thermostatic modes. You can switch between modes at any time with the handset unlocked by pressing and releasing mode button to toggle between modes. Note: If at any time the power button is pressed during operation, this will stop the fire and exit any automatic mode and return the handset to manual (MAN) operation mode.
Factory Reset of Display Handset (to enable handset to be paired again)
To reset a handset to factory conditions to enable it to be paired with a new control. Hold the handset to unlock. Press and hold set until handset beeps and release the set button. PROG will be at the top left corner. Press and release the mode button until the word SETUP is flashing in the top right corner. Press and release SET to enter the SETUP menu. Press and release the set button around 9 times until you see CA0 on the display. Press then release the + (or – button) to change the display to CA1 and press and release the SET button again. The word TESC will appear in the window to show that this handset is now reset and ready to pair again.
Snooze mode in manual operation
Snooze mode is a time period you can set which will turn off the fire after a certain time period has elapsed.
The snooze time period can be set before or during manual operation of the fire. Hold the handset to unlock as described previously and press the mode button as many times as necessary until the word MAN and the Zzz symbols are flashing at the top of the display. Press and release the set button and this will put the control into Manual snooze mode.
The default time period for the snooze time period is 1:00 hour. Pressing the set button again will show you the snooze time period remaining. This can be adjusted by pressing the “+” or “-“ buttons. The timer period that can be set is from 1 minute to 4:00 hours.
After adjusting the time, press set again to enter the time setting required (or if left for a few seconds this time is now stored and used).
Once this countdown timer has reached zero the fire will turn off (as if you had pressed off manually, it does not recycle).
17
USERS INSTRUCTIONS
Snooze mode in Thermostatic mode
The same thing as above can be done before or during a thermostatic mode operation (see below).
Thermostatic mode only
The handset has within it a thermostat sensor and this can be set so the fire will heat the room to match the temperature set in the handset.
There are 3 temperature types that can be set:-
-Day mode temperature that has a sun symbol on the display – the default temperature is 24 °C
- Night temperature that has a half moon symbol on the display- the default temperature setting is 18 °C
-frost protection that has a snowflake symbol on the display – the default temperature setting is 5 °C
Hold handset and press and release the mode button several times as necessary until the display has a thermometer symbol flashing at the top of the display. Press the set button to enter this mode. Press the set button again to see the temperature setting that is set and the mode (the default is 24 C ) and on the left of the display is a sun symbol showing it’s the day temperature.
If a different set temperature is required, while the display is showing this set temperature , press the + and – buttons to alter the setting. When finished either press set or leave and after a few seconds the new setting will be accepted and the display will return to the time of day screen.
On the anniversary of the net minute of the clock, the set temperature will be compared to the actual temperature displayed on the handset(i.e. the room ambient temperature around the handset).
Note: If at any time the power button is operated during Thermostat mode, the control will cancel any thermostat operation and return the control to manual mode.
For ease of setting there are two other modes that can be selected as stated above. Night mode (moon symbol) and frost protection setting (a snow flake). These can be selected (and adjusted if necessary) by pressing set then mode while in thermostat mode. Pressing mode button toggles through from day to frost modes.
Note: As stated in an earlier section, snooze function can also be operated in conjunction with thermostat mode. The thermostat symbol and the Zzz symbol will be on together when in this mode.
The remote control display handset supplied with this fire will have already been factory set and should not need to be adjusted or re-paired. Read the operation instructions fully before attempting to de-pair the handset.
De-pairing and re-pairing the handset.
Note: Reading this instruction fully, will help the user to carry out the quick set-up procedure, it may take a few
attempts to learn the sequence of commands due to the fast handset time-out period.
Should the handset fail to operate the fire control (and batteries are new), it may be necessary to re-pair it with the gas fire control system.
To do this the handset may need to be returned to factory settings.
1. Pick up in a grasp to activate handset and then press set button until PROG shows on top left of screen.
2. Use the mode button pressing twice to show SETUP on top right of screen.
3. Again press SET button and H24 should show, scroll through menu with 9 more presses of set button until CA0 shows, then immediately press + so CA1 shows, then again quickly press set so screen shows 7ESC r4.
The handset is now ready for repairing with the gas fire control.
The handset must be within 1 metre of the fire when pairing and must be initially held to illuminate and also initiate set up.
Simultaneously press the hold the – and + buttons on the gas fire control (i.e. not the handset) unit the red neon on top left of fire control begins to flash rapidly, then immediately release – and + quickly pressing the power button below. An audible command signal is sent out to the handset which is accepted by immediately pressing the set button (there is a 2 second time window to press the power button or – and + will have to be repeated).
The handset will make a noise and the handset will show a pattern (7- - r).
Immediately Press the Set button on the illuminated handset to accept the command for pairing.
Scroll through the menu using handset SET button, adjusting the day, time with buttons – and + then press SET button 6 times until screen shows a full display with wi- fi symbol.
18
Fig. 25
CLEANING AND MAINTENANCE - GAS SAFE ENGINEER
It is recommended that this appliance is serviced at regular 12 monthly intervals. The chimney or flue should also be checked regularly to ensure that all products of combustion are entering the flue and there is no excessive build up of soot. It is the users responsibility to ensure that the appliance is kept in a clean serviceable condition.
To remove the glass frame
1. Remove the top and bottom covers from the front of the stove (Fig. 26).
Top Cover
2. Remove the six screws at the top of the glass panels and slide out the frame (Fig. 27).
3. Remove the two side panels and slacken the six screws securing the glass rear clamps (Fig. 28).
4. Slide the glass out (Fig. 29).
5. Clean the glass with a damp cloth. For stubborn stains use a proprietary cream cleaner or ceramic hob cleaner.
Ceramic Components and Fuel Bed
Debris from any source should be removed with a soft brush. Please ensure that any debris including soot deposits are removed from the appliance and not left on the fuel bed. Carefully remove all ceramic components and thoroughly clean the stainless steel burner and the pilot assembly. Any build up of debris in this area could affect the operation of the appliance (Fig. 30).
NOTE: It is common to find surface cracks in the ceramic components. This is due to the expansion and contraction of the ceramic fibres caused by the intense heat that the burner generates. The cracks will not affect the safe operation of this appliance. However great care must be taken when handling the ceramic components as they will break if handled incorrectly. Do not use a vacuum cleaner to clean the ceramics.
Securing Screws
Fig. 26
Bottom Cover
Frame
Fig. 27
Side Panels
Radiant Box Ceramic Liners - Use only a soft brush to remove any soot deposits from the ceramic liners during cleaning as this is the only method that can be used to remove deposits. The ceramic liners are very delicate and should be treated accordingly.
5. Reassemble in reverse order.
Stainless Steel Burner
Pilot Assembly
Fig. 30
Fig. 28
3 x Clamping Screws
Fig. 29
Glass
19
LOG LAYOUT INSTRUCTIONS
CAUTION: The logs are extremely fragile and must be handled accordingly. Gloves should be worn and any inhalation of dust should be avoided. The logs must be kept away from children at all times. Never put additional logs on the fire. Never use logs other than those originally supplied, or genuine Legend Spare Parts.
1. Place the burner grille into position.
3. Arrange the slate ceramics onto the burner cover plate. ENSURE THAT THEY DO NOT COVER THE BURNER.
2. Place the front ceramic panel into position.
4. Place the rear log at the back of the burner grille.
5. Place the front log onto the front ceramic panel.
20
6. Place the small log on top of the rear log as shown.
LOG LAYOUT INSTRUCTIONS CONTINUED
7. Place the remaining logs as shown in the photographs below.
8.
10.
9.
11.
12.
21
LOG LAYOUT INSTRUCTIONS CONTINUED
13.
It is very important that all the logs are used and arranged as shown in order to achieve the desired flame picture. It may be necessary to remove some or all of the logs to clean them at some time. Cleaning must only be done using a soft brush.
22
TROUBLE SHOOTING (USER)
Non Display handset with pilot burner
If the fire does not start at the first attempt it may retry several times to do so. At the end of trying if it cannot ignite the burner; it will show a RED light on the handset and on the fire control and stop the fire.
• If the fire does not light first time, allow fire to cool and then repeat lighting fire up to 10 times, as it may only be a temporary reason that will clear after a few attempts..
• Reset the fire control by pressing the handset as if you were doing a normal start. This will clear the red light and allow another subsequent restart attempt.
• If the fire does not light, replace all the batteries in the handset and the fire control, (5 x AA Alkaline in total, with batteries that do not leak) with new and known to be good batteries and repeat the above starting of the fire.
• While replacing the batteries, check that the battery contacts are not contaminated with anything that may have leaked out of the batteries that may have damaged the contacts.
• If the fire still fails to light check to see if the pilot flame on the pilot burner, is lighting during the starting sequence. If not then clean the pilot as described in Cleaning the pilot section of the booklet.
• Check to see if there is a spark appearing on the pilot spark plug and check to see if there is any contamination around it that might be preventing the ignition spark from happening.
Display handset with pilot burner
As above except instead of the red LED light on the handset there will be a letter E and a to digit number where the time is usually displayed. Do the same actions as above to try and resolve the reason for non ignition of the burner.
If you cannot resolve the problem, then call:
01254 695244.
GUARANTEE
Your appliance is guaranteed for one year from proof of purchase. Should the appliance prove defective within that period we agree to repair or replace (at our discretion) the component or appliance provided that:
1. The user can produce a receipt for proof of purchase/installation.
2. The appliance has been supplied by an authorised stockist and has been installed by a qualified installer, all installation and operating instructions have been strictly adhered to.
3. No alterations have been carried out on the appliance or component parts without our written consent.
4. The appliance has not been used for any purpose other than those intended.
5. The appliance has not been damaged accidentally or due to fair wear and tear.
Guarantee claims should be made through your appliance supplier. The Guarantee is restricted to UK Mainland and is additional to your statutory rights.
Unit 404 Glenfield Park Business Centre Blakewater Road Blackburn Lancashire BB1 5QH
Tel: 01254 695244 Fax: 01254 695255 Web: www.legend-fires.com Email: info@legend-fires.com
Draft G - 19/09/16
Loading...