Legalett 4000W User Manual

HEATING UNIT - 4000W
January, 2006
Revised:May, 2008
Form № 0524
Page 1 of 2
The 4000W heating unit is installed in the foundation
slab or intermediate oor, and contains a fan and four water/air-exchangers, with valves that are controlled by 1
TECHNICAL DATA
Operating voltage ........................1 P - 230V/24V 60Hz
Fan motor power consumption ............................225W
Breaker rating (GFI required) .................................15A
Water-air exchanger output
with 8 - 100 mm duct ........approx. 5 kW @ 55°C/130°F
air ow .............. approx. 900 m3/h / 530 CFM
with 20 - 50 mm duct ........approx. 4 kW @ 55°C/130°F
air ow .............. approx. 750 m3/h / 440 CFM
Air temperature range.................... 30-55°C /85-130°F
Connection, pipe......lavatory style, 1/2" straight thread
FUNCTION
The 4000W is controlled by one (single zone) to four (quad zone) external electric room thermostats. These external thermostats operate the control valves in the unit, opening the control valve when the room needs heat. A water temperature sensor built into the 4000W starts the fan motor when the inlet water temperature reaches 30°C (85°F) When the control valve is closed and the inlet water temperature decreases to approximately 27°C (80°F), the fan motor stops. The fan operation is inde­pendent of the position of the zone valve, and responds only to water temperature.
When controlled by a programmable thermostat, the 4000W can use two-tiered energy rates for night storage of less expensive energy in the LEGALETT heated oor.
- 4 external electric room thermostats. It is used together with heating unit box 4000A 100/100 (100 mm (4") spiral pipes) or with heating unit box 4000A 50/50 (50 mm (2") plastic pipes).
Design data for all 4 exchangers and valves:
Design ow ................................ 400 l/h / 1.75 USGPM
Design pressure drop ................. 21.5 kPa/7.2’/3.1 PSI
Maximum full ow pressure drop (noise limited):
......................................................35 kPa/11.2’/5.1 PSI
Maximum zero ow pressure drop (i.e. maximum pump
pressure, noise limited) ..................... 40 kPa/15’/7 PSI
This data is generic. Each Legalett installation is unique. Refer to customized specications on your installation design drawing for actual design parameters.
1 P - 230V 60Hz
15A circuit breaker
thermostats 1-4
www.legalett.com
1
3
24
ASSEMBLY
Install the heating unit boxes in the correct location, with the height adjusted so that the lid is ush with the concrete surface, before pouring the concrete. Refer to the instructions on the box cover.
1. Run conduit from one of the cable inlets on the box to the local disconnect for 230V power. Run conduits from the remaining cable inlets to a convenient location above the slab for each of the 24V thermostats, external 24V transformer (not supplied) and optional signal wiring to the boiler.
2. Connect the sleeves for the inlet and outlet water pipes to the water pipe connections of the furnace box. Install the water pipes, and make sure they extend at least 100 mm (4") into the box.
3. After the concrete has dried sufciently with the construction heater, prepare the box for the heating unit according to the steps below, which are performed by an authorized electrician and plumber.
4. Clean the furnace box carefully. No water or dampness should be in the box or pipe system when installing the permanent insert.
heating unit box
4000A 50/50
electrical connections
oor hatch
sound insulation
mat, 30 mm
heating unit
cover
heating insert
heating unit box
electrical connections
hole for water pipe inlet hole for water pipe return
4000W
Heating unit box
4000A 100/100 is
similar
water pipe
connections
HOT WATER CONNECTIONS
1. Install threaded adaptors with integral gasket for ½” NPSM (lavatory-style straight threaded) on water pipe, and adjust pipe to length so that the end of the ttings stick 52 mm (2") inside the box as shown in picture 1.
2. Loosen the two vertical pipes with their elbow connections, which are loosely mounted on the
heating unit for mounting of inlet and return water
pipes. Then mount the lower elbow connections to the water pipes, as shown in picture 2.
3. Mount the heating insert, so that the vertical pipes stick into the elbow connection above and tighten the joints. See pictures 3 and 4.
4. Turn on water and check for leaks.
5. Once the electrical connections have been completed, bleed any air from the system after a test run.
#1.
52 mm
#2.
#3.
#4
www.legalett.com
Loading...
+ 1 hidden pages