IMPORTANT SAFETY INSTRUCTIONS – SAVE THESE INSTRUCTIONS
This manual is for Herytage UPS:
Horizontal Chassis 2kVA through 20kVA
DANGER: UPS contain HAZARDOUS VOLTAGES. Because of these voltages,
installation of the system should be performed by a qualified electrician. The
electrician must install according to local and national electrical codes.
There are NO USER SERVICEABLE PARTS inside the UPS, repairs of the
system should be performed by qualified service personnel.
CAUTION: Batteries can present a risk of electrical shock or burn from high short circuit
current. Observe proper precautions.
CAUTION: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
CAUTION: A UPS contains its own energy source (batteries). Output voltage may be
present even when the UPS is not connected to an AC supply.
CAUTION: Never dispose of batteries in a fire. Batteries may explode when exposed to
flame.
CAUTION: Never open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes, and may be extremely toxic.
CAUTION: To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants.
Ambient temperature must not exceed 40 C (104 F) without de-rating the
maximum load. Do not operate near water or excessive humidity (95% max).
CAUTION: Do not remove or unplug the input cord when the UPS is turned on. This
removes the safety ground from the UPS and the equipment connected to the
UPS.
SYMBOLS: Listed below are the symbols utilized on the product labels or within the
installation / user manual
BILS-10003 rev E
3
INTRODUCTION
Thank you for purchasing this quality product from Legacy Power Conversion, Inc.
Read this manual thoroughly before installing or operating your Herytage UPS system.
Keep this manual for future reference.
This unit will provide highly regulated and controlled power for your sensitive electronics
equipment, protecting it from frequent power glitches that are inherent in commercial power.
IF YOU HAVE ANY QUESTIONS OR PROBLEMS PLEASE LET US HELP… Legacy Power
Conversion, Inc is committed to outstanding customer service. Our customer service center
will be happy to help you with any problems or questions you may have. Service technicians
are available 24 hours a day, 365 days a year. Just call the telephone number below, or
send a fax to the service fax number. Please have your unit’s serial number available.
TELEPHONE NUMBER - 800-859-5711 or 608-565-5878
FAX NUMBER - 608-565-5879
Email – service @ lpc-ups.com
GENERAL DESCRIPTION
The Herytage UPS is an Electronically Controlled Ferroresonant Transformer based UPS
system designed to provide transient free, regulated power to your load equipment. Features
that differentiate the Herytage UPS are:
Line Cord Designators: C = 5-20P, I = L5-20P, J = L5-30P, E = 5-50P, O = 6-15P, K = L6-20P, L = L6-30P,
M = L14-30P, N = 6-50P, P = L6-50P
2
20 Amp Line Cord limits battery charger current to 4 Amps.
3
Weight and Dimensions are for UPS with standard internal runtime.
25.2 x 16.2 x 233 37.5 x 17.75 x 33.25
2083 2753 290
87% 88% 90%
120db common mode, 60db transverse (normal) mode
Output is completely isolated from commercial power with less than 2 pf effective capacitive
coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a
6000 volts are suppressed to safe levels per ANSI/IEEE C62.41 – 1997 category A & B
Max. altitude 10,000 ft – de-rate 1° C off max operating temp. per 1000 ft. above sea level
Keypad w/ LCD display, RS232 serial communications, dial in modem
3
separately derived power source
0 to 95% without condensation
3
565
91%
waveforms
0° to 40° C (32° to 104° F)
UL 1778, cUL listed
465
93%
530
93%
91%
39 x 22 x 34
570
665
91%
BILS-10003 rev E
5
Specifications* (continued)
Model
ttery)
Overload
DC & Inverter
Nominal DC voltage
DC Current
Charger Current
Runtime – (Std Ba100% Load
50% Load
Efficiency (on inverter)
Sound Level (Inverter)
* Specifications may change without notice.
2
20 Amp Line Cord limits battery charger current to 4 Amps.
2kVA
1.6kW
39 59 78 78 78 78 157 157
11 min
32 min
150% surge capability, overload alarm 101% load to 110% load for 10 min. before shutdown.
Greater than 110% the system will shutdown in 5 seconds.
50dBA 50dBA 52dBA
3kVA
2.4kW
48VDC
18 min
47 min
4kVA
3.2 kW
6kVA
4.8kW
72VDC
54dBA
8A
85%
8kVA
6.4kW
96VDC
2
55dBA
10kVA
8kW
120VDC 96VDC
11 min
32 min
55dBA
16kVA
12.8kW
53dBA
20kVA
16kW
120VDC
55dBA
BILS-10003 rev E
6
100 Receiving your Herytage UPS
Caution: The Herytage UPS assemblies are very heavy, insure you are prepared
to unload, unpack, and move these weights.
101 Unpacking and Inspection
Upon receiving shipment of your equipment, it is important to check items received
against the packing slip. Check all pieces for shipping damage by unpacking and
inspecting. If items are missing or damaged, call our customer service department.
They can assist in filing a claim with the shipping carrier.
If installation requirements are not immediate, it is best to repack the system into its
original packing material for storage.
102Storage
Store Herytage UPS prior to use at temperatures between –20º and +40º Celsius (-4º
to +104º Fahrenheit). Protect the system from moisture and weather.
If storing the Herytage UPS modules containing batteries, it is best to store them at
temperatures less than 77º Fahrenheit. This allows the batteries to have a longer shelf
life. If you plan to store them for more than 4 months it is important to unpack the
system to recharge the batteries. Consult with the factory customer service
department for assistance.
BILS-10003 rev E
7
200 Installation Guidelines
Herytage UPS are intended to be installed in a temperature controlled, indoor area
free of conductive contaminants.
See specifications for more details on the temperature range, environment, and
altitude. In addition consider any national and local codes you may have to follow.
201 Installation considerations
Before installation of your new Herytage UPS, be sure to take into consideration the
site you have selected. UPS systems produce heat and therefore require ventilation
as well as accessibility.
Consider these factors:
- Input Source Voltage - Ventilation
- Available Single Phase KVA - Size of the UPS
- Bypass Switch - Weight of UPS and Batteries
- Excessively Long Power Runs - Room Temperature
- Distance to Critical Load - Audible noise
- Proper Ground Techniques - Clearances
- Generator Applications - Accessibility
- Remote Emergency Power Off - Communications
202 Location
When you plan the location of your UPS, remember to:
• Avoid temperature and humidity extremes
• Provide shelter from the elements (especially moisture)
• Place as near as possible to the computer or other critical loads
• Maintain 8 inches of clearance in back for ventilation, and a minimum of 36 inches
in front for ventilation and maintenance. A larger clearance in front is helpful, but
not required.
BILS-10003 rev E
8
203 Remote battery installations
Front
Back
6 kVA
If the batteries are installed in a remote location (battery room) utilize DC circuit
protection rated at 250A and 20,000A AIC rating. If the batteries must be some
distance from the UPS you may need to install larger battery cables between the
battery cabinets and the UPS. Call your customer service representative if you would
intend to use anything other than standard cable lengths.
204 Customer Supplied batteries with Legacy battery cabinet(s)
Utilize the same number, size and type of battery as offered by Legacy Power
Conversion, Inc.
Enersys NP18-12BFR (Legacy Part Number BAT-0373)
C&D Technologies UPS 12 - 140 (Legacy Part number BBAT-0065)
Enersys NP33-12 (Legacy Part number BBAT-0065)
C&D Technologies UPS 12 - 270 (Legacy Part number BBAT-0103)
C&D Technologies UPS 12 - 310 (Legacy Part number BBAT-0122)
C&D Technologies UPS12-150MR (Legacy Part number BBAT-10031)
C&D Technologies UPS12-300MR (Legacy Part number BBAT-10032)
C&D Technologies UPS12-350MR (Legacy Part number BBAT-10033)
205 Dimensions and clearance requirements
Table 1 Dimensions and Clearances
Model
2kVA1
3kVA1
4 kVA1
8 kVA
10 kVA
16 kVA
20 kVA
Height
(In.)
25.2 16.2 23 36 8
37.5 17.75 33.25 36 8
39 22 34 36 8
1
Dimensions are for UPS with standard internal runtime.
BILS-10003 rev E
Width
(In.)
Depth
(In.)
Clearance
(In.)
Clearance
(In.)
9
206 External Bypass Switch
Dimension (in) A B C D E F G Weight
SW040xxxx 15.0 16.1 17.0 8.0 12.0 7.0 9.4 23
SW080xxxx 16.0 17.1 18.0 12.0 16.0 9.1 11.9 36
SW125xxxx 16.0 17.1 18.0 12.0 16.0 9.1 11.9 38
Allow 36” for service clearance in front of the bypass switch.
207 External Battery Cabinet
2 thru 4K battery cabinet dimensions
BILS-10003 rev E
10
6 thru 20K battery cabinet dimensions
Allow 36” for service clearance in front and on one side of the battery cabinet. Placing cables in flexible
metal conduit will allow for movement of battery cabinet for service.
300 Wiring Instructions
There are two basic installation configurations of the Herytage UPS system. Following
is an overview of each configuration.
- Soft-wired (Line cord & receptacles)
- Hard-wired with external bypass switch
Installation of electrical wiring should be completed by a qualified electrician.
National electrical code and applicable local codes should be followed.
301 Soft-wired installation (Line-cord and receptacle)
Installation requires a proper wall receptacle for the Herytage UPS power cord to plug
into, and installation of external bypass receptacles.
Note: External bypass receptacles provide power to your load equipment in the event
that the Herytage UPS requires maintenance.
Proper breaker sizing for the input line cord receptacle depends on the input voltage /
plug option ordered, see Table 301-1. Review the Herytage UPS input voltage on the
BILS-10003 rev E
11
name plate – if it differs from the power you have available in your building call Legacy
Power Conversion customer service.
General requirements for hardwire Herytage UPS installations
– Input over-current protection and Output over-current protection and AC output
disconnect switch for Herytage UPS must be provided by the installer. It should be
installed and sized according to national and local electrical codes.
– External bypass switches should be installed within sight of Herytage UPS.
– Follow applicable national and local electrical codes when installing the grounding
system. Herytage UPS grounding conductor should be at minimum the same size
(ampacity) as circuit conductors.
– All circuit conductors including the neutral should be the same size (ampacity).
– Use isolated ground receptacles to obtain the best protection against electrical
noise.
– A separate dedicated conduit system should be utilized for the Herytage UPS input
and output wiring.
– Flexible conduit should be used to allow movement of the Herytage UPS to gain
side service clearance.
– Load imbalance should not exceed 40% / 60%; 2-4K units do not have this
restriction. 6K units L1-N 100% max., L2-N 50% max.
302-1 External bypass switch installations
The 2kVA through 20kVA Herytage UPS may be ordered with an external bypass
switch. The external bypass switch is typically mounted on a wall within site of the
Herytage UPS. See Figure 302-1A.
1. The wiring access panel for the external bypass switch is located on the front
bottom half of the external bypass switch module, remove the screws securing
the bottom half of the front cover to obtain access to the terminal blocks. See
Figure 302-1B
2. Input and output wiring to and from the Herytage UPS and to and from the
external bypass switch should be routed through separate conduits. Conduit
connection points are located on the back of the UPS, the same conduit
connection points are on the external bypass switch. Locate the pre-punched
knockouts for starter holes.
3. Review input and output voltages on the unit data plate and insure they are
proper for your installation, select wiring connection diagram figure 1 or 2 for
appropriate connection. If the wrong input or output voltages were ordered –
call Legacy Power Conversion customer service for assistance.
BILS-10003 rev E
13
Figure 302-1A - Hard-wired Installation Overview
External Bypass Switch
Input and Output
Terminal Block located
under side panel
Herytage UPS
Figure 302-1B Bypass Switch Terminal Block
BILS-10003 rev E
14