Legacy Power Conversion HERYTAGE 6kVA 4.8kW, HERYTAGE 3kVA 2.4kW, HERYTAGE 8kVA 6.4kW, HERYTAGE 4kVA 3.2 kW, HERYTAGE 10kVA 8kW User And Installation Manual

...
HERYTAGE
User and Installation Manual
For H02KVA thru H20KVA Model UPS
IMPORTANT SAFETY INSTRUCTIONS, SAVE THESE INSTRUCTIONS
– This Manual contains important instructions for models 2kVA through
The Best Power Protection in the Business
TM
Contents
Page
Safety Warnings…………………………………………………………………………………. 3 Symbols…………………………………………………………………………………………… 3 Introduction………………………………………………………………………………………. 4 General Description……………………………………………………………………………… 4 Specifications……………………………………………………………………………………. 5
Section
100 Receiving your Herytage UPS………………………………………………………. 7 101 Unpacking and inspection………………………………………………………………. 7 102 Storage……………………………………………………………………………………. 7
200 Installation Guidelines……………………………………………………………… 8 201 Installation Considerations……………………………………………………………… 8 202 Location………………………………………………………………………………….. 8 203 Remote battery installation…………………………………………………………….. 9 204 Customer supplied batteries with Legacy cabinets…………...……………………… 9 205 Dimensions and clearance requirements…………………………………………….. 9 206 External bypass switch dimensions………………………………………………….. 10 207 External battery cabinet dimensions………………………………………………….. 10
300 Wiring Instructions…………………………………………………………………….. 11 301 Softwired Installations………………………………………………………………..… 11
Table 301-1 Minimum circuit breaker requirements……………………………..……….. 12
302 Hardwired Installations………………………………………………………..………..……. 13
302-1 External bypass switch Installations ……………………..………..……………… 13
Figure 302-1A Hard-wired Installation Overview……………………..…………………… 14 Figure 302-1B Bypass switch Terminal Block……………………..…………………… 14
302-2 Minimum input over-current protection…………………………………..……….... 15
Table 302-1 Minimum circuit breaker requirements……………………………..……….. 15
302-3 Installation Wiring Connection Diagrams……………………………….……….... 15
Figure 1 Wiring connection diagram/120 Input with External bypass ……………… 16 Figure 2 Wiring connection diagram/208-240 Input with External bypass …….. 17 Figure 3 Wiring connection diagram/208 Input with MBB External bypass ……… 18
303 Battery installation and connection……………………………………..………..……….... 19
304 Bypass switch wiring / Phase check……………………………………………..………… 20 305 User interface wiring connections…………………………………………………..……… 22
Table 305-1 DB 9 Serial communications pin outs…………………………..……….... 23
Table 305-2 User interface wiring connection block…………………………..………... 23
BILS-10003 rev E
1
400 System operation…………………………..………………………………..…. 24 401 Startup ……………………………………..………..……………………..………..……………. 24
401-1 Softwired units (Line cord and receptacles)… ……………..………..…………. 24
401-2 Hardwired units………………………………………………………..………..……. 25 402 Shutdown of the Herytage UPS ………………………..………..………………….…….. 26 402-1 Softwired systems………………………………………………………..………..…. 26
402-2 Hardwired units…………………………..………..…………………………………. 26
500 System Features……………………………………………………………………….. 27 501 On / Off Switch…………………………………………………..………..…………..…… 27 501-1 Herytage UPS On / Off Switch Positions………………………………..…… 27 502 Bypass switch / AC disconnect operation……………..…………..………………... 27
502-1 AC disconnect switch………………………………………..………………...… 27
502-2 Bypass switch……………………………………..………………...…………… 28 503 Display Panel / LED lights……………………………………..………………...……… 29
503-1 Bar Graph LEDs…………………………………..………………...…………… 29
503-2 Single LEDs…………………………………..………………...………………… 29 504 Keypad / LCD display……………………………………………..………………...…... 30
504-1 System Status/System Modes………………..………………...……………… 30
504-2 Passwords…………………………………..………………...………………..… 30
504-3 Keypad Functions and Programming…..……..…………...………………..… 31 505 Parameter Table…………………………………………………..………………...…… 32
600 RS 232 Serial communications…………………………………………………..….. 37 601 DB9 Serial Terminal / Computer hook up ……………….………………...…….…. 37 602 System Status/System Modes………………..…………….………………...……….. 37 603 Passwords…………………………………..………………...………………..….…….. 38 604 RS232 Commands…………………………………..…………...………………..……. 38 605 Modem Hook Up (optional) …………………………………..………….………..……. 39
700 Alarms……………………………………………………………………………………. 40 701 Shutdown and latching alarms……………………………...………………..………… 40
702 Alarm Table ...………………..………………………………....………………..……… 40
703 Alarm Mask...………………..………………………………....………………..……… 42
800 Battery removal / replacement………………………………………………………. 43 801 Battery safety / cautions……………………………………...………………..……….. 43
Warranty………………………………………………...………………..………………………. 44 Warranty registration form………………………………………...………………..…………… 46
BILS-10003 rev E
2
SAFETY WARNINGS
IMPORTANT SAFETY INSTRUCTIONS – SAVE THESE INSTRUCTIONS
This manual is for Herytage UPS:
Horizontal Chassis 2kVA through 20kVA
DANGER: UPS contain HAZARDOUS VOLTAGES. Because of these voltages,
installation of the system should be performed by a qualified electrician. The electrician must install according to local and national electrical codes.
There are NO USER SERVICEABLE PARTS inside the UPS, repairs of the system should be performed by qualified service personnel.
CAUTION: Batteries can present a risk of electrical shock or burn from high short circuit
current. Observe proper precautions.
CAUTION: Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
CAUTION: A UPS contains its own energy source (batteries). Output voltage may be
present even when the UPS is not connected to an AC supply.
CAUTION: Never dispose of batteries in a fire. Batteries may explode when exposed to
flame.
CAUTION: Never open or mutilate batteries. Released electrolyte is harmful to the skin
and eyes, and may be extremely toxic.
CAUTION: To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40 C (104 F) without de-rating the maximum load. Do not operate near water or excessive humidity (95% max).
CAUTION: Do not remove or unplug the input cord when the UPS is turned on. This
removes the safety ground from the UPS and the equipment connected to the UPS.
SYMBOLS: Listed below are the symbols utilized on the product labels or within the
installation / user manual
BILS-10003 rev E
3
INTRODUCTION
Thank you for purchasing this quality product from Legacy Power Conversion, Inc.
Read this manual thoroughly before installing or operating your Herytage UPS system. Keep this manual for future reference.
This unit will provide highly regulated and controlled power for your sensitive electronics equipment, protecting it from frequent power glitches that are inherent in commercial power.
IF YOU HAVE ANY QUESTIONS OR PROBLEMS PLEASE LET US HELP… Legacy Power Conversion, Inc is committed to outstanding customer service. Our customer service center will be happy to help you with any problems or questions you may have. Service technicians are available 24 hours a day, 365 days a year. Just call the telephone number below, or send a fax to the service fax number. Please have your unit’s serial number available.
TELEPHONE NUMBER - 800-859-5711 or 608-565-5878 FAX NUMBER - 608-565-5879
Email – service @ lpc-ups.com
GENERAL DESCRIPTION
The Herytage UPS is an Electronically Controlled Ferroresonant Transformer based UPS system designed to provide transient free, regulated power to your load equipment. Features that differentiate the Herytage UPS are:
Electronically controlled Ferroresonant Transformer
State of the art user interface
Keypad with a back lit LCD display, rear access RS232 communications interface port.
Detailed power quality, control, and unit metering information are all easily accessible.
Last 248 power quality and alarm events logged by time, date, including start and stop
time.
Dial in modem option.
BILS-10003 rev E
4
Specifications*
Input ACV &
Line Cord
1
Input Voltage
Window
Frequency
AC Output
Output ACV
Output Receptacles
Output waveform
Regulation
Load Compatible
Overload
Unit
Dimensions
Heat Loss BTU /
W
Noise Attenuation
Isolation
Surge Protection
Operating Temperature
Relative Humidity
High altitude operation
Agency
User Interface
Model 2kVA
1.6kW
AC Input
circuit breaker
requirements – standard hardwire connection
(optional)
120VAC 208VAC 240VAC
120VAC 208VAC 240VAC
– Hardwire
30A 15A 15A
C2, I2, J, E
O, K, L O, K, L
150% surge capability, overload alarm 101% load to 125% load for 10 min. before shutdown.
3kVA
2.4kW
30A 20A 15A
J, E K, L
O, K, L
Guaranteed compatible with all loads for 90 days from date of purchase
Greater than 125% the system will shutdown in 5 seconds.
4kVA
3.2 kW
50A 30A 30A
E L, M L, M
+15%, -20% of nominal VAC Input @ full load
+15%, -40% of nominal VAC Input @ 50% load
Computer grade sine wave output power
6kVA
4.8kW
60A 40A 40A
-
N, P N, P
60Hz, ± 3Hz. Adjustable window
120 / 208 / 240
± 3% voltage regulation
8kVA
6.4kW
-
60A 50A
-
-
-
Optional
10kVA
8kW
-
70A 60A
-
-
-
16kVA
12.8kW
-
100A
90A
-
-
-
20kVA
16kW
-
125A 110A
-
-
-
H x W x D
(in.)
Weight ( lbs.)
Efficiency
816/239 1116/327 1213/355 1619/475 1645/482 2055/602 2160/632 3238/95
* Specifications may change without notice.
1
Line Cord Designators: C = 5-20P, I = L5-20P, J = L5-30P, E = 5-50P, O = 6-15P, K = L6-20P, L = L6-30P,
M = L14-30P, N = 6-50P, P = L6-50P
2
20 Amp Line Cord limits battery charger current to 4 Amps.
3
Weight and Dimensions are for UPS with standard internal runtime.
25.2 x 16.2 x 233 37.5 x 17.75 x 33.25
2083 2753 290
87% 88% 90%
120db common mode, 60db transverse (normal) mode
Output is completely isolated from commercial power with less than 2 pf effective capacitive
coupling primary to secondary. Secondary has neutral to ground bond, qualifying as a
6000 volts are suppressed to safe levels per ANSI/IEEE C62.41 – 1997 category A & B
Max. altitude 10,000 ft – de-rate 1° C off max operating temp. per 1000 ft. above sea level
Keypad w/ LCD display, RS232 serial communications, dial in modem
3
separately derived power source
0 to 95% without condensation
3
565
91%
waveforms
0° to 40° C (32° to 104° F)
UL 1778, cUL listed
465
93%
530
93%
91%
39 x 22 x 34
570
665
91%
BILS-10003 rev E
5
Specifications* (continued)
Model
ttery)
Overload
DC & Inverter
Nominal DC voltage
DC Current
Charger Current
Runtime – (Std Ba 100% Load
50% Load
Efficiency (on inverter)
Sound Level (Inverter)
* Specifications may change without notice.
2
20 Amp Line Cord limits battery charger current to 4 Amps.
2kVA
1.6kW
39 59 78 78 78 78 157 157
11 min
32 min 150% surge capability, overload alarm 101% load to 110% load for 10 min. before shutdown. Greater than 110% the system will shutdown in 5 seconds.
50dBA 50dBA 52dBA
3kVA
2.4kW
48VDC
18 min 47 min
4kVA
3.2 kW
6kVA
4.8kW
72VDC
54dBA
8A
85%
8kVA
6.4kW
96VDC
2
55dBA
10kVA
8kW
120VDC 96VDC
11 min 32 min
55dBA
16kVA
12.8kW
53dBA
20kVA
16kW
120VDC
55dBA
BILS-10003 rev E
6
100 Receiving your Herytage UPS
Caution: The Herytage UPS assemblies are very heavy, insure you are prepared
to unload, unpack, and move these weights.
101 Unpacking and Inspection
Upon receiving shipment of your equipment, it is important to check items received against the packing slip. Check all pieces for shipping damage by unpacking and inspecting. If items are missing or damaged, call our customer service department. They can assist in filing a claim with the shipping carrier.
If installation requirements are not immediate, it is best to repack the system into its original packing material for storage.
102 Storage
Store Herytage UPS prior to use at temperatures between –20º and +40º Celsius (-4º to +104º Fahrenheit). Protect the system from moisture and weather.
If storing the Herytage UPS modules containing batteries, it is best to store them at temperatures less than 77º Fahrenheit. This allows the batteries to have a longer shelf life. If you plan to store them for more than 4 months it is important to unpack the system to recharge the batteries. Consult with the factory customer service department for assistance.
BILS-10003 rev E
7
200 Installation Guidelines
Herytage UPS are intended to be installed in a temperature controlled, indoor area free of conductive contaminants.
See specifications for more details on the temperature range, environment, and altitude. In addition consider any national and local codes you may have to follow.
201 Installation considerations
Before installation of your new Herytage UPS, be sure to take into consideration the site you have selected. UPS systems produce heat and therefore require ventilation as well as accessibility.
Consider these factors:
- Input Source Voltage - Ventilation
- Available Single Phase KVA - Size of the UPS
- Bypass Switch - Weight of UPS and Batteries
- Excessively Long Power Runs - Room Temperature
- Distance to Critical Load - Audible noise
- Proper Ground Techniques - Clearances
- Generator Applications - Accessibility
- Remote Emergency Power Off - Communications
202 Location
When you plan the location of your UPS, remember to:
Avoid temperature and humidity extremes
Provide shelter from the elements (especially moisture)
Place as near as possible to the computer or other critical loads
Maintain 8 inches of clearance in back for ventilation, and a minimum of 36 inches
in front for ventilation and maintenance. A larger clearance in front is helpful, but not required.
BILS-10003 rev E
8
203 Remote battery installations
Front
Back
6 kVA
If the batteries are installed in a remote location (battery room) utilize DC circuit protection rated at 250A and 20,000A AIC rating. If the batteries must be some distance from the UPS you may need to install larger battery cables between the battery cabinets and the UPS. Call your customer service representative if you would intend to use anything other than standard cable lengths.
204 Customer Supplied batteries with Legacy battery cabinet(s)
Utilize the same number, size and type of battery as offered by Legacy Power Conversion, Inc.
Enersys NP18-12BFR (Legacy Part Number BAT-0373) C&D Technologies UPS 12 - 140 (Legacy Part number BBAT-0065) Enersys NP33-12 (Legacy Part number BBAT-0065) C&D Technologies UPS 12 - 270 (Legacy Part number BBAT-0103) C&D Technologies UPS 12 - 310 (Legacy Part number BBAT-0122) C&D Technologies UPS12-150MR (Legacy Part number BBAT-10031) C&D Technologies UPS12-300MR (Legacy Part number BBAT-10032) C&D Technologies UPS12-350MR (Legacy Part number BBAT-10033)
205 Dimensions and clearance requirements
Table 1 Dimensions and Clearances
Model 2kVA1
3kVA1 4 kVA1
8 kVA 10 kVA
16 kVA 20 kVA
Height
(In.)
25.2 16.2 23 36 8
37.5 17.75 33.25 36 8
39 22 34 36 8
1
Dimensions are for UPS with standard internal runtime.
BILS-10003 rev E
Width
(In.)
Depth
(In.)
Clearance
(In.)
Clearance
(In.)
9
206 External Bypass Switch
Dimension (in) A B C D E F G Weight SW040xxxx 15.0 16.1 17.0 8.0 12.0 7.0 9.4 23 SW080xxxx 16.0 17.1 18.0 12.0 16.0 9.1 11.9 36 SW125xxxx 16.0 17.1 18.0 12.0 16.0 9.1 11.9 38
Allow 36” for service clearance in front of the bypass switch.
207 External Battery Cabinet
2 thru 4K battery cabinet dimensions
BILS-10003 rev E
10
6 thru 20K battery cabinet dimensions
Allow 36” for service clearance in front and on one side of the battery cabinet. Placing cables in flexible metal conduit will allow for movement of battery cabinet for service.
300 Wiring Instructions
There are two basic installation configurations of the Herytage UPS system. Following is an overview of each configuration.
- Soft-wired (Line cord & receptacles)
- Hard-wired with external bypass switch
Installation of electrical wiring should be completed by a qualified electrician. National electrical code and applicable local codes should be followed.
301 Soft-wired installation (Line-cord and receptacle)
Installation requires a proper wall receptacle for the Herytage UPS power cord to plug into, and installation of external bypass receptacles.
Note: External bypass receptacles provide power to your load equipment in the event that the Herytage UPS requires maintenance.
Proper breaker sizing for the input line cord receptacle depends on the input voltage / plug option ordered, see Table 301-1. Review the Herytage UPS input voltage on the
BILS-10003 rev E
11
name plate – if it differs from the power you have available in your building call Legacy Power Conversion customer service.
Table 301-1 Circuit breaker minimum requirements (Soft-wired installations)
Model Input Voltage Line Cord Option1 Minimum
Circuit Breaker
Requirements
2kVA / 1.6kW
3kVA / 2.4kW
4kVA / 3.2kW
6kVA / 4.8kW
1
Line Cord Designators: C = 5-20P, I = L5-20P, J = L5-30P, E = 5-50P, O = 6-15P, K = L6-20P, L = L6-30P,
M = L14-30P, N = 6-50P, P = L6-50P
120 120 208 240 120 208 240 120 208 240 120 208 240
C, I
J, E O, K, L O, K, L
J, E
K, L O, K, L
E L, M L, M
NA N, P N, P
20A
30A, 50A
15A 15A 30A 20A 15A 50A 30A 30A 60A 40A 40A
Figure 301-1 - 2kVA - 6kVA soft-wired installation overview
Herytage UPS
BILS-10003 rev E
Bypass Receptacles
12
302 Hard-wired Installations
General requirements for hardwire Herytage UPS installations
– Input over-current protection and Output over-current protection and AC output
disconnect switch for Herytage UPS must be provided by the installer. It should be installed and sized according to national and local electrical codes.
– External bypass switches should be installed within sight of Herytage UPS.
– Follow applicable national and local electrical codes when installing the grounding
system. Herytage UPS grounding conductor should be at minimum the same size (ampacity) as circuit conductors.
– All circuit conductors including the neutral should be the same size (ampacity).
– Use isolated ground receptacles to obtain the best protection against electrical
noise.
– A separate dedicated conduit system should be utilized for the Herytage UPS input
and output wiring.
– Flexible conduit should be used to allow movement of the Herytage UPS to gain
side service clearance.
– Load imbalance should not exceed 40% / 60%; 2-4K units do not have this
restriction. 6K units L1-N 100% max., L2-N 50% max.
302-1 External bypass switch installations
The 2kVA through 20kVA Herytage UPS may be ordered with an external bypass switch. The external bypass switch is typically mounted on a wall within site of the Herytage UPS. See Figure 302-1A.
1. The wiring access panel for the external bypass switch is located on the front
bottom half of the external bypass switch module, remove the screws securing the bottom half of the front cover to obtain access to the terminal blocks. See Figure 302-1B
2. Input and output wiring to and from the Herytage UPS and to and from the
external bypass switch should be routed through separate conduits. Conduit connection points are located on the back of the UPS, the same conduit connection points are on the external bypass switch. Locate the pre-punched knockouts for starter holes.
3. Review input and output voltages on the unit data plate and insure they are
proper for your installation, select wiring connection diagram figure 1 or 2 for appropriate connection. If the wrong input or output voltages were ordered – call Legacy Power Conversion customer service for assistance.
BILS-10003 rev E
13
Figure 302-1A - Hard-wired Installation Overview
External Bypass Switch
Input and Output
Terminal Block located
under side panel
Herytage UPS
Figure 302-1B Bypass Switch Terminal Block
BILS-10003 rev E