Legacy RMC-LC10NG, RMC-LC10LP, RMC-LC20NG, RMC-LC20NGF, RMC-LC20LP User's Operation And Installation Manual

...
INSTALLER / CONSUMER
SAFETY INFORMATION
Please read this manual before installing and using the heater.
WARNING:
If the infor
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch;
do not use any phone in your building.
Immediately call your gas supplier
from a neighbour’s phone. Follow the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fire department.
Installation and service must be
performed by a qualified installer, service agency or the gas supplier.
Installer: Leave this manual with the heater.
Consumer: Retain this manual for futur
e r
efer
ence.
This is an unvented gas-fir
ed heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be pr
ovided. Refer to the
Installation section on page 3.
Unvented
Gas-Fired Room Heater
Blue Flame Heaters
Models: RMC-LC10NG, RMC-LC10LP - 10,000 Btu/hr.
RMC-LC20NG(F), RMC-LC20LP(F) - 20,000 Btu/hr RMC-LC30NG(F), RMC-LC30LP(F) - 30,000 Btu/hr
RMC-LC10NG(T), RMC-LC10LP(T) - 10,000 Btu/hr. RMC-LC20NG(T),(F), RMC-LC20LP(T),(F) - 20,000 Btu/hr RMC-LC30NG(T),(F), RMC-LC30LP(T),(F) - 30,000 Btu/hr
Infra-Red Heaters
Models:
RMC-LI10NG, RMC-LI10LP - 10,000 Btu/hr RMC-LI18NG(F), RMC-LI18LP(F) - 18,000 Btu/hr RMC-LI30NG(F),
RMC-LI30LP(F)
- 30,000 Btu/hr
RMC-LI06NG, RMC-LI06LP - 6,000 Btu/hr. RMC-LI10NG
(T)
, RMC-LI10LP
(T)
- 10,000 Btu/hr
RMC-LI18NG
(T),(F)
, RMC-LI18LP
(T),(F)
- 18,000 Btu/hr
RMC-LI30NG
(T),(F)
, RMC-LI30LP
(T),(F)
- 30,000 Btu/hr
User’s Operation and Installation Manual
(F)=Fan, (T)=Thermostat Gas Control
(F)=Fan, (T)=Thermostat Gas Control
07/05 Rev 3.
2
General Information
SAFETY: Accidents are always tragic especially because so many of them could have been prevented with a little care and attention. These are some basic good practices we hope you will follow for safe use of your gas fired room heater.
IMPOR
TANT: Read this user's manual carefully and completely before trying to assemble, operate or service this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock (fan models) or carbon monoxide poisoning.
Early signs of carbon monoxide poisoning resemble the flu with headaches, dizziness or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol or those at high altitude.
Begin by ensuring proper installation and servicing. Ensure that your qualified technician who installs this heater follows the installa
tion instructions provided with this product.
Ha
ve the installer show you where the gas supply shut off valve is loca
ted so tha
t you kno
w where to shut off the gas to the
hea
ter
.
If the connections are not perfectly sealed or tightened, you may have a leak and therefore a faint gas smell.
F
inding a leak is NOT a do-it-yourself procedure. Some leaks can only be found with the main burner gas on and this must be done by a qualified technician.
Table of Contents
bathroom and an unvented room heater having an input rating of more than 6,000 BTU per hour shall not be installed in a bathroom.
• Do not install RMC-LC30,
LI30, LC20 or LI18 heaters in a
bedroom or a bathroom.
• Do not install RMC-LC10 or LI10 hea
ters in a bathroom, they
are allowed in bedrooms.
• LI06 heaters are allowed in bathrooms or bedrooms.
• This appliance is intended for supplemental heating.
• Do not use a blower or other accessory not approved for use with this heater.
• Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies. Keep flammable objects more than 36” from the front and top of the heaters and more than 10” from the sides of the heater ( 8”
for the L106 heater).
• Provide adequa
te clearances for accessibility for purposes of
servicing the heater.
• Maintain adequa
te clearances around the air openings to
allo
w for proper and safe operation of the heater.
WARNING: Do not allow fans to blow directly into the heater. Avoid any drafts that alter the burner flame patterns.
• This heater needs fresh, outside air for combustion to run properly. This heater has an oxygen depletion sensor (ODS) pilot light safety system. The ODS shuts down the heater if not enough fresh air (oxygen content > 18%) is available.
• Never run heater in confined space. Refer to page 4.
• If heater shuts off, do not relight until you provide fresh, outside air. If heater keeps shutting off, clean it and have it serviced.
• Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.
• Keep burner and control compartment clean. See maintenance section of this manual.
• Do not place clothing or other flammable material on or near the appliance.
• Children and adults should be alerted to the hazard of high surface temperatures and should stay away to avoid burns and clothing ignition.
• Young children should be carefully supervised when they are in the same room with the appliance. Never allow them to sit, stand or play on or around the heater.
• Make sure tha
t if the safety screen or guard is removed for
ser
vicing or lighting the a
ppliance,
it is replaced prior to
operating the heater.
Do not use the hea
ter if an
y part has been under water.
Immedia
tely call a qualified ser
vice technician to inspect the room heater and to replace any part of the control system and an
y gas control which has been under wa
ter
.
The ODS pilot light safety system is designed to prevent asphyxiation due to a lack of oxygen in the air.
The hea
ter does not monitor the air for CO.
This appliance may be installed in an aftermarket, per
manently located,
manufactur
ed (mobile) home
,
wher
e not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
Any c
hange to this heater or
its controls can be dangerous.
PRECAUTIONS
• Never use natural gas in a unit designed for propane gas.
• Never use propane in a unit designed for natural gas.
• Check all joints and connections.
T
o a
void the danger of fire, accident or explosion, never check a potential gas leak with an open flame.
An unvented room hea
ter ha
ving an input rating of more than
10,000 BTU per hour shall not be installed in a bedroom or
SAFE OPERATION OF YOUR LEGACY
VENT FREE HEATER
Installer / Consumer Safety Information . . . . 1
General information . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . 3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operating Instructions . . . . . . . . . . . . . . . . . 8
Troubleshooting . . . . . . . . . . . . . . . . . . . . . 10
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 11
Replacement Parts . . . . . . . . . . . . . . . . . . . 12
Accessories . . . . . . . . . . . . . . . . . . . . . . . . 14
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3
RMC-LCNG, RMC-LCLP, RMC-LING, RMC-LILP Specifications
Models
(Manual &
Thermostat)
Gas Type
Input Rating
(Btu/Hr) Variable
Regulator
Pressure
Setting
Inlet Gas Supply
Pressure
Size
of Heater
Weight
Min. Max Min. Max
RMC-LC30NG
Natural
15,000 30,000
4.0” w.c. 5.0” w.c. 11” w.c.
27”x24”x8
1/2
30 lbs.
RMC-LC20NG
10,000 20,000
19
3/8
”x22
7/8
”x8
1/2
22 lbs.
RMC-LC10NG
5,000 10,000
15
1/2
x20
7/8
x7
7/8
17 lbs.
RMC-LC30LP
LP
15,000 30,000
10” w.c. 11.0” w.c. 14.0” w.c.
27”
x24”x8
1/2
30 lbs.
RMC-LC20LP
10,000 20,000
19
3/8
”x22
7/8
”x8
1/2
22 lbs.
RMC-LC10LP
5,000 10,000
15
1/2
”x20
7/8
”x7
7/8
17 lbs.
RMC-LI30NG
Natural
6,400 30,000
27”x24”x8
1/2
30 lbs.
RMC-LI18NG
6,400 18,000
19
3/8
”x22
7/8
”x8
1/2
22 lbs.
RMC-LI10NG
5,500 10,000
15
1/2
”x20
7/8
”x7
7/8
17 lbs.
RMC-LI06NG
- 6,000
15
1/2
”x20
7/8
”x7
7/8
17 lbs.
RMC-LI30LP
LP
6,400 30,000
10” w.c. 11.0” w.c. 14.0” w.c.
27”x24”x8
1/2
30 lbs.
RMC-LI18LP
6,400 18,00
19
3/8
”x22
7/
8
”x8
1/2
22 lbs.
RMC-LI10LP
5,500 10,000
15
1/2
”x20
7/8
”x7
7/8
17 lbs.
RMC-LI06LP
- 6,000
15
1/2
”x20
7/8
”x7
7/8
17 lbs.
NOTE: For altitude above 2,000 feet, reduce the input ratings (Btu/Hr) 4% for each 1,000 feet above sea level.
DO NOT USE THIS HEATER AT AN ELEVATION ABOVE 4,500 FEET
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes,
use the la
test edition of the National
Fuel Gas Code
ANSI Z223.2,
also kno
wn as NFP
A54.
Available from: American Na
tional
Na
tional F
ire Protection
Standards Institute,
Inc.
Associa
tion,
Inc.
1430 Broadway
Batterymarch Park
New
Y
ork,
NY 10018
Quinc
y, MA 02269
RMC-LC30 / RMC-LC20 / RMC-LC10
RMC-LI30 / RMC-LI18 / RMC-LI10 / RMC-LI06
Certified to ANSI Z21.11.2b-2004 Unvented Heaters
This heater has a pilot with an Oxygen Depletion Sensor Shut­off system (ODS).
The ODS pilot is a required fea
ture for vent-
free hea
ters.
The ODS pilot shuts off the hea
ter if the normal air
oxygen content is reduced belo
w 18%.
This hea
ter has a piezo ignitor
.
This system requires no ma
tch
-
es,
ba
tteries or other electrical sources to light the heater.
PRODUCT FEATURES
SAFETY DEVICE
PIEZO IGNITION SYSTEM
4
Installation
• This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
This heater must have fresh air for proper operation. If not, poor fuel combustion could result. Read the following instructions to insure proper fresh air for this and other fuel burning appliances in your home.
Modern construction standards have resulted in homes that are highly energy efficient and that allow little heat loss. However, your home needs to breathe and all fuel burning appliances need fresh air to function properly and safely. Exhaust fans, clothes dryer, fireplaces and other fuel burning appliances all use the air inside the building. If the available fresh air supply is insufficient to meet the demands of these appliances, problems can result.
Confined Space:
The National fuel Gas Code, ANSI Z223.1 / NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1000 BTU per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space.
Unconfined Space:
An unconfined space is defined in the same standards as a space whose volume is not less than 50 cubic feet per 1000 BTU per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.
Example:
10,000 BTU Legacy heater should only be installed in a room whose volume is more than 500 cubic feet. A room that is 8' x 8' x 8' (512 cubic feet) would be acceptable for a Legacy 10,000 BTU/hour heater.
If an additional fuel fired appliance is installed in the same room,
the input ra
ting of tha
t a
ppliance should be added to
tha
t of the Legac
y hea
ter to determine the minimum sized
room that should be serviced by both appliances.
Unusually tight construction is defined as construction
where:
a) Walls and ceilings exposed to the outside atmosphere have a
continuous wa
ter va
pour retarder with a rating of 1 perm (6 x 10-11 kg per pa-sec-m2) or less with openings gasketed or sealed;
b)
Weather stripping has been added on openable windows and doors; and
c) Caulking or sealants are applied to areas such as joints
around windo
w and door frames, between sole plates and
floors,
between wall-ceiling joints,
between wall panels,
a
t penetrations for plumbing, electrical and gas lines and at other openings.
PROVIDE ADEQUATE COMBUSTION
AND VENTILATION AIR
WARNING: If the area in which the heater may be operated is
smaller that that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventila
tion air by one of the methods described in the National fuel Gas code, ANSI Z223.1 / NFPA 54,
Section 5.3 or applicable local codes.
Verify the type of gas supply to be used, either natural gas or LP (Propane), and make sure the marking on the appliance rating plate agrees with that of the supply gas. The rating plate is located on the side of the heater, which indicates the type of gas the heater is manufactured for.
WARNING: This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not convertible for use with other gases.
Before installing the heater, make sure you have these items:
• Gas piping (check local codes)
• Test gauge connection
• Sealant (resistant to LP gases) - approved thread compound
• Manual shut-off valve*
• Sediment trap - where required
• Ground joint union
• Tee joint and pipe wrench
*An installer supplied design-certified manual shut-off valve
with 1/8 NPT tap connection.
ITEMS NEEDED FOR
HEATER INSTALLATION
GAS TYPE
LOCATING THE HEATER
5
PREPARING FOR INSTALLATION
1. Remove heater from carton
2.
Remove all protective packa
ging applied to heater
for shipment.
3. Check heater for any shipping damage. If heater is dama
ged,
promptly inform dealer/distributor.
4.
Select a loca
tion for the hea
ter tha
t will provide maximum exposure of the radiant surface to the room, but will not be subjected to accidental contact.
5.
Adequa
te c
learance must be a
vailable around the air open
­ing. Refer to Figure 2 for clearances that must be main­tained to the side walls,
floor and horizontal surface sur-
rounding the hea
ter
.
Fig. 2 Minimum clearances from mounting holes to top surface of flooring,
adjacent walls and ceiling
ATTACH MOUNTING SCREWS TO WALL
Fig.
3
Use pa
per templa
te supplied to mark loca
tion of mounting holes.
Be sure templa
te is level.
NOTE: Wall anchors and mounting screws are in hardware
package provided with heater.
1. Install mounting screws on wall as shown in Figure 3. Use enclosed paper template for proper location of holes. Be sure template is level. It may be necessary to use plastic or lead anchors for plaster walls.
2. Drill holes at marked location using 9/64” drill bit. Insert mounting screws.
3. Leave screw head out from wall far enough to attach heater.
• Due to high tempera
tures, the appliance should be located out of traffic and away from furniture and draperies. Keep flam­mable objects more than 36” from the front and top of the heaters and more than 10” from the sides of the heater.
• Provide adequate clearances for accessibility for purposes of ser
vicing the heater.
• Maintain adequate clearances around the air openings to allow for proper and safe operation of the heater.
WARNING: Do not allow fans to blow directly into the heater.
Avoid any drafts that alter the burner flame patterns.
This heater is designed to be mounted on a wall or on the floor.
WARNING: Never install the heater;
• in a bathroom*
• in a recreational vehicle
• where curtains, furniture, clothing or other flammable are less than 36” from the front, top or sides of the heater
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
*Models RMC-L106NG or LP Permitted for bathroom installation.
WARNING: Vent-free heaters add moisture to the air. Although
this is beneficial, installing heater in rooms without enough ventilation may cause mildew formation from too much moisture content. See National Fuel Code for Fresh Air for Combustion and Ventilation.
This appliance may be installed in an aftermarket, permanently located manufactured (mobile) home, were not prohibited by state or local codes.
Caution: If you install the heater in a home garage:
• Heater must be at least 18” above floor
• Locate heater where moving vehicle will not hit it.
• Install to
ANSI Z223.2 / NFPA 54 using fixed gas supply piping.
6
FLOOR INSTALLATION
1. Heater may only be installed on a noncombustible flat surface. Where the flooring is carpeting, tile or of other combustible material other than wood flooring, maintain the minimum clearances to the floor as shown in figure 2 or else use a metal or wood panel (not supplied) extending the full width and depth of the appliance.
2. Measure heater mounting screw location “X” as desired above floor. (Fig. 5)
3. Use enclosed “paper template” for proper distance between holes. Be sure template is level. It maybe necessary to use plastic or lead anchors for plaster walls.
4. Leave screw head out from wall far enough to attach heater.
Fig. 5 Optional wall mounting screws for floor installation.
WALL ANCHOR METHOD
Fig. 4 Wall anchor.
When mounting hea
ter to hollow walls (wall areas between studs) or solid walls (concrete or masonry) it may be neces­sar
y to use wall anchors.
1. Place paper template on wall maintaining minimum clear-
ance. Be sure template is level.
2. Drill holes at marked locations using 5/16”drill bit.
For solid walls, concrete or masonry, drill holes at least 1”deep.
3. Insert plastic anchor. Tap anchor flush to wall. (Fig. 4)
4. Insert screw into wall anchor leaving screw head out far
enough to attach heater. (Fig. 4)
5. Hang heater on mounting screws in holes provided at the
rear of the heater.
x = 17
3/4
"
45 CM 30,000 BTU/hr units
16
1/2
"
42 CM 18 & 20,000 BTU/hr units
14
1/4
" 36 CM 6 & 10,000 BTU/hr units
7
Installation should be done by a qualified service person. Before connecting the appliance, turn off all gas appliances. Close the main gas valve a
t the gas meter or LP tank. Make certain there is good ventilation where the installation will be made.
Installation should comply with all applicable building codes and ANSI Z223.1, latest edition. Use PLP gas resistant pipe compound to seal threaded joints.
An installer supplied,
design certified gas pressure regulator must be installed to bring the gas supply pressure down to 14" w.c. for LP gas or 11" for natural gas.
WARNING: Never connect an unregulated gas line to the heater.
IMPORTANT: Check gas line pressure before connecting heater
to gas line. Gas line pressure must not be higher higher than 14" w.c. for LP gas or 11" for natural gas.
NOTE: The gas line connection can be made with 3/8”black or
steel pipe. Internally tinned copper tubing may be used in cer­tain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue pressure loss will occur.
CAUTION: Use pipe joint sealant that is resistant to liquefied
petroleum gases. Install sediment trap in supply as shown in Figure 6.
Locate sediment trap where it is within reach for cleaning. Locate sediment trap where matter is not likely to freeze. A sediment trap prevents moisture and contaminant's from going into the heater controls. If the sediment trap is not installed or is installed wrong, the heater may not operate properly.
Test for gas leaks with a mild soap and water solution. Apply water/soap solution with brush only - do not over apply.
NEVER test with an open flame.
CONNECT TO GAS SUPPLY
Fig. 6 Gas line connection
PRESSURE TEST GAS SUPPLY
PIPING SYSTEM
The a
ppliance and its individual shut off (control) valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressure in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing the individual manual shut-off valve (fig. 7) during any pressure testing of the gas supply system at test pressure equal to or less than 1/2 psi (3.5 kPa).
Fig. 7 Manual shut-off valve location.
LEAK TESTING HEATER
GAS CONNECTION
1. Make sure control knob of heater is in the OFF position.
2. Open manual shut-off valve.
3. Open main gas valve located near gas meter.
4. check all joints from manual gas valve up to control valve
and including the manifold assembly. Apply the soap solution around the connections, valve and tubing. Soap bubbles will appear where a leak is present.
5. If a leak is present, immediately turn off gas supply, tighten
any leaky fittings, turn gas on and recheck.
6. To check burner and safety valve, the burner must be lit. (See
Operating Instructions) Check the rest of the connections for leaks.
7. Turn off the heater prior to making any gas connection
repairs.
8
Operation Instructions
FOR YOUR SAFETY - READ THIS SECTION BEFORE LIGHTING
A. BEFORE LIGHTING smell all around the appliance area for
gas. Be sure to smell next to floor because some gas is heavier than air and will settle on the floor.
LIGHTING INSTRUCTIONS
W
ARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE
IF YOU SMELL GAS:
1. Do not try to light appliance.
2. Do not touch electrical switches; do not use any phone in your building.
3. Immediately call your gas supplier from a neighbour’s phone. Follow your gas suppliers instructions.
4. If you cannot reach you gas supplier’s, call the fire department.
B. Use only your hand to push in or turn the gas valve control
knob. Never use tools. If the knob will not push in or turn by hand, do not try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
C. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of this control system and any gas control which has been under water.
ATTENTION:
Keep burner and control compartment clean.
See installation and operating instructions accompanying the heater.
See the safety information on the sides of the heater.
WARNINGS:
Hot while in opera
tion.
Do not touch.
Keep children, clothing and furniture away.
Do not light or opera
te where gasoline and other liquids ha
ving
flammable va
pors are present.
1.
Stop! Read and Heed the Warnings and Cautions on the side of the heater.
2. Check that gas supply to the heater is on.
3. Push in gas control knob slightly and turn clockwise to “OFF” position.
NOTE: knob cannot be turned from "PILOT" to "OFF" unless
knob is pushed in slightly. Do not force.
4. Wait five (5) minutes to clean out any air. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the side of the heater. If you do not smell gas, go to the next step.
5. Push in gas control knob slightly and turn counterclockwise
to "PILOT/IGN” and depress for five (5) seconds.
NOTE: The first time that the heater is operated after connecting
the gas supply, the control knob should be depressed for about thirty (30) seconds. This will allow air to bleed from the gas system.
6. Release control knob and turn clockwise to "OFF".
7. Depress control knob while "OFF", then turn back to to "PILOT/IGN”. This should cause the spark from the piezo ignitor to light the pilot gas. Keep control knob depressed for ten (10) seconds before releasing. If pilot does not light, repeat steps 5, 6 and 7 or use a match.
8. When pilot is lit, turn the ignition knob to "ON".
9. To select the heating level desired, use the knob LOW to HIGH.
1. Stop! Read and Heed the Warnings and Cautions on the side of the hea
ter.
2. Check that gas supply to the heater is on.
3. Push in gas control knob slightly and turn clockwise to “OFF” position.
4. Wait five (5) minutes to clean out any air. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information on the side of the heater. If you do not smell gas, go to the next step.
5. Turn control knob counterclockwise to “PILOT” position. Press in control knob for five (5) seconds.
NOTE: The first time that the heater is operatedafter connecting
the gas supply, the control knob should be depressed for about thirty (30) seconds. This will allow air to bleed from the gas system.
6. With control knob pressed in, push down and release ignitor button. This will light pilot. If needed, keep pressing ignitor button until pilot lights.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
8. If pilot goes out, repeat steps 5 through 7 or use a match.
9. When pilot is lit, turn control knob to on.Turn control knob counterclockwise to desired heating level between 5 and 1.
Fig.
8
Control knobs
MANUAL GAS CONTROL
THERMOSTAT GAS CONTROL
RMC-LC10, RMC-LI10 & LI06 Only
9
Turning Heater Off
Push in gas control knob slightly and turn c
lockwise
to "OFF" position. Do not force.
Turning Burner Only Off (Pilot stays lit).
T
urn control knob clockwise to the PILOT position.
CAUTION: Do not try to adjust heating levels by using the manual shut-off valve.
NOTE: The thermostat sensing bulb measures the temperature
of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installa­tion location, room size, ect.). Frequent use of your heater will let you determine your own comfort levels.
MANUAL LIGHTING INSTRUCTION
1. Use a long match or a BBQ lighter. If not available, remove guard assembly by flexing it.
2. Follow steps 1 through 4 as stated under Lighting Instructions.
3.
Press and turn control knob counterc
lockwise to the
PILOT/IGN position
4. With control knob pressed in, strike match, hold match to pilot until pilot lights.
5. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
6.
Replace guard assembly if it was removed in step 1.
PILOT AND BURNING INSPECTION
Each time you light your heater check that the pilot flame and burner flame pa
tterns are as sho
wn in F
igures 9, 10 and 11. If
flame pa
tterns are incorrect,
turn the hea
ter off.
Contact your dealer or qualified gas technician for assistance. Do not operate the hea
ter until the pilot flame is correct.
W
ARNING:
If yello
w tipping occurs,
your heater could produce increased levels of carbon monoxide. If burning flame pattern shows yellow tipping, follow instruction in the Troubleshooting section on pa
ge 10.
NOTE: Do not mistake orange flames with yellow tipping. Dirt or
other partic
les may enter the hea
ter and cause transient pa
tches of
orange flame
.
Fig. 9 Proper pilot flame
Fig. 10 Correct burner flame pattern for the RMC-LC blue flame burner.
Fig.
11
Correct burner flame pa
ttern for the RMC-LC plaque hea
ter
.
TO TURN OFF GAS TO APPLIANCE
Turning Heater Off
Turn control knob clockwise to “OFF” position.
Turning Burner Only Off (Pilot stays lit).
Turn control knob clockwise to the PILOT position.
CAUTION: Do not try to adjust heating levels by using the manual shut-off valve.
NOTE: The thermostat sensing bulb measures the temperature
of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installa­tion location, room size, ect.). Frequent use of your heater will let you determine your own comfort levels.
THERMOSTAT GAS CONTROL
MANUAL GAS CONTROL
10
Problem Possible Cause What To Do
When control knob is pressed in and turned counterc
lockwise to ignition, there is no spark at ODS pilot.
1. Ignitor electrode positioned wrong.
2.
Ignitor electrode broken.
3. Ignitor cable pinched or broken.
4. Ignitor cable not connected to ignitor electrode.
1. Reposition ignitor electrode.
2.
Replace electrode.
3. Free ignitor cable, if damaged, replace.
4. Connect cable to electrode
When control knob is pressed in and turned counterc
lockwise to ignition/pilot position there is spark but no ignition
1. Gas supply turned off.
2.
Control knob not in pilot position.
3. Control knob not pressed in while in pilot position.
4. ODS pilot is clogged.
5. Air in gas lines.
1. Turn gas supply on.
2.
Turn control knob to pilot position.
3. Press in control while in pilot position.
4.
Call a qualified service technician.
5. Purge gas lines and repeat ignition operation.
ODS pilot lights but flame goes out when control knob is released.
1.Control knob not pressed long enough.
2. Safety interlock is triggered.
3. Pilot flame not touching the thermocouple. Problem could be result of one or both of the following:
• Partially clogged ODS pilot orifice.
• Low gas pressure.
4. Thermocouple damaged.
5. Thermocouple connection loose at gas control valve.
6. Gas control valve damaged.
1. After ODS pilot lights, keep control knob pressed in approximately 30 seconds.
2. Wait one minute, repeat ignition operation.
3. Contact your gas company, gas supplier or qualified service technician.
4. Replace thermocouple.
5. Hand tight until snug then tighten 1/4 turn with a wrench.
6. Replace gas control.
Burner does not light after ODS pilot is lit.
1. Burner orifice clogged.
2. Gas supply pressure is very low.
1. Clean burner orifice.
2. Contact gas supplier.
Delayed ignition. 1. Main burner carry over ports clogged.
2.
Gas supply pressure is very low.
1. Clean main burner ports.
2.
Contact gas supplier.
Burner backfiring during operation.
1. Burner orifice is clogged.
2. Burner ports damaged.
1. Clean burner orifice.
2. Replace burner.
Y
ello
w flames during burner
operation. (RMC-LC)
1.
Not enough air
1.
Check air passa
geways and burner for dirt and
debris (Refer to Maintenance section)
Burner plaque(s) does not glow. (RMC-LI)
1. Plaque(s) is damaged.
2. Inlet gas pressure too low.
3. Control knob set between locked positions.
1. Replace burner.
2. Contact local gas supplier.
3. Turn control knob until it locks at desired setting.
Slight smoke and odor during initial operation.
1. Residues from manufacturing processes. 1. Will stop after a few hours of operation.
Hea
ter produces a whistling
noise when burner is lit.
1.
Air passa
geways blocked.
2.
Air in gas line.
1.
Check minimum installa
tion c
learances and air
passageways for debris.
2.
Opera
te burner until the air is completely
purged.
Troubleshooting
11
Problem Possible Cause What To Do
Hea
ter produces a clicking noise just after burner is lit or turned off.
1.
Metal expanding and contracting.
1.
This is common with heaters. If noise is
excessive, contact a qualified service technician.
Gas odor even when control knob is in OFF position.
1. Gas leaks. Refer to front of page Warnings.
2. Gas control defective.
1. Locate and correct leaks immediately.
2. Replace gas control.
Gas odor during combustion. 1. Foreign matter in gas or on burner ports.
2. Heater burning vapors form paint, impurities in air.
3. Gas leaks, refer to front page Warnings.
1. Check gas passage way and burner.
2. Ventilate room, stop storing and using odor causing products near heater.
3. Locate and correct leaks immediately.
Heater shuts off on ODS. 1. Not enough fresh air is available.
2. Low gas pressure.
3. ODS pilot partially clogged.
1. Open window.
2. Contact gas supplier.
3. Clean the pilot.
Troubleshooting continued
Maintenance
BURNER AND ODS PILOT CLEANING
Repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners and circulating air passageways of the heater be kept clean. Dust, lint, cobwebs or debris may affect heater performance. The heater draws air into it during normal operation and in the process dust, lint or debris may be drawn in also. It is important to keep the burner, gas control and combustion and circulating air passageways clean. Inspect or have these areas inspected annually at the beginning of the heating season by a qualified service person. Depending on the surroundings, the room heater may require frequent clean­ing due to excessive lint or debris.
Before cleaning ensure the gas supply is off and the gas con­trol knob is in the OFF position.
Make sure the hea
ter is cool.
WARNING: Danger of bodily injury. If fan assembly accesso­ry is used, turn off power supply at disconnect switch or service panel before removing any access panels from heater.
Clean the exterior with soft bristle brush, vacuum cleaner or pressurized air. Never use a wooden toothpick as it may break off and clog the ODS pilot or main burner port.
Use a flashlight to inspect the main burner inlet to ensure it is not blocked. If obstruction can be seen, use a metal wire coat hanger that has been straightened out. Use a vacuum cleaner to clean the primary air openings to the main burner(s).
WARNING: Failure to keep the primary air openings to the burner(s) clean may result in sooting and property dam­age.
In order to clean ODS pilot orifice, use pressurized air to blow dust out.
Sometimes blowing air backwards through the pilot will get rid of the accumulated dirt. If that does not work blow out any dust through primary air openings of pilot assemblies (This unit has two openings; one benea
th the bimetal strip and the second one opposite from bimetal strip. Use the one wide open, do not try to lift the bimetal strip.)
CLEANING AIR PASSAGEWAYS AND
UNIT CASINGS
Use a vacuum c
leaner or pressurized air to c
lean the combus
­tion and circulating air passageways and dampened cloth to clean the cabinet/casing.
12
Item/Model Number RMC-LI06NG/LP RMC-LI10NG(T)/LP(T) RMC-LI18NG(T)/LP(T) RMC-LI30NG(T)/LP(T)
1. Lower Heat Cover LI10LP-01-01-02 LI10LP-01-01-02 LI18LPT-01-01-03 LI30NG-01-01-02
2. Guard Assembly LC10NG-01-04 LC10NG-01-04 LI18LPT-01-04 LC30NGTF-01-04
3. Reflector LI10LP-01-01-01 LI10LP-01-01-01 LI18LPT-01-01-01 LI30NG-01-01-01
4. Upper Heat Cover LC10NG-01-01-02 LC10NG-01-01-02 LI18LPT-01-01-02 LC30NGTF-01-01-02
5. Leg Front LC10NG-05 LC10NG-05 LC10NG-05 LC10NG-05
6. Front Panel LC10NG-01-03 LC10NG-01-03 LI18LPT-01-03 LC30NGTF-01-03
7. Burner Assembly Body LI6LP-03-00 LI10LP-03-00 LI18LPT-03-00 LI30LPTF-03-00
8. Ceramic Plate LI18LPT-03-09 LI10LP-03-03 LI18LPT-03-09 LI18LPT-03-09
9. Body Frame Assembly LC10NG-02-00 LC10NG-02-00 LC20NG-02-00 LC30LP-02-00
10. Knob – Valve LC10NG-12-00 LC10NG-12-00 LC10NG-12-00 LC10NG-12-00
11. Leg – Rear LC10NG-04 LC10NG-04 LC10NG-04 LC10NG-04
12. Valve Link LI6LP-02 LI6LP-02 LI18LPF-02 LI30NG-02
13. Fix Pin – Link LI6LP-03 LI6LP-03 LI6LP-03 LI6LP-03
14a. Gas Control CK-890SL-A1/00(B) CK-890SL-A1/00(D) CK-890SL-A1/00(E) CK-890SL-A1/00(E)
14b. Thermostat Gas Control LI18LPT-04-00 LI18LPT-04-00 LI18LPT-04-00
15. Tubing Inlet Assembly LI6LP-07-00 LI10LP-07-00 LI18LPF-07-01 LI30NG-07-01
16a. Outlet Tubing Assembly LI10NGT-08-00 LI18LPT-08-00 LI30LPTF-08-00
16b. Tubing Outlet – A Assembly LI6LP-08-00 LI10LP-08-00 LI18LPF-08-00 LI30NG-08-00
17. Tubing Outlet – B Assembly LI10LP-10-00 LI18LPF-10-00 LI30NG-10-01-00
18. Tubing Outlet – BL Assembly LI30NG-10-02-00
19. Tubing Outlet – BR Assembly LI30NG-10-03-00
20. Tubing Outlet – C Assembly LI18LPF-11-00 LI30NG-11-01-00
21. Tubing Outlet – CL Assembly LI30NG-11-02-00
22. Tubing Outlet – CR Assembly LI30NG-11-03-00
23a. Manifold – “C” LI30NG-10-02
23b. Manifold Assembly - LI10NGT-03-02-00 LI18LPT-03-02-00 LI30LPTF-03-02-00
24. ODS Tubing Assembly LI6LP-09-00 LI10LP-09-00 LI18LPF-09-00 LI30NG-09-00
25a. ODS Pilot
Assembly – Na
tural
144NG 4-7" NG 8224 NG 8224 NG 8224
25b. ODS Pilot Assembly – LP 158LP 8-11" LPG 8420 LPG 8420 LPG 8420
26a. Main Nozzle – Natural LI6NG-08-05 LI10NG-08-05 LI6NG-08-05 LI6NG-08-05
26b. Main Nozzle – LP LI6LP-08-05 LI10LP-08-05 LI06LP-08-05 LI06LP-08-05
27. Connector – “B” LC10NG-05-02 LC10NG-05-02 LC10NG-05-02 LC10NG-05-02
28a. Pressure Regulator – Natural RTZ-11/20B3 RTZ-11/20B1 RTZ-11/20B3 RTZ-11/20B3
28b. Pressure Regula
tor – LP
R
TZ-11/20B4
R
TZ-11/20B2
R
TZ-11/20B4
R
TZ-11/20B4
29. Rear Radiant Hea
t Shield
LC10NG-01 LC10NG-01 - LC30NGTF-01
30. Shield - - LI18LPT-01 -
31. Optional Fan-Natural/LP - - RMA-FT RMA-FT
RMC-LI NG/LP Unvented Room Heater
13
CFM Home Products reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
WARNING: Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this
heater may result in property damage or personal injury.
14
The following accessories are available from your local distributors/dealer. Each accessory comes with a separate installation instruction. Be sure to read each instruction thoroughly before installation.
Accessories
OPERATION & MAINTENANCE INSTRUCTIONS
FMA-(F,FT) MANUALLY & THERMOSTATICALLY CONTROLLED BLOWERS
IMPOR
T
ANT
:
The blo
wer po
wer cord is equipped with a three prong grounding plug for your safety and protection against electric shock.
Do not modify the plug provided if it will not fit the
outlet source.
Ha
ve the proper source outlet installed near the heater location to avoid damage to the power cord. Source outlet and grounding plug are illustra
ted in the F
ig.
12.
Description Model Number
Manual Fan Kit
Thermostat Fan Kit
FMA-F
FMA-FT
Fig. 12
Item/Model Number RMC-LC10NG/LP RMC-LC20NG/LP RMC-LC30NG/LP
1. Guard
Assembly
LC10NG-01-04 LI18LPT
-01-04
LC30NGTF-01-04
2. Glass Panel LC10NG-01-02-01 LC20NGT-01-02-01 LC30NGTF-01-02-01
3. Glass Holder LC10NG-01-02-02 LC10NG-01-02-02 LC10NG-01-02-02
4. Reflector LC10NG-01-01-01 LC20NGT-01-01-01 LC30NGTF-01-01-01
5. Heat Cover – Upper LC10NG-01-01-02 LI18LPT-01-01-02 LC30NGTF-01-01-02
6a. Pressure Regula
tor – Natural
R
TZ-11/20B5
R
TZ-11/20B1
R
TZ-11/20B1
6b. Pressure Regulator – LP RTZ-11/20B2 RTZ-11/20B2 RTZ-11/20B2
7. Nozzle Holder LC10NG-03-13 LC10NG-03-13 LC10NG-03-13
8a. ODS Pilot Assembly – Natural NG 8224 NG 8224 NG 8224
8b. ODS Pilot Assembly – LP LPG 8420 LPG 8420 LPG 8420
9. Fix Nut – Nozzle Holder LC10NG-03-11 LC10NG-03-11 LC10NG-03-11
10a. Main Nozzle – Na
tural
LC10NG-03-12 LC20NG-03-12 LC30NGTF-03-12
10b. Main Nozzle – LP LC10LP-03-12 LC20LP-03-12 LC30LP-03-12
11a. Valve Bracket-Manual Gas Control LC10NG-04-02 LC10NG-04-02 LC10NG-04-02
11b. Valve Bracket-Thermostat Gas Control LI18LPT-04-02 LI18LPT-04-02 LI18LPT-04-02
12a. Manual Gas Control-Na
tural
CK-890SL-A1/00(C) CK-890SL-A1/00(F) CK-890SL-A1/00(F)
12b. Manual Gas Control-LP CK-890SL-A1/00(C) CK-890SL-A1/00(F) CK-890SL-A1/00(F) 12c. Thermostat Gas Control-Natural LC10NGT-04-00 LC20NGT-04-00 LC30NGTF-04-00
12d. Thermostat Gas Control-LP LC10NGT-04-00 LC20NGT-04-00 LC30NGTF-04-00
13. Outlet Tubing Assembly LC10NG-08-00 LC20NG-08-00 LC30LP-08-00
14. ODS Tubing Assembly LC10NG-09-00 LC20NG-09-00 LC30LP-09-00
15. Inlet Tubing Assembly LC10NG-07-00 LC20NG-07-00 LC30LP-07-00
16. Leg – Front LC10NG-05 LC10NG-05 LC10NG-05
17. Front Panel LC10NG-01-03 LI18LPT-01-03 LC30NGTF-01-03
18. Burner Assembly LC10NG-03-00 LC20NGT-03-00 LC30NGTF-03-00
19a. Burner Support – Left LC10NG-03-08 LC10NG-03-08 LC10NG-03-08
19b. Burner Support – Right LC10NG-03-09 LC10NG-03-09 LC10NG-03-09
20. Bod
y F
rame
Assembly
LC10NG-02-00 LC20NG-02-00 LC30LP-02-00
21. Leg – Rear LC10NG-04 LC10NG-04 LC10NG-04
22. Knob – Valve LC10NG-12-00 LC10NG-12-00 LC10NG-12-00
23. Shield - LI18LPT
-01
-
24. Rear Radiant Shield LC10NG-01 LC30NGTF-01
25. Optional Fan-Natural/LP - RMA-FT RMA-FT
RMC-LC NG/LP Unvented Room Heater
15
Accessories continued
CAUTION: Damaged power cord can cause a fire or electric shock.
Prior to installing the blower, check for blower for any shipping dama
ge.
If blo
wer is damaged, promptly inform dealer where
you bought the blo
wer
.
INSTALLATION: Plug the blower power cord into a 110-120V
properly grounded type outlet (three prong receptacle) protected by a 15 amp time delay or Circuit Sa
ver fuse for circuit breaker
.
WARNING: Do not let your fingers touch the prongs of plug
when installing or removing the plug from the power outlet.
OPERATION:
Manually Oper
ated:
Use the ON/OFF rocker s
witch to manually
s
witch the blo
wer ON or OFF as desired.
Manually & Thermostatically Controlled: Use the MAN/OFF/AUTO rocker switch to MAN for manual ON or AUTO
for thermosta
tically controlled operation as desired. Thermostat
turns the blo
wer ON when the tempera
ture near the discharge area reaches 105F and turns it OFF when the temperature at the aforementioned location goes down to 86F.
MAINTENANCE:
WARNING: For your safety, turn switch “OFF” and remove plug from po
wer source outlet before c
leaning and maintaining blower. If power cord is worn, cut, or damaged in any way, have it replaced immediately.
CARE OF BLOWER
In normal use, blower may accumulate excessive lint or dust, so the blower should be vacuumed or brushed and checked for proper operation at least once each year by a qualified service personnel. Excessive accumulation of lint and dust can cause the blower motor to overheat frequently and burn out.
CFM Home Products reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time, without notice.
WARNING: Failure to position the parts in accordance with this diagram or failure to use only parts specifically approved with this
heater may result in property damage or personal injury.
Service and Limited Warranty
CFM Home Products warrants this product to be free from defects in materials and components for three (3) years from the da
te of first purchase, provided that the product has been properly installed, operated and maintained in accordance with all a
pplicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be present­ed. This warranty is extended only to the original retail pur­chaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and labor when provided by a CFM Home Products Authorized Service Center.
Warranty part(s) MUST be obtained through authorized dealers of this product and/or CFM Home Products who will provide original factory replacement parts. Failure to use original fac­tory replacement parts voids this warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installa­tion. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing defective heater will be the responsibility of the owner.
TO
THE FULL EXTENT ALLOWED BY THE LAW OF THE JURIS­DICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANT
ABILITY AND FITNESS FOR A PARTICULAR PUR­POSE TO THREE (3) YEARS FROM THE DATE OF FIRST PUR­CHASE; AND CFM HOME PRODUCTS' LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND CFM HOME PRODUCTS SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some sta
tes do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages, so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights,
and you may also have other rights that vary from state to state. Always specify model and serial number when communicating with the factory.
WARRANTY
Contact CFM Home Products with questions concerning prices and policies covering replacement parts. Parts may be ordered through CFM Home Products distributor or dealer
. You will
need the follo
wing informa
tion when ordering replacement
parts:
The appliance model number.
The serial number.
A description of the part.
Should you need additional information beyond
what your dealer can furnish, contact:
DISTRIBUTOR:
CFM Home Products 2695 Meadowv
ale Boulevard Mississauga, Ontario, L5N 8A3 C
ANAD
A
Telephone: 1-800-668-5323
Model and serial numbers are listed on the rating plate (located on right side of heater).