Lega 2KVA, 1KVA, 3KVA, 6KVA, 10KVA User Manual

USER MANUAL
RACK UPS
1 - 10 KVA
2
3
USER MANUAL
Rack Series
1 - 10 KVA
4
About The Manual
This manual is prepared for the users of Rack Series 1-10 kVA.
Companion Manuals
For further information about this device and its options, please visit www.LEGA.com
Updates
Please visit www.LEGA.com for updates. Always use the latest manuals.
Thanks for using our products. Please strictly obey all the instructions in this manual and pay attention to all the warning and operation information. It is not advisable to install or operate the machine before reading this manual.
5
CONTENTS
1 SAFETY INSTRUCTIONS ................................................................................................................ 7
2 INSTALLATION INSTRUCTIONS ................................................................................................. 8
2.1 Unpacking Inspection ........................................................................................................... 8
2.2 Attention Items of Installation .......................................................................................... 9
2.3 UPS and Battery Pack Rear Panel View ............................................................................. 9
2.3.1 The Type of 120V (Output could be 100V, 110V, 115V, 127V) ................................... 10
2.3.2 The Type of 220V (Output could be 208V, 210V, 220V, 230V, 240V) ......................... 11
2.4 UPS Output Connection ................................................................................................... 12
2.5 External Battery Connection Procedure For Long Back Up Type ..................................... 12
2.6 Installation....................................................................................................................... 13
3 PANEL FUNCTION and OPERATION ........................................................................................... 15
3.1 Keys Function ..................................................................................................................... 15
3.2 LED Function....................................................................................................................... 17
3.3 LED Display Function.......................................................................................................... 17
3.4 Turn On/Off Operation ....................................................................................................... 19
3.4.1 Turn On Operation .......................................................................................................... 19
3.4.2 Turn Off Operation ................................................................................................ .......... 19
3.5 UPS Self-Test / Mute Operation .......................................................................................... 20
3.6 Panel Function Setting ........................................................................................................ 20
3.6.1 ECO Mode Setting ............................................................................................................. 20
3.6.2 Bypass Mode Setting ........................................................................................................ 21
3.6.3 Output Mode Setting ........................................................................................................ 22
3.6.4 Low Voltage of Battery Setting ........................................................................................ 23
3.7 Parameters Inquiring Operation .......................................................................................... 24
4 WORKING MODE INTRODUCTION ............................................................................................. 26
4.1 Bypass Mode ....................................................................................................................... 26
4.2 Line Mode............................................................................................................................ 26
4.3 Battery Mode ...................................................................................................................... 26
4.4 ECO Mode ............................................................................................................................ 27
4.5 Fault Mode. ......................................................................................................................... 27
5 THE WARNING LIST OF THE LOGHT and DISPLAY PANEL ................................................... 28
6 TROUBLE SHOOTING ................................................................................................................ 31
6
7 ATTETTION BOF BATTERY DISPOSAL ....................................................................................... 33
8 NETWORK COMMUNICATION .................................................................................................... 33
9 COMMUNICATION INTERFACE INTRODUCTION ....................................................................... 33
10 GUARANTEE .............................................................................................................................. 39
10.1 Terms of Guarantee ............................................................................................................ 39
10.2 Cases Not Covered by the Guarantee................................ .................................................. 40
11 CONTACT INFORMATION ......................................................................................................... 44
7
Do not touch the battery connection terminals. Battery loop and input voltage loop is without
isolation, which may cause high voltage risk between the battery terminal and ground.
Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for
UPS
1 SAFETY INSTRUCTIONS
 The power output voltage may still have 220V or 120V even not connect to the mains power.
 For the battery cable or power cord replacement, please contact our service station or
dealer to purchase, in order to avoid fire caused by inadequate capacity or heat ignition.
 Do not place the battery or battery pack in the fire, which will injure due to explosion.
 Please do not open the UPS case as you will, there is risk of electric shock
the
8
2 INSTALLATION INSTRUCTIONS
2.1 Unpacking Inspection
 Open the UPS package, please check the enclosed accessories including a user manual,
communication cable, support feet, CD-ROM. The long-back model also includes the cable for connection to battery bank.
 Check the UPS if any damage in transport. If find it’s damaged or parts missing, do not power
on, please turn to the carrier and dealer.
 To determine whether this UPS is the model you want to buy. Check the model name showed
both on the front panel and rear panel of UPS to confirm.
Model
Type
Model
Type
1KVA
1KVA Standard model
1KVA
1KVA Long backup model
2KVA
2KVA Standard model
2KVA
2KVA Long backup model
3KVA
3KVA Standard model
3KVA
3KVA Long backup model
6KVA
6KVA Standard model
6KVA
6KVA Long backup model
10KVA
10KVA Standard model
10KVA
10KVA Long backup model
NOTE:
Please save the packaging box and packaging materials for future transport use. As heavy product, please transit the UPS with care.
9
2.2 Attention Items of Installation
 The UPS installation environment must be with good ventilation, away from water, flammable
gases and corrosive entities.
 Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel
air outtake hole will be unobstructed.
 The peripheral environment temperature around the UPS should be within 0 ~ 40 .
 If dismantling the machine at low temperatures, there may be condensation droplets, users can
not install or operate it before UPS completely got dry both inside and outside, otherwise there will be danger of electric shock.
 Place the UPS near the mains socket to cut off AC mains without any delay at any emergent
case.
ATTENTION:
 Make sure the load behind the UPS is off when users connect the load to UPS, and then turn on
the load one by one later.
 Please connect the UPS with the socket which is over-current protected. Do not connect the
UPS with the socket which rated current is less than the Maximum input current of the UPS.
 All the power socket should be configured with earthling device for safety.
 UPS could be electrified or powered no matter the input power cable is tied or not, even when
the UPS is off. The only way to cut off the output is switching off the UPS, disable the EPO and disconnecting the mains power supply.
 For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the
AC mains power energizes the UPS, it will automatically charge the battery. Without prior charging, UPS output remains as usual but with shorter back-up time than normal.
 When connected to motor, display equipment, laser printer etc, UPS power selection should be
based on the startup power of the load which is usually twice as rated power.
2.3 UPS and Battery Pack Rear Panel View
NOTE:
Following diagrams take the type of 0.9PF for example, the type of 0.8PF is similar.
10
2.3.1 The Type of 120V (Output could be 100V, 110V, 115V, 127V)
A. Standard Model
2 3 4 5
6
2
11 7
8
S
S
EPO
FUSE 250VAC 35A
RESET
FUSE 125VAC, 15A
RESET
USB
INP UT OUT PUT
L N N L
INPUT
9 1
OUTPUT SOCKE T
10
IN OUT
TEL/MODEM/FAX
8
7
OUTPUT SOCKET
9
10
6 5 4
a. 0.9PF 1KVA rear panel b. 0.9PF 2KVA&3KVA rear panel
B. Long-Run Model
2 3 4 5
6
9
2 3 4
7
ON
INTELLIGEN T SLO T
S
EPO
FUSE 125VAC, 15A
RESET
USB
INPUT
OUT PUT
OFF
L N L N
INPUT
9 1
OUTPUT SOCKE T
10
IN OUT
TEL/MODEM/F AX
8
7
11
5 8 6
a. 0.9PF 1KVA rear panel b. 0.9PF 2KVA rear panel
2
10
3
4 6
9 9
S
FUSE 125VAC,35A
RESET
INPUT OU TPU T
L N N L
+
72VDC 40A
-
EXT.BATTERY
OUTPUT SOCKET
EPO
INTELLIGENT
SLOT
9 11 8 5
7
c. 0.9PF 3KVA rear panel d. 0.9PF Battery Pack rear panel
+
-
INTELLIG
ENT SLOT
INTELLIGE
NT SLOT
+
24VDC 40A
-
EXT.BATTE
RY
+
24VDC 40
A
-
EXT.BATTERY
IN
OUT
TEL/MODEM/FAX RS232
US B RS232
RS232
72VDC 40A
EXT.BATTERY
EPO
IINNTTEELLLLIIGEENNTT SSLLOTT
USB
RS232
RS232
EPO
USB
IN
OUT
TEL/MODEM/ FAX
DC OU TPUT
DC OU TPUT
+
72VDC -
+
72VDC -
11
2.3.2 The Type of 220V (Output could be 208V, 210V, 220V, 230V, 240V)
A. Standard Model
2
4
5 6
8
3
7 1 2
S
EPO
INTELLIGENT S LOT
S
FUSE 250VAC,8A
RESET
USB
INPUT
FUSE 250VAC, 20A
RESET
INPUT
OUTPUT S OCKET
IN OUT
TEL/MODE M/FAX
+
48VDC 40A
-
EXT.BATTERY
9 1
10
3
8
7
6 5 4
OUTPUT SOCKE T
10
9
a. 0.9PF 1KVA rear panel b. 0.9PF 2KVA rear panel
9
2
3
4
7
8
3
7 1 2
ON
INTELLIGENT SLOT
INTELLIGENT SLOT
S
INPUT
FUSE 250VAC, 20A
RESET
OFF
OUTPUT SOCKE T
+
72VDC 40A
-
EXT.BATTERY
6 5 4
10 9
11
5 8 6
c. 0.9PF 3KVA rear panel d. 0.9PF 6/10KVA rear panel
B. Long-Run Model
2
4
5 6
2 1
4 6
S
EPO
S
FUSE 250VAC ,8A
RESET
USB
FUSE 250 VAC,15A INPUT
RESET
INPUT
OUTPUT S OCKET
IN OUT
TEL/M ODEM/F AX
+
48VDC 40A
-
EXT.BATT ERY
OUTPUT S OCKET
EPO
INTELLIGENT
SLOT
9 1
10
3
8
7
9 10 8 5 7
a. 0.9PF 1KVA rear panel b. 0.9PF 2KVA rear panel
9
2
3
4
7
2 1
4 6
ON
INTELLIGENT SLOT
S
FUSE 250 VAC,20A INPUT
RESET
INPUT OUTPU T
OFF
+
72VDC 40A
-
EXT.BATTERY
OUTPUT S OCKET
EPO
INTELLIGENT
SLOT
L N L N
9 10
8
3 5 7
11
5 8 6
c. 0.9PF 3KVA rear panel d. 0.9PF 6/10KVA rear panel
1. Input Power Terminals
2. Over Current Protector
3. Fan
4. USB
5. Emergency Power Off
6. RS232 Communication Interface
INTELLIGENT SL OT
INTELL IGENT
SLOT
+
24VDC
40A
-
EXT.BA
TTER
Y
+
24VDC 40A
-
EXT.BA
TTER
Y
OUT
IN
TEL/MODEM/FAX
IN
OUT
TEL/MODEM/FAX
RS232
EPO
USBB
USB
RS232
RS232 RS232
OUT
IN
TEL/MODEM/FAX
IN
OUT
TEL/MODEM/FA X
RS232
EPO
USB EPO
EPO
USB
USB
USB
RS232
RS232
RS232
INP
UT
OU
L
N
L
N
12
7. Intelligent Slot
8. Surge Protection for Network/Fax/Modem
9. Battery Slot
10. Output Socket
11. Terminal Block
NOTE:
Diagrams take the type of 0.9PF for example, the type of 0.8PF is similar. Due to the technology upgrading and development, goods and diagrams might have some differences.
13
INPUT
OUTPUT
L N
N L
which rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
Over Current
Protector
Battery
ON
Over Current
Protector
OFF
Battery
Input
output
LOAD
Input
output
2.5 External Battery Connection Procedure For Long Back Up Type
For different UPS type, users are instructed to configure different battery voltage as below sheet. More or less units are forbidden, or else something abnormal or faulty will appear.
2.4 UPS Output Connection
Output connection of 1~10KVA type is configured with sockets or terminal blocks, users can plug the load cable into the UPS socket to energize the load as below. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
NOTE:
To the type of 6-10KVA, do not use the wall receptacle as the input power source for the UPS,
Type
Battery Quantity
(unit)
Battery Voltage
(volt)
1KVA
2/3
24/36
2KVA
4/6
48/72
3KVA
6/8
72/96
6KVA
16
192
10KVA
16
192
 One end of battery cable is for UPS terminals while the other end with triple cables is for battery
terminals. Correct installation procedure is highly vital or else probable electric shock will arise. Users are strictly required to follow the below procedure.
 Connect battery in correct way and make sure the total battery voltage is available for UPS.
OUT
IN
/MODEM /
14
m
 Correctly connect the long battery cable to battery terminals first, red wire is to positive plate
while black is to negative. If users connect the UPS first, electric shock or other danger could not be avoided.
 Before connecting load after UPS, users should supply main power to UPS and energize it.
 Connect long battery cable to UPS terminals with correct poles link
(red is for “+”, black is for“-”), UPS will start the charging work automatically.
+
S
RED
-
+
-
FUSE 125VAC,20A
RESET
INPUT OUTPUT
+
48VDC 40A
-
EXT.BATTERY
Battery
L N N L
OUTPUT
BLACK
+
+
-
+
-
-
+
-
2.6 Installation
 UPS installation work should comply with local electrical standard and only can be done by
professional technician. 1KVA~3KVA units could use wall socket as input power connection.
 For all type UPS, it is advised to charge the battery over 8 hours before the first use. Once the AC
mains power energizes the UPS, it will charge the battery automatically. Without prior charging, UPS output remains as usual but with shorter back up time than normal.
Installation steps
1. Please take out two groups of support feet from package, assemble by embedding them with each other as shown below.
2. Place the two support feet in parallel on horizontal surface, and then put the machine into two support feet carefully. Make sure the main power is off when you move it.