Lega 1-1 Series, 6KVAS, 10KVAS, 6KVAH, 10KVAH User Manual

LEGA 1-1 SERIES MANUEL USER
Thanks for using our products Please strictly obey all the instructions in this manual and pay attention to all the warning and operation information. It is not advisable to install or operate the machine before reading this manual.
Model
Type
Model
Type
1KVAS
1KVA Standard model
1KVAH
1KVA Long backup model
1.5 KVAS
1.5 KVA Standard model
1.5 KVAH
1.5 KVA Long backup model
2KVAS
2KVA Standard model
2KVAH
2KVA Long backup model
3KVAS
3KVA Standard model
3KVAH
3KVA Long backup model
6KVAS
6KVA Standard model
6KVAH
6KVA Long backup model
10KVAS
10KVA Standard model
10KVAH
10KVA Long backup model
1. Safety instructions
The power output voltage may still have 220V or 120V even not connect to the mains power.
For the battery cable or power cord replacement, please contact our service station or dealer to purchase, in
order to avoid fire caused by inadequate capacity or heat ignition.
Do not place the battery or battery pack in the fire, which will injure due to explosion.
Please do not open the UPS case as you will, there is risk of electric shock
Do not touch the battery connection terminals. Battery loop and input voltage loop is without isolation, which
may cause high voltage risk between the battery terminal and ground.
●Do not connect to the equipment like hair dryer or electric heater, to ensure the safety for the UPS
Attention:
UPS has high voltage inside, for personal safety, please do not repair by yourself. If any questions, please contact local service center or dealer.
2. Installation instructions
2.1 Unpacking inspection
●Open the UPS package, please check the enclosed accessories including a user manual, communication cable, CD-ROM. The long-back model also includes the cable for connection to battery bank.
Check the UPS if any damage in transport. If find damaged or parts missing, do not power on, please turn to the carrier and dealer.
To determine whether this UPS is the model you want to buy. Check the model name showed both on the front panel and rear panel of UPS to confirm.
Note:
Please save the packaging box and packaging materials for future transport use. As heavy product, please transit the UPS with care.
2.2 Attention items of installation
The UPS installation environment must be with good ventilation, away from water, flammable gases and
corrosive entities.
Do not lie down the UPS against the wall so that front and side panel air intake hole, rear panel air outtake
hole will be unobstructed.
●The peripheral environment temperature around the UPS should be within 0 ~ 40 ℃.
If dismantling the machine at low temperatures, there may be condensation droplets, users can not install
or operate it before UPS completely got dry both inside and outside, otherwise there will be danger of
electric shock.
RS232
EPO
USB
TEL/MODEM/FAX
IN
OUT
OUTPUT
RESET
FUSE 250VAC
INPUT
-+
36VDC 30A
EXT.BATTERY
2
1
3
5
6
4
8
7
10
9
TEL/MODEM/FAX
OUT
IN
USB
EPO
OUTPUT SOCKET
RS232
-+-
+
72VDC 30A
EXT.BATTERY
-+-
+
RESET
FUSE 250VAC
INPUT
2
1
6
8
10
7
4
5
9
TEL/MODEM/FAX
OUT
IN
USB
EPO
OUTPUT SOCKET
RS232
-+-
+
96VDC 30A
EXT.BATTERY
RESET
FUSE 250VAC
INPUT
-+ -+
2
1
6
8
10
7
4
5
9
3
Place the UPS near the mains socket to cut off AC mains without any delay at any emergent case.
Attention:
Make sure the load behind the UPS is off when users connect the load to UPS, and then turn on the load one by one later.
●Please connect the UPS with the socket which is over-current protected. Do not connect the UPS with the
socket which rated current is less than the Maximum input current of the UPS.
●All the power socket should be configured with earthling device for safety.
●UPS could be electrified or powered no matter the input power cable is tied or not, even when the UPS is off.
The only way to cut off the output is switching off the UPS and disconnecting the mains power supply.
●For all standard type UPS, it is advised to charge the battery over 8 hours before used. Once the AC mains
power energizes the UPS, it will automatically charge the battery. Without prior charging, UPS output remains as usual but with shorter back-up time than normal.
●When connected to motor, display equipment, laser printer etc, UPS power selection should be based on the startup power of the load which is usually twice as rated power.
2.3 UPS rear panel view
Note: following diagrams take the type of 0.9PF for example, the type of 0.8PF is similar.
2.3.1 The type of 220V (output could be 208V, 210V, 220V, 230V, 240V)
a. 0.9PF 1KVA rear panel b. 0.9PF 1.5KVA&2KVA rear panel c. 0.9PF 3KVA rear panel
计算机接口
N
L L
N
++
--
11
12
6
7
8
3
2
N
L L
N
6
2
12
11
3
8
7
INPUT BREAKER 80A 250VAC
ON
OFF
TEL/MODEM/FAX
INTELLIGENT SLOT
-+-
+
192VDC
EXT.BATTERY
DO NOT OPEN EXCEPT QUALIFIED TECHNICIAN
RS232
USB
EPO
N L L2 N2
INPUT
OUTPUT
WARNING
HIGH LEAKAGE CURRENT EARTH CONNECTION ESSENTIAL BEFORE CONNECTING SUPPLY
L1 N1
N
L L2
N2
L1 N1
9
12
11
8
7
6
5
4
3
2
RESET
-
+
24VDC 40A EXT.BATTERY
INTELLIGENT SLOT
RS232
INPUT
OUTPUT SOCKET
TEL/MODEM/FAX
IN
OUT
USB
EPO
FUSE 125VAC,15A
R
E
S
E
T
R
E
S
E
T
T
O
1
2
4
5
6
8
3
7
10
9
RESET
FUSE 125VAC,25A
INPUT
OUTPUT SOCKET
RS232
USB
EPO
TEL/MODEM/FAX
OUTIN
OUTPUT
L N
GND
R
E
S
E
T
R
E
S
E
T
T
O
-+
48VDC 40A
EXT.BATTERY
INTELLIGENT SLOT
1
2
5
6
7
4
9
8
10
11
RESET
FUSE 125VAC,35A
INPUT
OUTPUT SOCKET
TEL/MODEM/FAX
OUT
IN
RS232
USB
EPO
INTELLIGENT SLOT
OUTPUT
L N
GND
R
E
S
E
T
R
E
S
E
T
T
O
-
+
72VDC 40A
EXT.BATTERY
5
6
4
1
2
3
7
9
8
10
11
d. 6KVA &10KVA Long back up e. 6KVA & 10KVA Standard type f . 0.8/0.9PF 6/10KVA with ISO
2.3.2 The type of 120V (output could be 100V, 110V, 115V, 120V, 127V)
a. 0.9PF 1KVA rear panel b. 0.9PF 2KVA rear panel c. 0.9PF 3KVA rear panel
Input Power Terminals;⑵Over Current Protector;⑶Fan;⑷USB Emergency Power Off;⑹RS232 Communication Interface;⑺Intelligent Slot Surge Protection for Network/Fax/Modem;⑼Battery Slot;⑽Output Socket
2.4 UPS output connection
Output connection of 1~10KVA type is configured with sockets or terminal blocks, users can plug the load cable into the UPS socket to energize the load as below. Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the hazards of electric shock or fire.
Note: To the type of 6-10KVA, do not use the wall receptacle as the input power source for the UPS, which rated current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed.
(1) In general, users can easily connect the load cable into the socket or terminal block of the UPS as
Terminal Block⑿Manual bypass switch cover.
following pictures.
LOAD
Input
Output
Ground
N
L L
N
+
-
Battery
Protector
Over Current
R
E
S
E
T
R
E
S
E
T
T
O
+
-
Input
Output
Model
Wiring spec(AWG)
Input
Output
Battery
Non-isolated Neutral
Ground
6KVAS
6mm2
6mm2
6mm2
6mm2
6mm2
6KVAH
6mm2
6mm2
6mm2
6mm2
6mm2
10KVAS
10mm2
10mm2
10mm2
10mm2
10mm2
10KVAH
10mm2
10mm2
10mm2
10mm2
10mm2
(2) To the type of 6~10KVA witch contains isolation transformer, there are more methods of output connection. Before installing, prepare wires for terminal block of the UPS based on the following table.
Note: The cable for 6KVAS/6KVAS should withstand over 40A current. It is recommended to use 10AWG
or thicker wire for safety and efficiency.
The cable for 10KVAS/10KVAS should withstand over 63A current. It is recommended to use 8AWG
or thicker wire for safety and efficiency.
The selections for color of wires should be followed by the local electrical laws and regulations.
Installation:
A. Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: Connect the earth wire first when making wire connection. Disconnect the earth wire last when making wire disconnection!)
OFF
-+-
+
192VDC
EXT.BATTERY
N L L2 N2
INPUT
OUTPUT
L1 N1
N1
Ground
Input
Battery
Output1
Output2
Protector
Over Current
L2
L2
L1
L1
N1
GND L1 N1 L2 N2
To Load2
To Load1
L2
L1
Note: Make sure the wires are connected tightly with the terminals.
There are two output terminals to meet customers diverse requirements for serial or parallel
connection. We will introduce the methods of connection later.
Please install the output breaker between the output terminal and the load, and the breaker should
be qualified with leakage current protective function if necessary. B. Insert the EPO plug into the EPO slot on the real panel. C. Put the terminal block cover back to the rear panel of the UPS. Warning: (only for long-run model) Make sure a DC breaker or other protection device between UPS and external battery pack is installed. if
not, Please install it carefully. Switch off the battery breaker before installation.
Note: Set the battery pack breaker in OFF position and then install the battery pack.
Pay highly attention to the rated battery voltage marked on the rear panel. if you want to change the
numbers of the battery pack, please make sure you modify the setting simultaneously. The connection with wrong battery voltage may cause permanent damage of the UPS. Make sure the voltage of the battery pack is correct.
Pay highly attention to the polarity marking on external battery terminal block, and make sure the correct
battery polarity connected. Wrong connection may cause permanent damage of the UPS.
Make sure the protective earth ground wiring is correct. The wire current spec, color, position, connection
and conductance should be checked carefully.
Make sure the utility inputoutput wiring is correct. The wire current spec, color, position, connection and
conductance should be checked carefully. Make sure the L/N site is correct, not reverse or short-circuited.
Output Configuration Option 1:
There are 2 sets of low-voltage output (100V/110V/115V/120V) with L1-N1 and L2-N2. Each of them is able to
provide 50% of UPS rating power. Connect one load to L1-N1 and the other load to L2-N2.
GND L1 N1 L2 N2
To Load
L2
L1
GND L1 N1 L2 N2
To Load
L2
L1
GND
L1 N1 L2 N2
To Load 1
To Load 2
To Load 3
L2
L1
Option 2:
After connecting L1&L2 and N1&N2, it becomes one low-voltage output (100V/110V/115V/120V) at L1-N1 for 100% of UPS rating power. Connect load to L1-N1 or L2-N2.
Option3:
After connecting N1 and L2, it becomes one low-voltage output (208V/220V/230V/240V) at L1-N2 for 100% of UPS rating power. Connect load to L2-N1
Option4:
After connecting N1L2, it becomes three outputs, one high-voltage((208v/220v/230v/240V) at L1-N2 two low-voltage outputs (100v/110v/115v/120V) at L1-N1 and L2-N2. However, there is a limit for current rating at L1-N1 and L2-N2: 25A is for 6KVA model and 42A is for 10KVA model. You must connect the load under the limitation. Please read Note first before installation. Connect low-voltage load to L1-N1 and L2-N2, and connect high-voltage load to L1-N2.
Note: if any load current in L1-N1 or L2-N2 is higher than 25A in 6KVA model and 42A in 10KVA model.
The UPS will still operate normally without overload warning because the total load is under the specification. However, the isolation transformer will be damaged with overheat due to high current.
Hence, the installation must be done with technician and make sure that the load current does not
Type
Battery Quantity
(unit)
Battery Voltage
(volt)
1KVA
2/3
24/36
1.5KVA 4 48
2KVA
4/6
48/72
3KVA
6/8
72/96
6KVA
14/16
168/192
10KVA
14/16
168/192
RED
BLACK
-
+
-
+
-
+
-
+
-
+
-
+
exceed this limitation.
When connecting to low-voltage and high –voltage at the same time like option 4, it will cause the
L1-N1L2-N2 with low-voltage loads in Non-Isolated status, we recommend that you may only use two low-voltage at L1-N1 or L2-N2 like option 1, and also make sure that the total current in L1-N1 or
L2-N2 does not exceed the value on Note 1.
2.5 External battery connection procedure for long back up type
●For different UPS type, users are instructed to configure different battery voltage as below sheet. More or
less units are forbidden, or else something abnormal or faulty will appear.
●One end of battery cable is for UPS terminals while the other end with triple cables is for battery terminals.
Correct installation procedure is highly vital or else probable electric shock will arise. Users are strictly required to follow the below procedure.
●Connect battery in correct way and make sure the total battery voltage is available for UPS.
●Correctly connect the long battery cable to battery terminals first, red wire is to positive plate while black is to
negative. If users connect the UPS first, electric shock or other danger could not be avoided.
●Before connecting load after UPS, users should supply main power to UPS and energize it.
●Connect long battery cable to UPS terminals with correct poles link (red is for “+”, black is for“-”), UPS will
start the charging work automatically.
2.6 Installation
●UPS installation work should comply with local electrical standard and only can be done by professional
technician. 1KVA~3KVA units could use wall socket as input power connection.
●For all type UPS, it is advised to charge the battery over 8 hours before the first use. Once the AC mains
power energizes the UPS, it will charge the battery automatically. Without prior charging, UPS output remains as usual but with shorter back up time than normal.