LEDlite LTEM26 User guide

Page 1
Emergency Lighting
Power Pack
for Mains Voltage LED Lamps
The product package contains the following:
• Emergency Light Unit
LTEM26
Please read this Manual prior to the installation and commissioning of the LTEM26. The LTEM26 emergency pack is suitable for 5-20W LED lamps with internal Integrated Circuit (IC) driver (This device CANNOT be used for LED lights with Resistive Circuit (RC) driver).
Operating principle:
The LTEM26 emergency pack charges when AC power is present. When fully charged, the circuit will protect the battery from over-charging and the emergency pack will enter stand-by mode. As soon as the AC power fails the battery will supply power to the LED lights.
Technical Specifications:
• 2600mAh 11.1V Li-Ion Battery
• Pre-wired Status LED
• Instruction Manual
Working Voltage
Emergency Output
Voltage/Current
Emergency
Switching Time
Suitable for Lamps
Power (W)
Lamp Type
Charging Time
AC85-265V
DC 230V
0.12A~0.01A
≤5sec.
5-20W
LED Lamps
24h
Battery Type
Battery Cycle
Use Times
Emergency Time
IP Rating
Luminous Flux
Weight
18650 Li-Ion
11.1V 2600mAh
≥500 times
≥180 minutes
IP30
up to 1000 lumens
0.39kg
Dimensions
Battery
Dimensions
Working
Temperature
Storage
Temperature
Warranty
Body Material
L105*W45*H23mm
L220*W20*H20mm
0 0
-25 C - +50 C
0 0
-25 C - +50 C
3 years
Plastic
Installation Standards:
• The installation of the LTEM26 must be done by a certified electrician according to the EN60598 part 1 and 2-22 as well as additional local standards (see basic wiring instructions on Page 2).
• The LTEM26 has no internal adjustments or serviceable parts and therefore the main cover should never be removed.
• For installation in combination with a LED Driver, the wiring instructions in this manual must be followed or the LTEM26 may not function as expected.
• The green Status LED should be positioned in such a way as to be easily visible under all circumstances to ensure quick and convenient functionality check.
• The LTEM26 should be installed indoors (stairs, corridor, ceiling, etc.) and it is not for outdoor use.
Battery Maintenance:
• Initial battery charge must be for a minimum of 24 hours before testing.
• To achieve best performance the LTEM26 must be properly maintained. The LTEM26 should be tested fully by switching into emergency mode regularly in accordance with local testing regulations to check emergency operation time (according to battery capacity). Any warranty claim must be accompanied by documentation which records the dates of this maintenance procedure and signed by maintenance personnel.
1
Page 2
Dimensions:
105mm
45mm
23mm
220mm
ø20mm
Fig. 1 Inverter Dimensions
Fig. 2 Battery Dimensions
Installation and Wiring Instructions:
1. The LTEM26 emergency pack can be mounted on surfaces using the two installation holes. First mark the hole positions and then use 4mm tapping screws to mount it on the surface. The product is safe to fit on materials combustible above 200°C.
2.C onnect according to the wiring diagrams below observing the correct polarity where applicable.
WIRING DIAGRAMS
Switc h
LIV E
NEU TRAL
INP UT A C22 0V 50Hz
Emer ge nc y Driver
Ind icate s a conne ction
Fig. 4 - Wiring for LED Lights with External Driver
LED D river
inp ut
INP UT A C22 0V 50Hz
Emerge nc y Driver
OUT PUT
Batte ry Batte ry
LED LIG HT
LED LIG HT LED LIG HT
Ind icate s a conne ction
Fig. 3 - Wiring for LED Lights with Internal Driver
3. When first connecting to AC power check if the LED lights work normally: a. The Green indicator light is ON. b. Turn the switch to the LED lights ON and OFF to check the correct function of the lights.
4. Cut off the emergency pack AC power - the LED lamp will be in emergency mode and the Green indicating light will be OFF.
After testing all the above steps the installation is finished.
Switc h
+
-
out put
LIV E
NEU TRAL
Keep a record of maintenance and maintain the emergency pack and LED lamp regularly. Check regularly to ensure its lifespan and usage.
Troubleshooting:
Most failures experienced are not due to the LTEM26 itself and are caused by improper installation or connection of the unit. Please check that:
• Wires are properly clamped into terminals.
• Installation is done according to the wiring diagram.
• Proper polarities are observed.
• Proper LED load maximums are observed.
In case of electromagnetic interference:
• Do not cross-wire the power input line and the light connection output line.
• When parallel wiring, a distance between 5 and 10 cm should be reserved.
• Shorten the distance between the power supply input line and the device.
• When running in parallel, the connection between the power input line and the lamp should be as short as possible.
2