Lea LS Plus 300 Installation Manual

Page 1
REV.
MPD
4/6/11
4/6/11
4/6/11
JRA
DLR
MPD
A
DOCUMENT RELEASE
DESCRIPTION
REVISIONS
ECN
DD2922
DATE
3/8/2011
LS Plus 300
ALL DIMENSIONS IN INCHES UNLESS OTHERWISE SPECIFIED.
TOLERANCES:
FRACTIONS=±
ANGLES=±
MATERIAL
NOTED .
THIRD-ANGLE PROJECTION
.
.XX=±
.
°
.XXX=±
DRAWN
DAW
CHECKED
ENG APPD
. .
PROJ APPD
PROJECT NO.
NOTICE: THE INFORMATION AND DESIGN IN THIS DOCUMENT IS THE PROPERTY OF LEA INTERNATIONAL. ALL RIGHTS RESERVED.
DATE
3/8/11
.
.
.
.
.
.
DD2922
TITLE
SIZE
A
SCALE
LS Plus 300 with
Disconnect Switch
10701 Airport Drive, Hayden, ID 83835, USA
.
+1.208.772.8515 FAX +1.208.762.6117
.
800.882.9110 www.protectiongroup.com
INSTALLATION MANUAL
LS PLUS 300 AC PROTECTOR
1
REV
12
CAGE
30992
1:8
DRAWING NUMBER
B39-38-0003
PRODUCT CATEGORY
ACL
PAGE OF
A
Page 2
2
Page 3

Pre-Install Notes

READ ALL WARNINGS BEFORE ANY SERVICE OR TESTING
Do not install, make any adjustments, or replace any components inside the enclosure with the power supply turned on. Under certain circumstances, dangerous potentials may exist even when the power supply is off. To avoid casualties, always turn the main power supply off before performing maintenance and/or testing.
HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION
CAUTION
The installation of a surge protection device (SPD) must be done by qualified electrical personnel. A SPD must be grounded through the power system ground for proper operation.
WARNING
Before installing the suppressor, AC power must be OFF. Failure to do so could result in damage to the suppressor and poses a potential electrical shock hazard to personnel. is off.
Read SPD label on side of the enclosure to verify voltage configuration.
Discontinue installation if the measured voltage is not in the range of the model voltage configuration of the SPD being installed. Contact LEA International technical support with any questions concerning the voltage configuration prior to installation and application of power.
Perform such work only after reading and understanding all of the instructions contained in this manual.
Beware of potential hazards, wear personal protective equipment and take adequate safety precautions.
Before performing visual inspections, tests, or maintenance on the equipment, disconnect all sources of electric power. Assume that all circuits are live until they have been completely de-energized, tested, grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including
Always use a properly rated voltage sensing device to confirm that power
Handle this equipment carefully and install, operate and maintain it correctly in order for it to function properly. Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as damage to electrical equipment or other property.
Carefully inspect your work area and remove any tools and objects left on /or in the enclosure.
Replace all devices and covers before turning on the power to this equipment. All instructions in this manual are written with the assumption that the customer has taken these measures before performing installation or testing.
Failure to follow these instructions could result in DEATH or serious injury.
3
Page 4
Installation Procedure
Notes
Please read the entire installation manual before installing this SPD. Carefully unpack the SPD, removing all packaging material. Inspect for any signs of damage that may have occurred during shipment. If any damage is found, stop installation and contact LEA International.
The SPD should only be installed by a licensed electrician.
All local and National Electric Codes must be observed.
Verify the voltage configuration on the SPD label matches the actual system voltage configuration of service point.
For optimal SPD performance, verify that earth ground resistance is less than 25 ohms (per NEC).
Before installation, shut off power to prevent accidental electrical shock or injury.
Make sure all conductors are sized appropriately for this SPD.
Mounting
The SPD should be mounted as close as possible to the connection of service point.
The SPD is mounted using the four mounting holes located near the enclosure corners.
Electrical conductors should enter the top of the SPD enclosure, or on either side near the top of SPD enclosure.
Electrical conduit should be of sufficient size per NFPA 70 and National Electrical Code. For optimum SPD performance, conduit with no sharp bends.
Conductor Size
Terminal Block
The lugs accept phase and Neutral conductors #8 to #1/0 AWG, the Neutral and Safety Ground accept #8 to #1/0 AWG. All conductors recommended to be insulated stranded copper greater than #6 AWG diameter.
Disconnect
The disconnect switch lugs accept phase conductors #10 to # 4 AWG, the Neutral and Safety Ground accept #8 to #1/0 AWG. All conductors recommended to be insulated stranded copper greater than #6 AWG diameter.
.
4
Page 5
AC Power Connection
The SPD is installed in parallel with the incoming phase conductors.
It is recommended to connect the SPD to a 60A circuit breaker. This allows for servicing of the SPD without shutting power off at the panel main breaker.
Route all SPD conductors taking care to avoiding sharp bends and keeping all leads as short as possible.
To ensure optimum SPD performance, verify that all electrical connections are clean.
Connect the phase and neutral wires to the terminals marked Phase 1, Phase 2, Phase 3, and Neutral.
Connect the green safety ground wire (building ground system) to the Safety Ground lug.
Tighten all connections to the recommended torque value.
Remote Alarm Connection
The SPD offers one set of dry contacts for remote alarm monitoring. These screw terminal connections are located on the PC board as shown on Pages 8 or 10. The three connections are labeled NC (Normally Closed), NO (Normally Open) and C (Common).
Remote Alarm Contact Maximum Ratings:
125 Vdc / 0.24 A 125 Vac / 0.5 A 30 Vdc / 2.0 A
Final Check
Apply AC power to the SPD.
The SPD
If the technical support at 800.882.9110.
If the the audible alarm. The
TVSS Status
TVSS Status
Alarm Disabled
LED is red or not illuminated, contact LEA International’s
LED should be illuminated green.
LED is red, press the audible alarm
Alarm Disabled
LED will turn dark
Enable
button to
Enable
5
Page 6

Troubleshooting

The SPD operational status can be seen on the front door of the enclosure. There is no need to open the unit for any reason.
TVSS Status LED
A green LED indicates power is applied and all SPD protection modes are normal. A red LED indicates the SPD needs servicing.
Surge Counter
Surge Counter Display
The LCD display indicates there was an event and has recorded the number of surge/transients events since the counter has been reset. If the surge counter display is blank, the battery may be defective or dead. Please contact LEA Technical support.
Counter Reset button
Press to reset the surge counter to zero.
Audible Alarm
Alarm Disabled LED
A dark LED indicates the audible alarm circuit is enabled. A red LED indicates the Audible Alarm has been silenced and serves as a reminder that the SPD needs to be serviced.
Audible Alarm Disable button
Press to turn off the audible alarm. The
Alarm Disabled LED
will turn red and serves as a reminder that the SPD needs to be serviced. If the SPD has been severely damaged disconnect power to the SPD using the circuit breaker or disconnect switch to silence the alarm. Maintenance of electrical devices should be done only by trained professional electrician.
Audible Alarm Enable button
Press the Enable button for the audible alarm. The
Alarm Disabled LED
will turn
dark
Maintenance
The SPD should be scheduled for periodic inspection to ensure the SPD is operational and all wire connections are tight.
If the SPD needs replacement, please contact LEA International for replacement at
800.882.9110 or online at www.protectiongroup.com.
.
6
Page 7
Please Note:
LS Plus 300 shown without the Disconnect Switch. The Operation of the Surge Counter and Audible Alarm Switch is same for both models.
Surge Counter
Records any
Suppressed Transients
Counter Reset
Press to reset
Surge Counter to zero
Alarm Disabled
A Red Illuminated Light Indicates Audible Alarm is Disabled
1
Audible Alarm
Disable
Turns OFF the Alarm
and Illuminates the
Alarm Disable Light
.
Button
TVSS Status Indicator
Light Illuminated Green Indicates Normal Operation with All Protection Modes Functioning
Light Illuminated Red Indicates SPD Needs Replacement
Audible Alarm Enable
Enables the Alarm and Turns OFF the Alarm Disabled Light
Button
7
Page 8
179 mm
7-1/16"
406 mm
16"
Use 3/8" [ 10 mm ]
Mounting Hardware
508 mm
20"
152 mm
586 mm
23-1/16"
6"
Mounting:
External mounting brackets with 0.41" [ 10.3 mm ] mounting holes.
Dimensions: Weight:
42 lbs / 19 kg
548 mm 21-9/16"
368 mm
14-1/2"
Mechanical Specifications for LS Plus 300
[ Dimensions for Reference Only ]
20" X 16" X 6" [ 508 mm X 406 mm X 152 mm ]
8
Page 9
Note: Remote Alarm Contacts
Change State with Loss of Power
Remote Alarm Contacts
Normally
Open
Common
Normally Closed
Contact is Closed
when SPD is Powered
and Functional
[ Normal State ]
Wire Range #24 to #14 AWG
PLEASE NOTE:
Alarm Wires from SPD are hidden to show proper placement of Wires for the Remote Alarm Contacts
3X Torque Specification
4.5 in-lbs [ 0.5Nm ]
Remote Alarm Contacts
NC
Contact Closed with SPD powered and Functional [ Normal State ]
Remote Alarm Contacts
NO
Contact Open with Power OFF or SPD Requires Replacement
NC C NO NC C NO
4X Wire Strip Lengths for Phase & Neutral Connections
0.5" [ 13 mm ] 4X Torque Specification
50 in-lbs [ 5.6 Nm ]
Wire Range #8 to #1/0 AWG
Wire Strip Length
0.5" [ 13 mm ]
Lug Torque Specification 50 in-lbs [ 5.6 Nm ]
Wire Range #8 to #1/0 AWG
9
Page 10
218 mm
8-5/8"
179 mm
7-1/16"
406 mm
16"
Use 3/8" [ 10 mm ]
Mounting Hardware
508 mm
20"
152 mm
548 mm
21-9/16"
585 mm
23-1/16"
6"
Mounting: Dimensions: Weight:
External mounting brackets with 0.41" [ 10.3 mm ] mounting holes.
43 lbs / 19.5 kg
368 mm
14-1/2"
Mechanical Specifications for LS Plus 300
with Disconnect Switch
[ Dimensions are for Reference Only ]
20" X 16" X 6" [ 508 mm X 406 mm X 152 mm)
10
Page 11
Note: Remote Alarm Contacts
Change State with Loss of Power
Wire Range
#24 to #14 AWG
Remote Alarm Contacts
Normally Open
Common
Normally Closed
Contact is Closed
when SPD is
Powered and Functional
[ Normal State ]
PLEASE NOTE:
Alarm Wires from SPD are hidden to show proper placement of Wires for the Remote Alarm Contacts
3X Torque Specification
4.5 in-lbs [ 0.5 Nm ]
Wire
Range
#10 to #4 AWG
Remote Alarm Contacts
NC
Contact Closed with SPD powered and Functional [ Normal State ]
Remote Alarm Contacts
NO
Contact Open with Power OFF or SPD Requires Replacement
NC C NO NC C NO
3X Wire Strip Lengths for Phase Connections into the Disconnect Switch
0.5" [ 13 mm ]
3X Torque Specification for Disconnect Switch 25 in-lbs [ 2.8 Nm ]
Torque
Specification
50 in-lbs [ 5.6 Nm ]
Wire Range
#8 to #1/0 AWG
Ground
Lug
Strip
Length
0.5" [ 13 mm ]
Wire Range #8 to #1/0 AWG
Wire Strip Length Neutral Block
0.7" [ 17.4 mm ]
11
Page 12
Lock Out of Enclosure in the OFF Position
if Required
Step 1
Turn Handle
to the OFF
Position
ON
Pull Out Locking Tab to Install Locking Device
O F F
1
2
Install Lock
Disconnect Handle must be in the OFF Position to Open or Close the Enclosure Door
1
3/16"-5/16"
[ 5-8 mm ]
ON
O F F
Step 2
Press Release as
Shown to Release
Disconnect Handle
from the Disconnect
Switch to Open
or Close the
Enclosure Door
2
Handle Locking Tab only accepts a Shackle Diameter as shown. (Lock not supplied by LEA)

Disconnect Handle Operation

12
Loading...