3183-G Airway Ave, Costa Mesa, CA, 92626, USA
Tel: (714) 434-6131 Fax: (714) 434-3766 Website: www.laurels.com
1. ORDERING GUIDE, LTM “CTR” SERIES TRANSMITTERS
Configure a model number in this format: LTM600VF1, CBL04
LTA Transmitter with serial I/O, Modbus or
Custom ASCII protocol. Includes 4-20 mA,
0-20 mA or 0-10V isolated analog output,
isolated 5V, 10V or 15V transducer excitation output, and dual solid state relays.
Default jumpered for full duplex RS485 and
RS232, and 10V excitation.
Main Board
6............................... Standard pulse or AC input
8............................... Extended pulse of AC input
2....................................... Dual solid state relays
Input Type
FR .................. .. Dual Channel Pulse or AC Input
Standard main board
Frequency (2 channels), rate (2 channels), total
(2 channels), period, stopwatch, time interval.
Extended main board
Above plus rate and total simultaneously, linearized inputs using up to 180 points, arithmetic
functions applied to channels A & B (A+B, A-B,
A*B, A/B, A/B-1), phase angle, duty cycle, up/
down counting, batch control.
VF1 ............................... 4-20 mA Process Input
VF2 ................................. 0-1 mA Process Input
VF3 ................................. .. 0-10V Process Input
This manual covers “CTR” Series DIN rail transmitters with an isolated serial data output and a
pulse, AC or process signal input (converted to a frequency by the unit’s voltage-to-frequency
converter). The transmitters duplicate the signal conditioning and signal processing features of
their 1/8 DIN panel-mounted counter / timer counterparts for exceptional accuracy at high read
rate. A wide range of counter / timer functions are accommodated by three signal conditioners:
• Dual-channel pulse input signal conditioner (for frequency, rate, total, arithmetic combinations of two channels, stopwatch, timer, phase angle, duty cycle).
•Voltage-to-frequency signal conditioner (for rate or total from 4-20 mA, 0-1 mA or 0-10V
process signals).
• Quadrature signal conditioner (for position or rate from quadrature encoder signals).
Serial communications are standard.
The transmitter serial port
is default jumpered for RS232 or
full-duplex RS485 (same jumper settings). Half-duplex RS485 is also selectable either via internal
or external jumpers. Three serial protocols are software selectable: Modbus RTU, Modbus ASCII
and Custom ASCII. Modbus allows devices by different manufacturers to be addressed on the
same data line. The simpler Custom ASCII protocol is recommended when there are no devices by
other manufacturers on the data line.
An isolated 4-20 mA, 0-20 mA or 0-10V output is standard.
This output is generated by an
ultralinear 16-bit digital to analog converter. It is scaled in software and tracks an internal linearized
digital reading.
An isolated transducer excitation output is standard. Three output levels are jumper selectable:
5V at 100 mA, 10V at 120 mA, or 24V at 50 mA.
Dual solid state relays are standard. 130 mA at 140 Vac or 180 Vdc.
Isolation to 250V rms is provided for power, signal input, analog output, relay outputs, and com-
munications. Isolation adds safety and avoids possible ground loops. The transducer excitation
output is isolated to 50V from signal ground.
Internal jumpers are used to select the signal range, communication type, and excitation level.
The transmitter configuration is specified by the model number on the transmitter label. A user
can reconfigure the transmitter by opening the case and moving jumpers.
Transmitter scaling is via serial connection to a PC using MS Windows based Instrument Setup
Software, which can be downloaded at no charge. The required transmitter-to-PC interface cable
is available for purchase.
-
- 4 -
4. RECEIVING & UNPACKING YOUR TRANSMITTER
Your transmitter was carefully tested and inspected prior to shipment. Should the transmitter be
damaged in shipment, notify the freight carrier immediately. In the event the transmitter is not
configured as ordered or is inoperable, return it to the place of purchase for repair or replacement.
Please include a detailed description of the problem.
5. SAFETY CONSIDERATIONS
Warning: Use of this transmitter in a manner other than specified may impair the protection
of the device and subject the user to a hazard. Visually inspect the unit for signs of damage. If
the unit is damaged, do not attempt to operate.
Caution:
• This unit may be powered with AC (mains) from 95-240 Vac ±10% with the worldwide voltage
power supply option, or 12-30 Vac or 10-48 Vdc with the low voltage power supply option.
Verify that the proper power option is installed for the power to be used. This transmitter has
no AC (mains) switch. It will be in operation as soon as power is applied.
• The 95-240 Vac ±10% mains connector (P1 Pins 1-3) is colored Green to differentiate it from
other input and output connectors. The 12-30 Vac or 10-48 Vdc mains connector is colored
Black.
• To avoid dangers of electrocution and/or short circuit, do not attempt to open the case while
the unit is under power. However, signal wiring changes external to the case can be made
safely while the unit is under power.
• To prevent electrical or fire hazard, do not expose the transmitter to excessive moisture.
• Do not operate the transmitter in the presence of flammable gases or fumes. Such an
environment constitutes an explosion hazard.
•
Secure the transmitter to a 35 mm DIN rail.
Symbols used:
Caution (refer to accompanying documents)
Caution, risk of electric shock.
Earth (ground) terminal.
Both direct and alternating current.
Equipment protected throughout by double
insulation or reinforced insulation.
Operating environment:
Transmitter Class II (double insulated) equipment designed for use in Pollution degree 2.
-
- 5 -
See manuals
for different
signal types
Control input 2
Control input 1
GND
Analog out - 1
Analog out + 2
AL2 1
AL2 2
AL1 3
AL1 4
6. TRANSMITTER FIELD WIRING
1
2
3
4
5
6
1
2
3
P6 Signal
input &
excitation
output
P5 Control
inputs 1 & 2
P4 Analog
output
P3 Solid
state relays
Signal
conditioner
board
P2 Serial
data I/O
P1 Power
input
RS485
6 N/C
5 ARX
4 ATX
3 GND
2 BRX
1 BTX
RS232
TX
RX
NC
GND
GND
N/C
3 Power GND
2 AC neutral or -DC
1 AC high or +DC
6 TX
5 RX
4 NC
3 GND
2 BRX
1 N/C
Transmitter
RS232 wiring
6 N/C
5 ARX / ATX
4 N/C
3 GND
2 BRX / BTX
1 N/C
Transmitter
RS485 wiring, half duplex
with internal jumpers.
5
9
4
8
3
7
2
6
1
DB9 connector
to PC
(rear view)
ATX / ARX
GND
BTX / BRX
Master
-
- 6 -
6 N/C
5 ARX
4 ATX
3 GND
2 BRX
1 BTX
ATX
ARX
GND
BTX
BRX
TransmitterMaster
RS485 wiring, full duplex-
6 N/C
5 ARX
ATX / ARX
4 ATX
3 GND
2 BRX
GND
BTX / BRX
1 BTX
Transmitter
Master
RS485 wiring, half duplex
with external jumpers.
P6 - SIGNAL INPUT DETAIL
digital logic, magnetic pickups, or AC inputs to 250V .
PROCESS / TOTALIZER SIGNAL INPUT
DC & Externally Powered Process
Excitation return 1
+ Excitation 2
- Signal input 3
+ Signal input 4
2-Wire Process Transmitter
Excitation return 1
+ Excitation 2
- Signal input 3
+ Signal input 4
QUADRATURE SIGNAL INPUTS
Differential or Complementary Inputs
A Input 1
A Input 2
B Input 3
B Input 4
Z Input (+Excitation) 5
Z Input (Exc. return) 6
Single Ended Inputs
A Input 1
+Excitation 2
B Input 3
Excitation return 4
Z Input 5
Signal Ground 6
-DC
+DC
+
-
A Channel In
B Channel In
Zero Index In or
Excitation Output
A Channel In
+ Power Output
B Channel In
- Power Output
Zero Index In
Sensor common
DUAL CHANNEL PULSE SIGNAL INPUT..
Single Powered Sensor Input
Excitation return 1
+ Excitation 2
+B Signal Input 3
Signal Ground 4
+A Signal Input 5
Signal Ground 6
Power to sensor
+
Sensor 1
-
Two Powered Sensor Inputs
Excitation return 1
+ Excitation 2
+B Signal Input 3
Signal Ground 4
+A Signal Input 5
Signal Ground 6
Power to sensor
+
Sensor 2
-
+
Sensor 1
-
Active and Passive Inputs
Excitation return 1
+ Excitation 2
+B Signal Input 3
Signal Ground 4
+A Signal Input 5
Signal Ground 6
Inputs can be proximity switches, contact closures,
Warning: Dual-channel signal grounds 4 & 6 are
connected internally.
MOUNTING FOR COOLING
P4 - ANALOG OUTPUT DETAIL
Driving a Load with 4-20 mA
Analog return 1
4-20 mA output 2
500 Ohms max
Driving a Load with 0-10V
Analog GND 1
0-10V output 2
5 kOhms min
-
- 7 -
AL 1
AL 2
RESET
POWER
AL 1
AL 2
RESET
POWER
AL 1
AL 2
RESET
POWER
AL 1
AL 2
RESET
POWER
AL 1
AL 2
RESET
POWER
Mount transmitters with ventilation holes at
top and bottom. Leave minimum of 6 mm (1/4")
between transmitters, or force air with a fan.
7. PROGRAMMING YOUR TRANSMITTER
OVERVIEW
Our transmitters are easily programmed using a PC with an RS232 port and Instrument Setup
(IS) software, which provides a graphical user interface. The software allows uploading, editing,
downloading and saving of setup data, execution of commands under computer control, listing,
plotting and graphing of data, and computer prompted calibration.
USING IS SOFTWARE
Use a 3-wire RS232 cable (P/N CBL04) to connect your transmitter to the COM port of your PC.
Download the file
from our website and double-click on the file name. Click on
and follow the prompts. To launch IS software, press on
or on the desktop icon that you may have
Communications Setup
screen will appear.
RS232 cable with rear view of DB9 connector to PC
-
- 8 -
In the Communications Setup screen, select the
factory default setting. Select
RS-232 (USB)
button. This will take you to the
Transmitter LTA, LTM, LTS
Establish Communications
Custom ASCII
as the Device Type. Then click on the
as the protocol, as this is the
screen.
-
- 9 -
In the
You will be able to change your protocol and baud rate later under the
tab. Click on
on the
From the
from your counter transmitter. Click on
easily edit the setup file using pull-down menus and other selection tools. You can download
(or put) your edited file into the transmitter by clicking on
your setup file to disk by clicking on
disk by click on
The best way to learn IS software is to experiment with it.
For detailed help on any data entry field under any tab, select that field and press on the F1
key.
Establish Communications
Establish
Main Menu
Main Menu
File
, and the two fields at the bottom of the screen should turn green. Click
button.
, click on
=>
Open
Counter
.
screen, select your Com Port and
=>
File
Get Setup
View
=>
=>
Save Setup
to retrieve (or get) the existing setup data
Setup
to bring up screens which allow you to
Counter
and retrieve a previously saved file from
=>
9600
as the Baud Rate.
Communication
Put Setup
. You can save
setup
-
- 10 -
Click on
transmitter, then on
screen to set up
Counter
=>
Signal Input, Display
Get Setup
View
=>
to retrieve the current setup information from your counter
Setup
, which will take you to the
, and
Control Inputs
.
Input+Display
tab. Use this
Click on the
methods: 1) direct entry of Scale and Offset, and 2) the Coordinates of 2 Points method, where
(Low In, Low Read) and (High In, High Read) data points are entered numerically.
Reminder: for detailed help on any data entry field under any tab, select that field and press on
the F1 key.
Scaling
tab to scale your transmitter. You will be given the choice of two scaling
-
- 11 -
Click on the
Filter
tab to set to set up filtering for your readings.
Click on the
Relay Alarms
tab to set up your transmitter’s two solid state relays, which are
standard.
Reminder: for detailed help on any data entry field under any tab, select that field and press on
the F1 key.
-
- 12 -
Click on the
establish default communications with your transmitter. You can reselect
Address
values to establish initial communications with your PC.
,
Communication
Serial Protocol
tab to view the communication parameters that you used to
, and
Full/Half Duplex
, even though you may have selected different
Baud Rate, Device
Click on the
select
0-20 mA Current, 0-10V Voltage
Range reading
Reminder: for detailed help on any data entry field under any tab, select that field and press on
the F1 key.
Analog Out
. These will create the two endpoints of your analog output range.
tab to scale your analog output, which is standard. Under
, or
4-20 mA
-
- 13 -
. Type in your
Lo Range Reading
Range
and
,
Hi
ADDITIONAL FEATURES
•The Commands pull-down menu allows you to execute certain functions by using your
computer mouse. This menu will be grayed out unless a
• The Readings pull-down menu provides three formats to display input data on your PC
monitor. Use the
press
Print
for a hardcopy on your PC printer.
Pause
and
Continue
buttons to control the timing of data collection, then
Get Setup
has been executed.
- List presents the latest internal readings in a 20-row by 10-column table. Press
time to freeze the display. Press
- Plot generates a plot of internal readings vs. time in seconds. It effectively turns the
transmitter-PC combination into a printing digital oscilloscope.
- Graph generates a histogram, where the horizontal axis is the internal reading, and the
vertical axis is the number of occurrences of readings. The display continually resizes itself
as the number of readings increases.
Print
for a hardcopy.
Pause
at any
Plot
-
- 14 -
Graph
• The Jumpers pull-down menu shows jumper positions for the selected signal conditioner
boards and the main board, duplicating information in this manual.
-
- 15 -
8. OPENING YOUR TRANSMITTER CASE
WHEN TO CHANGE JUMPERS
Most users will never have the need to open the transmitter case. The transmitters are
shipped fully jumpered and ready for scaling. The signal conditioner type, range and temperature sensor are specified by the model number on the transmitter label.
To select a different signal conditioner range, you may open the transmitter case and change
jumper settings. Your selected range should encompass your maximum expected signal levels.
All ranges of each signal conditioner board are factory calibrated, with calibration factors stored
in EPROM on the board.
The selection serial signal (RS232 or RS485) and excitation (5V, 10V or 15V) is achieved by
jumpers on the main board. The factory default setting for the serial signal level is RS232. The
default excitation setting for pulse input transmitters is 10V.
After changing jumper settings, you will need to enter the new information into Instrument
Setup software. While this software can sense the instrument type (transmitter, panel meter or
counter) and signal conditioner type, it cannot sense jumper settings which modify the
electrical circuit. You should also update the information on the transmitter label.
HOW TO OPEN & CLOSE THE CASE
The two clamshell halves of the case are held together with 4 bolts and 4 nuts. When removing
these, take care to ensure that they are not lost. Separate the case halves. When closing the
case, make sure the ventilation grills are properly aligned.
-
- 16 -
9. DUAL CHANNEL PULSE OR AC INPUT SIGNAL CONDITIONER BOARD
This signal conditioner board is used for the frequency, rate, period, timing, phase angle, or
duty cycle functions. The board needs to be configured via jumpers for the input signal type
and level. It is recognized by Instrument Setup software, which will bring up the applicable
menu items for the Input Option “Dual Sig Cond.” The board does not require calibration, since
the quartz crystal oscillator used for frequency and timing applications is located on the
transmitter main board.
Jumper Settings for Expected Signal Levels
The jumper settings for Channel A (A2 & A3) and Channel B (B2 & B3) need to be set for the
expected signal voltage. This voltage must be outside of the high and low thresholds per the
following table, or the transmitter will not operate properly. The larger the difference between
the high and low thresholds, the more immune the transmitter is to input signal noise.
Input must be Input must be Input must be A3
below above
-12 mV
-150 mV
-1.15V
+12 mV
+150 mV
+1.15V
A3
B3
a
a
a
A2
B2
a
b
-
below above
+30 mV
+350 mV
+1.25V
+60 mV
+600 mV
+2.1V
A3
B3
b
b
b
A2
B2
a
b
-
below above
-60 mV
-600 mV
-2.1V
-30 mV
-350 mV
-1.25V
B3
-
-
-
A2
B2
a
b
-
Jumper Settings for Frequency Response, Bias Resistor, Debounce Time
Pull-up or pull-down resistors are used with open collector devices and dry contact closures
to provide input signal bias. They should not be connected for other inputs. Debounce
circuitry keeps the transmitter from counting extra pulses due to contact bounce.
-
- 17 -
Function Block Jumper Setting
Frequency Response A0 & B0 -
b
a
Bias Resistor A1 & B1 a
b
Contact Debounce A4 & B4 b
a, c
c
Common Jumper Settings
1 MHz max
30 kHz max
250 Hz max
10 kOhm pull-up to 5V
10 kOhm pull-down to -5V
None
3 msec
50 msec
Logic levels 250V - - - a b
NPN open collector NA b a - a b
PNP open collector NA b b - b b
Contact closures NA a or b a - a a, c
Line frequency 250V b - - - a, c
Turbine flow meter 250V b - a - b
RATE & FREQUENCY MODES
Frequency in Hz is determined by timing an integral number of pulses over a user-specified
Gate Time from 0 to 199.99 sec and taking the inverse of average period. The typical internal
display update rate is Gate Time + 1 period + 30 ms. Selecting a longer Gate Time produces a
more stable reading as more cycles are averaged, but slows down the update rate. At very low
frequencies, the update rate is controlled by the period. A Time Out from 0 to 199.99 sec is also
selectable. This is the time the transmitter waits for a signal to start or end a conversion. If the
signal is not received before the Time Out ends, the transmitter reads zero. The longer the Time
Out, the lower the minimum frequency that can be processed.
Rate in engineering units can be obtained by applying a scale factor to frequency, or by using
the Coordinates of 2 Points method, where two inputs in Hz and the corresponding desired two
internal readings are entered directly.
•Rate A, B determines rate independently for Channel A (Item #1) and Channel B (Item #2).
Either item can be selected for the analog output.
• Rate A Only determines rate only for Channel A. Channel B is not used.
• Rate A, A Total (Extended counter) determines Rate for Channel A (Item #1) and Total for
Channel A (Item #2) since last reset. Total can count down from an offset by entering a
negative scale factor. Only used for non-linear inputs.
-
- 18 -
•
Rates A+B, A-B, AxB, A-B, A/B, A/B-1 (Extended counter) can output arithmetic combinations of Rates A and B (Item #1), Rate A (Item #2), or Rate B (Item #3). With rates A and
B scaled to produce a ratio close to 1 and an offset of -1, the special combination A/B-1,
called “Draw,” can output percentage changes, such as elongation of material as it passes
between rollers.
PERIOD MODES
The inverse of frequency. Normally expressed in seconds.
TOTAL MODES
•
Total A, B determines Total independently for Channel A (Item #1) and Channel B (Item #2).
Either item can be selected for the analog output.
• Total A Only determines Total only for Channel A (Item #1). Channel B is not used.
• Total Burst (Extended counter) determines the total number of signal bursts applied to
Channel A (Item #1) and signal frequency within a burst (Item #2). Gate time must be
greater than the period of the lowest signal frequency and less than the minimum time
between bursts. Time Out must be greater than the maximum time between bursts.
•Total B, A Rate (Extended counter) determines Total for Channel B (Item #1) and Rate for
Channel A (Item #2).
•Total A, B UpDnCtl (Extended counter) determines Total A (Item #1), where the up or down
count direction is determined by an input on Channel B. If the menu item SLOPE is set to 0
for Channel B, an input level on B below the jumper set Low Threshold B causes the count to
go up, and an input level above the jumper set High Threshold causes the count to go down.
If SLOPE for Channel B is set to 1, the opposite occurs. The maximum frequency on A that
can be counted is 250 kHz, or a minimum of 4 µs between pulses.
•Total A, B InhibitCtl (Extended counter) determines Total A (Item #1), where counting may
be inhibited by a control input on Channel B. If the menu item SLOPE is set to 0 for Channel
B, a low input level on B allows counting, and a high input level inhibits counting. If the
SLOPE for Channel B is set to 1, the opposite occurs. The maximum frequency on A that can
be counted is 1 MHz.
Total A (Item #2) and Total B (Item #3) are also tracked and can
TIMING MODES
•
Time Interval A to B determines the time between periodic inputs on Channels A and B.
Timing starts when a pulse is applied to Channel A (positive edge if slope A is 0, negative
edge if slope A is 1), and ends when a pulse is applied to Channel B (positive edge if slope B
is 0, negative edge if slope B is 1). Pulse width may be measured by tying inputs A and B
-
- 19 -
together and selecting a positive or negative edge to start (Slope A) and the opposite polarity
edge to stop (Slope B). If multiple start and stop pulses occur during the Gate Time, the
displayed value is the average of pulse widths. The value is updated at the end of each Gate
Time. With a scale factor of 1, one count is one microsecond.
•
Stopwatch A to A times individual events applied to Channel A (Item #1) and the accumulated “Grand Total Time” of all events since last reset (Item #2). Timing is based on the
same positive (or negative) edge of start and stop pulses. Time of individual events is reset
to 0 when a new start pulse occurs. Time of accumulated events is reset via a reset line.
With a scale factor of 1, one count is one microsecond.
•
Stopwatch A to B measures time between a start pulse on Channel A and a stop pulse on
Channel B. Timing is the same as for A to A, except that positive or negative edges may be
selected separately for Channels A and B. This allows the pulse width measurement of single
pulses by tying Channels A and B together. One slope is selected to start timing, and the
opposite slope to stop timing.
PHASE ANGLE MODES (Extended counter).
•
Phase A to B (0-360) measures the phase difference between signals of the same period
applied to Channels A and B over a span from 0° to 360°. Select this span if no negative
readings are expected, as negative readings would cause high readings.
•
Phase A to B (+/-180) measures the phase difference between signals of the same period
applied to Channels A and B over a span from -180° to +180°. Select this span if negative
readings are expected, which will then not cause high readings.
DUTY CYCLE (Extended counter)
•
Duty Cycle (A to B)/A measures On or Off period of periodic square waves as a percentage
of total period over a Gate Time which is selectable from 10 ms to 199.99 s. The same signal
is applied to Channels A and B. Time is measured between positive and negative edges of
the signal, with averaging over multiple integral periods over the selected Gate Time. Scaling
can be via Scale and Offset, or the Coordinates of 2 Points method.
-
- 20 -
10. V-TO F CONVERTER SIGNAL CONDITIONER BOARD
This process receiver signal conditioner board converts 0-1 mA, 4-20 mA or 0-10 V analog
process signals to a frequency signal, which is then processed mathematically by the counter
main board to produce an internal reading of rate, total (time x rate), or 1/rate (time based on
rate). Square root extraction is selectable in software. With this capability, the transmitter can
output a 4-20 mA process signal which tracks flow rate or totalized flow from a differential
pressure flow transducer. The board needs to be configured via jumpers for the input signal
type. It is recognized by Instrument Setup software, which will bring up the applicable menu
items for the V-F Converter input option.
JUMPER SETTINGS
Input Range Jumper Position A1
0-10V
0-1 mA
4-20 mA
None
a
b
OPERATING MODES
•A Only (Rate A, Basic counter) accepts 0-1 mA, 4-20 mA or 0-10 V analog process signals
to calculate an internal rate reading, which is then converted to the analog output. Scaling
can be done by entering Scale and Offset, or using the Coordinates of 2 Points method.
Measurements are averaged over a Gate Time, which is programmable from 10 ms to
199.99 sec. Selecting a long Gate Time provides a slower display update rate, but superior
noise filtering. Moving average filtering is selectable for noise reduction. Square root
extraction is selectable for use with differential pressure flow transducers. Custom curve
linearization is available with the Extended counter.
•
A, A Total (Rate A, Total A, Basic Counter) allows rate to be determined as Item #1 and total
as Item #2. Rate can be scaled using Scale and Offset, or the Coordinates of 2 Points
method. Total can only be scaled using Scale and Offset. Total is calculated as the product of
rate and time in seconds. If square root extraction or custom curve linearization (available
with Extended counter) are selected, totalizing is of the linearized rate readings.
•1/(A Rate) (Extended Counter) determines the inverse of rate. For example, this can be the
time it takes an item to traverse an oven at a measured rate. Like Rate, 1/Rate can be scaled
using Scale and Offset, or the Coordinates of 2 Points method. Square Root extraction can
be selected for rate. 1/Rate is not available with custom curves.
-
- 21 -
11. QUADRATURE SIGNAL CONDITIONER BOARD
This signal conditioner can be used for quadrature position (Basic or Extended main board) or
for quadrature position and rate (Extended main board). Two quadrature signals, which are 90º
out of phase, are applied to the Channel A and B inputs. Their phase relationship determines
whether the count is clockwise (+) or counterclockwise (-). A zero index signal may be applied
to a Z Channel as a position reference.
JUMPER SETTINGS
Input Type E2 E4 E6 E5
Single-ended (signal & return)
Differential
Differential (with excitation and no zero index)
A positive, negative B transition (A leads B)
A positive, positive B transition (B leads A)
none
a
Count-by Options E9
X1 = positive edge of A input
X2 = positive & negative edges of A input
X4 = positive & negative edges of A & B inputs
none
a
b
Zero Index Polarity E8
Positive
Negative
c
none
Zero Index ANDing E10 E8
Zero Index (no ANDing)
Zero Index AND /A
Zero Index AND /B
Zero Index AND A
Zero Index AND B
Zero Index AND /A AND /B
Zero Index AND /A AND B
Zero Index AND A AND /B
Zero Index AND A AND B
c
a
a
a
a
b
b
b
b
-
a
b
a, b
a
b
a, b
OPERATING MODES
•Quadrature Total (Basic or Extended counter) determines position in engineering units by
subtracting counterclockwise transitions from clockwise transitions, as determined by the
signal phase relationship, applying a programmable scale factor to the total, and adding a
programmable offset to the scaled total. The output update rate is set by a Gate Time, which
should be set to its minimum of 10 ms. When the scaled total reaches a programmable
Preset, it is reset to Offset.
A zero index function can zero the counts when a pulse is applied to a zero index (or Z)
channel. Zero indexing uses the programmable Pulses per Rev, which is the number of
pulses between zero index marks times the edges per pulse (1, 2 or 4). Since a wide zero
index pulse could cause a discrepancy in the region between transitions, the zero index
pulse can be shaped by an AND combination with the A or B channels, as set by jumpers.
•Quadrature Rate (Extended counter) determines rate engineering units by subtracting coun-
terclockwise rate from clockwise rate. Both rates can be scaled using Scale and Offset, or
the Coordinates of 2 Points method.
programmable from 10 ms to 199.99 sec. Since one of the two channels may not be
measuring any pulses over the gate time, a Time Out from 10 ms to 199.99 sec is also
programmable. The transmitter update rate will never be less than every Time Out.
Rate is measured over a gate time, which is
-
- 23 -
12. MAIN BOARD JUMPER SETTINGS
a
d
c
a
E4
b
b
E6
E1
E2
E3
a
cab
b
cd
Serial Signal Duplex Jumpers Termination Resistor*
E6 a = Transmit
Full None
RS485
E6 c = Receive
Half E6 b + d** E6 c
RS232 Full None None
* The termination resistor jumper settings should only be selected if the transmitter is the last
device on an RS485 line longer than 200 feet (60 m).
** Or jumper external BTX to BRX and ATX to ARX (same effect as internal jumpers).
To reset communications to 9600 baud, command mode, Custom ASCII protocol, and Address 1,
place a jumper at E1 and power up the transmitter.
Analog Output Jumpers
Current E2 a + d
Voltage E2 b + c
Excitation Output* Jumpers
5V, 100 mA E3 a + c; E4 a
10V, 120 mA E3 a + c; E4 b
24V, 50 mA E3 b, E4 none
* Attempting to draw more than the rated current will shut down the output.
-
- 24 -
13. DUAL RELAY OPERATION
The optional dual solid state relays can operate in a basic alarm mode, in a hysteresis band mode,
or in a deviation band modes, as explained below. Setpoint operation is referenced to the digital
reading in engineering units that is internal to the transmitter. For example, rate alarm or control
would be referenced to a setpoint in RPM.
1000
g
n
i
d
a
e
R
l
a
t
i
g
i
D
Setpoint
ON
OFFOFF
Time
1000
g
n
i
d
a
e
R
l
a
t
i
g
i
D
Setpoint
OFF
ONON
Time
Active High Basic Alarm Active Low Basic Alarm
A basic alarm changes state automatically when the reading rises above a specified limit, and
changes back automatically when the reading falls below that limit. A red LED indicates the
relay is in an alarm condition, which can be active high or active low, as programmed.
A hysteresis band controls relay action symmetrically around a setpoint. The relay closes (or
opens) when the reading goes above the setpoint plus one hysteresis limit, and opens (or
closes) when the reading falls below the setpoint less one hysteresis limit. A narrow hysteresis
-
- 25 -
band is often used to minimize relay chatter. A wide hysteresis band can be used for on-off
control applications. The hysteresis band equals two hysteresis limits.
A deviation band controls relay action symmetrically around a setpoint. The relay actuates
when the reading falls within the deviation band, and de-actuates when the reading falls
outside. A limit (such as 50 counts) is set up around both sides of the setpoint to create the
deviation band, which equals two limits. Passbands around a setpoint are often used for
component testing.
14. INPUT SIGNAL FILTERING
A moving average filter is selectable in software to process the internal digital readings, which
are taken at 60/sec with 60 Hz power and 50/sec with 50 Hz power. Eight moving average
settings are selectable with the following equivalent RC time constants: 0.08 sec, 0.15 sec, 0.3
sec, 0.6 sec, 1.2 sec, 2.4 sec, 4.8 sec, 9.6 sec. The longer time constants provide superior
noise filtering at the expense of fast response time.
Adaptive moving average filtering allows the transmitter to respond rapidly to actual changes
in signal while filtering out normal noise. An adaptive filter threshold causes the moving
average filter to be reset to the latest reading when the accumulated difference between
individual readings and the filtered reading exceeds that threshold. The accumulated difference
is also reset to zero when the latest reading has a different polarity than the filtered reading. The
adaptive filter threshold can be selected as low or high. Low is normally selected. High should
be selected if the signal has large transients.
15. TRANSMITTER CALIBRATION
All ranges of transmitters have been digitally calibrated at the factory prior to shipment using
computers and calibration equipment certified to NIST standards. If recalibration is required, the
transmitter may be returned to the factory or to an authorized distributor.
The counter main board contains an EEPROM, which stores calibration constants for the quartz
crystal oscillator and the analog output. The V-to-F converter signal conditioner board stores its
own stores its own voltage-to-frequency calibration constants EEPROM. The dual channel pulse
input signal conditioner and quadrature signal conditioner boards do not require calibration. As a
result, transmitter boards can be interchanged without requiring recalibration.
-
- 26 -
Calibration of the quartz crystal is easily accomplished using Instrument Setup software. Select
Calibration from the Main Menu. Apply a frequency reference signal, and enter the known
frequency in Hz. Calibration of the V-to-F signal conditioner requires use of voltage reference
signals and the calibration program vfcal3.exe, which is available for download.
16. CUSTOM CURVE LINEARIZATION
Curve.exe is a DOS-based, executable PC program used to set up an Extended transmitter so
that the analog output and internal digital readings have a user-defined, non-linear relationship
with the input signal. The calculated linearizing parameters are downloaded into non-volatile
memory of the transmitter. The curve-fitting algorithm uses quadratic segments of varying
length and curvature, and includes diagnostics to estimate curve fitting errors. The program is
self-prompting, avoiding the need for detailed printed instructions. This manual section is only
intended as an introduction.
GETTING STARTED
Download curve.exe from the distribution CD into the same directory that will contain your
data files, such as c:\curves. Connect your transmitter to the PC and double-click on curve.exe,
which is an executable file. Follow the steps on the computer screens, which will prompt you
and provide extensive help information. Pressing R (Enter) returns to the main menu. You will
be given the choice of four data entry modes, all of which are explained in detail.
1) Text file entry mode,
2) 2-coordinate keyboard entry mode,
3) 2-coordinate file entry mode, and
4) Equation entry mode.
-
- 27 -
17. MODBUS PROTOCOL TRANSMITTER COMMUNICATIONS
1.0 GENERAL
The Modbus capability conforms to the Modbus over Serial Line Specification & Implementation guide, V1.0. Both the Modbus RTU and Modbus ASCII protocols are implemented:
Modbus RTU
Baud Rate........... 300, 600, 1200, 2400, 4800, 9600 or 19200
Data Format ....... 1 start bit, 8 data bits, 1 parity bit, 1 stop bit (11 bits total)
Parity.................. None, Odd, Even (if None, then 2 Stop bits for 11 total)
Address.............. 0 for broadcast, 1-247 for individual meters
Modbus ASCII
Baud Rate........... 300, 600, 1200, 2400, 4800, 9600 or 19200
Data Format ....... 1 Start bit, 7 Data bits, 1 Parity bit, 1 Stop bit (10 bits total)
Parity.................. None, Odd, Even (if None, then 2 Stop bits for 10 total)
Address.............. 0 for broadcast, 1-247 for individual meters
2.0 FRAMING
Modbus RTU
Message frames are separated by a silent interval of at least 3.5 character times. If a silent
interval of more than 1.5 character times occurs between two characters of the message frame,
the message frame is considered incomplete and is discarded. Frame Check = 16 bit CRC of the
complete message excluding CRC characters.
Modbus ASCII
The message begins immediately following a colon (:) and ends just before a Carriage Return/
Line Feed (CRLF). All message characters are hexadecimal 0-9, A-F (ASCII coded). The system
allowable time interval between characters may be set to 1, 3, 5 or 10 seconds. Frame Check =
1 byte (2 hexadecimal characters) LRC of the message excluding the initial colon (:) and trailing
LRC and CRLF characters.
3.0 ELECTRICAL INTERFACE
RS232, two-wire half-duplex RS485, or four-wire full-duplex RS485 signal levels are selectable
via jumpers on the transmitter main board and a the connector. Please see Section 13. The
RS485 selection provides a jumper selection for insertion of a line termination resistor. In case
of a long line (greater then 500 ft) to the first device, a termination resistor should be selected
for the first device. In case of a long line between the first and last devices, a termination
resistor should be selected for the first and last devices. Never add termination resistors to
more than two devices on the same line.
-
- 28 -
4.0 COMMUNICATIONS SETUP
Parameters selectable via Instrument Setup software, distributed on CD ROM:
Serial Protocol ...............................Custom ASCII, Modbus RTU, Modbus ASCII
Reads measurement values and alarm status. Returns values in 2's Complement Binary Hex
format without a decimal point. The displayed system decimal point can be read with FC03 at
address 0057. Use only odd Register Addresses and an even number of Registers.
Register
Address TM Transmitter Response
------- ----------------------------------------------00 01 Returns Hi word of Alarm status
00 02 Returns Lo word of Alarm status
00 03 Returns Hi word of Measurement value
00 04 Returns Lo word of Measurement value
00 05 Returns Hi word of Peak value
00 06 Returns Lo word of Peak value
00 07 Returns Hi word of Valley value
00 08 Returns Lo word of Valley value
Returns total number of Exception Code 6 (Slave Busy)
Checks communications between the Master and Slave, and returns the count in the Modbus
Slave counters (which are reset when the meter is reset).
Hex Sub
Function
Data
Send
Response
Description
Data
Code
00 00 Any Same
Returns Query Data (N x 2 bytes). Echo Request.
as sent
00 01
Restarts Communications. If in the Listen-Only mode, no
response occurs. Takes Slave out of the Listen-Only mode
and one of the following:
FF 00
00 00
FF 00
00 00
Clears communications event counters.
Does not clear communications event counters.
00 04 00 00 None Forces Listen-Only. All addressed and broadcast
Messages are monitored and counters are incremented,
but no action is taken or response sent. Only SubFunction 00 01 causes removal of this Listen-Only state.
Returns total number of messages detected on the bus,
including those not addressed to this Slave. Excludes bad
LRC/CRC, parity error or length < 3.
00 0C 00 00 Checksum
Error
Count
00 0D 00 00 Exception
Error
Count
00 0E 00 00 Slave
Message
Count
00 0F 00 00 No
Response
Count
00 11 00 00 Slave
Busy
Returns total number of messages with bad LRC/ CRC,
parity or length < 3 errors detected on the bus including
those not addressed to the Slave.
Returns total number of Exception responses returned by
the Addressed Slave or that would have been returned if
not a broadcast message or if the Slave was not in a
Listen-Only mode.
Returns total number of messages, either broadcast or
addressed to the Slave. Excludes bad LRC/CRC, parity or
length < 3 errors.
Returns total number of messages, either broadcast or
addressed to the Slave, for which Slave has returned No
Response, neither a normal response nor an exception
response. Excludes bad LRC/CRC, parity or length < 3
errors.
responses.
- 30 -
-
6.0 SUPPORTED EXCEPTION RESPONSE CODES
Code Name Error Description
---- -------------------- -----------------------------------------------------01 Illegal Function Illegal Function Code for this Slave. Only hex Function
Codes 03, 04, 05, 08, 10 (dec 16) are allowed.
02 Illegal Data Address Illegal Register Address for this Slave.
03 Illegal Data Value Illegal data value or data length for the Modbus protocol.
04 Slave Device Failure Slave device failure (eg. Transmitter set for external gate).
7.0 MESSAGE FORMATTING
MA = Meter Address DD = Data (Hex) CL = CRC Lo Byte
FC = Function Code WW = Data (On/Off) CH = CRC Hi Byte
RA = Register Address SF = Sub-Function CR = Carriage Return
NR = Number of Registers EC = Error Code LF = Line Feed
NB = Number of bytes LRC = ASCII Checksum
Modbus RTU Format
FC Action
03
Request
03
Response
04
Request
04
Response
05
Request
05
Response
08
Request
08
Response
10
Request
10
Response
Exception
Response
> 3.5
Char
NoTx
NoTx
NoTx
NoTx
NoTx
NoTx
NoTx
NoTx
NoTx
NoTx
1 2 3 4 5 6 7 8 9 10 11
MA
MA
MA
MA
MA
MA
MA
MA
MA
MA
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
NoTx MA FC
RA
RA
NB
DD*
RA
RA
NB
DD*
RA
RA
RA
RA
SF
SF
RA
RA
SF
SF
RA
RA
EC CL CH
Byte Number
NR
DD*
NR
DD*
WW
WW
WW
DD
NR
NR
NR
CL
NR
CL
WW
WW
WW
DD
NR
NR
CL
CH
CL
CH
CL
CL
CL
CL
NB
CL
+80
DD* = (DD DD) times NR (Number of Registers)
CH
CH
CH
CH
CH
CH
DD*
DD* CL CH
CH
-
- 31 -
Modbus ASCII Format
FC Action
1 2 3 4 5 6 7 8 9 10 11 12 13
03
Request
03
Response : :
04
Request
04
Response : :
05
Request
05
Response : :
08
Request
08
Response : :
10
Request
10
Response : :
Exception
: MA FC
Response
DD* = (DD DD) times NR (Number of Registers)
8.0 MESSAGE EXAMPLES
MA
MA
MA
MA
MA
MA
MA
MA
MA
MA
FC
FC
FC
FC
FC
FC
FC
FC
FC
FC
+80
Byte Number
RA
NB
RA
NB
RA
RA
SF
SF
RA
RA
RA
DD*
RA
DD*
RA
RA
RA
RA
SF
SF
NR
DD*
NR
DD*
WW
WW
WW
DD
NR
NR
NR
LRC
NR
LRC
WW
WW
WW
DD
NR
NR
LRC
CR
LRC
CR
LRC
LRC
LRC
LRC
NB
LRC
CR
LF
CR
LF
CR
CR
CR
CR
DD*
CR
LF
LF
LF
LF
LF
LF
DD*
LRC CR LF
LF
EC LRC CR LF
All examples are for Transmitter Address = 01 and No Parity.
* Suggested as first message after power-up. If transmitter is in Listen-Only mode, no response
is returned. ** Example while reading +25.18 *** Decimal point is ignored.
9.0 INTERNAL REGISTERS: Please refer to the full Modbus Protocol Communications Manual,
which is downloadable from our website.
The basic measurement data format consists of 8 ASCII characters for analog input “DPM”
transmitters, such as +999.99<CR>, where <CR> is the carriage return character. The first
character is always a plus or minus sign. A decimal point is always furnished, even when it
follows the last digit.
Adding a Line Feed Character to the Basic Format
Printers and other devices that receive the data may require a line feed character <LF> following
the <CR>. The line feed character <LF> may be selected using Instrument Setup software.
Adding a Coded Data Character to the Basic Format
A coded character from A to H may be added to the data string according to the table below to
indicate the alarm and overload status of the device. If used, this character precedes the <CR>,
so that it is the last printable character in the string. With the optional <LF> and coded
character selected, the data string will consist of 10 characters for analog input “DPM”
transmitters, such as +999.99A<CR><LF>.
Alarm Status No Overload Overload
Neither Alarm set
Alarm 1 set only
Alarm 2 set only
Both Alarms set
A
B
C
D
E
F
G
H
For example, a coded character “G” indicates that Alarm 2 only is set and that the transmitter is
in the overload condition. This information is useful when data is supplied to a computer for
listing and analysis, or when data is supplied to a Remote Display in a Master-Slave configuration.
-
- 33 -
Values are transmitted in a continuous string with no intervening spaces. If the 5th digit in is
set to 1 using Instrument Setup software, the termination characters of <CR> and optional
<LF> appear after each value. If the 5th digit is et to 0, the termination characters appear only
once at the end of the string. In either case, if included, the coded character appears at the end
of the last value only.
3.0 NETWORK CONFIGURATIONS
Using the Custom ASCII protocol, TM Series transmitters can operate in a point-to-point mode
using RS232 or RS485, or in a multi-point mode using RS485.
The point-to-point mode is a direct connection between a computer (or other digital device)
and the transmitter. An device address can be selected; however, it is suggested that address 1
be selected as a standard for the point-to-point mode.
The multi-point mode is a connection from a host computer to a multiplicity of transmitters
bused together with their inputs and outputs connected in parallel. For long cable runs, the last
device should have a termination resistor installed. It is necessary to set up each device on the
bus with a different address from 1 to 31. To command a particular device, its address is used
in conjunction with the command, and only that device responds. The outputs of all of the
devices on the bus are set to a high impedance state, except the device being addressed. The
device addresses range from 1 to 31, with 0 being a special address to which a meter responds
only internally (e.g. Reset), but does not transmit any response on the output lines. All devices
may be commanded simultaneously with a 0 address, and there will not be any output
response contention. Addressing of transmitters can be set with Instrument Setup software.
4.0 COMMAND MODE OVERVIEW
Using the Custom ASCII protocol, TM Series transmitters operate in the Command Mode only.
In this mode, the device does not send data automatically, but responds to commands received
from a host computer. These commands can be:
• To transmit the latest or peak measurement
• To reset the meter completely or just the peak value and/or latched alarms
• To display a value sent from the computer
• To transmit present setup parameters
• To receive new setup parameters,
• To monitor or alter data in selected memory locations of the meter.
5.0 COMMAND MODE FORMAT
CHAR 1 - Command Identifier
All commands begin with “*” followed by the meter address, then a command letter
followed by a sub-command number or letter. Additional characters may be appended. All commands terminate with <CR> (<LF> ignored).
-
- 34 -
Char # Character Description
1
2
3
4
*
0-V
A-Z
0-U
Command Identifier. Recognition Character.
Device Address. 0 addresses all devices, 1-V specific devices.
Command Function
Sub-command. Number of Bytes of RAM or Words (2 Bytes) of
non-volatile memory data being transferred.
CHAR 2 - Address Codes
A Serial Communications Address Code from 1 to V follows the “*” to indicate the device
address number from 1 to 31.
Device #
1
2
3
4
5
6
7
8
9
10
11
Address
Code
1
2
3
4
5
6
7
8
9
A
B
Device #
12
13
14
15
16
17
18
19
20
21
22
Address
Code
C
D
E
F
G
H
I
J
K
L
M
Device #
23
24
25
26
27
28
29
30
31
Address
Code
N
O
P
Q
R
S
T
U
V
CHARS 3 & 4 - Commands and Subcommands
The examples below use a default address of 1 following the “*“. Substitute the desired
address from the above table of Serial Comm Address Codes. All command sequences shown
must terminate with <CR>, followed by an optional <LF>.
Request DPM Values
Get reading** *1B1
Peak reading *1B2
Valley reading *1B3
** The meter transmits the value or values selected with Instrument Setup software.
Reset Functions, DPM Transmitter
Cold reset *1C0 Reads NVMEM into RAM locations after RAM is zeroed.
Latched alarms reset *1C2
-
- 35 -
Peak value reset *1C3
Remote display reset *1C4
Valley reset *1C9
Tare function *1CA
Tare reset *1CB
6.0 READING AND WRITING TO RAM AND NONVOLATILE MEMORY
CHAR 1, 2
The Recognition character and Meter Address Code are the same as shown in previous table.
CHAR 3
Command character:
G Read bytes from RAM Memory
F Write bytes to RAM Memory (DPM and Scale meter only)
R Read bytes from Upper RAM Memory
Q Write bytes to Upper RAM Memory
X Read words from Non-Volatile Memory
W Write words to Non-Volatile Memory
CHAR 4
Command character. Sub-command. Number of Bytes of RAM or Words (2 Bytes) of nonvolatile memory data being transferred.
Code # Number Code # Number Code # Number
1
2
3
4
5
6
7
8
9
A
1
2
3
4
5
6
7
8
9
10
B
C
D
E
F
G
H
I
J
K
11
12
13
14
15
16
17
18
19
20
L
M
N
O
P
Q
R
S
T
U
21
22
23
24
25
26
27
28
29
30
CHAR 5, 6
See tables for the RAM MEMORY ADDRESSES and NONVOLATILE MEMORY ADDRESSES with
their respective data definitions.
-
- 36 -
General, Reading and Writing Ram Memory Data
RAM memory data is read and written as a continuous string of bytes consisting of 2 hex
characters (0-9,A-F) per byte. Included in the command are the total number of bytes to be
transferred and the most significant address in RAM of the continuous string of bytes. The
format is:
Read lower RAM data *1Gnaa
Write lower RAM data *1Fnaa<data>
Read upper RAM data *1Rnaa
Write upper RAM data *1Qnaa<data>
where: n is the number of bytes to be read or written.
aa is the most significant address in RAM of the bytes to be read
or written.
<data> is n bytes of 2 hex characters per byte in order from the most
to the least significant byte.
The number of bytes n consists of a single code character representing values from 1 to 30 as
shown above under CHARACTER 4. The most significant address aa consists of 2 hex characters as shown below under RAM MEMORY ADDRESSES AND DATA DEFINITIONS.
General, Reading and Writing Nonvolatile Memory Data
Nonvolatile data is read and written as a continuous string of words consisting of 2 bytes or 4
hex characters (0-9,A-F) per word. Included in the command is the total number of words to
be transferred and the most significant address in nonvolatile memory of the continuous string
of words. The format is:
Read nonvolatile memory data *1Xnaa (followed by Meter reset)
Write non-volatile memory data *1Wnaa <data> (followed by Meter reset)
where: n is the number of words to be read or written.
aa is the most significant address in nonvolatile memory of the words to be
read or written.
<data> is n words of 2 bytes or 4 hex characters per word in order from the most to
the least significant address.
The coded number of words n consists of a single character representing values from 1 to 30
as shown under CHARACTER 4. The most significant address aa consists of 2 hex characters
as shown under NONVOLATILE MEMORY ADDRESSES.
-
- 37 -
19. “CTR” TRANSMITTER SPECIFICATIONS
Mechanical
Case Dimensions ......................................................................................... 120 x 101 x 22.5 mm
Case Mounting................................................................................ 35 mm DIN rail per EN 50022
Relay type ...................................................Two solid state relays, SPST, normally open, Form A
Load rating ................................................................................... 130 mA at 140 Vac or 180 Vdc
-
- 38 -
DUAL CHANNEL SIGNAL CONDITIONER
Crystal Accuracy at 25ºC....................................................................................................±2 ppm
Crystal Tempco...................................................................................................±1 ppm/degree C
Long-Term Drift of Crystal .........................................................................................±5 ppm/year
Signal Types .................... AC, NPN, PNP transistor outputs, contact closures, magnetic pickups
Max Pulse Rate ........................................................ 1 MHz on Channel A, 250 kHz on Channel B
Channel Isolation ..................................................Channel A & channel B share common ground
Low Pass Filter ................................................................................ 250 Hz or 30kHz (selectable)
Hysteresis..................................................................................... 15 mV to 2.2 Vp-p (selectable)
Trigger level ....................................................................................±15 mV to ±1.7 V (selectable)
Debounce Circuitry ...................................................................................0, 3, 50 ms (selectable)
V-TO-F PROCESS RECEIVER & TOTALIZER SIGNAL CONDITIONER
Signal Levels.......................................................................0-1 mA, 4-20 mA, 0-10 V (selectable)
Accuracy at 25ºC............................................................................................................. ±0.025%
Span Tempco........................................................................................... ±0.003% of reading /°C
Zero Tempco.......................................................................................... ±0.003% of full scale /°C
QUADRATURE SIGNAL CONDITIONER
Signal Type .......................................................................Differential or single-ended quadrature
Transitions Monitored................................................................................................. x1, x2 or x4
Max Pulse Rate ........................................................ 250 kHz at x1, 125 kHz at x2, 62.5 kHz at x4
Maximum Differential Signal Amplitude...................................................................................14V
Conversion Technique for Rate.........................................................................................1/period
Conversion Time for Rate ................................................ Gate time + 30 ms + 0-2 signal periods
Time Before Zero Output for Rate...................................................... 0 to 199.99 sec (selectable)
Zero Wait Time for Rate..................................................................... 0 to 199.99 sec (selectable)
Output & Display Update Rate ................................................................Same as conversion rate
Time Base Accuracy for Rate........................................................................Calibrated to ±2 ppm
-
- 39 -
20. WARRANTY
Laurel Electronics Inc. warrants its products against defects in materials or workmanship for a
period of one year from the date of purchase.
In the event of a defect during the warranty period, the unit should be returned, freight prepaid
(and all duties and taxes) by the Buyer, to the authorized Laurel distributor where the unit was
purchased. The distributor, at its option, will repair or replace the defective unit. The unit will be
returned to the buyer with freight charges prepaid by the distributor.
LIMITATION OF WARRANTY
The foregoing warranty shall not apply to defects resulting from:
1.Improper or inadequate maintenance by Buyer.
2.Unauthorized modification or misuse.
3.Operation outside the environmental specifications of the product.
4.Mishandling or abuse.
The warranty set forth above is exclusive and no other warranty, whether written or oral, is
expressed or implied. Laurel specifically disclaims the implied warranties of merchantability
and fitness for a particular purpose.
EXCLUSIVE REMEDIES
The remedies provided herein are Buyer’s sole and exclusive remedies. In no event shall Laurel
be liable for direct, indirect, incidental or consequential damages (including loss of profits)
whether based on contract, tort, or any other legal theory.
Copyright 2006-2012, Laurel Electronics, Inc. Rev 6 February 2012
-
- 40 -
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.