Laurel Electronics LT 4-20 User Manual

LAUREL
4-20 mA & Serial Data Output Transmitter
Features
20, 50, 100, 250 and 500 mV full-scale input ranges
4 or 6-wire hookup to avoid power supply and lead resistance effects
Digital span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999
RS232 or RS485 serial data output, half or full duplex, isolated
Modbus RTU, Modbus ASCII or Laurel ASCII protocol
4-20 mA or 0-10V transmitter output, jumper selectable, isolated
Easy setup using PC-based Instrument Setup Software
DIN rail mount housing only 22.5 mm wide
Detachable screw clamp connectors
5V, 10V or 24V dc transducer excitation output, isolated
Dual solid state relay for alarm or control, isolated
Universal AC power, 85-264 Vac, or low voltage power, 10-48 Vdc or 12-32 Vac
Custom curve linearization and rate from successive readings (optional)
Description
The Laureate load cell or microvolt input transmitter is
designed for use with load cells, strain gauges and microvolt input signals where exceptional sensitivity and stability are required. A most sensitive full-scale input range ±20 mV can be scaled internally to ±99,999 counts. The selected input range for the full 0-20 mA output span can be as wide as ±99,999 counts or as narrow as 150 counts, limited only by considerations of electrical noise and time constants of the programmable moving average digital filter.
A built-in, isolated, 10V, 120 mA excitation supply can power up to four 350-ohm load cells in parallel. Load cell connection can be via 4 or 6 wires. With 4-wire load connection, the transmitter operates in a ratiometric mode to eliminate errors due to power supply variations. With 6-wire load connection, it also compensates for lead resistance, allowing long cable runs.
Fast read rate at up to 50 or 60 conversions per second while integrating the signal over a full power line cycle is provided by Concurrent Slope (Pat 5,262,780) analog-to-digital conversion. High read rate is ideal for peak or valley capture and for real-time computer interface and control.
Digital signal filtering modes are selectable for stable readings in electrically noisy environments.
An unfiltered selection provides true peak and valley readings and aids in control applications.
A batch average filter selection averages each 16 conversions for an update every 1/4 sec.
An adaptive moving average filter selection provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, the filter adapts by briefly switching to the shortest time to follow the change, then reverts back to its selected time constant. An Auto setting selects the time constant selection based on signal noise.
for Load Cell & Microvolt Signals
Standard features of Laureate transmitters include:
4-20 mA, 0-20 mA or 0-10V analog transmitter output, isolated, jumper-selectable and user scalable. All selections provide 16-bit (0.0015%) resolution of output span and 0.02% output accuracy of a reading from -99,999 to +99,999 counts that is also transmitted digitally. Output isolation from signal and power grounds eliminates potential ground loop problems. The supply can drive 20 mA into a 500Ω (or lower) load for 10V compliance, or 10V into a 5kΩm (or higher) load for 2 mA compliance.
Serial communications output, isolated. User selectable RS232 or RS485, half or full duplex. Three protocols are user selectable: Modbus RTU, Modbus ASCII, or Laurel ASCII. Modbus operation is fully compliant with Modbus Over Serial Line Specification V1.0 (2002). The Laurel ASCII protocol allows up to 31 Laureate devices to be addressed on the same RS485 data line. It is simpler than the Modbus protocol and is recommended when all devices are Laureates.
Dual solid state relays, isolated. Available for local alarm or control. Rated 120 mA at 130 Vac or 170 Vdc.
Transducer excitation output, isolated. User selectable 5V@100 mA, 10V@120 mA or 24V@50 mA.
Universal 85-264 Vac power. Low-voltage 10-48 Vdc or 12-32 Vac power is optional.
Easy Transmitter programming is via Laurel's Instrument Setup Software, which runs on a PC under MS Windows. This software can be downloaded from this website at no charge. The required transmitter-to-PC interface cable is available from Laurel (P/N CBL04).
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 1
Specifications
Input Resolution Input Accuracy Update Rate, Max Max applied voltage
Analog Output (standard)
Output Levels Compliance, 4-20 mA Compliance, 0-10V Output Resolution Output Accuracy Output Isolation Step response time
Serial Communications Output (standard)
Signal Types Data Rates Output Isolation Serial Protocols Modbus Modes Modbus Compliance Digital Addressing
Dual Relay Output (standard)
Relay Type Load Rating
Transducer Excitation Output (standard)
Output Levels Output Isolation
Power Input
Standard Power Low Power Option Power Frequency Power Isolation Power Consumption
Mechanical
Dimensions Mounting Electrical Connections
Environmental
Operating Temperature Storage Temperature Relative Humidity Cooling Required
Analog Input Range Input Ohms Input Ohms
Load Cell Input
Microvolt Input
±20.000 mV
±50.0000 mV
±100.00 mV ±250.00 mV ±500.00 mV
±20.000 mV
±50.0000 mV
±100.00 mV ±250.00 mV ±500.00 mV
16 bits (65,536 steps) ±0.01% of full scale ± 2 counts 50/sec at 50 Hz, 60/sec at 60 Hz 100 V
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable) 10V ( 0-500Ω load ) 2 mA ( 5 kΩ load or higher) 16 bits (65,536 steps)
0.02% of output span plus conversion accuracy 250V rms working, 2.3 kV rms per 1 minute test 50 ms
RS232 or RS485 (half or full duplex) 300, 600, 1200, 2400, 4800, 9600, 19200 baud 250V rms working, 2.3 kV rms per 1 min test Modbus RTU, Modbus ASCII, Laurel ASCII RTU or ASCII Modbus over Serial Line Specification V1.0 (2002) 247 Modbus addresses. Up to 32 devices on an RS485 line w/o a repeater.
Two solid state relays, SPST, normally open, Form A 120 mA at 140 Vac or 180 Vdc
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable) 50V from signal ground
85-264 Vac or 90-300 Vdc (DC operation not ETL approved) 10-48 Vdc or 12-32 Vac DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test 2Watts
129 x 104 x 22.5 mm case 35 mm rail per DIN EN 50022 Plug-in screw-clamp connectors
0°C to 55°C
-40°C to 85°C 95% at 40°C, non-condensing Mount transmitters with ventilation holes at top and bottom. Leave 6 mm (1/4") between transmitters, or force air with a fan.
-99,999 to +99,999 zero adjust.
0 to ±99,999 span adjust.
1 µV
2.5 µV
5.0 µV
12.5 µV 25 µV
1 GΩ
1 GΩ
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 2