4-20 mA & Serial Data Output Transmitter
Features
•
20, 50, 100, 250 and 500 mV full-scale input ranges
•
4 or 6-wire hookup to avoid power supply and lead resistance effects
•
Digital span adjust from 0 to ±99,999, zero adjust from -99,999 to +99,999
•
RS232 or RS485 serial data output, half or full duplex, isolated
•
Modbus RTU, Modbus ASCII or Laurel ASCII protocol
•
4-20 mA or 0-10V transmitter output, jumper selectable, isolated
•
Easy setup using PC-based Instrument Setup Software
•
DIN rail mount housing only 22.5 mm wide
•
Detachable screw clamp connectors
•
5V, 10V or 24V dc transducer excitation output, isolated
•
Dual solid state relay for alarm or control, isolated
•
Universal AC power, 85-264 Vac, or low voltage power, 10-48 Vdc or 12-32 Vac
•
Custom curve linearization and rate from successive readings (optional)
Description
The Laureate load cell or microvolt input transmitter is
designed for use with load cells, strain gauges and microvolt
input signals where exceptional sensitivity and stability are
required. A most sensitive full-scale input range ±20 mV can be
scaled internally to ±99,999 counts. The selected input range for
the full 0-20 mA output span can be as wide as ±99,999 counts
or as narrow as 150 counts, limited only by considerations of
electrical noise and time constants of the programmable moving
average digital filter.
A built-in, isolated, 10V, 120 mA excitation supply can power
up to four 350-ohm load cells in parallel. Load cell connection
can be via 4 or 6 wires. With 4-wire load connection, the
transmitter operates in a ratiometric mode to eliminate errors due
to power supply variations. With 6-wire load connection, it also
compensates for lead resistance, allowing long cable runs.
Fast read rate at up to 50 or 60 conversions per second while
integrating the signal over a full power line cycle is provided by
Concurrent Slope (Pat 5,262,780) analog-to-digital conversion.
High read rate is ideal for peak or valley capture and for real-time
computer interface and control.
Digital signal filtering modes are selectable for stable readings
in electrically noisy environments.
•
An unfiltered selection provides true peak and valley
readings and aids in control applications.
•
A batch average filter selection averages each 16
conversions for an update every 1/4 sec.
•
An adaptive moving average filter selection provides a
choice of 8 time constants from 80 ms to 9.6 s. When a
significant change in signal level occurs, the filter adapts by
briefly switching to the shortest time to follow the change, then
reverts back to its selected time constant. An Auto setting
selects the time constant selection based on signal noise.
for Load Cell & Microvolt Signals
Standard features of Laureate transmitters include:
•
4-20 mA, 0-20 mA or 0-10V analog transmitter output,
isolated, jumper-selectable and user scalable. All selections
provide 16-bit (0.0015%) resolution of output span and 0.02%
output accuracy of a reading from -99,999 to +99,999 counts
that is also transmitted digitally. Output isolation from signal
and power grounds eliminates potential ground loop problems.
The supply can drive 20 mA into a 500Ω (or lower) load for
10V compliance, or 10V into a 5kΩm (or higher) load for 2 mA
compliance.
•
Serial communications output, isolated. User selectable
RS232 or RS485, half or full duplex. Three protocols are user
selectable: Modbus RTU, Modbus ASCII, or Laurel ASCII.
Modbus operation is fully compliant with Modbus Over Serial
Line Specification V1.0 (2002). The Laurel ASCII protocol
allows up to 31 Laureate devices to be addressed on the
same RS485 data line. It is simpler than the Modbus protocol
and is recommended when all devices are Laureates.
•
Dual solid state relays, isolated. Available for local alarm or
control. Rated 120 mA at 130 Vac or 170 Vdc.
•
Transducer excitation output, isolated. User selectable
5V@100 mA, 10V@120 mA or 24V@50 mA.
•
Universal 85-264 Vac power. Low-voltage 10-48 Vdc or
12-32 Vac power is optional.
Easy Transmitter programming is via Laurel's Instrument
Setup Software, which runs on a PC under MS Windows. This
software can be downloaded from this website at no charge. The
required transmitter-to-PC interface cable is available from Laurel
(P/N CBL04).
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA • Tel 714-434-6131 • www.laurels.com 1
Specifications
Input Resolution
Input Accuracy
Update Rate, Max
Max applied voltage
Analog Output (standard)
Output Levels
Compliance, 4-20 mA
Compliance, 0-10V
Output Resolution
Output Accuracy
Output Isolation
Step response time
Serial Communications Output (standard)
Signal Types
Data Rates
Output Isolation
Serial Protocols
Modbus Modes
Modbus Compliance
Digital Addressing
Dual Relay Output (standard)
Relay Type
Load Rating
Transducer Excitation Output (standard)
Output Levels
Output Isolation
Power Input
Standard Power
Low Power Option
Power Frequency
Power Isolation
Power Consumption
Mechanical
Dimensions
Mounting
Electrical Connections
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Cooling Required
Analog Input Range Input Ohms Input Ohms
Load Cell Input
Microvolt Input
±20.000 mV
±50.0000 mV
±100.00 mV
±250.00 mV
±500.00 mV
±20.000 mV
±50.0000 mV
±100.00 mV
±250.00 mV
±500.00 mV
16 bits (65,536 steps)
±0.01% of full scale ± 2 counts
50/sec at 50 Hz, 60/sec at 60 Hz
100 V
4-20 mA, 0-20 mA, 0-10 Vdc (jumper selectable)
10V ( 0-500Ω load )
2 mA ( 5 kΩ load or higher)
16 bits (65,536 steps)
0.02% of output span plus conversion accuracy
250V rms working, 2.3 kV rms per 1 minute test
50 ms
RS232 or RS485 (half or full duplex)
300, 600, 1200, 2400, 4800, 9600, 19200 baud
250V rms working, 2.3 kV rms per 1 min test
Modbus RTU, Modbus ASCII, Laurel ASCII
RTU or ASCII
Modbus over Serial Line Specification V1.0 (2002)
247 Modbus addresses.
Up to 32 devices on an RS485 line w/o a repeater.
Two solid state relays, SPST, normally open, Form A
120 mA at 140 Vac or 180 Vdc
5V@100 mA, 10 @120 mA, 24V@50 mA (jumper selectable)
50V from signal ground
85-264 Vac or 90-300 Vdc (DC operation not ETL approved)
10-48 Vdc or 12-32 Vac
DC or 47-63 Hz
250V rms working, 2.3 kV rms per 1 min test
2Watts
129 x 104 x 22.5 mm case
35 mm rail per DIN EN 50022
Plug-in screw-clamp connectors
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
Mount transmitters with ventilation holes at top and bottom.
Leave 6 mm (1/4") between transmitters, or force air with a fan.
-99,999 to +99,999
zero adjust.
0 to ±99,999
span adjust.
1 µV
2.5 µV
5.0 µV
12.5 µV
25 µV
1 GΩ
1 GΩ