Laurel Electronics Laureate Thermocouple Panel Meter-Controller User Manual

LAUREL
Thermocouple
Features
Factory calibrated for thermocouple types J, K, T, E, N, R, S
Entire range of each thermocouple in one scale
Highly accurate and repeatable
Selectable 1° or 0.°1, degrees Celsius, Fahrenheit, Kelvin or Rankin
Up to 60 conversions per second
Peak or valley display
Universal AC power, 85-264 Vac
1/8 DIN case sealed to NEMA-4X from front panel
Optional serial I/O: Ethernet, USB, RS232, RS485, Ethernet-to-RS485 converter
Optional relay output: dual or quad relays, contact or solid state
Optional isolated analog output: 4-20 mA, 0-20 mA, 0-10V, -10 to +10V
Optional low voltage power: 10-48 Vdc or 12-32 Vac
Description
The Laureate thermocouple meter is factory calibrated for type
J, K, T, E, N, R and S thermocouples for exceptional accuracy and repeatability. The entire span of each thermocouple type is presented in a single range. The thermocouple type, unit of measure (°C or °F), resolution (1° or 0.1°), and upscale or down­scale open sensor indication are selectable from the front panel or via the serial interface. Display in Kelvin or Rankin is selected by offsetting the Celsius or Fahrenheit ranges. Cold junction compensation is standard.
All ranges for all thermocouple types are digitally calibrated at the factory, with calibration factors stored in an EEPROM on the signal conditioner board. This allows temperatures sensors and signal conditioner boards to be changed in the field without recalibrating the meter.
High read rates at up to 60 or 50 conversions per second
while integrating the signal over a full power cycle are provided by Concurrent Slope (US Pat 5,262,780) analog-to-digital conversion. High read rates are ideal for peak or valley capture, real-time computer interface, and control. Peak and valley values are automatically captured. These may be displayed via a front panel pushbutton command or a control signal at the rear connector, or be transmitted as serial data.
Specifications
Laureate™
Panel Meter / Controller
Digital filtering is selectable for electrically noisy environments,
including a batch averaging filter and an adaptive moving aver­age filter which provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, that filter adapts by briefly switching to the shortest time to follow the change, then reverts back to the selected time constant. In a selectable Auto filter mode, the filter time constant is automatic­ally selected based on detected signal noise.
Designed for system use. Optional plug-in boards include Ethernet and other serial communication boards, dual or quad relay boards, and an isolated analog output board. Laureates may be powered from 85-264 Vac or optionally from 12-32 Vac or 10-48 Vdc. The display is available with red or green LEDs. The 1/8 DIN case meets NEMA 4X (IP65) specifications from the front when panel mounted. Any setup functions and front panel keys can be locked out for simplified usage and security. All power and signal connections are via UL / VDE / CSA rated screw clamp plugs.
LAUREL
TC Type Range Conformity Error
J -210°C to +760°C (-347°F to +1400°F) ±0.09°C (±0.16°F)
K -244°C to +1372°C (-408°F to +2501°F) ±0.1°C (±0.17°F)
T
E -240°C to +1000°C (-400°F to +1830°F) ±0.18°C (±0.32°F)
N -245°C to +1300°C (-410°F to +2370°F) ±0.10°C (±0.17°F)
R -45°C to +1768°C (-49°F to +3214°F) ±0.17°C (±0.31°F)
S -46°C to +1768°C (-51°F to +3213°F) ±0.12°C (±0.22°F)
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 1
0°C to +400°C (32°F to 752°F)
-257°C to 0°C (-430°F to +32°F)
±0.03°C (±0.05°F)
±0.2°C (±0.36°F)
Accuracy
Calibration Overall accuracy at 25°C Span tempco Reference junction accuracy Span tempco
Electrical
Input resistance Input current Max lead resistance Overvoltage protection NMR at 50/60 Hz CMR, DC-60 Hz CMV, DC-60 Hz
A-to-D Conversion
Technique A-to-D Rate Output Update Display Update
Display
Readout Color Indicators Open sensor indication
Power
NIST Monograph 125 (IPTS-68) ±0.01% of full span + conformity error ±0.003% of reading/°C
0.5°C, 10°C to 40°C ±0.003% of reading/°C
1 GΩ 100 pA 1 kΩ max for rated accuracy 125 Vac 80 dB plus selectable digital filter 120 dB with 500 ohm imbalance 250 Vac from power and earth grounds
Concurrent Slope (Pat 5,262,780) 60/s at 60 Hz, 50/s at 50 Hz 56/s at 60 Hz, 47/s at 50 Hz
3.5/s at 60 Hz, 3/s at 50 Hz
5 digits, 7-segment, 14.2 mm (.56") Red or green LED Minus sign plus 4 red LED lamps for relays Flashes full-scale
Voltage, standard Voltage, optional Frequency Power Isolation
Analog Output (optional)
Output Levels Current compliance Voltage compliance Scaling Resolution Isolation
Relay Outputs (optional)
Relay Types
Current Ratings
Output common Isolation
Serial Data I/O (optional)
Board Selections
Protocols Data Rates Digital Addresses Isolation
85-264 Vac or 90-300 Vdc (DC operation not UL approved) 12-32 Vac or 10-48 Vdc DC or 47-63 Hz 250V rms working, 2.3 kV rms per 1 min test
4-20 mA, 0-20 mA, 0-10V, -10 to +10V (jumper selectable) 2 mA at 10V ( > 5 kΩ load) 12V at 20 mA ( < 600Ω load) Zero and full scale adjustable from -99999 to +99999 16 bits (0.0015% of full scale) 250V rms working, 2.3 kV rms per 1 min test
2 Form C contact relays or 4 Form A contact relays (normally open) 2 or 4 Form A, AC/DC solid state relays (normally open) 8A at 250 Vac or 24 Vdc for contact relays 120 mA at 140 Vac or 180 Vdc for solid state relays Isolated commons for dual relays or each pair of quad relays 250V rms working, 2.3 kV rms per 1 min test
Ethernet, Ethernet-to-RS485 server, USB, USB-to-RS485 server, RS485 (dual RJ11), RS485 Modbus (dual RJ45), RS232. Modbus RTU, Modbus ASCII, Laurel ASCII protocol 300 to 19200 baud 247 (Modbus), 31 (Laurel ASCII), 250V rms working, 2.3 kV rms per 1 min test
Environmental
Operating temperature Storage temperature Relative humidity Protection
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 2
0°C to 60°C
-40°C to 85°C 95% at 40°C, non-condensing NEMA-4X (IP-65) when panel mounted
Mechanical
Application Examples
Operation as a 4-20 mA Transmitter
With the optional analog output board, Laureate temperature meters can serve as superb, isolated 4-20 mA transmitters. The analog output is scaled to the display, which is linearized to °C or °F and is exceptionally accurate. The analog output further tracks the high read rate of the meter, at up to 60 readings per second at 60 Hz power. Fast update rates are beneficial in many closed-loop and PID control applications.
Operation as a Fast Controller
With the dual contact relay or dual solid state relay output board options, Laureate temperature meters can serve as extremely fast and accurate ON/OFF controllers for closed-loop temperature control. Multiple setpoint operating modes are individually selectable for each relay, as explained in the dual­setpoint controller section. Relay duty cycles and chatter can be minimized with programmable hysteresis and time delays. High duty cycles and extremely fast response times are possible with the solid state relay, which has a typical response time of only 17 ms.
Operation as a Supervisory Monitor
By using the optional dual contact relay or dual solid state relay output options, Laureate temperature meters can monitor processes and provide alarms or shutoffs when these processes exceed normal limits. A band deviation operating mode can be selected for each relay, where an alarm is generated whenever the reading is a selected number of counts above or below the setpoint. Relay operation can be selected as latching or non-latching. When an alarm or shutdown condition is reached, a latched output will remain in the alarm condition until it is reset by a front panel pushbutton, via the serial interface, or via the rear connector.
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 3
Ordering Guide
Create a model a model number in this format: L10000JC, IPC
DPM Type L Laureate Digital Panel Meter
Main Board 1 Standard Main Board, Green LEDs
2 Standard Main Board, Red LEDs
Power
(isolated)
Relay Output
(isolated)
Analog Output
(isolated)
Digital Interface
(isolated)
Signal Input
(isolated)
Add-on Options BL Blank Lens without Button Pads
0 85-264 Vac 1 12-32 Vac or 10-48 Vdc
0 None 1 Two 8A Contact Relays 2 Two 120 mA Solid State Relays 3 Four 8A Contact Relays 4 Four120 mA Solid State Relays
0 None 1 Isolated 4-20 mA, 0-20 mA, 0-10 V, -10 to +10V
0 None 1 RS232 2 RS485(dual RJ11 connectors) 4 RS485 Modbus (dual RJ45 connectors) 5 USB 6 USB-to-RS485 device server 7 Ethernet 8 Ethernet-to-RS485 device server
Thermocouple Type JC Thermocouple Type J, -210°C to 760°C JF Thermocouple Type J, -347°F to 1400°F KC Thermocouple Type K, -347°C to 1372°C KF Thermocouple Type K, -408°F to 2501°F TC Thermocouple Type T, -257°C to 400°C TF Thermocouple Type T, -430°F to 752°F EC Thermocouple Type E, -240°C to 1000°C EF Thermocouple Type E, -400°F to 1830°F EC Thermocouple Type N, -245°C to 1300°C NF Thermocouple Type N, -410°F to 2370°F SC Thermocouple Type S, -46°C to 1768°C SF Thermocouple Type S, -51°F to 3214°F RC Thermocouple Type R, -45°C to 1768°C RF Thermocouple Type R, -49°F to 3213°F
CBL01 RJ11-to-DB9 Cable CBL02 USB-to-DB9 Adapter CBL05 USB Cable, A to B IPC Splash-proof Cover BOX1 NEMA-4 Enclosure BOX2 NEMA-4 Enclosure plus IPC
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 4