Laurel Electronics Ethernet Interface Board User Manual

Description
LAUREL
Ethernet Interface Board for 1/8 DIN Laureate
Meters, Counters, Timers & Remote Displays
Features
Connects all 1/8 DIN Laureate DPMs, counters, timers & remote displays to a LAN via a standard Ethernet cable.
Easily networked using Node Manager Software or Node resident web server software for discovery and setup.
Meters on an RS485 bus connected to the Internet via an Ethernet-to-RS485 device server board.
Selectable baud rates to 19,200.
Powered by instrument.
Isolated from meter and power grounds.
The basic Laureate Ethernet interface board plugs into a host
1/8 DIN digital panel meter, counter, timer or emote display to provide a 10/100Base-T Ethernet interface via an industry­standard RJ45 connector. Multiple meters, each with its own Ethernet cable, can be connected to a local area network (LAN) or to the Internet via a router, or directly to a host computer. LAN, WAN, and Internet connectivity are fully supported so that the meter can be read and set up remotely.
Node Manager software is shipped on a mini CD with each Ethernet board. This free Windows-based application automatic­ally discovers all Laurel Nodes (or Laurel Ethernet boards) on a LAN or WAN, plus the host meter connected to the Node. Node Manager software is also used to configure each Node, such as naming the Node and associated devices, entering email addres­ses for alarm notification and data requests, selecting the Node's time zone for time-stamping of streaming data, and setting com­munication parameters for associated meters. Please see our Ethernet Manual.
On a Wide Area Network (WAN), such as the Internet, the host computer is outside of the LAN and must know the public IP address of the LAN router to discover the Laurel Nodes.
Web server software is built into each Node and can be used to discover and configure all Laurel Nodes over the Internet.
Built-in DHCP server capability allows Laurel Nodes to con­stitute themselves into a network and be connected directly to a host computer when no router or dedicated DHCP server is present, as illustrated below. When a Node fails to find a DHCP server that responds to its request for a private IP address, it assigns one. When several Nodes fail to receive a Private IP address, they mutually agree to make one of the Nodes a temporary DHCP server that assigns a Private IP address to each device on the network.
Data can be sent by Laurel Nodes in the form of real-time stream data upon request or in the form of emails. Emails can be sent in response to email requests from the host computer, periodically, or when devices encounter an alarm condition or go off-line.
Laurel's separate Ethernet-to RS458 server board can be used as an alternative to Ethernet board for connecting to the Ethernet up to 31 Laurel Instruments on an RS485 bus.
Easy connection of an RS485 bus with Laureate meters to a PC via an Ethernet cable.
LAUREL
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 1
No need for a separate router or dedicated DHCP server.
Electrical Specifications
Ethernet Board Specifications
Data rates
Devices per Node Ethernet connector Ethernet cable Ethernet compliance Isolation ESD Protection EMI Immunity EFT Protection Short Circuit Protection
300, 600, 1200, 2400, 4800, 9600, 19200 baud with Laureate instruments. Up to 614,400 baud with non-Laureate instruments. Host digital panel meter, counter, timer or remote display RJ45 jack 10/100Base-T EIA/TIA-485 250V rms working, 2.3 kV rms per 1 min test 15 kV per IEC 1000-4-2 10 V/m per IEC 1000-4-3 2 kV per IEC 1000-4-4 Continuous
Protocol Specifications
(Protocol is implemented by meter main board)
Modbus RTU
Standards Compliance Data Formats (selectable)
Applicable Interface Boards Conversion to Modbus TCP Main Board Revision Level
Modbus ASCII
Standards Compliance Data Formats (selectable)
Applicable Interface Boards Conversion to Modbus TCP Main Board Revision Level
Modbus over Serial Line Specification V1.0 (2002)
1. No parity, 8 data bits, 2 stop bits
2. Odd parity, 8 data bits, 1 stop bit
3. Even parity, 8 data bits, 1 stop bit Ethernet, USB, RS232, RS485, RS485 Modbus Automatic Level 5 or above
Modbus over Serial Line Specification V1.0 (2002)
1. No parity, 7 data bits, 2 stop bits
2. Odd parity, 7 data bits, 1 stop bit
3. Even parity, 7 data bits, 1 stop bit Ethernet, USB, RS232, RS485, Modbus RS485 Automatic Level 5 or above
Laurel ASCII
Data Format Protocol Applicable Interface Boards Main Board Revision Level
LAUREL
No parity, 8 data bits, 1 stop bit Laurel Laurel ASCII Ethernet, USB, RS232, RS485, RS485 Modbus Any
ELECTRONICS INC., 3183-G Airway Ave., Costa Mesa, CA 92626, USA Tel 714-434-6131 www.laurels.com 2