The equipment must only be operated for the intended use
under the conditions stated in this operating manual. Any other
type of operation is considered to be not-intended use and can
impair the protection provided by the device.
The operating manual is part of the device. The information in
this operating manual must therefore be available in close
vicinity to the device. Also store this copy of the operating
manual carefully.
If you lose this operating manual, contact the LAUDA
Constant Temperature Equipment service. The contact
details can be found in Ä Chapter 12.3 ‘LAUDA contact’
on page 63.
Use of the device results in hazards from high or low temperatures,
fire and from the use of electrical energy. The hazards of the
device must be eliminated as much as possible by the design in
accordance with the appropriate standards. Residual hazards are
reduced using any of the following measures:
If relevant, there are safety devices for the device. These
devices are essential for the safety of the device. Their functionality must be ensured with appropriate maintenance activities.
The safety devices of the device are described in this "Safety"
chapter.
If relevant, there are warning symbols on the device. These
symbols must always be observed.
The warning symbols on the device are described in this
chapter “Safety”.
There are safety instructions in this operating manual. These
instructions must always be observed.
There are additional specific requirements for the personnel
and for the personal protective equipment.
These requirements are described in this "Safety" chapter.
An overview of the authorised personnel and the protec-
Ä
tive equipment can be found in
sonnel qualification’ on page 8 and
‘Personal protective equipment’ on page 9.
Further information about the general structure of safety
instructions can be found in
of safety instructions’ on page 9.
Chapter 1.9 ‘Per-
Ä
Chapter 1.10
Ä
Chapter 1.11 ‘Structure
Microcool 6
Safety
1.2
Intended use
Intended use
Non-intended use
1.3
Foreseeable misuse
The present device is exclusively permitted to be used for tempering and delivering non-combustible heat transfer liquids in a
closed circuit.
The following applications are considered to be not-intended:
medical applications
in potentially explosive areas
for tempering foodstuffs
with a glass reactor without overpressure protection
Misuse of the device must always be prevented.
Among other things, the following uses are considered to be foreseeable misuse:
Operation of the device without heat transfer liquid
Incorrect connection of hoses
Placement of the device on a tabletop surface, only permitted
for MC 600
Setting an incorrect pump pressure
and MC 1200 (W)
1.4
Modifications to the device
1.5
Heat transfer liquid
Any technical modifications to the machine are prohibited. Service
works may be carried out only by the LAUDA Constant Temperature Devices service or one of the service partners authorized
by LAUDA.
The device is exclusively designed for nonflammable heat
transfer liquids in Class I according to DIN 12876-1.
Heat transfer liquids are used for the temperature control. Only
LAUDA heat transfer liquids are approved for the device.
LAUDA heat transfer liquids are heat transfer liquids that have
been tested and approved by the company LAUDA DR. R.
WOBSER GMBH & CO. KG.
Microcool7
Safety
In each case, the heat transfer liquids cover a specific tem-
perature range. This temperature range must match the temperature range of your application.
The use of heat transfer liquids can cause hazards from high or
low temperatures and fire if certain temperature thresholds are
exceeded or undercut or if the container breaks and there is a
reaction with the heat transfer liquid .
The heat transfer liquid safety data sheet specifies all possible
hazards and appropriate safety measures for handling the
liquid. The safety data sheet must therefore be consulted for
the intended use of the device.
1.6
Materials
1.7
Hoses
1.8
Application area
All parts coming into contact with the heat transfer liquid are made
of high quality materials suitable for the operating temperature.
Stainless steel and temperature-resistant plastics are used.
Only LAUDA hoses are permitted to be used for the external
hydraulics circuit. LAUDA hoses are hoses that are approved by
LAUDA DR. R. WOBSER GMBH & CO. KG. When selecting suitable hoses for the application, the permissible temperature range
and the maximum permissible pressure must be particularly
observed.
The device is exclusively permitted to be used in the following
areas.
Commercial area
Indoor use, no outdoor installation
Ambient temperatures from 5 to 40 °C
1.9
Personnel qualification
Operating personnel
Operating personnel are employees that have been instructed by
technical staff in the intended use of the device according to the
operating manual.
Microcool 8
Safety
1.10
1.11
Danger
Personal protective equipment
Protective clothing
Protective clothing is required for certain activities. This protective
clothing must comply with the legal requirements for personal protective equipment. Protective clothing should have long sleeves.
Safety footwear is additionally required.
Protective gloves
CE protective gloves are required for certain activities. These protective gloves must comply with the legal requirements for personal
protective equipment of the European Union.
Protective goggles
Protective goggles are required for certain activities. These protective goggles must comply with the legal requirements for personal
protective equipment of the European Union.
Structure of safety instructions
A safety instruction of the type "Danger" indicates an immedi-
This results in death or severe, irreversible injuries if the
ately hazardous situation.
safety instruction is disregarded.
Warning
DANGER!
Type and source
Consequences in the case of non-compliance
Measure 1
Measure…
A safety instruction of the type "Warning" indicates a poten-
tially hazardous situation.
This can result in death or severe, irreversible injuries if the
safety instruction is disregarded.
WARNING!
Type and source
Consequences in the case of non-compliance
Measure 1
Measure…
Microcool9
Safety
Caution
Notice
A safety instruction of the type "Caution" indicates a poten-
tially hazardous situation.
This can result in minor, reversible injuries if the safety
instruction is disregarded.
CAUTION!
Type and source
Consequences in the case of non-compliance
Measure 1
Measure…
A"notice" warns about possible property or environmental damage.
NOTICE!
Type and source
Consequences in the case of non-compliance
Measure 1
Measure…
Microcool 10
Unpacking
2
Unpacking
DANGER!
Transport damage
Electric shock
Inspect the device for transport damage before
commissioning.
Never put the device into operation if you have dis-
covered any transport damage.
Personnel:
1.Unpack the device.
Keep the original packaging of the device for later
transport.
2.Inspect the device and the accessories immediately after
delivery for completeness and transport damage.
Operating personnel
If there is unexpected damage to the device or
accessories, inform the carrier immediately so that
a damage report is produced and a check of the
transport damage can be made. Also inform
LAUDA Constant Temperature Equipment Service
immediately. Contact details can be found in
Ä
Chapter 12.3 ‘LAUDA contact’ on page 63.
Accessories included as standard
Device typeDesignationQuantity
MC 600, MC 1200 (W)¾" olive with ¾" union nut2EOA 004
All equipmentOperating manual1--
Catalogue
number
Microcool11
Design and function
3
3.1
Available device types
Design and function
Device types
The type designation of the equipment is composed of the following elements.
ElementDescription
MCMicrocool
<number>, e.g. 600Specification of the cooling capacity in
watts
WDevice with water cooling
This specification in the device type is
optional. It identifies water-cooled equipment.
Device typeDescription
MC 250Air-cooled tabletop device with a cooling
capacity of 250 watts
MC 600Air-cooled floor-standing device with a
cooling capacity of 600 watts. The pump
pressure can be adjusted using a bypass
adjustment wheel.
MC 1200Air-cooled floor-standing device with a
cooling capacity of 1200 watts. The pump
pressure can be adjusted using a bypass
adjustment wheel.
MC 1200 WWater-cooled floor-standing device with a
cooling capacity of 1200 watts. The pump
pressure can be adjusted using a bypass
adjustment wheel.
1Display
2LEDs
3Display buttons
4Mains power switch
3.3
3.3.1
Controls
Mains power switch
The mains power switch can be put in the following positions:
In position [I], the device is switched on.
In position [O], the device is switched off.
Microcool17
Design and function
3.3.2
Display buttons
Fig. 6: Display buttons
1UP arrow button
2ENTER button
3DOWN arrow button
Functions in the display of the device can be controlled using the
display buttons.
A selection in the display can be confirmed with the ENTER
button.
The UP and DOWN arrow buttons can be used to navigate in
the display.
Microcool 18
Design and function
3.4
Function elements
3.4.1
LEDs for function display
Fig. 7: LEDs
1Yellow LED
2Blue refrigeration LED
3Red error LED
Each device has three LEDs with the following functions:
3.4.2
Hydraulic circuit
Hydraulic circuit
The yellow glycol LED lights if Kryo 30 is necessary as heat
transfer liquid.
The blue refrigeration LED indicates whether the refrigeration
unit is active.
The red error LED lights in the event of device faults.
The hydraulic circuit designates the circuit through which the heat
transfer liquid flows.
The circuit basically consists of the following components:
internal storage bath with heat transfer liquid
pump for conveying the heat transfer liquid into the external
consumer via the pump connections
Starting with MC 600, devices are equipped with an adjustable
bypass to be able to adapt the pump pressure to the requirements of the external consumer.
Microcool19
Design and function
Pump
3.4.3
Manometer
The devices are equipped with a magnetically coupled pressure
pump.
Further information about the technical data of the pump
and the pump characteristic curve can be found
Ä
Table on page 62.
The device types with bypass have a manometer for reading the
set pump pressure. The pump pressure is regulated using the
bypass adjustment wheel on the rear side.
Fig. 8: Manometer
3.4.4
Level indicator
The fill level of the heat transfer liquid in the circuit can be read
using the level indicator.
The top arrow indicates the maximum liquid level of the
machine.
The bottom arrow indicates the minimum liquid level of the
machine.
Fig. 9: Level indicator
1Maximum level
2Minimum level
3.4.5
Refrigeration unit
The refrigeration unit includes the following components:
Microcool 20
Design and function
Compressor
A hermetically sealed compressor is used in the refrigeration
unit. The compressor is equipped with overload protection
which trips on the compressor temperature and compressor
current consumption.
Condenser
Depending on the device type, an air-cooled or water-cooled
condenser is used in the refrigeration unit. In air-cooled condensers, the condensation heat is discharged to the environment. The fresh air is sucked in through the front of the device
using a fan, heated and discharged on the rear of the device.
In water-cooled condensers, the condensation heat is discharged via cooling water.
Evaporator
In the internal bath, heat is discharged using a pipe coil evaporator.
Technical information for the refrigeration unit can be
found in
Ä
on page 61.
3.4.6
RS232 interface
Alarm output
Interfaces
Note the following:
The equipment connected to the low voltage inputs and out-
puts must have safe separation from dangerous voltages
according to DIN EN 61140 such as by double or reinforced
insulation according to DIN EN 60730-1 or DIN 60950-1.
Specific functions of the device such as the setpoint temperature
can be controlled with the RS232 interface using a PC. Thus,
custom programs for controlling the device can be developed.
Further information about the connection and configura-
Ä
tion can be found in
RS232 interface’ on page 44.
Changeover contact which switches in the event of a device fault.
For example, faults can be registered on a system.
Using the display, it can be set in which fault situations
a signal is output via the interface.
Chapter 6.7.1 ‘Configuring
Microcool21
Design and function
3.5
Rating plate
The rating plate information is explained in detail in the following
table. Certain information is dependent on installed device options.
This information is noted with an appropriate suffix.
SpecificationDescription
TypeDevice type
Catalogue No.Catalogue number of the device
Serial No.Serial number of the device
Refrigerant IRefrigerant that is used in the compressor
of the device
Filling charge IFill quantity of the refrigerant
PS high pressure Imaximum permitted operating pressure
on the refrigerant high pressure side
(compressor, condenser)
on the refrigerant low pressure side
(expansion, evaporation)
Fig. 10: Rating plate
3.6
Serial number
VoltageDevice must only be connected to this
voltage and frequency
Power consumptionPower consumption of the device during
operation
Protection classIP protection class of the device
FuseFuse used in the device
Class according to
DIN 12876-1
The serial number of a LAUDA device has the following structure:
LAUDA catalogue number
Year of manufacture
The year is indicated with two digits.
Sequential number of the device in the year of manufacture.
The sequential number is a four-digit number.
This information is displayed in the format <catalogue number><year of manufacture>-<sequential number>.
An example for Microcool devices: LWM118-13-0130.
German standard for electrical laboratory
equipment
Microcool 22
Before commissioning
4
4.1
Before commissioning
EMC classification
Approval of the equipment according to EMC classification
CountriesEMC Class
EuropeClass A
This classification has been made according
to the EMC standard DIN EN 61326-1 (corresponds to VDE 0843-20-1).
USAClass A
This classification has been made according
to the FCC (Federal Communications Commission) regulations, Section 15.
CanadaClass A
This classification has been made according
to the ICES-003 (Interference Causing
Equipment Standards) and NMB-003 regulations.
Instructions for machines, Europe
Instructions for Class A digital
device, USA
Instructions for Class A digital
device, Canada
EMC classification of the equipment:
Class A: Operation only on mains power supplies without con-
nected residential areas.
Class B: Operation on mains power supplies with connected
residential areas.
In the case of unfavourable mains conditions, disruptive voltage
fluctuations can occur.
"This equipment has been tested and found to comply with the
limits for Class A digital device, pursuant to Part 15 of the FCC
(Federal Communication Commission) Rules. These limits are
designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense."
“This Class A digital apparatus complies with Canadian ICES-003”
(ICES = Interference Causing Equipment Standards).
« Cet appareil numérique de la classe A est conforme à la norme
NMB-003 du Canada ».
Microcool23
Before commissioning
4.2
Device Placement
Very specific placement conditions are applicable for the equipment. These placement conditions are specified in the technical
data of the device for the most part.
Further information about the technical data can be
found in
Additional placement conditions are described below.
Toxic vapours can be produced depending on the heat transfer
liquid used and type of operation. Ensure sufficient extraction
of the vapours.
Observe the requirements of the device for electromagnetic
compatibility (EMC).
Do not cover the ventilation openings.
Further information about EMC requirements can be
found in
Ä
Chapter 11.1 ‘General data’ on page 60.
Ä
Chapter 4.1 ‘EMC classification’ on page 23.
WARNING!
Rolling away, falling over of the device
Impact, crushing
Do not tilt the device.
Place the device on a level, non-slip surface with
sufficient load bearing capacity.
Engage the castor brake when setting up the
device.
Do not place any heavy parts on the device.
1.Place the device at a suitable location in the room.
Place tabletop devices on a suitable table. Support the
device for this by reaching under the device.
Place floor-standing devices on a suitable base.
Floor-standing devices can be moved. Release
the locking brakes of the castors for this by
pressing the [Off] lever downwards.
Several devices can be positioned next to each
other.
2.Lock the castors of the device for floor-standing devices.
Press the [On] lever downwards to lock.
Microcool 24
Before commissioning
4.3
External consumer
4.3.1
Hoses
CAUTION!
Discharge of heat transfer liquid during operation
caused by use of unsuitable hoses
Frostbite
Use hoses with temperature resistance that is
appropriate for the operating temperature range of
the device.
CAUTION!
Contact with cold hoses
Frostbite
Use insulated hoses for temperatures below 0 °C.
The hoses specified below can be used for all heat
transfer liquids that are approved for the devices.
Approved hoses, adapters and
hose clamps
Hoses, not insulated
TypeOliveApplication area
EPDM hose10 mm
EPDM hose
Rubber hose with
fabric reinforcement
Rubber hose with
fabric reinforcement
½"
(13 mm)
½"
(13 mm)
¾"
(19 mm)
Further information about the pump connections of the
individual devices can be found in
‘Hydraulic circuit’ on page 62.
Devices with max-
imum pump pressure
of < 1 bar
Devices with max-
imum pump pressure
of < 1 bar
no restrictions
no restrictions
Ä
Chapter 11.3
Internal
Ø in mm
911-35 ... 90RKJ 111
1214-35 ... 90RKJ 112
13 (½")
19 (¾")
External
diameter
in mm
19-40 ... 100RKJ 031
27-40 ... 100RKJ 032
Temperature
range in
°C
Cata-
logue
number
Microcool25
Before commissioning
Hoses, insulated at the factory
Type
Pump connec-
tions
Application area
Internal Ø
in mm
External diam-
eter in mm
Tem-
perature
range in
°C
Catalogue
number
EPDM
hose, insu-
lated
Insulated hoses for subsequent insulation, length 1 m
Insulation
catalogue
number
RKJ 0581051954RKJ 112
RKJ 0241251636RKJ 112
RKJ 0091052343RKJ 031
RKJ 0131252950RKJ 032
Adapters, suitable for MC 600 and MC 1200 (W)
DesignationDescriptionCatalogue number
Olive 13 mm,
M16 x 1
Max. temperature in
°C
Olive¾" union nut, ½ " oliveLWZ 016
Devices with
maximum pump
pressure of
< 1 bar
Internal Ø in mm
1223-35 ... 90LZS 021
External diameter in
mm
Suitable for hose
Olive¾" union nut, 10 mm oliveLWZ 040
Hose clamps
Stainless steel10 ... 16EZS 012
Stainless steel12 ... 22EZS 013
Stainless steel20 ... 32EZS 015
MaterialØ from ... to in mmCatalogue number
Microcool 26
Before commissioning
4.3.2
Connecting external consumer
Note the following:
Temperature control hoses: Always use the largest possible
Secure the temperature control hoses with hose clamps.
If the external consumer is at a higher level than the device,
In the event of hose rupture, cold liquid can escape and
CAUTION!
Discharge of heat transfer liquid during operation
caused by open consumer
Electric shock, frostbite
Only use closed consumers.
CAUTION!
Bursting of the external hydraulic circuit due to
overpressure
Impact, cutting, frostbite
Lay hoses so that they do not kink.
diameters and shortest possible hose lengths in the external
liquid circuit.
If the temperature control hose diameter is too small, a temperature drop between device and external consumer occurs
due to flow rate too low. In this case, increase or lower the temperature accordingly.
emptying of the external volume can occur if the pump is
stopped and there is ingress of air in the external liquid circuit
even for closed circuits. In this case, you risk device overflow.
become a danger for persons and material.
4.4
Cooling water
4.4.1
Cooling water requirements
This section is relevant for the following:
For water-cooled devices
Microcool27
Before commissioning
General requirements
There are specific requirements for the cooling water concerning
its purity. In accordance with the cooling water requirements, a
suitable process for treatment and maintenance of the water must
be used. The condenser and the complete cooling water circuit can
be clogged, damaged and leak due to unsuitable cooling water.
Extensive consequential damage to the complete refrigerant circuit
can occur. The cooling water quality is dependent on the local conditions.
Free chlorine, e.g. from disinfectants and water containing
chloride results in pitting corrosion in the cooling water circuit.
Distilled, deionised or demineralised water is not suitable due
to its corrosive properties and results in corrosion in the cooling
water circuit.
Seawater is not suitable due to its corrosive properties and
results in corrosion in the cooling water circuit.
Water containing iron and iron particles in the water result in
rust formation in the cooling water circuit.
Hard water is not suitable for cooling due to the high lime con-
tent and results in calcification in the cooling water circuit.
Cooling water with suspended matter is not suitable.
Untreated, not purified water, e.g. river or cooling tower water
is not suitable due to its microbiological content (bacteria)
which can settle in the cooling water circuit.
Suitable cooling water quality
DataValue Unit
pH value7.5 – 9.0
Sulphates [SO4 2-]
Hydrogen carbonate [HCO
-
] / Sul-
3
< 70 mg/l
> 1.0
phates [SO4 2-]
Water hardness (alkaline earth ions
0.71 - 1.52 mmol/l
content)
Hydrogen carbonate [HCO
-
]
3
70 – 300 mg/l
Conductivity10 - 500 μs/cm
Chlorides (Cl-)
Sulphite (SO3 2-)
< 50 mg/l
< 1 mg/l
Free chlorine gas (Cl2)< 1 mg/l
Nitrates (NO
-
)
3
< 100 mg/l
Ammonia (NH3)< 2 mg/l
Iron (Fe), dissolved< 0.2 mg/l
Manganese (Mn), dissolved< 0.1 mg/l
Aluminium (Al), dissolved< 0.2 mg/l
Free, aggressive carbonic acid (CO2)< 5 mg/l
Microcool 28
Before commissioning
DataValue Unit
Hydrogen sulphide (H2S)< 0.05 mg/l
Algae growthnot permitted
Suspended matternot permitted
4.4.2
Connecting cooling water
This section is relevant for the following:
For water-cooled devices
SpecificationValue
Maximum cooling water
6 bar
pressure
Differential pressure
1 ... 6 bar
cooling water rp
approx. 15 °C recommended
Cooling water temperature
10 ... 30 °C permissible (with performance limitations)
Note the following:
Fix the cooling water hoses in place with hose clamps.
Fix the supply hose of the water cooling in place in the sink
area to prevent uncontrolled sliding, also in the event of pressure surges.
Fix the supply hose of the water cooling in place in the sink
area so that spraying out of hot cooling water is not possible.
Prevent kinking or squeezing of the hoses.
We recommend using a leak detector with water shut-off to
prevent damage due to cooling water system leaks.
Ensure that the cooling water meets the required criteria.
In the case of leaks in the condenser, there is the danger that
refrigerator oil and refrigerant from the refrigerant circuit of the
device can get into the cooling water. Comply with all applicable legal provisions and the requirements of the water supply
companies at the operating site.
Microcool29
Before commissioning
4.5
RS232 interface
4.5.1
Cable and interface test RS232
ComputerThermostat
Signal9-pin Sub-D female con-
nector
with hardware handshake
RxD223322TxD
TxD332233RxD
DTR4204DSR
Signal
Ground
DSR666DTR
RTS747CTS
CTS858RTS
557755Signal
without
hardware
handshake
25-pin Sub-D female
connector
with hardware handshake
Note the following:
without
hardware
handshake
9-pin Sub-D female connector
with hardware handshake
without
hardware
handshake
Signal
Ground
4.6
Alarm output 12N
Available functions
With hardware handshake: Use a straight-through and not a
null modem cable for connecting a thermostat to the PC. The
RS232 interface can be connected directly to the PC using a
straight-through cable.
Without hardware handshake: Set the corresponding operating
mode on the PC. Use shielded connection cables. Connect
shield to connector case. The cables must be galvanically isolated from the rest of the electronics. Do not connect unassigned pins.
The RS232 interface can be easily checked on a connected
PC with the Microsoft Windows operating system. Using the
HyperTerminal program for Windows®
Starting with Windows Vista, HyperTerminal is no longer
an integral part of Windows. However, it is possible to
purchase and download the program. Alternatively,
there are also free Open Source terminal programs
such as putty with a similar range of functions.
FunctionDescription
95/98/NT/XP.
Alarm output--
Alarm and standbyfor on-site return flow protection
Microcool 30
Before commissioning
View of flange connector (front) or solder side coupling socket
Max. 30 V DC; 1 A
Fig. 11: Flange connector (front) in idle state
1Normally open contact
2Centre
3Normally closed contact
Idle state
The device is in idle state when it is switched off and in the
case of failure.
Pins 1 and 2 are open.
Pins 3 and 2 are closed.
GO state
The device is in GO state immediately after switching on and
during normal operation without faults.
Pins 1 and 2 are closed.
Pins 3 and 2 are open.
Note the following:
The equipment connected to the low voltage inputs and out-
puts must have safe separation from dangerous voltages
according to DIN EN 61140 such as by double or reinforced
insulation according to DIN EN 60730-1 or DIN 60950-1.
Only use shielded connection cables; connect the shield to the
connector case. Cover unused plug connections with protective
caps.
Microcool31
Commissioning
5
5.1
Approved heat transfer liquids
Commissioning
LAUDA heat transfer liquids
LAUDA
designa-
tion
Chemical
designation
perature
range in °C
Tem-
Note the following:
The heat transfer liquids each cover a recommended tem-
perature range and must be suitable for the temperature range
of your application.
At the lower limit of the temperature range, the heat transfer
liquid becomes more viscous and influences temperature constancy, pump power and cooling capacity. The formation of
vapours and odours increases in the upper range. Therefore,
only use all of the temperature range if required. Particularly
with Aqua 90 (water), ice forms which can result in destruction
of the device.
Never use contaminated or degenerated heat transfer liquids.
You can request the safety data sheets of the heat transfer
liquid at any time if required.
Viscosity
(kin) in mm²/s
(at 20 °C)
Viscosity
(kin) in mm²/s
for
temperature
Container size
Catalogue number
5 l10 l20 l
Mono eth-
Kryo 30
Aqua 90
Heat transfer liquid water
ylene
glycol /
water
decalcified
water
-30 ... 90450 at -25 °CLZB 109LZB 209LZB 309
5 ... 901---LZB 120LZB 220LZB 320
Note the following for Kryo 30:
The water content reduces during long operating with higher
temperatures and the mixture becomes flammable (flame point
128 °C). Check the mixture ratio using a hydrometer.
The alkaline earth ions content (hardness) of the water must be
between 0.71 mmol/l
8.0 °dH). Harder water results in lime deposits in the device.
The pH value of the water must be between 6.0 and 8.5.
Distilled, deionised, demineralised (DM) water or seawater
must not be used due to the corrosive properties. Ultra-pure
water and distillates are suitable as medium after addition of
0.1 g soda (Na2CO3, sodium carbonate) per litre of water.
Any chlorine content in the water must be strictly avoided. Do
not add any chlorine to the water. Chlorine is contained, for
example, in cleaning agents and disinfectants.
and 1.42 mmol/l (equivalent to 4.0 and
Microcool 32
Commissioning
The water must be free of impurities. Water containing iron is
unsuitable due to rust formation and untreated river water is
unsuitable due to algae formation.
The addition of ammonia is not permitted.
5.2
Filling device with heat transfer liquid
Personnel:
Protective equipment:
Operating personnel
Protective goggles
Protective clothing
Protective gloves
DANGER!
Use of incorrect heat transfer liquid
Fire
Select a heat transfer liquid with a temperature
range 20 K above the temperature range of the
application.
WARNING!
Overflow of heat transfer liquid
Electric shock
Ensure that the device is not overfilled. Note the
level indicator and the thermal volume expansion of
the heat transfer liquid.
WARNING!
Spraying of heat transfer liquid
Electric shock
Avoid spraying heat transfer liquid. Use a funnel for
filling.
1.Close the drain plug. For this, turn the plug clockwise as far
as the stop.
2.Attach a suitable hose to the overflow connection of the
device.
The permitted hose diameter for the overflow must
be complied with. Further information about the
suitable hose diameter can be found in the technical data Ä Chapter 11.3 ‘Hydraulic circuit’
on page 62.
Microcool33
Commissioning
3.Insert this hose into a suitable canister to collect overflowing
heat transfer liquid.
Running dry of the consumer can also occur in a
closed temperature control circuit with consumer
at a higher level in the case of stopped pump and
ingress of air into the temperature control circuit
(for example, a not completely closed or defective
bleed valve). Match the size of the overflow container to this if possible.
4.Carefully pull up the cover of the filler nozzle; do not turn.
5.Fill the heat transfer liquid into the filler nozzle carefully. Mon-
itor the level indicator. Fill the device up to the maximum fill
level.
If necessary, use a funnel for the filling.
The level indicator must not be above the maximum fill level.
5.3
Establishing power supply
6.Press the cover carefully into the filler nozzle.
Personnel:
NOTICE!
Use of unauthorised mains voltage or mains frequency
Device damage
Compare the rating plate with available mains
voltage and mains frequency.
Also note the following:
The mains plug of the device provides a mains power discon-
nection component. The mains plug must be easily recognisable and easily accessible.
Only connect the device to an earthed (PE) power socket.
Operating personnel
Microcool 34
Commissioning
5.4
Switching on the device
WARNING!
Overheating of the pump
Device damage
Never operate device without heat transfer liquid.
Personnel:
1.Switch on the device using the mains power switch.
A signal tone sounds. The actual temperature is shown
on the display. The pump is started. The refrigeration unit
is started after approx. 2 minutes. The blue LED lights if
the refrigeration unit is active.
2.Depending on the size of the consumer, heat transfer liquid
must be refilled if necessary. Monitor the level indicator for
this.
Further information about refilling heat transfer
liquid can be found in
heat transfer liquid’ on page 35.
Operating personnel
Ä
Chapter 5.5 ‘Refilling
5.5
Refilling heat transfer liquid
Personnel:
Protective equipment:
DANGER!
Use of incorrect heat transfer liquid
Fire
Select a heat transfer liquid with a temperature
range 20 K above the temperature range of the
application.
Operating personnel
Protective goggles
Protective clothing
Protective gloves
Microcool35
Commissioning
WARNING!
Overflow of heat transfer liquid
Electric shock
Ensure that the device is not overfilled. Note the
level indicator and the thermal volume expansion of
the heat transfer liquid.
1.Check whether the drain plug is closed.
The drain plug is closed if it is turned clockwise as
far as the stop.
2.Carefully pull up the cover of the filler nozzle; do not turn.
3.Fill the heat transfer liquid into the filler nozzle carefully. Mon-
itor the level indicator.
If necessary, use a funnel for the filling.
5.6
Setting pump pressure
The level indicator must not be above the maximum fill level.
The level indicator must be above the minimum
level. Otherwise a warning is output and the
device is switched off with an alarm after approx.
5 minutes.
4.Press the cover carefully into the filler nozzle.
For devices with bypass (starting from MC 600), the pump
pressure can be set using a control valve on the rear side of the
device. Individual setting of the pump pressure is possible with this
when using pressure-sensitive external consumers.
Microcool 36
Commissioning
Personnel:
CAUTION!
Bursting of the external consumer
Scalding, impact, cutting
A bypass regulator is provided to set the pump
pressure (starting from MC 600).
For consumers with a maximum permissible oper-
ating pressure below the maximum pressure of the
pump, use a safety valve for protection. This safety
valve must be installed in the outlet of the device.
1.To reduce the pump pressure, turn the bypass adjustment
wheel anticlockwise until the maximum permitted pressure
for the external consumer is reached.
Monitor the display on the manometer for this.
2.To increase the pump pressure, turn the bypass adjustment
wheel clockwise until the required pressure for the external
consumer is reached.
Operating personnel
Microcool37
Operation
6
6.1
Operation
Switching on the device
WARNING!
Overheating of the pump
Device damage
Never operate device without heat transfer liquid.
Personnel:
1.Switch on the device using the mains power switch.
A signal tone sounds. The actual temperature is shown
on the display. The pump is started. The refrigeration unit
is started after approx. 2 minutes. The blue LED lights if
the refrigeration unit is active.
2.Depending on the size of the consumer, heat transfer liquid
must be refilled if necessary. Monitor the level indicator for
this.
Further information about refilling heat transfer
liquid can be found in
heat transfer liquid’ on page 35.
Operating personnel
Ä
Chapter 5.5 ‘Refilling
6.2
Default display and menu items
1.Press the ENTER button to reach the menu items from the
default display of the actual temperature.
If no button has been pressed for longer than 4
seconds, you exit from the menu item or input
window.
2.Scroll from menu item to menu item using the arrow buttons.
3.Press the ENTER button at the selected menu item.
The display flashes.
4.The value or the setting can be changed using the arrow but-
tons.
5.The changed value or setting is applied immediately by
pressing the ENTER button.
If no button has been pressed for longer than 4
seconds, changed values or settings are applied
automatically and you exit from the menu item or
input window.
Microcool 38
Operation
Fig. 12: Menu
Microcool39
Operation
6.3
Screen displays
Default display
Fig. 13: Default display
Menu
Editing display
6.4
Specifying the setpoint temperature
The default display is the indication shown in the screen if no other
operations such as configuring settings are being performed. The
actual temperature of the machine is shown in the default display.
The machine menu with possible settings can be invoked using the
ENTER button.
The display flashes when a menu item in the screen has been
selected. The setting can now be made. The value entered is
applied when the setting is confirmed.
Further information about the menu structure and the
Ä
menu navigation can be found in
display and menu items’ on page 38.
Chapter 6.2 ‘Default
Relationship between temperature
setpoint and temperature limit
values
You specify a setpoint for the temperature control. This value
specifies to which temperature the heat transfer liquid will be
cooled. The upper and lower temperature limit values of the device
have been set to the default values
perature limits define the temperature range of your application, i.e.
in which range any temperature control can take place. A warning
is output by the device if the temperature is outside the limits. This
range is necessary so that no unnecessary warnings are output
during transient conditions of the temperature regulation. The
default values can be limited subsequently depending on the heat
transfer liquid.
For operation of the device with Aqua 90, the temperature setpoint
must not be set smaller than 5 °C. Also use the lower temperature
Ä
limit value Lo
set this to 3 °C so that a warning is output for lower temperatures.
The yellow LED on the device lights if any temperature setpoint or
actual temperature is less than 5 °C. It warns about incorrect use
of the heat transfer liquid and consequential damage to the device.
‘Lower temperature limit value’ on page 42 and
If the device is operated with liquid temperatures below
5 °C, Kryo 30 (glycol / water) must be used in the device
as heat transfer liquid.
45.0 °C and 5.0 °C. The tem-
Microcool 40
Operation
Personnel:
1.Select the menu item for specifying the temperature setpoint.
2.Specify the setpoint.
Fig. 14: Setpoint input
3.Confirm with the ENTER button.
6.5
Restricting temperature limit values
The range of the temperature limit values must be restricted for
safety reasons. These two values depend on the heat transfer
liquid used. The default settings of
device cannot be changed.
Practical temperature limit values are:
Aqua 90- Set the range to the values 42 °C and 3 ℃.
Kryo 30 (water /
glycol)
Operating personnel
If the entered setpoint is outside the specified temperature limit values, the value cannot be
adopted. Editing mode is active. An audible signal
is also output. You can input the setpoint again.
45.0 °C and
- Set the range to the values 42 °C and
-12 ℃.
5.0 °C stored in the
Upper temperature limit value
Fig. 15: Upper limit value
By adjusting the temperature limit values, the configurable setpoint range is automatically limited to as 2 °C
below the upper temperature limit and 2 °C above the
lower temperature limit.
Personnel:
1.Select the menu item for the upper temperature limit value.
2.Confirm with the ENTER button.
3.Specify the upper limit value.
The maximum value of the upper limit is 45 °C.
4.Confirm with the ENTER button.
Operating personnel
Microcool41
Operation
Lower temperature limit value
Personnel:
1.Select the menu item for the lower temperature limit value.
2.Confirm with the ENTER button.
3.Specify the lower limit value.
Operating personnel
Fig. 16: Lower limit
6.6
Configuring timer
Special features of the timer
Functions for automatic switching
off - Auto-Shut-Down
The minimum value of the lower limit is 5 °C when
using Aqua 90 and -15 °C when using Kryo 30.
4.Confirm with the ENTER button.
The integrated timer can be used for switching the device on and
off automatically. The timer can be viewed and configured during
normal operation of the device.
The timer is configured using a number of hours and minutes in
the format hh.mm. The first two digits represent the number of
hours and the last two are the minutes. The timer can be set to
a maximum of 99 hours and 59 minutes.
The timer is only active while the machine is switched on. If the
machine is switched off using the mains power switch during
the running time of the timer, the timer is reset.
If Auto-Shut-Down of the timer is active, the current actual tem-
perature on the display is shown with a flashing decimal point.
If Auto-Shut-Down is invoked using the corresponding menu
item, the remaining time, for example 05.30 , is shown flashing.
If Auto-Shut-Down is deactivated, 00.00 is shown flashing.
Once the time for Auto-Shut-Down has elapsed, the device is
not switched off completely but switched to standby. Standby
means all components of the device are switched off and only
the display of the device is still supplied with power.
Functions for automatic switching
on - Auto-Start
If Auto-Start of the timer is configured, the device switches to
standby and Auto-Start is active immediately. If any Auto-ShutDown is active, the Auto-Start is not active until after completion of the Auto-Shut-Down.
If Auto-Start is active, the remaining time until the automatic
start is shown on the display. An audible signal is also output
during the complete last minute before starting the device.
Microcool 42
Configuring Auto-Shut-Down
Fig. 17: Auto-Shut-Down
Fig. 18: Standby
Operation
1.Select the menu item for specifying the Auto-Shut-Down.
2.Confirm with the ENTER button.
3.Specify the time until the device should be switched to
standby.
Wait for approx. 4 seconds if you would not like to
apply the specified value. The screen automatically returns to the default display.
4.Confirm with the ENTER button.
The value must be confirmed within 4 seconds
after the last input. Otherwise the screen returns
to the default display.
The device will be switched to standby after the time
entered. This is shown on the display as follows.
5.Auto-Start can now be configured before the expiry of Auto-
Shut-Down to switch the device on again afterwards after a
specified time. Otherwise you can start the device manually
by pressing the ENTER button.
Configuring Auto-Start
Fig. 19: Auto-Start
CAUTION!
Automatic device start using the auto-start timer
Frostbite, risk of injury, device damage
Before using the auto-start timer, ensure that all
preparations for the intended use have been made.
1.Select the menu item for specifying the Auto-Start.
2.Confirm with the ENTER button.
3.Specify the time until the device should be switched on
again.
If no Auto-Shut-Down is configured for the device,
the device is switched directly into standby with
the confirmation.
Wait for approx. 4 seconds if you would not like to
apply the specified value. The screen automatically returns to the default display.
Microcool43
Operation
Displaying and editing remaining
time
4.Confirm with the ENTER button.
The value must be confirmed within 4 seconds
after the last input. Otherwise the screen returns
to the default display.
1.Select the menu item for the Auto-Shut-Down or Auto-Start.
2.Confirm with the ENTER button.
The remaining time is displayed.
3.You have the following options:
Wait approx. 4 seconds if you only want to display the
remaining time. The default display is shown again.
To edit the remaining time, set the time accordingly. Con-
firm with the ENTER button.
Reset
Restart manually
6.7
RS232 interface
6.7.1
Configuring RS232 interface
1.Select the menu item for the Auto-Shut-Down or Auto-Start.
2.Input 00.00.
3.Confirm with the ENTER button.
The value must be confirmed within 4 seconds
after the last input. Otherwise the screen returns
to the default display.
If the device has been switched to standby using Auto-Shut-Down
and no Auto-Start is configured, the device can be switched on
again manually.
1.Press the ENTER button to switch the device on again.
This function is only available if no Auto-Start is
active.
The baud rate for the RS232 interface can be configured using the
display.
Microcool 44
Operation
Fig. 20: RS232 interface
6.7.2
Protocol
RS232 protocol
Personnel:
Operating personnel
1.Select the menu item for configuration of the RS232 inter-
face.
2.Select the appropriate baud rate.
The following baud rates can be selected:
2.4
4.8
9.6
19.2
The hundreds and thousands digits are not visible
on the display.
3.Confirm with the ENTER button.
Your input is applied automatically after approx. 4
seconds.
Note the following:
The interface operates with 1 stop bit, no parity bit and 8 data
The RS232 interface can be operated with or without hardware
handshake (RTS/CTS).
The command from the computer must be terminated with CR,
CRLF or LFCR.
CR = Carriage Return (hex: 0D); LF = Line Feed (hex: 0A)
The response from the thermostat is always terminated with
CRLF.
Example for setpoint transfer of 30.5 °C to the thermostat.
ComputerThermostat
"OUT_SP_00_30.5"CRLF
"OK"CRLF
Microcool45
Operation
6.7.3
Write commands
The write commands are data specifications to the thermostat.
CommandMeaning
OUT_SP_00_XXX.XXSetpoint transfer with max. 3 digits before the dec-
imal point and max. 2 digits afterwards
OUT_SP_04_XXX[Hi] Upper limit of flow temperature
OUT_SP_05_XXX[Lo] Lower limit of flow temperature
STARTSwitches on device (from standby)
STOPSwitches device to standby (pump, refrigeration unit
off).
Note the following:
For "_", " " (space character) is also permitted.
Response from the thermostat “OK” or “ERR_X” in the case of
an error.
Permitted data formats
-XXX.XX-XXX.X-XXX.-XXXXXX.XXXXX.XXXX.XXX
-XX.XX-XX.X-XX.-XXXX.XXXX.XXX.XX
-X.XX-X.X-X.-XX.XXX.XX.X
-.XX-.X.XX.X
6.7.4
Read commands
The following read commands are data requests to the thermostat.
CommandMeaning
IN_PV_00Query of the bath temperature (outlet temperature)
IN_SP_00Query of the temperature setpoint
IN_SP_04Query of the outlet temperature limit Hi
IN_SP_05Query of the outlet temperature limit Lo
TYPEQuery of the device type (response = "MC").
VERSIONQuery of the software version number
Microcool 46
Operation
CommandMeaning
STATUSQuery of the device status, 0 = OK, -1 = fault
STATQuery for the fault diagnosis, response: XXXXXXX;
X = 0 no fault, X = 1 fault
Character 1 = error
Character 2 = not assigned
Character 3 = not assigned
Character 4 = not assigned
Character 5 = low level
Character 6 = not assigned
Character 7 = not assigned
Note the following:
For "_", " " (space character) is also permitted.
Unless otherwise specified for the command, the reply is
always in fixed decimal format "XXX.XX" or "-XXX.XX" for negative values or "ERR_X".
6.7.5
6.8
Error messages
Configuring alarm output
The error messages of the modules are described in the following.
ErrorDescription
ERR_2Incorrect input (e.g. buffer over-
flow)
ERR_3Incorrect command
ERR_5Syntax error in the value
ERR_6Impermissible value
ERR_32The upper temperature limit is
less than or equal to the lower
temperature limit.
In the case of an alarm or error, an electrical signal is output via
the alarm output of the device as default. However, you can also
configure that a signal will also be output in the case of a warning.
Microcool47
Operation
Fig. 21: Alarm output
Fig. 22: Option error and alarm
Fig. 23: Option with additional warning
Personnel:
1.Select the menu item for configuring the alarm output.
2.Select the following option for the output of an electrical
signal for alarms and errors.
3.Select the following option for the additional output of an
electrical signal for warnings.
Wait for approx. 4 seconds if you would not like to
apply the specified value. The screen automatically returns to the default display.
4.Confirm with the ENTER button.
The value must be confirmed within 4 seconds
after the last input. Otherwise the screen returns
to the default display.
Operating personnel
6.9
Inputting offset of the temperature sensor
If any temperature difference is discovered when checking the
device with a reference thermometer, the offset (additive part of the
characteristic curve) of the internal measurement chain can be
adjusted using the CAL menu item.
A calibrated reference thermometer (e.g. from the LAUDA DigiCal
series) with the required degree of accuracy is required. Otherwise
the factory calibration should not be changed.
The reference thermometer must be installed in the flow of the
device in accordance with the specifications in the calibration certificate.
Personnel:
1.Select the menu item CAL.
2.Enter the temperature value read from the reference ther-
mometer at the device.
Fig. 24: Calibrating temperature
sensor
The calibration overwrites the factory calibration.
Operating personnel
Microcool 48
Operation
3.Keep the ENTER button pressed for approx. 3 seconds after-
wards.
The display shows donE . The new value has been
applied.
6.10
Fig. 25: Factory settings
Restoring the factory settings
Execute this menu item if you would like to restore the factory settings stored in the device.
The range of the temperature limit values is reset to
5 °C.
The timers are reset to 00.00 .
The signal output at the alarm output is reset to alarms and
faults .
The baud rate is reset to 9600 baud .
Personnel:
1.Select the menu item (dEF) for restoring the factory settings.
2.Confirm with the ENTER button.
3.Keep the ENTER button pressed for approx. 3 seconds after-
wards.
The display shows donE . The factory settings have been
restored.
Operating personnel
45 °C and
Microcool49
Maintenance
7
7.1
Maintenance
General safety instructions
DANGER!
Contact with live or moving parts
Electric shock, impact, cutting, crushing
The device must be disconnected from the mains
power supply before any maintenance work.
CAUTION!
Contact with hot / cold device parts, accessories
and heat transfer liquid.
Burns, scalding, frostbite
Ensure device parts, accessories and heat transfer
liquid are at room temperature before touching
them.
NOTICE!
Contact with rotating part
7.2
Maintenance intervals
Severed parts of the body
Repairs must only be performed by specialist per-
sonnel.
Also note the following:
Before all maintenance work, you should ensure that decon-
tamination of the device has been performed if it came into
contact with hazardous materials.
The maintenance intervals described in the following table must be
complied with. The following maintenance work is mandatory
before every longer unsupervised operation.
Microcool 50
Maintenance
IntervalMaintenance work
dailyInspection of the drain plug by visual inspection from the outside
monthlyInspection of the external hoses for material fatigue
Cleaning of the condenser
(only air-cooled devices)
Cleaning of the water filter
(only for water-cooled devices)
quarterlyDecalcification of the cooling water circuit (a shorter interval must be selected depending
on water hardness and operating time)
(only for water-cooled devices)
half-yearlyInspection of the heat transfer liquid
7.3
Cleaning the device
7.4
Cleaning air-cooled condenser
Personnel:
WARNING!
Ingress of cleaning agents in the device
Electric shock
Use a moist cloth for cleaning.
Also note the following:
Only clean the control panel with water and detergent. Do not
use acetone or solvents. The consequence would be permanent damage of the plastic surfaces.
Operating personnel
Personnel:
1.Switch off the device.
2.Remove the front cover by holding underneath with both
hands and pulling the grating to the front. Remove the front
cover slowly and carefully to prevent damage.
3.Brush off or vacuum the condenser.
4.Replace the front cover carefully.
Microcool51
Operating personnel
Maintenance
7.5
Cleaning the water filter
Fig. 26: Removing water filter
7.6
Decalcification of the cooling water circuit
Personnel:
1.Switch off the device using the mains power switch.
2.Undo the union nut at the supply of the water cooling.
3.Remove the cooling water hose with the hose nozzle from
the threaded connection.
4.Remove the water filter from the threaded connection care-
fully.
5.Clean the water filter and then put it back into the threaded
connection.
6.Press the cooling water hose with the hose nozzle back onto
the threaded connection of the supply. Carefully tighten the
water hose using the union nut at the threaded connection.
Personnel:
Operating personnel
If necessary, use tweezers to remove / insert the
water filter.
Operating personnel
Fig. 27: Decalcification
1.Switch off the device and prepare the decalcification process
accordingly.
The descaling agent should be fed to the water
cooling using a pump or a funnel through the
supply hose. The descaling agent return flow
should be via flow hose of the water cooling into a
container with sufficient capacity (at least 10
litres).
LAUDA descaling agent (catalogue number LZB
126, 5 kg packaging) is required for decalcification. Read the safety instructions and the instructions for use on the packaging for handling the
chemical.
2.Clean the water filter of the device. The water filter is in the
supply of the water cooling.
Further information for cleaning the water filter can
be found in
filter’ on page 52.
3.Fill the supply hose of the water cooling with LAUDA desca-
ling agent (pump or funnel). Continuously refill or pump the
descaling agent. Continue this process until the foaming
reaction goes down. This is usually the case after approx. 20
to 30 minutes.
Ä
Chapter 7.5 ‘Cleaning the water
Microcool 52
Maintenance
4.Drain the condenser afterwards.
Further information about draining the condenser
can be found in .
5.Reconnect the device to the water supply and rinse it thor-
oughly.
Allow at least 10 litres of water to flow through the
device.
7.7
Checking the heat transfer liquid
Soiled or degenerated heat transfer liquid must be replaced. Further use of the heat transfer liquid is only permitted with appropriate test results.
The heat transfer liquid must be checked according to DIN 51529.
Microcool53
Faults
8
8.1
Procedure in the event of alarms
Procedure in the event of warnings
Procedure in the event of errors
Faults
Alarms, errors and warnings
Any alarms, error signals and warnings triggered on the device are
shown on the display as 7-segment text.
Alarms can be cancelled using the ENTER button after rectification
of the cause of the fault.
A list of alarms can be found in
on page 55.
Warnings can be cancelled using the ENTER button after rectification of the cause of the fault.
A list of warnings can be found in
view’ on page 55.
A two-tone signal is output if any error occurs. The red LED on the
device also lights.
In the case of an error, switch off the device at the mains power
switch. If the error occurs again after restarting the device, note the
error code and contact LAUDA Service Constant Temperature
Equipment. Contact details can be found in
‘LAUDA contact’ on page 63.
Ä
Chapter 8.2 ‘Alarms overview’
Ä
Chapter 8.3 ‘Warnings over-
Ä
Chapter 12.3
Errors are symbolised with an E and a sequential threedigit number.
Microcool 54
Faults
8.2
Alarms overview
Output on the displayDescription
Alarms are relevant for safety. The components of the device such
as the pump switch off. A two-tone signal is output by the device.
The red LED on the device also lights.
In the event of a Low Level alarm, the fill level of the heat transfer
liquid is below the minimum limit. The fault which caused this low fill
level must be rectified to cancel the alarm. Heat transfer liquid must
also be refilled.
Warnings are output before the alarm is emitted. The alarm is output
after approx. 5 minutes.
The pump is blocked for any pump alarm. This can be caused by
unacceptably high viscosity of the heat transfer liquid or by foreign
bodies in the circuit.
The temperature of the electronics is higher than 75 °C.
8.3
Warnings overview
Indication on the displayDescription
Warnings are not relevant for safety. The device continues running.
A continuous tone is output for a short time by the device. Warnings are output periodically. You are therefore reminded in the
event of an existing fault.
In the event of a Low Level warning, the fill level of the heat transfer
liquid is below the minimum limit.
The fault which caused this low fill level must be rectified to cancel
the warning. Heat transfer liquid must also be refilled.
If this warning is ignored, a Low Level alarm will be output after
approx. 5 minutes and the components of the device such as the
pump will be switched off.
The upper temperature limit has been exceeded for this warning.
The device fault must be rectified to remove this warning.
The lower temperature limit has been undercut for this warning.
The device fault must be rectified to remove this warning.
Microcool55
Faults
Indication on the displayDescription
NTC sensor break
NTC short circuit
Microcool 56
Decommissioning
9
9.1
Decommissioning
Draining the device
Personnel:
WARNING!
Contact with cold heat transfer liquid
Frostbite
Bring the heat transfer liquid to room temperature
before draining.
Also note the following:
Observe the regulations for disposal of the used heat transfer
liquid.
1.Switch off the device.
2.Let the device and the heat transfer liquid cool down or heat
up to room temperature.
3.Position a container with appropriate capacity directly under
the drain plug.
Operating personnel
The heat transfer liquid discharges directly from
the device when the drain plug is opened.
4.Open the drain plug. Turn anticlockwise for this.
9.2
Draining condenser (only water-cooled devices)
Personnel:
1.Bring the device to room temperature if required and switch
off the device.
2.Unscrew the water hose from the supply nozzle of the
device.
3.Remove the water filter from the threaded connection. Clean
the water filter and then put it back into the threaded connection.
Further information for cleaning the water filter can
be found in
filter’ on page 52.
4.Unscrew the water hose from the outlet nozzle of the device.
5.Place a bucket under the outlet nozzle to collect the dis-
charging water.
Operating personnel
Ä
Chapter 7.5 ‘Cleaning the water
Microcool57
Decommissioning
6.Without switching on the device, blow compressed air
through the supply nozzle into the device. Continue blowing
compressed air through the device until all the water has
flowed out of the device.
Microcool 58
Disposal
10
10.1
Disposal
Disposing of refrigerant
The refrigerant must be disposed of in accordance with EC regulations 303/2008/EC in combination with 842/2006/EC.
CAUTION!
Uncontrolled escape of refrigerant
Impact, cutting
Do not dispose of any pressurised cooling circuit.
The decommissioning is only permitted by a spe-
cialist.
RefrigerantGWP
R134a1430
Global Warming Potential (GWP) time horizon 100
years - according to IPCC IV (2007). Comparisons CO
= 1.0.
(100a)
2
10.2
10.3
Device disposal
Disposing of packaging
Type and fill quantity of the refrigerant can be seen on
the rating plate.
The device must be disposed of according to EC Directive
2002/96/EC.
The packaging must be disposed of in accordance with EU Directive 94/62/EC.
Microcool59
Technical data
11
11.1
Technical data
General data
The device sound pressure level is below 70 dB.
According to EC Directive 2006/42/EC. the sound pressure level of the devices is therefore not specified further.
DataValue Unit
PlacementIndoor areas
Height above sea levelup to 2,000 m
Relative humidityHighest rela-
tive humidity
80% at 31 °C
and up to 40
°C
decreasing
linearly by up
to 50%
Ambient temperature range5 ... 40 °C
IP degree of protectionIP 32
Contamination level2
Clearance from surroundings (front
and rear sides)
OvervoltageOvervoltage
category II
and transient
surge vol-
according to
category II
Protection class for electrical operating equipment DIN EN 61 140 (VDE
0140-1)
Classification according to
DIN 12 876-1
identification)
Display7-segment,
Display resolution0,1
Setting resolution0,1
(class designation /
40 cm
tages
I/NFL
LED
1
°C
°C
Temperature constancy±
Storage temperature range5 ... 40 °C
0,5 K
Microcool 60
Technical data
DataValue Unit
Transport temperature range-20 ... 60 °C
Operating temperature
range
°Cmmkg
MC 250-10 ... 40200 x 350 x 46526
MC 600-10 ... 40350 x 480 x 59551
MC 1200-10 ... 40450 x 550 x 65064
MC 1200 W-10 ... 40450 x 550 x 65064
11.2
Cooling capacity
Cooling
kWkWkWkW
MC 2500.230.20.150.09R134a
MC 6000.60.50.360.15R134a
Refrigeration unit
capacity
(20 °C)
Cooling
capacity
(10 °C)
Dimensions (W x D x H)Weight
Cooling
capacity
(0 °C)
Cooling
capacity
(-10 °C)
Refrigerant
MC 12001.151.050.750.4R134a
MC 1200 W1.151.050.750.4R134a
The cooling capacity is measured for a specified temperature of the heat transfer liquid. Information is provided
in brackets. The ambient temperature for the measurement is 20 °C; ethanol was used as heat transfer liquid.
The cooling water temperature is 15 °C and the cooling
water differential pressure is 3 bar for the measurement
of water-cooled devices.
Microcool61
Technical data
11.3
Fill capacityMaximum
Litres
MC 2502 ... 4160.35
MC 6004 ... 8351.3
MC 12007 ... 14351.3
MC 1200 W7 ... 14351.3
11.4
Power consumption
Hydraulic circuit
Voltage-dependent data
flow
l/min (water
20 °C)
Maximum
flow pres-
bar (water
sure
20 °C)
Pump con-
nection
(internal
diameter
in mm)
Olive ½" (10)G ½"Olive ½" (10)
G ¾ (15),
olive ¾"
G ¾ (15),
olive ¾"
G ¾ (15),
olive ¾"
Drain tapOverflow con-
nection
G ½"
G ½"
G ½"
(internal diam-
eter in mm)
Olive 16 mm
(12)
Olive 16 mm
(12)
Olive 16 mm
(12)
MC 250MC 600MC 1200MC 1200 W
kWkWkWkW
230 V; 50 Hz0.230.71.151.2
Catalogue numbers
MC 250MC 600MC 1200MC 1200 W
230 V; 50 HzLWM 118LWM 120LWM 121LWM 122
220 V; 60 HzLWM 218LWM 220LWM 221LWM 222
115 V; 60 HzLWM 418LWM 420LWM 421LWM 422
100 V; 50/60 HzLWM 618LWM 620LWM 621LWM 622
Microcool 62
General
12
12.1
12.2
12.3
General
Copyright
Technical changes
LAUDA contact
This manual is protected by copyright and is exclusively intended
for the purchaser for internal use.
The transfer of this manual to third parties, reproductions of any
type and form, whether in whole or in part, and the dissemination
and/or communication of the contents are not authorised without
the written permission of the manufacturer.
Infringements will result in legal action for damages. We reserve
the right to assert further claims.
Technical details subject to change.
Contact LAUDA Service Constant Temperature Equipment in the
following cases:
Contact details
12.4
EC conformity
In the event of faults on the device
For technical questions about the device
For spare part orders
Contact our Sales Department for application-specific questions.
LAUDA Service Constant Temperature Equipment
Telephone: +49 (0)9343 503 372
Fax: +49 (0)9343 503 283
E-Mail:
The device complies with the applicable basic occupational health
and safety requirements of the Directives listed below.
LAUDA DR. R. WOBSER GMBH & CO. KG - Pfarrstraße 41/43 97922 Lauda-Königshofen - Germany
service@lauda.de
Microcool63
General
The device does not come under the Pressure Equipment Directive 97/23/EC as the device is classified in
the area of Article 3.3. The requirements from the above
mentioned Directives are thus sufficiently met for the
pressure-relevant hazards of the device.
LAUDA Dr. R. Wobser•LAUDA Service Center•Fax: +49 (0) 9343 - 503-222
:
Von
Firma
Straße
Ort
Tel
Fax
Betreiber
From / De
/
/ C
/ S
City / Ville
/
:
ompany / Entreprise
treet / Rue
:
:
:
.:
:
esponsible person / Personne responsable
/ R
:
Hiermit bestätigen wir, daß nachfolgend aufgeführtes LAUDA-Gerät (Daten vom Typenschild):
We herewith confirm that the following LAUDA-equipment (see label):
Par la présente nous confirmons que l’appareil LAUDA (voir plaque signalétique):
Typ
Type / Type
/
:
Serien-Nr.
Serial no. / No. de série:
/
mit folgendem Medium betrieben wurde
was used with the below mentioned media
a été utilisé avec le liquide suivant
Darüber hinaus bestätigen wir, daß das oben aufgeführte Gerät sorgfältig gereinigt wurde,
die Anschlüsse verschlossen sind, und sich weder giftige, aggressive, radioaktive noch
andere gefährliche Medien in dem Gerät befinden.
Additionally we confirm that the above mentioned equipment has been cleaned, that all connectors are closed
and that there are no poisonous, aggressive, radioactive or other dangerous media inside the equipment.
D’autre part, nous confirmons que l’appareil mentionné ci-dessus a été nettoyé correctement, que les
tubulures sont fermées et qu’il n’y a aucun produit toxique, agressif, radioactif ou autre produit nocif ou
dangeureux dans la cuve.
Stempel
Seal / Cachet.
Formblatt / Form / Formulaire: Unbedenk.doc
Erstellt / published / établi: LSC
Änd.-Stand / config-level / Version: 0.1
Datum / date:30.10.1998