Lauda MC 250, MC 1200, MC 600, MC 1200 W Operating Instructions Manual

The right temperature worldwide
Operating instructions
Microcool
MC 250, MC 600, MC 1200, MC 1200 W
Circulation chiller
LAUDA DR. R. WOBSER GMBH & CO. KG
Postfach 1251
Germany
Phone: +49 (0)9343 / 503-0
Fax: +49 (0)9343 / 503-222
E-Mail: info@lauda.de
Internet: www.lauda.de
Translation of the original operating instructions
YAWE0033 V02REV60 10/022/2014 © LAUDA 2013
Microcool 2

Table of contents

Table of contents
1 Safety.................................................................................................................................................... 6
1.1 General safety instructions.......................................................................................................... 6
1.2 Intended use................................................................................................................................ 7
1.3
Foreseeable misuse.................................................................................................................... 7
1.4 Modifications to the device.......................................................................................................... 7
1.5 Heat transfer liquid...................................................................................................................... 7
1.6 Materials...................................................................................................................................... 8
1.7 Hoses.......................................................................................................................................... 8
1.8 Application area........................................................................................................................... 8
1.9 Personnel qualification................................................................................................................ 8
1.10 Personal protective equipment.................................................................................................... 9
1.11 Structure of safety instructions.................................................................................................... 9
2 Unpacking.......................................................................................................................................... 11
3 Design and function.......................................................................................................................... 12
3.1 Device types.............................................................................................................................. 12
3.2 Design of the circulation chiller.................................................................................................. 13
3.3 Controls..................................................................................................................................... 17
3.3.1 Mains power switch.................................................................................................... 17
3.3.2 Display buttons........................................................................................................... 18
3.4 Function elements..................................................................................................................... 19
3.4.1 LEDs for function display........................................................................................... 19
3.4.2 Hydraulic circuit.......................................................................................................... 19
3.4.3 Manometer................................................................................................................. 20
3.4.4 Level indicator............................................................................................................ 20
3.4.5 Refrigeration unit........................................................................................................ 20
3.4.6 Interfaces................................................................................................................... 21
3.5 Rating plate............................................................................................................................... 22
3.6 Serial number............................................................................................................................ 22
4 Before commissioning...................................................................................................................... 23
4.1 EMC classification..................................................................................................................... 23
4.2 Device Placement..................................................................................................................... 24
4.3 External consumer.................................................................................................................... 25
4.3.1 Hoses......................................................................................................................... 25
4.3.2 Connecting external consumer.................................................................................. 27
4.4 Cooling water............................................................................................................................ 27
4.4.1 Cooling water requirements....................................................................................... 27
Microcool 3
Table of contents
4.4.2 Connecting cooling water........................................................................................... 29
4.5 RS232 interface......................................................................................................................... 30
4.5.1 Cable and interface test RS232................................................................................. 30
4.6 Alarm output 12N...................................................................................................................... 30
Commissioning.................................................................................................................................. 32
5
5.1 LAUDA heat transfer liquids...................................................................................................... 32
5.2 Filling device with heat transfer liquid........................................................................................ 33
5.3 Establishing power supply......................................................................................................... 34
5.4 Switching on the device............................................................................................................. 35
5.5 Refilling heat transfer liquid....................................................................................................... 35
5.6 Setting pump pressure.............................................................................................................. 36
6 Operation............................................................................................................................................ 38
6.1 Switching on the device............................................................................................................. 35
6.2 Default display and menu items................................................................................................ 38
6.3 Screen displays......................................................................................................................... 40
6.4 Specifying the setpoint temperature.......................................................................................... 40
6.5 Restricting temperature limit values.......................................................................................... 41
6.6 Configuring timer....................................................................................................................... 42
6.7 RS232 interface......................................................................................................................... 44
6.7.1 Configuring RS232 interface...................................................................................... 44
6.7.2 Protocol...................................................................................................................... 45
6.7.3 Write commands........................................................................................................ 46
6.7.4 Read commands........................................................................................................ 46
6.7.5 Error messages.......................................................................................................... 47
6.8 Configuring alarm output........................................................................................................... 47
6.9 Inputting offset of the temperature sensor................................................................................. 48
6.10 Restoring the factory settings.................................................................................................... 49
7 Maintenance....................................................................................................................................... 50
7.1 General safety instructions........................................................................................................ 50
7.2 Maintenance intervals............................................................................................................... 50
7.3 Cleaning the device................................................................................................................... 51
7.4 Cleaning air-cooled condenser.................................................................................................. 51
7.5 Cleaning the water filter............................................................................................................. 52
7.6 Decalcification of the cooling water circuit................................................................................. 52
7.7 Checking the heat transfer liquid............................................................................................... 53
8 Faults.................................................................................................................................................. 54
8.1 Alarms, errors and warnings..................................................................................................... 54
8.2 Alarms overview........................................................................................................................ 55
Microcool 4
Table of contents
8.3 Warnings overview.................................................................................................................... 55
9 Decommissioning.............................................................................................................................. 57
9.1 Draining the device.................................................................................................................... 57
9.2 Draining condenser (only water-cooled devices)...................................................................... 57
Disposal.............................................................................................................................................. 59
10
10.1 Disposing of refrigerant............................................................................................................. 59
10.2 Device disposal......................................................................................................................... 59
10.3 Disposing of packaging............................................................................................................. 59
11 Technical data.................................................................................................................................... 60
11.1 General data.............................................................................................................................. 60
11.2 Refrigeration unit....................................................................................................................... 61
11.3 Hydraulic circuit......................................................................................................................... 62
11.4 Voltage-dependent data............................................................................................................ 62
12 General............................................................................................................................................... 63
12.1 Copyright................................................................................................................................... 63
12.2 Technical changes.................................................................................................................... 63
12.3 LAUDA contact.......................................................................................................................... 63
12.4 EC conformity............................................................................................................................ 63
13 Index................................................................................................................................................... 65
Microcool 5

Safety

1
1.1
Safety

General safety instructions

The equipment must only be operated for the intended use
under the conditions stated in this operating manual. Any other type of operation is considered to be not-intended use and can impair the protection provided by the device.
The operating manual is part of the device. The information in
this operating manual must therefore be available in close vicinity to the device. Also store this copy of the operating manual carefully.
If you lose this operating manual, contact the LAUDA Constant Temperature Equipment service. The contact details can be found in Ä Chapter 12.3 ‘LAUDA contact’ on page 63.
Use of the device results in hazards from high or low temperatures, fire and from the use of electrical energy. The hazards of the device must be eliminated as much as possible by the design in accordance with the appropriate standards. Residual hazards are reduced using any of the following measures:
If relevant, there are safety devices for the device. These
devices are essential for the safety of the device. Their func­tionality must be ensured with appropriate maintenance activi­ties.
The safety devices of the device are described in this "Safety" chapter.
If relevant, there are warning symbols on the device. These
symbols must always be observed. The warning symbols on the device are described in this
chapter “Safety”.
There are safety instructions in this operating manual. These
instructions must always be observed.
There are additional specific requirements for the personnel
and for the personal protective equipment. These requirements are described in this "Safety" chapter.
An overview of the authorised personnel and the protec-
Ä
tive equipment can be found in
sonnel qualification’ on page 8 and ‘Personal protective equipment’ on page 9.
Further information about the general structure of safety instructions can be found in
of safety instructions’ on page 9.
Chapter 1.9 ‘Per-
Ä
Chapter 1.10
Ä
Chapter 1.11 ‘Structure
Microcool 6
Safety
1.2

Intended use

Intended use
Non-intended use
1.3

Foreseeable misuse

The present device is exclusively permitted to be used for tem­pering and delivering non-combustible heat transfer liquids in a closed circuit.
The following applications are considered to be not-intended:
medical applicationsin potentially explosive areasfor tempering foodstuffswith a glass reactor without overpressure protection
Misuse of the device must always be prevented.
Among other things, the following uses are considered to be fore­seeable misuse:
Operation of the device without heat transfer liquidIncorrect connection of hosesPlacement of the device on a tabletop surface, only permitted
for MC 600
Setting an incorrect pump pressure
and MC 1200 (W)
1.4

Modifications to the device

1.5

Heat transfer liquid

Any technical modifications to the machine are prohibited. Service works may be carried out only by the LAUDA Constant Tem­perature Devices service or one of the service partners authorized by LAUDA.
The device is exclusively designed for nonflammable heat
transfer liquids in Class I according to DIN 12876-1.
Heat transfer liquids are used for the temperature control. Only
LAUDA heat transfer liquids are approved for the device. LAUDA heat transfer liquids are heat transfer liquids that have been tested and approved by the company LAUDA DR. R. WOBSER GMBH & CO. KG.
Microcool 7
Safety
In each case, the heat transfer liquids cover a specific tem-
perature range. This temperature range must match the tem­perature range of your application.
The use of heat transfer liquids can cause hazards from high or
low temperatures and fire if certain temperature thresholds are exceeded or undercut or if the container breaks and there is a reaction with the heat transfer liquid .
The heat transfer liquid safety data sheet specifies all possible hazards and appropriate safety measures for handling the liquid. The safety data sheet must therefore be consulted for the intended use of the device.
1.6

Materials

1.7

Hoses

1.8

Application area

All parts coming into contact with the heat transfer liquid are made of high quality materials suitable for the operating temperature. Stainless steel and temperature-resistant plastics are used.
Only LAUDA hoses are permitted to be used for the external hydraulics circuit. LAUDA hoses are hoses that are approved by LAUDA DR. R. WOBSER GMBH & CO. KG. When selecting suit­able hoses for the application, the permissible temperature range and the maximum permissible pressure must be particularly observed.
The device is exclusively permitted to be used in the following areas.
Commercial areaIndoor use, no outdoor installation
Ambient temperatures from 5 to 40 °C
1.9

Personnel qualification

Operating personnel
Operating personnel are employees that have been instructed by technical staff in the intended use of the device according to the operating manual.
Microcool 8
Safety
1.10
1.11
Danger

Personal protective equipment

Protective clothing
Protective clothing is required for certain activities. This protective clothing must comply with the legal requirements for personal pro­tective equipment. Protective clothing should have long sleeves. Safety footwear is additionally required.
Protective gloves
CE protective gloves are required for certain activities. These pro­tective gloves must comply with the legal requirements for personal protective equipment of the European Union.
Protective goggles
Protective goggles are required for certain activities. These protec­tive goggles must comply with the legal requirements for personal protective equipment of the European Union.

Structure of safety instructions

A safety instruction of the type "Danger" indicates an immedi-
This results in death or severe, irreversible injuries if the
ately hazardous situation.
safety instruction is disregarded.
Warning
DANGER! Type and source
Consequences in the case of non-compliance
Measure 1Measure…
A safety instruction of the type "Warning" indicates a poten-
tially hazardous situation.
This can result in death or severe, irreversible injuries if the
safety instruction is disregarded.
WARNING! Type and source
Consequences in the case of non-compliance
Measure 1Measure…
Microcool 9
Safety
Caution
Notice
A safety instruction of the type "Caution" indicates a poten-
tially hazardous situation.
This can result in minor, reversible injuries if the safety
instruction is disregarded.
CAUTION! Type and source
Consequences in the case of non-compliance
Measure 1Measure…
A"notice" warns about possible property or environmental damage.
NOTICE! Type and source
Consequences in the case of non-compliance
Measure 1Measure…
Microcool 10

Unpacking

2
Unpacking
DANGER! Transport damage
Electric shock
Inspect the device for transport damage before
commissioning.
Never put the device into operation if you have dis-
covered any transport damage.
Personnel:
1. Unpack the device.
Keep the original packaging of the device for later transport.
2. Inspect the device and the accessories immediately after
delivery for completeness and transport damage.
Operating personnel
If there is unexpected damage to the device or accessories, inform the carrier immediately so that a damage report is produced and a check of the transport damage can be made. Also inform LAUDA Constant Temperature Equipment Service immediately. Contact details can be found in
Ä
Chapter 12.3 ‘LAUDA contact’ on page 63.
Accessories included as standard
Device type Designation Quantity
MC 600, MC 1200 (W) ¾" olive with ¾" union nut 2 EOA 004
All equipment Operating manual 1 --
Catalogue
number
Microcool 11

Design and function

3
3.1
Available device types
Design and function

Device types

The type designation of the equipment is composed of the fol­lowing elements.
Element Description
MC Microcool
<number>, e.g. 600 Specification of the cooling capacity in
watts
W Device with water cooling
This specification in the device type is optional. It identifies water-cooled equip­ment.
Device type Description
MC 250 Air-cooled tabletop device with a cooling
capacity of 250 watts
MC 600 Air-cooled floor-standing device with a
cooling capacity of 600 watts. The pump pressure can be adjusted using a bypass adjustment wheel.
MC 1200 Air-cooled floor-standing device with a
cooling capacity of 1200 watts. The pump pressure can be adjusted using a bypass adjustment wheel.
MC 1200 W Water-cooled floor-standing device with a
cooling capacity of 1200 watts. The pump pressure can be adjusted using a bypass adjustment wheel.
Microcool 12
Design and function
Rear side MC 250
Fig. 2: Overview of the rear side
1 Pump connection, outlet 2 Overflow connection 3 Pump connection, return 4 Rating plate 5 Drain plug 6 RS232 interface 7 Alarm output 8 Mains cable 9 Ventilation openings
Microcool 14
Design and function
3.2

Design of the circulation chiller

Front side MC 250
Fig. 1: Overview of the front side
1 Filler nozzle with cover 2 Level indicator 3 Control panel 4 Front panel with ventilation openings 5 Four support feet
Microcool 13
Front side MC 600, MC 1200 (W)
Design and function
Fig. 3: Overview of the front side
1 Filler nozzle with cover 2 Control panel 3 Level indicator 4 Manometer 5 Front panel with ventilation openings 6 Four castors with locking brakes
Microcool 15
Design and function
Rear side MC 600, MC 1200 (W)
Fig. 4: Overview of the rear side
1 Pump connection, outlet 2 Bypass adjustment wheel 3 Pump connection, return 4 Overflow connection 5 Rating plate 6 Drain plug 7 RS232 interface 8 Alarm output 9 Mains cable 10 Ventilation openings
Microcool 16
Control panel
Design and function
Fig. 5: Control panel
1 Display 2 LEDs 3 Display buttons 4 Mains power switch
3.3
3.3.1

Controls

Mains power switch

The mains power switch can be put in the following positions:
In position [I], the device is switched on.In position [O], the device is switched off.
Microcool 17
Design and function
3.3.2

Display buttons

Fig. 6: Display buttons
1 UP arrow button 2 ENTER button 3 DOWN arrow button
Functions in the display of the device can be controlled using the display buttons.
A selection in the display can be confirmed with the ENTER
button.
The UP and DOWN arrow buttons can be used to navigate in
the display.
Microcool 18
Design and function
3.4

Function elements

3.4.1

LEDs for function display

Fig. 7: LEDs
1 Yellow LED 2 Blue refrigeration LED 3 Red error LED
Each device has three LEDs with the following functions:
3.4.2

Hydraulic circuit

Hydraulic circuit
The yellow glycol LED lights if Kryo 30 is necessary as heat
transfer liquid.
The blue refrigeration LED indicates whether the refrigeration
unit is active.
The red error LED lights in the event of device faults.
The hydraulic circuit designates the circuit through which the heat transfer liquid flows.
The circuit basically consists of the following components:
internal storage bath with heat transfer liquidpump for conveying the heat transfer liquid into the external
consumer via the pump connections
Starting with MC 600, devices are equipped with an adjustable
bypass to be able to adapt the pump pressure to the require­ments of the external consumer.
Microcool 19
Design and function
Pump
3.4.3

Manometer

The devices are equipped with a magnetically coupled pressure pump.
Further information about the technical data of the pump and the pump characteristic curve can be found
Ä
Table on page 62.
The device types with bypass have a manometer for reading the set pump pressure. The pump pressure is regulated using the bypass adjustment wheel on the rear side.
Fig. 8: Manometer
3.4.4

Level indicator

The fill level of the heat transfer liquid in the circuit can be read using the level indicator.
The top arrow indicates the maximum liquid level of the
machine.
The bottom arrow indicates the minimum liquid level of the
machine.
Fig. 9: Level indicator
1 Maximum level 2 Minimum level
3.4.5

Refrigeration unit

The refrigeration unit includes the following components:
Microcool 20
Design and function
Compressor
A hermetically sealed compressor is used in the refrigeration unit. The compressor is equipped with overload protection which trips on the compressor temperature and compressor current consumption.
Condenser
Depending on the device type, an air-cooled or water-cooled condenser is used in the refrigeration unit. In air-cooled con­densers, the condensation heat is discharged to the environ­ment. The fresh air is sucked in through the front of the device using a fan, heated and discharged on the rear of the device. In water-cooled condensers, the condensation heat is dis­charged via cooling water.
Evaporator
In the internal bath, heat is discharged using a pipe coil evapo­rator.
Technical information for the refrigeration unit can be found in
Ä
on page 61.
3.4.6
RS232 interface
Alarm output

Interfaces

Note the following:
The equipment connected to the low voltage inputs and out-
puts must have safe separation from dangerous voltages according to DIN EN 61140 such as by double or reinforced insulation according to DIN EN 60730-1 or DIN 60950-1.
Specific functions of the device such as the setpoint temperature can be controlled with the RS232 interface using a PC. Thus, custom programs for controlling the device can be developed.
Further information about the connection and configura-
Ä
tion can be found in RS232 interface’ on page 44.
Changeover contact which switches in the event of a device fault. For example, faults can be registered on a system.
Using the display, it can be set in which fault situations a signal is output via the interface.
Chapter 6.7.1 ‘Configuring
Microcool 21
Design and function
3.5

Rating plate

The rating plate information is explained in detail in the following table. Certain information is dependent on installed device options. This information is noted with an appropriate suffix.
Specification Description
Type Device type
Catalogue No. Catalogue number of the device
Serial No. Serial number of the device
Refrigerant I Refrigerant that is used in the compressor
of the device
Filling charge I Fill quantity of the refrigerant
PS high pressure I maximum permitted operating pressure
on the refrigerant high pressure side (compressor, condenser)
PS low pressure I maximum permitted operating pressure
on the refrigerant low pressure side (expansion, evaporation)
Fig. 10: Rating plate
3.6

Serial number

Voltage Device must only be connected to this
voltage and frequency
Power consumption Power consumption of the device during
operation
Protection class IP protection class of the device
Fuse Fuse used in the device
Class according to DIN 12876-1
The serial number of a LAUDA device has the following structure:
LAUDA catalogue numberYear of manufacture
The year is indicated with two digits.
Sequential number of the device in the year of manufacture.
The sequential number is a four-digit number.
This information is displayed in the format <catalogue number>­<year of manufacture>-<sequential number>.
An example for Microcool devices: LWM118-13-0130.
German standard for electrical laboratory equipment
Microcool 22

Before commissioning

4
4.1
Before commissioning

EMC classification

Approval of the equipment according to EMC classification
Countries EMC Class
Europe Class A
This classification has been made according to the EMC standard DIN EN 61326-1 (corre­sponds to VDE 0843-20-1).
USA Class A
This classification has been made according to the FCC (Federal Communications Com­mission) regulations, Section 15.
Canada Class A
This classification has been made according to the ICES-003 (Interference Causing Equipment Standards) and NMB-003 regula­tions.
Instructions for machines, Europe
Instructions for Class A digital device, USA
Instructions for Class A digital device, Canada
EMC classification of the equipment:
Class A: Operation only on mains power supplies without con-
nected residential areas.
Class B: Operation on mains power supplies with connected
residential areas.
In the case of unfavourable mains conditions, disruptive voltage fluctuations can occur.
"This equipment has been tested and found to comply with the limits for Class A digital device, pursuant to Part 15 of the FCC (Federal Communication Commission) Rules. These limits are designed to provide reasonable protection against harmful interfer­ence when the equipment is operated in a commercial environ­ment. This equipment generates, uses, and can radiate radio fre­quency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense."
“This Class A digital apparatus complies with Canadian ICES-003” (ICES = Interference Causing Equipment Standards).
« Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada ».
Microcool 23
Before commissioning
4.2

Device Placement

Very specific placement conditions are applicable for the equip­ment. These placement conditions are specified in the technical data of the device for the most part.
Further information about the technical data can be found in
Additional placement conditions are described below.
Toxic vapours can be produced depending on the heat transfer
liquid used and type of operation. Ensure sufficient extraction of the vapours.
Observe the requirements of the device for electromagnetic
compatibility (EMC).
Do not cover the ventilation openings.
Further information about EMC requirements can be found in
Ä
Chapter 11.1 ‘General data’ on page 60.
Ä
Chapter 4.1 ‘EMC classification’ on page 23.
WARNING! Rolling away, falling over of the device
Impact, crushing
Do not tilt the device.Place the device on a level, non-slip surface with
sufficient load bearing capacity.
Engage the castor brake when setting up the
device.
Do not place any heavy parts on the device.
1. Place the device at a suitable location in the room.
Place tabletop devices on a suitable table. Support the
device for this by reaching under the device.
Place floor-standing devices on a suitable base.
Floor-standing devices can be moved. Release the locking brakes of the castors for this by pressing the [Off] lever downwards.
Several devices can be positioned next to each other.
2. Lock the castors of the device for floor-standing devices.
Press the [On] lever downwards to lock.
Microcool 24
Before commissioning
4.3

External consumer

4.3.1

Hoses

CAUTION! Discharge of heat transfer liquid during operation caused by use of unsuitable hoses
Frostbite
Use hoses with temperature resistance that is
appropriate for the operating temperature range of the device.
CAUTION! Contact with cold hoses
Frostbite
Use insulated hoses for temperatures below 0 °C.
The hoses specified below can be used for all heat transfer liquids that are approved for the devices.
Approved hoses, adapters and hose clamps
Hoses, not insulated
Type Olive Application area
EPDM hose 10 mm
EPDM hose
Rubber hose with
fabric reinforcement
Rubber hose with
fabric reinforcement
½"
(13 mm)
½"
(13 mm)
¾"
(19 mm)
Further information about the pump connections of the individual devices can be found in ‘Hydraulic circuit’ on page 62.
Devices with max-
imum pump pressure
of < 1 bar
Devices with max-
imum pump pressure
of < 1 bar
no restrictions
no restrictions
Ä
Chapter 11.3
Internal
Ø in mm
9 11 -35 ... 90 RKJ 111
12 14 -35 ... 90 RKJ 112
13 (½")
19 (¾")
External
diameter
in mm
19 -40 ... 100 RKJ 031
27 -40 ... 100 RKJ 032
Tem­perature range in
°C
Cata-
logue
number
Microcool 25
Before commissioning
Hoses, insulated at the factory
Type
Pump connec-
tions
Application area
Internal Ø
in mm
External diam-
eter in mm
Tem-
perature
range in
°C
Catalogue
number
EPDM
hose, insu-
lated
Insulated hoses for subsequent insulation, length 1 m
Insulation catalogue
number
RKJ 058 105 19 54 RKJ 112
RKJ 024 125 16 36 RKJ 112
RKJ 009 105 23 43 RKJ 031
RKJ 013 125 29 50 RKJ 032
Adapters, suitable for MC 600 and MC 1200 (W)
Designation Description Catalogue number
Olive 13 mm,
M16 x 1
Max. temperature in
°C
Olive ¾" union nut, ½ " olive LWZ 016
Devices with
maximum pump
pressure of
< 1 bar
Internal Ø in mm
12 23 -35 ... 90 LZS 021
External diameter in
mm
Suitable for hose
Olive ¾" union nut, 10 mm olive LWZ 040
Hose clamps
Stainless steel 10 ... 16 EZS 012
Stainless steel 12 ... 22 EZS 013
Stainless steel 20 ... 32 EZS 015
Material Ø from ... to in mm Catalogue number
Microcool 26
Before commissioning
4.3.2

Connecting external consumer

Note the following:
Temperature control hoses: Always use the largest possible
Secure the temperature control hoses with hose clamps.If the external consumer is at a higher level than the device,
In the event of hose rupture, cold liquid can escape and
CAUTION! Discharge of heat transfer liquid during operation caused by open consumer
Electric shock, frostbite
Only use closed consumers.
CAUTION! Bursting of the external hydraulic circuit due to overpressure
Impact, cutting, frostbite
Lay hoses so that they do not kink.
diameters and shortest possible hose lengths in the external liquid circuit.
If the temperature control hose diameter is too small, a tem­perature drop between device and external consumer occurs due to flow rate too low. In this case, increase or lower the tem­perature accordingly.
emptying of the external volume can occur if the pump is stopped and there is ingress of air in the external liquid circuit even for closed circuits. In this case, you risk device overflow.
become a danger for persons and material.
4.4

Cooling water

4.4.1

Cooling water requirements

This section is relevant for the following:
For water-cooled devices
Microcool 27
Before commissioning
General requirements
There are specific requirements for the cooling water concerning its purity. In accordance with the cooling water requirements, a suitable process for treatment and maintenance of the water must be used. The condenser and the complete cooling water circuit can be clogged, damaged and leak due to unsuitable cooling water. Extensive consequential damage to the complete refrigerant circuit can occur. The cooling water quality is dependent on the local con­ditions.
Free chlorine, e.g. from disinfectants and water containing
chloride results in pitting corrosion in the cooling water circuit.
Distilled, deionised or demineralised water is not suitable due
to its corrosive properties and results in corrosion in the cooling water circuit.
Seawater is not suitable due to its corrosive properties and
results in corrosion in the cooling water circuit.
Water containing iron and iron particles in the water result in
rust formation in the cooling water circuit.
Hard water is not suitable for cooling due to the high lime con-
tent and results in calcification in the cooling water circuit.
Cooling water with suspended matter is not suitable.Untreated, not purified water, e.g. river or cooling tower water
is not suitable due to its microbiological content (bacteria) which can settle in the cooling water circuit.
Suitable cooling water quality
Data Value Unit
pH value 7.5 – 9.0
Sulphates [SO4 2-]
Hydrogen carbonate [HCO
-
] / Sul-
3
< 70 mg/l
> 1.0
phates [SO4 2-]
Water hardness (alkaline earth ions
0.71 - 1.52 mmol/l
content)
Hydrogen carbonate [HCO
-
]
3
70 – 300 mg/l
Conductivity 10 - 500 μs/cm
Chlorides (Cl-)
Sulphite (SO3 2-)
< 50 mg/l
< 1 mg/l
Free chlorine gas (Cl2) < 1 mg/l
Nitrates (NO
-
)
3
< 100 mg/l
Ammonia (NH3) < 2 mg/l
Iron (Fe), dissolved < 0.2 mg/l
Manganese (Mn), dissolved < 0.1 mg/l
Aluminium (Al), dissolved < 0.2 mg/l
Free, aggressive carbonic acid (CO2) < 5 mg/l
Microcool 28
Before commissioning
Data Value Unit
Hydrogen sulphide (H2S) < 0.05 mg/l
Algae growth not permitted
Suspended matter not permitted
4.4.2

Connecting cooling water

This section is relevant for the following:
For water-cooled devices
Specification Value
Maximum cooling water
6 bar
pressure
Differential pressure
1 ... 6 bar
cooling water rp
approx. 15 °C recommended
Cooling water tem­perature
10 ... 30 °C permissible (with perform­ance limitations)
Note the following:
Fix the cooling water hoses in place with hose clamps.Fix the supply hose of the water cooling in place in the sink
area to prevent uncontrolled sliding, also in the event of pres­sure surges.
Fix the supply hose of the water cooling in place in the sink area so that spraying out of hot cooling water is not possible.
Prevent kinking or squeezing of the hoses.We recommend using a leak detector with water shut-off to
prevent damage due to cooling water system leaks.
Ensure that the cooling water meets the required criteria.In the case of leaks in the condenser, there is the danger that
refrigerator oil and refrigerant from the refrigerant circuit of the device can get into the cooling water. Comply with all appli­cable legal provisions and the requirements of the water supply companies at the operating site.
Microcool 29
Before commissioning
4.5

RS232 interface

4.5.1

Cable and interface test RS232

Computer Thermostat
Signal 9-pin Sub-D female con-
nector
with hard­ware hand­shake
RxD 2 2 3 3 2 2 TxD
TxD 3 3 2 2 3 3 RxD
DTR 4 20 4 DSR
Signal Ground
DSR 6 6 6 DTR
RTS 7 4 7 CTS
CTS 8 5 8 RTS
5 5 7 7 5 5 Signal
without hardware handshake
25-pin Sub-D female connector
with hard­ware hand­shake
Note the following:
without hardware handshake
9-pin Sub-D female con­nector
with hard­ware hand­shake
without hardware handshake
Signal
Ground
4.6

Alarm output 12N

Available functions
With hardware handshake: Use a straight-through and not a
null modem cable for connecting a thermostat to the PC. The RS232 interface can be connected directly to the PC using a straight-through cable.
Without hardware handshake: Set the corresponding operating
mode on the PC. Use shielded connection cables. Connect shield to connector case. The cables must be galvanically iso­lated from the rest of the electronics. Do not connect unas­signed pins.
The RS232 interface can be easily checked on a connected
PC with the Microsoft Windows operating system. Using the HyperTerminal program for Windows®
Starting with Windows Vista, HyperTerminal is no longer an integral part of Windows. However, it is possible to purchase and download the program. Alternatively, there are also free Open Source terminal programs such as putty with a similar range of functions.
Function Description
95/98/NT/XP.
Alarm output --
Alarm and standby for on-site return flow protection
Microcool 30
Before commissioning
View of flange connector (front) or solder side coupling socketMax. 30 V DC; 1 A
Fig. 11: Flange connector (front) in idle state
1 Normally open contact 2 Centre 3 Normally closed contact
Idle state
The device is in idle state when it is switched off and in the
case of failure.
Pins 1 and 2 are open.Pins 3 and 2 are closed.
GO state
The device is in GO state immediately after switching on and
during normal operation without faults.
Pins 1 and 2 are closed.Pins 3 and 2 are open.
Note the following:
The equipment connected to the low voltage inputs and out-
puts must have safe separation from dangerous voltages according to DIN EN 61140 such as by double or reinforced insulation according to DIN EN 60730-1 or DIN 60950-1.
Only use shielded connection cables; connect the shield to the
connector case. Cover unused plug connections with protective caps.
Microcool 31

Commissioning

5
5.1
Approved heat transfer liquids
Commissioning

LAUDA heat transfer liquids

LAUDA
designa-
tion
Chemical
designation
perature
range in °C
Tem-
Note the following:
The heat transfer liquids each cover a recommended tem-
perature range and must be suitable for the temperature range of your application.
At the lower limit of the temperature range, the heat transfer
liquid becomes more viscous and influences temperature con­stancy, pump power and cooling capacity. The formation of vapours and odours increases in the upper range. Therefore, only use all of the temperature range if required. Particularly with Aqua 90 (water), ice forms which can result in destruction of the device.
Never use contaminated or degenerated heat transfer liquids.You can request the safety data sheets of the heat transfer
liquid at any time if required.
Viscosity
(kin) in mm²/s
(at 20 °C)
Viscosity
(kin) in mm²/s
for
temperature
Container size
Catalogue number
5 l 10 l 20 l
Mono eth-
Kryo 30
Aqua 90
Heat transfer liquid water
ylene
glycol /
water
decalcified
water
-30 ... 90 4 50 at -25 °C LZB 109 LZB 209 LZB 309
5 ... 90 1 --- LZB 120 LZB 220 LZB 320
Note the following for Kryo 30:
The water content reduces during long operating with higher
temperatures and the mixture becomes flammable (flame point 128 °C). Check the mixture ratio using a hydrometer.
The alkaline earth ions content (hardness) of the water must be
between 0.71 mmol/l
8.0 °dH). Harder water results in lime deposits in the device.
The pH value of the water must be between 6.0 and 8.5.Distilled, deionised, demineralised (DM) water or seawater
must not be used due to the corrosive properties. Ultra-pure water and distillates are suitable as medium after addition of
0.1 g soda (Na2CO3, sodium carbonate) per litre of water.
Any chlorine content in the water must be strictly avoided. Do
not add any chlorine to the water. Chlorine is contained, for example, in cleaning agents and disinfectants.
and 1.42 mmol/l (equivalent to 4.0 and
Microcool 32
Commissioning
The water must be free of impurities. Water containing iron is
unsuitable due to rust formation and untreated river water is unsuitable due to algae formation.
The addition of ammonia is not permitted.
5.2

Filling device with heat transfer liquid

Personnel:
Protective equipment:
Operating personnel
Protective goggles
Protective clothing
Protective gloves
DANGER! Use of incorrect heat transfer liquid
Fire
Select a heat transfer liquid with a temperature
range 20 K above the temperature range of the application.
WARNING! Overflow of heat transfer liquid
Electric shock
Ensure that the device is not overfilled. Note the
level indicator and the thermal volume expansion of the heat transfer liquid.
WARNING! Spraying of heat transfer liquid
Electric shock
Avoid spraying heat transfer liquid. Use a funnel for
filling.
1. Close the drain plug. For this, turn the plug clockwise as far
as the stop.
2. Attach a suitable hose to the overflow connection of the
device.
The permitted hose diameter for the overflow must be complied with. Further information about the suitable hose diameter can be found in the tech­nical data Ä Chapter 11.3 ‘Hydraulic circuit’ on page 62.
Microcool 33
Commissioning
3. Insert this hose into a suitable canister to collect overflowing
heat transfer liquid.
Running dry of the consumer can also occur in a closed temperature control circuit with consumer at a higher level in the case of stopped pump and ingress of air into the temperature control circuit (for example, a not completely closed or defective bleed valve). Match the size of the overflow con­tainer to this if possible.
4. Carefully pull up the cover of the filler nozzle; do not turn.
5. Fill the heat transfer liquid into the filler nozzle carefully. Mon-
itor the level indicator. Fill the device up to the maximum fill level.
If necessary, use a funnel for the filling.
The level indicator must not be above the max­imum fill level.
5.3

Establishing power supply

6. Press the cover carefully into the filler nozzle.
Personnel:
NOTICE! Use of unauthorised mains voltage or mains fre­quency
Device damage
Compare the rating plate with available mains
voltage and mains frequency.
Also note the following:
The mains plug of the device provides a mains power discon-
nection component. The mains plug must be easily recognis­able and easily accessible.
Only connect the device to an earthed (PE) power socket.
Operating personnel
Microcool 34
Commissioning
5.4

Switching on the device

WARNING! Overheating of the pump
Device damage
Never operate device without heat transfer liquid.
Personnel:
1. Switch on the device using the mains power switch.
A signal tone sounds. The actual temperature is shown
on the display. The pump is started. The refrigeration unit is started after approx. 2 minutes. The blue LED lights if the refrigeration unit is active.
2. Depending on the size of the consumer, heat transfer liquid
must be refilled if necessary. Monitor the level indicator for this.
Further information about refilling heat transfer liquid can be found in heat transfer liquid’ on page 35.
Operating personnel
Ä
Chapter 5.5 ‘Refilling
5.5

Refilling heat transfer liquid

Personnel:
Protective equipment:
DANGER! Use of incorrect heat transfer liquid
Fire
Select a heat transfer liquid with a temperature
range 20 K above the temperature range of the application.
Operating personnel
Protective goggles
Protective clothing
Protective gloves
Microcool 35
Commissioning
WARNING! Overflow of heat transfer liquid
Electric shock
Ensure that the device is not overfilled. Note the
level indicator and the thermal volume expansion of the heat transfer liquid.
1. Check whether the drain plug is closed.
The drain plug is closed if it is turned clockwise as far as the stop.
2. Carefully pull up the cover of the filler nozzle; do not turn.
3. Fill the heat transfer liquid into the filler nozzle carefully. Mon-
itor the level indicator.
If necessary, use a funnel for the filling.
5.6

Setting pump pressure

The level indicator must not be above the max­imum fill level.
The level indicator must be above the minimum level. Otherwise a warning is output and the device is switched off with an alarm after approx. 5 minutes.
4. Press the cover carefully into the filler nozzle.
For devices with bypass (starting from MC 600), the pump pressure can be set using a control valve on the rear side of the device. Individual setting of the pump pressure is possible with this when using pressure-sensitive external consumers.
Microcool 36
Commissioning
Personnel:
CAUTION! Bursting of the external consumer
Scalding, impact, cutting
A bypass regulator is provided to set the pump
pressure (starting from MC 600).
For consumers with a maximum permissible oper-
ating pressure below the maximum pressure of the pump, use a safety valve for protection. This safety valve must be installed in the outlet of the device.
1. To reduce the pump pressure, turn the bypass adjustment
wheel anticlockwise until the maximum permitted pressure for the external consumer is reached.
Monitor the display on the manometer for this.
2. To increase the pump pressure, turn the bypass adjustment
wheel clockwise until the required pressure for the external consumer is reached.
Operating personnel
Microcool 37

Operation

6
6.1
Operation

Switching on the device

WARNING! Overheating of the pump
Device damage
Never operate device without heat transfer liquid.
Personnel:
1. Switch on the device using the mains power switch.
A signal tone sounds. The actual temperature is shown
on the display. The pump is started. The refrigeration unit is started after approx. 2 minutes. The blue LED lights if the refrigeration unit is active.
2. Depending on the size of the consumer, heat transfer liquid
must be refilled if necessary. Monitor the level indicator for this.
Further information about refilling heat transfer liquid can be found in heat transfer liquid’ on page 35.
Operating personnel
Ä
Chapter 5.5 ‘Refilling
6.2

Default display and menu items

1. Press the ENTER button to reach the menu items from the
default display of the actual temperature.
If no button has been pressed for longer than 4 seconds, you exit from the menu item or input window.
2. Scroll from menu item to menu item using the arrow buttons.
3. Press the ENTER button at the selected menu item.
The display flashes.
4. The value or the setting can be changed using the arrow but-
tons.
5. The changed value or setting is applied immediately by
pressing the ENTER button.
If no button has been pressed for longer than 4 seconds, changed values or settings are applied automatically and you exit from the menu item or input window.
Microcool 38
Operation
Fig. 12: Menu
Microcool 39
Operation
6.3

Screen displays

Default display
Fig. 13: Default display
Menu
Editing display
6.4

Specifying the setpoint temperature

The default display is the indication shown in the screen if no other operations such as configuring settings are being performed. The actual temperature of the machine is shown in the default display.
The machine menu with possible settings can be invoked using the ENTER button.
The display flashes when a menu item in the screen has been selected. The setting can now be made. The value entered is applied when the setting is confirmed.
Further information about the menu structure and the
Ä
menu navigation can be found in
display and menu items’ on page 38.
Chapter 6.2 ‘Default
Relationship between temperature setpoint and temperature limit values
You specify a setpoint for the temperature control. This value specifies to which temperature the heat transfer liquid will be cooled. The upper and lower temperature limit values of the device have been set to the default values perature limits define the temperature range of your application, i.e. in which range any temperature control can take place. A warning is output by the device if the temperature is outside the limits. This range is necessary so that no unnecessary warnings are output during transient conditions of the temperature regulation. The default values can be limited subsequently depending on the heat transfer liquid.
For operation of the device with Aqua 90, the temperature setpoint must not be set smaller than 5 °C. Also use the lower temperature
Ä
limit value Lo set this to 3 °C so that a warning is output for lower temperatures.
The yellow LED on the device lights if any temperature setpoint or actual temperature is less than 5 °C. It warns about incorrect use of the heat transfer liquid and consequential damage to the device.
‘Lower temperature limit value’ on page 42 and
If the device is operated with liquid temperatures below 5 °C, Kryo 30 (glycol / water) must be used in the device as heat transfer liquid.
45.0 °C and 5.0 °C. The tem-
Microcool 40
Operation
Personnel:
1. Select the menu item for specifying the temperature setpoint.
2. Specify the setpoint.
Fig. 14: Setpoint input
3. Confirm with the ENTER button.
6.5

Restricting temperature limit values

The range of the temperature limit values must be restricted for safety reasons. These two values depend on the heat transfer liquid used. The default settings of device cannot be changed.
Practical temperature limit values are:
Aqua 90 - Set the range to the values 42 °C and 3 .
Kryo 30 (water / glycol)
Operating personnel
If the entered setpoint is outside the specified tem­perature limit values, the value cannot be adopted. Editing mode is active. An audible signal is also output. You can input the setpoint again.
45.0 °C and
- Set the range to the values 42 °C and
-12 .
5.0 °C stored in the
Upper temperature limit value
Fig. 15: Upper limit value
By adjusting the temperature limit values, the configu­rable setpoint range is automatically limited to as 2 °C below the upper temperature limit and 2 °C above the lower temperature limit.
Personnel:
1. Select the menu item for the upper temperature limit value.
2. Confirm with the ENTER button.
3. Specify the upper limit value.
The maximum value of the upper limit is 45 °C.
4. Confirm with the ENTER button.
Operating personnel
Microcool 41
Operation
Lower temperature limit value
Personnel:
1. Select the menu item for the lower temperature limit value.
2. Confirm with the ENTER button.
3. Specify the lower limit value.
Operating personnel
Fig. 16: Lower limit
6.6

Configuring timer

Special features of the timer
Functions for automatic switching off - Auto-Shut-Down
The minimum value of the lower limit is 5 °C when using Aqua 90 and -15 °C when using Kryo 30.
4. Confirm with the ENTER button.
The integrated timer can be used for switching the device on and off automatically. The timer can be viewed and configured during normal operation of the device.
The timer is configured using a number of hours and minutes in
the format hh.mm. The first two digits represent the number of hours and the last two are the minutes. The timer can be set to a maximum of 99 hours and 59 minutes.
The timer is only active while the machine is switched on. If the
machine is switched off using the mains power switch during the running time of the timer, the timer is reset.
If Auto-Shut-Down of the timer is active, the current actual tem-
perature on the display is shown with a flashing decimal point.
If Auto-Shut-Down is invoked using the corresponding menu
item, the remaining time, for example 05.30 , is shown flashing. If Auto-Shut-Down is deactivated, 00.00 is shown flashing.
Once the time for Auto-Shut-Down has elapsed, the device is
not switched off completely but switched to standby. Standby means all components of the device are switched off and only the display of the device is still supplied with power.
Functions for automatic switching on - Auto-Start
If Auto-Start of the timer is configured, the device switches to
standby and Auto-Start is active immediately. If any Auto-Shut­Down is active, the Auto-Start is not active until after comple­tion of the Auto-Shut-Down.
If Auto-Start is active, the remaining time until the automatic
start is shown on the display. An audible signal is also output during the complete last minute before starting the device.
Microcool 42
Configuring Auto-Shut-Down
Fig. 17: Auto-Shut-Down
Fig. 18: Standby
Operation
1. Select the menu item for specifying the Auto-Shut-Down.
2. Confirm with the ENTER button.
3. Specify the time until the device should be switched to
standby.
Wait for approx. 4 seconds if you would not like to apply the specified value. The screen automati­cally returns to the default display.
4. Confirm with the ENTER button.
The value must be confirmed within 4 seconds after the last input. Otherwise the screen returns to the default display.
The device will be switched to standby after the time
entered. This is shown on the display as follows.
5. Auto-Start can now be configured before the expiry of Auto-
Shut-Down to switch the device on again afterwards after a specified time. Otherwise you can start the device manually by pressing the ENTER button.
Configuring Auto-Start
Fig. 19: Auto-Start
CAUTION! Automatic device start using the auto-start timer
Frostbite, risk of injury, device damage
Before using the auto-start timer, ensure that all
preparations for the intended use have been made.
1. Select the menu item for specifying the Auto-Start.
2. Confirm with the ENTER button.
3. Specify the time until the device should be switched on
again.
If no Auto-Shut-Down is configured for the device, the device is switched directly into standby with the confirmation.
Wait for approx. 4 seconds if you would not like to apply the specified value. The screen automati­cally returns to the default display.
Microcool 43
Operation
Displaying and editing remaining time
4. Confirm with the ENTER button.
The value must be confirmed within 4 seconds after the last input. Otherwise the screen returns to the default display.
1. Select the menu item for the Auto-Shut-Down or Auto-Start.
2. Confirm with the ENTER button.
The remaining time is displayed.
3. You have the following options:
Wait approx. 4 seconds if you only want to display the
remaining time. The default display is shown again.
To edit the remaining time, set the time accordingly. Con-
firm with the ENTER button.
Reset
Restart manually
6.7

RS232 interface

6.7.1

Configuring RS232 interface

1. Select the menu item for the Auto-Shut-Down or Auto-Start.
2. Input 00.00.
3. Confirm with the ENTER button.
The value must be confirmed within 4 seconds after the last input. Otherwise the screen returns to the default display.
If the device has been switched to standby using Auto-Shut-Down and no Auto-Start is configured, the device can be switched on again manually.
1. Press the ENTER button to switch the device on again.
This function is only available if no Auto-Start is active.
The baud rate for the RS232 interface can be configured using the display.
Microcool 44
Operation
Fig. 20: RS232 interface
6.7.2

Protocol

RS232 protocol
Personnel:
Operating personnel
1. Select the menu item for configuration of the RS232 inter-
face.
2. Select the appropriate baud rate.
The following baud rates can be selected:
2.4 4.8
9.6
19.2
The hundreds and thousands digits are not visible on the display.
3. Confirm with the ENTER button.
Your input is applied automatically after approx. 4 seconds.
Note the following:
The interface operates with 1 stop bit, no parity bit and 8 data
bits.
Selectable transmission speed: 2400, 4800, 9600 (factory set-
ting) or 19200 baud.
The RS232 interface can be operated with or without hardware
handshake (RTS/CTS).
The command from the computer must be terminated with CR,
CRLF or LFCR. CR = Carriage Return (hex: 0D); LF = Line Feed (hex: 0A)
The response from the thermostat is always terminated with
CRLF.
Example for setpoint transfer of 30.5 °C to the thermostat.
Computer Thermostat
"OUT_SP_00_30.5"CRLF
"OK"CRLF
Microcool 45
Operation
6.7.3

Write commands

The write commands are data specifications to the thermostat.
Command Meaning
OUT_SP_00_XXX.XX Setpoint transfer with max. 3 digits before the dec-
imal point and max. 2 digits afterwards
OUT_SP_04_XXX [Hi] Upper limit of flow temperature
OUT_SP_05_XXX [Lo] Lower limit of flow temperature
START Switches on device (from standby)
STOP Switches device to standby (pump, refrigeration unit
off).
Note the following:
For "_", " " (space character) is also permitted.Response from the thermostat “OK” or “ERR_X” in the case of
an error.
Permitted data formats
-XXX.XX -XXX.X -XXX. -XXX XXX.XX XXX.X XXX. XXX
-XX.XX -XX.X -XX. -XX XX.XX XX.X XX. XX
-X.XX -X.X -X. -X X.XX X.X X. X
-.XX -.X .XX .X
6.7.4

Read commands

The following read commands are data requests to the thermostat.
Command Meaning
IN_PV_00 Query of the bath temperature (outlet temperature)
IN_SP_00 Query of the temperature setpoint
IN_SP_04 Query of the outlet temperature limit Hi
IN_SP_05 Query of the outlet temperature limit Lo
TYPE Query of the device type (response = "MC").
VERSION Query of the software version number
Microcool 46
Operation
Command Meaning
STATUS Query of the device status, 0 = OK, -1 = fault
STAT Query for the fault diagnosis, response: XXXXXXX;
X = 0 no fault, X = 1 fault
Character 1 = error
Character 2 = not assigned
Character 3 = not assigned
Character 4 = not assigned
Character 5 = low level
Character 6 = not assigned
Character 7 = not assigned
Note the following:
For "_", " " (space character) is also permitted.Unless otherwise specified for the command, the reply is
always in fixed decimal format "XXX.XX" or "-XXX.XX" for neg­ative values or "ERR_X".
6.7.5
6.8

Error messages

Configuring alarm output

The error messages of the modules are described in the following.
Error Description
ERR_2 Incorrect input (e.g. buffer over-
flow)
ERR_3 Incorrect command
ERR_5 Syntax error in the value
ERR_6 Impermissible value
ERR_32 The upper temperature limit is
less than or equal to the lower temperature limit.
In the case of an alarm or error, an electrical signal is output via the alarm output of the device as default. However, you can also configure that a signal will also be output in the case of a warning.
Microcool 47
Operation
Fig. 21: Alarm output
Fig. 22: Option error and alarm
Fig. 23: Option with additional warning
Personnel:
1. Select the menu item for configuring the alarm output.
2. Select the following option for the output of an electrical
signal for alarms and errors.
3. Select the following option for the additional output of an
electrical signal for warnings.
Wait for approx. 4 seconds if you would not like to apply the specified value. The screen automati­cally returns to the default display.
4. Confirm with the ENTER button.
The value must be confirmed within 4 seconds after the last input. Otherwise the screen returns to the default display.
Operating personnel
6.9

Inputting offset of the temperature sensor

If any temperature difference is discovered when checking the device with a reference thermometer, the offset (additive part of the characteristic curve) of the internal measurement chain can be adjusted using the CAL menu item.
A calibrated reference thermometer (e.g. from the LAUDA DigiCal series) with the required degree of accuracy is required. Otherwise the factory calibration should not be changed.
The reference thermometer must be installed in the flow of the device in accordance with the specifications in the calibration certif­icate.
Personnel:
1. Select the menu item CAL.
2. Enter the temperature value read from the reference ther-
mometer at the device.
Fig. 24: Calibrating temperature sensor
The calibration overwrites the factory calibration.
Operating personnel
Microcool 48
Operation
3. Keep the ENTER button pressed for approx. 3 seconds after-
wards.
The display shows donE . The new value has been
applied.
6.10
Fig. 25: Factory settings

Restoring the factory settings

Execute this menu item if you would like to restore the factory set­tings stored in the device.
The range of the temperature limit values is reset to
5 °C.
The timers are reset to 00.00 .The signal output at the alarm output is reset to alarms and
faults .
The baud rate is reset to 9600 baud .
Personnel:
1. Select the menu item (dEF) for restoring the factory settings.
2. Confirm with the ENTER button.
3. Keep the ENTER button pressed for approx. 3 seconds after-
wards.
The display shows donE . The factory settings have been
restored.
Operating personnel
45 °C and
Microcool 49

Maintenance

7
7.1
Maintenance

General safety instructions

DANGER! Contact with live or moving parts
Electric shock, impact, cutting, crushing
The device must be disconnected from the mains
power supply before any maintenance work.
CAUTION! Contact with hot / cold device parts, accessories and heat transfer liquid.
Burns, scalding, frostbite
Ensure device parts, accessories and heat transfer
liquid are at room temperature before touching them.
NOTICE! Contact with rotating part
7.2

Maintenance intervals

Severed parts of the body
Repairs must only be performed by specialist per-
sonnel.
Also note the following:
Before all maintenance work, you should ensure that decon-
tamination of the device has been performed if it came into contact with hazardous materials.
The maintenance intervals described in the following table must be complied with. The following maintenance work is mandatory before every longer unsupervised operation.
Microcool 50
Maintenance
Interval Maintenance work
daily Inspection of the drain plug by visual inspection from the outside
monthly Inspection of the external hoses for material fatigue
Cleaning of the condenser
(only air-cooled devices)
Cleaning of the water filter
(only for water-cooled devices)
quarterly Decalcification of the cooling water circuit (a shorter interval must be selected depending
on water hardness and operating time)
(only for water-cooled devices)
half-yearly Inspection of the heat transfer liquid
7.3

Cleaning the device

7.4

Cleaning air-cooled condenser

Personnel:
WARNING! Ingress of cleaning agents in the device
Electric shock
Use a moist cloth for cleaning.
Also note the following:
Only clean the control panel with water and detergent. Do not
use acetone or solvents. The consequence would be perma­nent damage of the plastic surfaces.
Operating personnel
Personnel:
1. Switch off the device.
2. Remove the front cover by holding underneath with both
hands and pulling the grating to the front. Remove the front cover slowly and carefully to prevent damage.
3. Brush off or vacuum the condenser.
4. Replace the front cover carefully.
Microcool 51
Operating personnel
Maintenance
7.5

Cleaning the water filter

Fig. 26: Removing water filter
7.6

Decalcification of the cooling water circuit

Personnel:
1. Switch off the device using the mains power switch.
2. Undo the union nut at the supply of the water cooling.
3. Remove the cooling water hose with the hose nozzle from
the threaded connection.
4. Remove the water filter from the threaded connection care-
fully.
5. Clean the water filter and then put it back into the threaded
connection.
6. Press the cooling water hose with the hose nozzle back onto
the threaded connection of the supply. Carefully tighten the water hose using the union nut at the threaded connection.
Personnel:
Operating personnel
If necessary, use tweezers to remove / insert the water filter.
Operating personnel
Fig. 27: Decalcification
1. Switch off the device and prepare the decalcification process
accordingly.
The descaling agent should be fed to the water cooling using a pump or a funnel through the supply hose. The descaling agent return flow should be via flow hose of the water cooling into a container with sufficient capacity (at least 10 litres).
LAUDA descaling agent (catalogue number LZB 126, 5 kg packaging) is required for decalcifica­tion. Read the safety instructions and the instruc­tions for use on the packaging for handling the chemical.
2. Clean the water filter of the device. The water filter is in the
supply of the water cooling.
Further information for cleaning the water filter can be found in filter’ on page 52.
3. Fill the supply hose of the water cooling with LAUDA desca-
ling agent (pump or funnel). Continuously refill or pump the descaling agent. Continue this process until the foaming reaction goes down. This is usually the case after approx. 20 to 30 minutes.
Ä
Chapter 7.5 ‘Cleaning the water
Microcool 52
Maintenance
4. Drain the condenser afterwards.
Further information about draining the condenser can be found in .
5. Reconnect the device to the water supply and rinse it thor-
oughly.
Allow at least 10 litres of water to flow through the device.
7.7

Checking the heat transfer liquid

Soiled or degenerated heat transfer liquid must be replaced. Fur­ther use of the heat transfer liquid is only permitted with appro­priate test results.
The heat transfer liquid must be checked according to DIN 51529.
Microcool 53

Faults

8
8.1
Procedure in the event of alarms
Procedure in the event of warnings
Procedure in the event of errors
Faults

Alarms, errors and warnings

Any alarms, error signals and warnings triggered on the device are shown on the display as 7-segment text.
Alarms can be cancelled using the ENTER button after rectification of the cause of the fault.
A list of alarms can be found in on page 55.
Warnings can be cancelled using the ENTER button after rectifica­tion of the cause of the fault.
A list of warnings can be found in view’ on page 55.
A two-tone signal is output if any error occurs. The red LED on the device also lights.
In the case of an error, switch off the device at the mains power switch. If the error occurs again after restarting the device, note the error code and contact LAUDA Service Constant Temperature Equipment. Contact details can be found in ‘LAUDA contact’ on page 63.
Ä
Chapter 8.2 ‘Alarms overview’
Ä
Chapter 8.3 ‘Warnings over-
Ä
Chapter 12.3
Errors are symbolised with an E and a sequential three­digit number.
Microcool 54
Faults
8.2

Alarms overview

Output on the display Description
Alarms are relevant for safety. The components of the device such as the pump switch off. A two-tone signal is output by the device. The red LED on the device also lights.
In the event of a Low Level alarm, the fill level of the heat transfer liquid is below the minimum limit. The fault which caused this low fill level must be rectified to cancel the alarm. Heat transfer liquid must also be refilled.
Warnings are output before the alarm is emitted. The alarm is output after approx. 5 minutes.
The pump is blocked for any pump alarm. This can be caused by unacceptably high viscosity of the heat transfer liquid or by foreign bodies in the circuit.
The temperature of the electronics is higher than 75 °C.
8.3

Warnings overview

Indication on the display Description
Warnings are not relevant for safety. The device continues running. A continuous tone is output for a short time by the device. Warn­ings are output periodically. You are therefore reminded in the event of an existing fault.
In the event of a Low Level warning, the fill level of the heat transfer liquid is below the minimum limit.
The fault which caused this low fill level must be rectified to cancel the warning. Heat transfer liquid must also be refilled.
If this warning is ignored, a Low Level alarm will be output after approx. 5 minutes and the components of the device such as the pump will be switched off.
The upper temperature limit has been exceeded for this warning.
The device fault must be rectified to remove this warning.
The lower temperature limit has been undercut for this warning.
The device fault must be rectified to remove this warning.
Microcool 55
Faults
Indication on the display Description
NTC sensor break
NTC short circuit
Microcool 56

Decommissioning

9
9.1
Decommissioning

Draining the device

Personnel:
WARNING! Contact with cold heat transfer liquid
Frostbite
Bring the heat transfer liquid to room temperature
before draining.
Also note the following:
Observe the regulations for disposal of the used heat transfer
liquid.
1. Switch off the device.
2. Let the device and the heat transfer liquid cool down or heat
up to room temperature.
3. Position a container with appropriate capacity directly under
the drain plug.
Operating personnel
The heat transfer liquid discharges directly from the device when the drain plug is opened.
4. Open the drain plug. Turn anticlockwise for this.
9.2

Draining condenser (only water-cooled devices)

Personnel:
1. Bring the device to room temperature if required and switch
off the device.
2. Unscrew the water hose from the supply nozzle of the
device.
3. Remove the water filter from the threaded connection. Clean
the water filter and then put it back into the threaded connec­tion.
Further information for cleaning the water filter can be found in filter’ on page 52.
4. Unscrew the water hose from the outlet nozzle of the device.
5. Place a bucket under the outlet nozzle to collect the dis-
charging water.
Operating personnel
Ä
Chapter 7.5 ‘Cleaning the water
Microcool 57
Decommissioning
6. Without switching on the device, blow compressed air
through the supply nozzle into the device. Continue blowing compressed air through the device until all the water has flowed out of the device.
Microcool 58

Disposal

10
10.1
Disposal

Disposing of refrigerant

The refrigerant must be disposed of in accordance with EC regula­tions 303/2008/EC in combination with 842/2006/EC.
CAUTION! Uncontrolled escape of refrigerant
Impact, cutting
Do not dispose of any pressurised cooling circuit.The decommissioning is only permitted by a spe-
cialist.
Refrigerant GWP
R134a 1430
Global Warming Potential (GWP) time horizon 100 years - according to IPCC IV (2007). Comparisons CO
= 1.0.
(100a)
2
10.2
10.3

Device disposal

Disposing of packaging

Type and fill quantity of the refrigerant can be seen on the rating plate.
The device must be disposed of according to EC Directive 2002/96/EC.
The packaging must be disposed of in accordance with EU Direc­tive 94/62/EC.
Microcool 59

Technical data

11
11.1
Technical data

General data

The device sound pressure level is below 70 dB. According to EC Directive 2006/42/EC. the sound pres­sure level of the devices is therefore not specified fur­ther.
Data Value Unit
Placement Indoor areas
Height above sea level up to 2,000 m
Relative humidity Highest rela-
tive humidity
80% at 31 °C
and up to 40
°C
decreasing
linearly by up
to 50%
Ambient temperature range 5 ... 40 °C
IP degree of protection IP 32
Contamination level 2
Clearance from surroundings (front and rear sides)
Overvoltage Overvoltage
category II
and transient
surge vol-
according to
category II
Protection class for electrical oper­ating equipment DIN EN 61 140 (VDE 0140-1)
Classification according to DIN 12 876-1 identification)
Display 7-segment,
Display resolution 0,1
Setting resolution 0,1
(class designation /
40 cm
tages
I/NFL
LED
1
°C
°C
Temperature constancy ±
Storage temperature range 5 ... 40 °C
0,5 K
Microcool 60
Technical data
Data Value Unit
Transport temperature range -20 ... 60 °C
Operating temperature
range
°C mm kg
MC 250 -10 ... 40 200 x 350 x 465 26
MC 600 -10 ... 40 350 x 480 x 595 51
MC 1200 -10 ... 40 450 x 550 x 650 64
MC 1200 W -10 ... 40 450 x 550 x 650 64
11.2
Cooling capacity
Cooling
kW kW kW kW
MC 250 0.23 0.2 0.15 0.09 R134a
MC 600 0.6 0.5 0.36 0.15 R134a

Refrigeration unit

capacity
(20 °C)
Cooling
capacity
(10 °C)
Dimensions (W x D x H) Weight
Cooling
capacity
(0 °C)
Cooling
capacity
(-10 °C)
Refrigerant
MC 1200 1.15 1.05 0.75 0.4 R134a
MC 1200 W 1.15 1.05 0.75 0.4 R134a
The cooling capacity is measured for a specified temper­ature of the heat transfer liquid. Information is provided in brackets. The ambient temperature for the measure­ment is 20 °C; ethanol was used as heat transfer liquid. The cooling water temperature is 15 °C and the cooling water differential pressure is 3 bar for the measurement of water-cooled devices.
Microcool 61
Technical data
11.3
Fill capacity Maximum
Litres
MC 250 2 ... 4 16 0.35
MC 600 4 ... 8 35 1.3
MC 1200 7 ... 14 35 1.3
MC 1200 W 7 ... 14 35 1.3
11.4
Power consumption

Hydraulic circuit

Voltage-dependent data

flow
l/min (water
20 °C)
Maximum flow pres-
bar (water
sure
20 °C)
Pump con-
nection
(internal
diameter
in mm)
Olive ½" (10) G ½" Olive ½" (10)
G ¾ (15),
olive ¾"
G ¾ (15),
olive ¾"
G ¾ (15),
olive ¾"
Drain tap Overflow con-
nection
G ½"
G ½"
G ½"
(internal diam-
eter in mm)
Olive 16 mm
(12)
Olive 16 mm
(12)
Olive 16 mm
(12)
MC 250 MC 600 MC 1200 MC 1200 W
kW kW kW kW
230 V; 50 Hz 0.23 0.7 1.15 1.2
Catalogue numbers
MC 250 MC 600 MC 1200 MC 1200 W
230 V; 50 Hz LWM 118 LWM 120 LWM 121 LWM 122
220 V; 60 Hz LWM 218 LWM 220 LWM 221 LWM 222
115 V; 60 Hz LWM 418 LWM 420 LWM 421 LWM 422
100 V; 50/60 Hz LWM 618 LWM 620 LWM 621 LWM 622
Microcool 62

General

12
12.1
12.2
12.3
General

Copyright

Technical changes

LAUDA contact

This manual is protected by copyright and is exclusively intended for the purchaser for internal use.
The transfer of this manual to third parties, reproductions of any type and form, whether in whole or in part, and the dissemination and/or communication of the contents are not authorised without the written permission of the manufacturer.
Infringements will result in legal action for damages. We reserve the right to assert further claims.
Technical details subject to change.
Contact LAUDA Service Constant Temperature Equipment in the following cases:
Contact details
12.4

EC conformity

In the event of faults on the deviceFor technical questions about the deviceFor spare part orders
Contact our Sales Department for application-specific questions.
LAUDA Service Constant Temperature Equipment
Telephone: +49 (0)9343 503 372
Fax: +49 (0)9343 503 283
E-Mail:
The device complies with the applicable basic occupational health and safety requirements of the Directives listed below.
Machinery Directive 2006/42/ECEMC Directive 2004/108/EC
LAUDA DR. R. WOBSER GMBH & CO. KG - Pfarrstraße 41/43 ­97922 Lauda-Königshofen - Germany
service@lauda.de
Microcool 63
General
The device does not come under the Pressure Equip­ment Directive 97/23/EC as the device is classified in the area of Article 3.3. The requirements from the above mentioned Directives are thus sufficiently met for the pressure-relevant hazards of the device.
Microcool 64

Index

13
Index
A
Air-cooled
Cleaning condenser........................................ 51
Alarm
Codes.............................................................. 55
Description...................................................... 54
Arrow buttons (position)....................................... 18
C
Calibration (actual temperature)
Specifying....................................................... 48
Checking
Heat transfer liquid.......................................... 53
Classification (EMC).............................................
Cleaning............................................................... 51
Code
Alarms............................................................. 55
Conformity (EC)................................................... 63
Cooling water
Connecting...................................................... 29
Pressure.......................................................... 29
Requirements.................................................. 27
Temperature................................................... 29
Copyright.............................................................. 63
23
D
Demineralised water ........................................... 32
Design
Device............................................................. 13
Device
Cleaning.......................................................... 51
Design............................................................. 13
Disposal (packaging)...................................... 59
Disposal (refrigerant)...................................... 59
Draining........................................................... 57
Draining the condenser (water-cooled)........... 57
Filling............................................................... 33
Placement....................................................... 24
Unpacking....................................................... 11
Display buttons
Operation........................................................ 18
Disposal
Packaging....................................................... 59
Refrigerant...................................................... 59
Disposing of refrigerant........................................ 59
DM water.............................................................. 32
Draining
Condenser (water-cooled).............................. 57
Device............................................................. 57
E
EC conformity....................................................... 63
EMC classification................................................ 23
ENTER button (position)...................................... 18
Error
Description...................................................... 54
Establishing power supply....................................
External consumer
Connecting...................................................... 27
34
F
Factory settings
Overview......................................................... 49
Restoring......................................................... 49
Filling.................................................................... 33
H
Heat transfer liquid
Checking......................................................... 53
Removing........................................................ 57
Heat transfer liquids
Overview (approved)....................................... 32
Hydraulic circuit
Description...................................................... 19
I
Intended use.......................................................... 7
Microcool 65
Index
L
LAUDA heat transfer liquids................................. 32
LAUDA Service Constant Temperature Equipment
Address........................................................... 63
Contact............................................................ 63
LED, yellow.......................................................... 40
M
Machine
Cleaning condenser (air-cooled)..................... 51
Machinery Directive.............................................. 63
Mains power (connection).................................... 34
Mains power switch
Operation
Maintenance
Intervals.......................................................... 50
Manometer
Description...................................................... 20
........................................................ 17
O
Offset (actual temperature)
Calibration....................................................... 48
Overflow connection
Hose................................................................ 33
Overflow hose...................................................... 33
P
Packaging
Disposal.......................................................... 59
Personal protective equipment (overview)............. 9
Personnel qualification (overview)......................... 8
Placement (device).............................................. 24
Placement location............................................... 24
Protective equipment (personal, overview)............ 9
R
Rating plate.................................................... 13, 22
S
Safety instruction
General............................................................. 6
Service (LAUDA, Temperature Equipment)......... 63
Specifying limit values (temperature)................... 41
Specifying temperature limit values..................... 41
Specifying the setpoint......................................... 40
Specifying the setpoint temperature.................... 40
T
Technical changes............................................... 63
U
Unpacking............................................................ 11
W
Warning
Description...................................................... 54
Water-cooled
Condenser draining
......................................... 57
Y
yellow LED........................................................... 40
Microcool 66
BESTÄTIGUNG / CONFIRMATION / CONFIRMATION
An
To / A
/
LAUDA Dr. R. Wobser LAUDA Service Center Fax: +49 (0) 9343 - 503-222
:
Von
Firma
Straße
Ort
Tel
Fax
Betreiber
From / De
/
/ C
/ S
City / Ville
/
:
ompany / Entreprise
treet / Rue
:
:
:
.:
:
esponsible person / Personne responsable
/ R
:
Hiermit bestätigen wir, daß nachfolgend aufgeführtes LAUDA-Gerät (Daten vom Typenschild):
We herewith confirm that the following LAUDA-equipment (see label): Par la présente nous confirmons que l’appareil LAUDA (voir plaque signalétique):
Typ
Type / Type
/
:
Serien-Nr.
Serial no. / No. de série:
/
mit folgendem Medium betrieben wurde
was used with the below mentioned media a été utilisé avec le liquide suivant
Darüber hinaus bestätigen wir, daß das oben aufgeführte Gerät sorgfältig gereinigt wurde, die Anschlüsse verschlossen sind, und sich weder giftige, aggressive, radioaktive noch andere gefährliche Medien in dem Gerät befinden.
Additionally we confirm that the above mentioned equipment has been cleaned, that all connectors are closed and that there are no poisonous, aggressive, radioactive or other dangerous media inside the equipment.
D’autre part, nous confirmons que l’appareil mentionné ci-dessus a été nettoyé correctement, que les tubulures sont fermées et qu’il n’y a aucun produit toxique, agressif, radioactif ou autre produit nocif ou dangeureux dans la cuve.
Stempel
Seal / Cachet.
Formblatt / Form / Formulaire: Unbedenk.doc Erstellt / published / établi: LSC Änd.-Stand / config-level / Version: 0.1 Datum / date: 30.10.1998
Datum
Date / Date
LAUDA DR. R. WOBSER GmbH & Co. KG
Pfarrstraße 41/43 Tel: +49 (0)9343 / 503-0 D - 97922 Lauda-Königshofen Fax: +49 (0)9343 / 503-222 Internet: http://www.lauda.de E-mail: info@lauda.de
Betreiber
Responsible person / Personne responsable
UNBEDENK.DOC
LAUDA DR. R. WOBSER GMBH & CO. KG Postfach 1251 ◦ 97922 Lauda-Königshofen ◦ Germany Phone: +49 (0)9343 / 503-0 ◦ Fax: +49 (0)9343 / 503-222 E-Mail: info@lauda.de ◦ Internet: www.lauda.de
Loading...