Commercial
Upright Refrigerator & Freezer
Service Manual

TABLE OF CONTENS
1. SPECIFICATIONS ……………………………………………… 4~6
2. PARTS …………………………………………………………… 7~44
3. WIRING DIAGRAM …………………………………………… 45~47
4. MAIN COMPONENTS …………………………………………. 48~62
5. ELECTRONIC CONTROL INSTRUCTIONS ……………… 63~85
6. PART LIST ……………………………………………………… 86~89

Safety cautions during service
ㆍ When exchanging or repairing electric parts, pull the plug out before
exchanging and repairing.
ㆍ When exchanging electric parts, use a rating part.
- Be sure to check marks such as MODEL name, rating voltage,
rating currents, movement temperature etc.
ㆍ During repairing, make sure wirings such as Harness, wire joint are
sturdy so that it is free of danger due to disclosure of core wire.
- Don’t let it derail when certain strength is put on.
ㆍ When repairing, take out the dust or foreign body (Housing part, wiring part,
contact point part).
- It prevents danger of fire such as TRACKING, SHORT.
ㆍ Check whether water has gone into the electric parts.
- When there are traces of water, exchange the parts or enact the TRACKING
prevention device.
ㆍ After repairing, check the assembly status of the parts.
- Keep the status as it was before the repairing. .
ㆍ After checking the usage environment of the product and if the installation is
unstable, change the usage location.
- For installations in places with moisture, water and for heat devices, prevent
placing products near igniting materials etc.
ㆍ When earthing is needed, earth it.
- For cases when electric leakage is concerned due to moisture or water,
be sure to earth it.
ㆍ For products that consumes power such as electric products, make sure
numerous plugs are not used in a single outlet.

2. PART
A. MainAssembly
a. LRT-771H
1 - SK1A1B-L2W (220V 60HZ)
Screw Machine-Comp
(Samsung)
EPDM HS 48±2% BLDC COMP 용

1 - SC12CLX2 220V/50/60HZ
Screw Machine-Comp
(Danfos)

1 - SK1A1B-L2W (220V 60HZ)
Screw Machine-Comp
(Samsung)
EPDM HS 48±2% BLDC COMP 용

1 - SC18CLX.2 208~230V60HZ
Screw Machine-Comp
(Danfos)

Screw Machine-Comp
(Danfos)

Screw Machine-Comp
(Samsung)
EPDM HS 48±2% BLDC
COMP 용

B. Assembly Uint
a. LRT-771H
Condenser Fan Motor Blade
1 - 220V 50~60Hz. 9W. CCW.

Condenser Fan Motor
Blade
1 - 220V 50~60Hz. 9W. CCW.

Condenser Fan Motor
Blade
1 - 220V 50~60Hz. 9W. CCW.

Condenser Fan Motor
Blade
1 - 220V 50~60Hz. 9W. CCW.

1 - SC18G 115V60HZ 117-7053 72R
Pipe Cross Bar Outlet
TM72F
Pipe Cross Bar Connect
TM72F
Condenser Fan Motor
Blade
1 - 220V 50~60Hz. 9W. CCW.

Condenser Fan Motor Blade

D. Top Grill Assembly
a. LRT-771H, LFT-771H
LIGHT COUNTRY(R19A)
10A/115V

LIGHT COUNTRY(R19A)
10A/115V

LIGHT COUNTRY(R19A)
10A/115V

E. Main PCB Box
a. LRT-771H
FR1 TM 220V ℃ 냉동
TMF220C-06

FR1 TM 220V ℃ 냉장 TMR220C-06
1 - 220V 50/60HZ, DT-1213K

FR1 TM 220V ℃ 냉동 TMF220C-06
1 - 220V 50/60HZ, DT-1213K

FR1 TM 115V℉ FRE TMF115F-A2
1 - 220V 50/60HZ, DT-1213K
1 - OMRON G7L-2A-TUB 220~240VAC
HARNESS MAIN AC-A
T49F HALF

FR1 TM 115V℉ REF TMR115F-A2
1 - 220V/50~60HZ DT-1215K
1 - OMRON G7L-2A-TUB 220~240VAC
HARNESS MAIN AC-B
T72R HALF

FR1 TM 115V℉ FRE TMF115F-A2
1 - PANASONIC HE2AN-Q-DC12V 25A
HARNESS MAIN AC-B
T72F HALF

G. Evaporator Assembly
a. LRT-771H
Evaporator Fan Motor Guard
1 - AT25℃, 10.75KΩ±1% -25~25

Evaporator Fan Motor Guard
1 - AT25℃, 10.75KΩ±1%. -25~25
1 - AT25℃, 10.75KΩ±1%. -25~25

Evaporator Fan Motor Guard
1 - AT25℃, 10.75KΩ±1%. -25~25

Evaporator Fan Motor Guard
1 - AT25℃, 10.75KΩ±1%. -25~25
1 - AT25℃, 10.75KΩ±1%. -25~25

Evaporator Fan Motor Guard
1 - AT25℃, 10.75KΩ±1%. -25~25

1 - BM/TM 72F 220V 10W 4840Ω
Evaporator Fan Motor Guard
1 - AT25℃, 10.75KΩ±1%. -25~25
1 - AT25℃, 10.75KΩ±1%. -25~25

H. Vapori Assembly
a. LRT-771H, LFT-771H, LFT-1471H
Bracket Case Vapori Front

220V 50W 968Ω SHEATH HEATER
Bracket Case Vapori Front

220V 50W 968Ω SHEATH
HEATER
Bracket Case Vapori Front
Fitting Divider Vapori Nut

220V 50W 968Ω SHEATH
HEATER
Bracket Case Vapori Front
Fitting Divider Vapori Nut

4. MAIN COMPONENTS
4-1.COMPRESSOR
4-2.POWER-RELAY(COMP. RELAY)
OMRON G7L-2A-TUB 220~240VAC
PANASONIC HE2AN-Q-DC12V 25A

4-10. EVAPORATOR FAN MOTOR

4-12. EVAPORATOR DEFROST HEATER
4-14. EVAPORATOR FAN MOTOR GUARD

LRT-771PC, LRT-1471PC, LRT-72T
LFT-771PC, LFT-1471PC, LFT-72T
FR1 TM 220V ℃ REF TMR220C-05
FR1 TM 220V ℃ FRE TMF220C-05
PC-SHEET, T0.25*141.7*43.7

LRT-771PC,LFT-771PC,LRT-1471PC,LFT-
1471PC,LRT-72T
4-20. EVAPORATOR THERMAL FUSE (BIMETAL)
4-21. TEMP-THERMISTOR, REF/FRE
AT25℃, 10.75KΩ±1%, -25~25

4-22. DEFROST SENSOR (D/-SENSOR, Evap-SENSOR)
AT25℃, 10.75KΩ±1%, -25~25
LRT-771PC,
LFT-771PC,
LFT-1471PC

4-26. ASSY MOTOR DC VAPORI
DC 12V, 3000RPM, DA08025B12MF
220V 50W 968Ω SHEATH HEATER
4-28. WICKING DRAIN WATER
LRT-771H, LFT-771H, LFT-1471H, LFT-72H

R3323-240, R3323-230 , R397A-020 (WASHER CASTER)

LIGHT COUNTRY(R19A) 10A/115V

LRT-771H, LFT-771H, LRT-1471H
LFT-1471H, LRT-72H,
LFT-72H

5. ELECTRONIC CONTROL INSTRUCTIONS
5-1. FREEZER CONTROL
5-1-1. HOW TO USE THE DISPLAY PCB PANEL

5. ELECTRONIC CONTROL INSTRUCTIONS
5-1-2. FUNCTION TABLE & MANUAL DEFROST
1. OFF for 2 sec
2. Display current Temp. and BUZZ 1 time.
3. Eva sensor Temp.
over 41℉(5℃) : Operate
under 41℉(5℃) : Operate after 5 min
. First 2 sec Ver.
℉ : F8, ℃ : FC
After 2 sec
Present ℃/℉
1. Push △/▼ to change Temp.
(Each time you push, 1 buzz sound.)
2. The set-up is memorized in the EEPROM and remains
even after Power Off.
. Hit △/▼
1 time - Display final set
2 times - Change set-up
value
1. Operate by Temperature Value
2. Operates on Comp ON/OFF Set Value
3. If Temp. Value hits the OFF Temp. the Comp. does not
operate for 5 min
1. Operate with Comp.
2. If the door opens, the fan stops.
1. Temp Sensor over 78℉(26℃): Box Heater Relay On.
2. Temp Sensor under 78℉(26℃).
Box Heater Operates by each mode
- 1. 1MODE : 10 min on/ 10 min off
- 2. 2MODE : 15 min on/ 10 min off
- 3. 3MODE : 20 min on/ 10 min off(Default)
- 4. 4MODE : 25 min on/ 15 min off
3. Push ▼ 5 sec to display Mode.
Hit ▼ to change Mode
4. First Cycle operates by 1 Mode
1. Door Open - LED Lamp Off
Door Close - LED Lamp On
2. Maximum 2 Lamps can be Controlled.

1. If the defrost period passes defrost starts from pre-cool.
2. - 1. 5H : 5 Hr
- 2. 6H : 6Hr
- 3. 8H : 8 Hr(DEFAULT)
- 4. AH : 10Hr
3. Push △ for 5 sec to display defrost period
4. Hit △ to get the Value desire
1. Operate for 30 min, before defrost heater on
2. If Temp. goes under -12℉(-24.6℃) in 30 min defrost
heater goes on mode
1. Operate after Pre-Cool
2. If the defrost sensor reaches 12℃ defrost completes and
heater goes Off
3. Heater on goes maximum 40 min
4. If fails, defrost Error Code will be saved.
If Temp. is over 23℉(-5℃) after precool, or the sensor
malfunctioned, heater will go atleast 20 min and at
28℉(-2℃) it will go Off
1. After heater is Off there is a 5 min resting period.
1. Push △&▼ for 3 Sec at the same time.
2. Push △&▼ for 3 Sec at the same time during Defrost
for cancel
1. Push ▼ & hit △ 3 times
2. Error Display
D1 : D-Sensor Error
F3 : Defrost Error
C1 : Cycle Error
3. Return if nothing has done for 15 sec
1. Door Open LED will blink until closer every 0.5 sec.
2. When Door is open over 3 min, Buzzer will chirp every
0.5 sec until closer.

1. Sensor Temp. Check & Set-up
1) Push △ & hit ▼ 3 times.
2) 1. dS : Displays D-Sensor → hit ▼
2. D-Sensor Temp → hit ▼
3. rS : Displays R-S → hit ▼
4. R-Sensor Temp → hit ▼
5. Return(return to last status. Displays current Temp
or dF(Defrost)
- After access return after the last procedure
- Return after 20 min auto(D-Sensor display)
. dS
. 888(D-Sensor)
. rS
. 888(R-Sensor)
1. Alarms for an hour if set-up period is passed..
2. 1) Push △ & hit ▼ 3 times
2) dS : Displays D-Sensor → hit △
- 0 : Disabled.
- 3 : 3 months
- 6 : 6 months(Default)
- 9 : 9 months
3) Hit △ to get the Value desire.
4) . Alarms every 1 sec for an hour.
5) Return
- Power On after Off
- Push △ & ▼ at the same time for 3 sec

5. ELECTRONIC CONTROL INSTRUCTIONS
5-1-3. ERROR CODE TABLE
- Comp ON : 18 MINUTES
- Comp OFF: 6 MINUTES 28.4℉
CS
- If R-Sensor is above 28.4℉
20 min. after the Defrost
started, terminate the Defrost.
Poor Defrost
(If D-Sensor lower than 53.6℉ in
40 min. later)
- Terminate the Defrost 40 min.
after its start.
Poor Cycle
(If D-Sensor is above 32℉ in 30
min later.
- BOX HEATER 100% On (72R)
5-1-4. SENSOR DESCRIPTION
. Defrost Sensor
. HEATER ON/OFF CONTROL during Defrost.
. Room Sensor
. DISPLAY & COMP ON/OFF CONTROL
. Room Temp Sensor
. BOX HEATER Control for energy efficiency

5. ELECTRONIC CONTROL INSTRUCTIONS
5-2. REFRIGERATOR CONTROL
5-2-1. HOW TO USE THE DISPLAY PCB PANEL

5. ELECTRONIC CONTROL INSTRUCTIONS
5-2-2. FUNCTION TABLE
- OFF for 2 sec
- First 2 sec Ver. ℉ : F8, ℃ : FC
- After 2 sec Present ℃/℉
- Blinks Model name 5 times.
- LED blinks 3 times.
- Present ℃/℉.
2. Defrost Check
<F Model > : LFT-23S, LFT-49D
- Defrost Sensor Operation
1) COMP On above 38℉(3.5℃)
2) Defrost On, under 38℉(3.5℃)
※ After 5min COMP delay pre-cool operate before defrost.
<R Model > : LRT-23S, LRT-49D
- Room Sensor Operation.
1) COMP On above 41℉(5.0℃)
2) Defrost On, under 41℉(5.0℃)
- COMP 5min delay (COMP OFF for 5 min)
- COMP ON/OFF by Room Sensor Temp.
- Defrost Period can be set to 5/6/7/8/9/10Hr
- Default 8hr
Defrost System
-FRE.
Defrost System
1. PRE-COOL
- To Lower Room Temp. before HEATER ON
- When Defrost Period, PRE-COOL on before HEATER ON
- HEATER ON if Temp. is under 17℉(-8℃) in 45min
- Maximum PRE-COOL time is 45min
- If the defrost sensor reaches 51℉/11℃ defrost completes and heater goes Off
- Heater on goes maximum 50 min.
- When Defrost SENSOR ERROR, HEATER is on for 20min.
HEATER OFF when Temp. is 28℉(-2℃)
- When Defrost Sensor / Room Sensor error HEATER is on for 20min
- If HEATER ON goes maximum 50min and does not reach the Defrost Return Temp.
ERROR CODE will be saved.
※ This ERROR Occurs Pre-COOL disable

- After heater is Off there is a 5 min resting period.
- HEATER, FAN, COMP ALL OFF.
- After Resting Period FAN is off for Maximum 5min.
- Only COMP Operates for the EVA
- If Temp. is under 14℉(-10℃) before 5 min, FAN will go off and activate normal
operation.
- Operate FAN for Defrost.
- If Air Sensor ERROR, Defrost for 30 min and return.
- After 30min Defrost, Air Sensor displays return Temp.
- When Temp. reachs the return temp. normal operation.
※When Set-up Temp. is under 30℉(-1℃), Return Temp. is 37℉(+3℃)
When Set-up Temp. is above 32℉(0℃) Return Temp. is 41℉(5℃).
- When COMP ON POINT Temp. is higher than RT Temp. HTR goes OFF.
- When RT Temp. is above 78℉(26℃) HTR is On.
- When RT Temp. is between 78℉(26℃)~Comp On Tem,p. HTR is 10min ON 10min OFF
- When RT Temp is below Comp On Temp. HTR goes OFF.
REF.
Frost Prevent
System
- COMP OFF → EVA FAN OFF.
- To prevent REF. EVA Frost, If Room Temp. is under 32℉(0℃) FAN activates.
1. Door Open LED will blink until closer every 0.5 sec.
2. When Door is open over 3 min, Buzzer will chirp every 0.5 sec until closer.
1. Operate with Comp.
2. If the door opens, the fan stops.
1. Door Open - LED Lamp Off
Door Close - LED Lamp On
- Door Error : LED Lamp Off
- Vapor fan ERROR : beeping sounds with SEGMENT blinks
Temp.(3sec) -uFn(0.5sec) repeat.
- Beeping sounds goes for 5min.
- Vapor Pan ERROR can be disabled or enabled by OPTION.
- Alarms for an hour if set-up period is passed..
- Alarms goes on with SEGMENT "CL".
- Alarms every 1 sec for an hour.
- Return : Power On after Off, Push △ & ▼ at the same time for 3 sec

a) COMP Operation
1) COMP 5 min OFF (COMP disabled for 5 min)
2) Operate by Temperature Value.
3) If Temp. Value hits the OFF Temp. the Comp. does not operate for 5 min.
b) AC Load Control
1) Each Part does not operate together, each operate by a 1.5 sec term.
Push △/▼ KEY.for 3 sec to enter control mode
888SEGMENT
.
Display after 2 sec
(888 SEGMENT & LED OFF.)

a) Forced Defrost
1) Display : 888SEGMENT – “ds”
2) Content : ① Press SW3(▽) during 1) to Force Defrost.
② 888 SEGMENT - "dF"
b) Mode Control
1) Display : 888 SEGMENT.
2) Content : Press SW(△) to change mode - OFF Temp.-> DIF Change ->
Adjust Temp.gap -> Defrost Time Change.
① 0F 1 sec 00 : 23℉(-5.0)~41℉(+5.0) - 32℉(0.5℃) change
(32℉(0.5℃)->32(5) Display)
② 0d 1 sec 20 : 32(0.25) -> 32(0.5) -> 33(0.75) -> 33(1.0) -> 34(1.5) ->
35(2.0) -> 37(3.0) -> 39(4.0) -> 41(5.0)
③ CA 1 sec 00 : 23℉(-5.0)~41℉(+5.0) - 33℉(1℃) change
(Room Temp. gap adjustment)
④ dt 1 sec 6 : FRE. Defrost Time (0, 5 ~ 10 Hr) – 1Hr Change
(0 : Disable)
REF. Defrost Time (0, 5~10 Hr) – 1Hr Change
- SW(▽) button for adjustment.
- Auto-save for change in the set-up.
- 15sec auto return.

c) Each part TEST
1) Display : 888SEGMENT – “St”
2) Content : Press SW4(△) 0~3 Mode Change.
3) Each part TEST Cancel : 15sec auto return.
COMP OFF
FAN OFF
Defrost HTR ON
R Model does not have
function
COMP OFF
FAN OFF
Defrost HTR OFF
Cord HTR ON
d) Error Check
1) Display
- No Error
- Error
: S1-SENSOR SHORTAGE
- Press SW(△) to check the errors
- Specific errors are below.
e) Ver. Change
1) Press SW(▽) - "rEF" -> "FrE"
2) 15sec auto save.
※ Re-enter the power plug to confirm change.
(Ver. Change initializes set-up.)

f) ℃/℉ Change
1) Press SW(▽) - F -> C
2) 15sec auto save.
g) Cord H/T Change
① Press SW(▽)
- "00"->"02"->"04" -> ~ "30" -> "40" -> "100" -> "00"
- Default "10"
② 5sec auto save.
h) LED check & E²PROM clear
1) LED blinks 5 times & returns.
2) E²PROM Clear & reset.
(set-up ℃/℉ is remembered.)
i) Vapor Pan ERROR
① Hold ▼ & hit △ 5 times to display Vapor Pan enable or disable mode.
② Press ▼
③ 15sec auto save
j) Temp. Check Mode.
1) Content
Hold △ & hit ▼ 3 times to enter Mode.
① SEGMENT : display value
② Operation : Normal Operation
2) Adjustment
① Press ▼
- Display DS ->D-SENSOR Temp. -> RS ->R-SENSOR Temp. -> Return
(REF. : D-Sensor OPEN : tO
D-Sensor SHORT : tS
3) Return
① Press ▼ until Return.
② 20min return after “DS”.

k) Condenser Alarm
1) Content
Hold △ & hit ▼ 3 times to enter Mode.
Press △ To Check period..
① SEGMENT : display value
② Operation : Normal Operation
2) Adjustment
① Press △ to adjust period.
0 -> 3 -> 6 -> 9 -> 0 cycle.
0 : Disable
3 : 3 months
6 : 6 months
9 : 9 months
3) Return
① 15sec Return.
a) S1 - Sensor Error
1) S1 - Sensor SHORTAGE or Temp. is over 143℉(62℃)
SEGMENT – “ESH” & Blinks.
2) S1 - Sensor OPEN or Temp. is under -58℉(-50℃)
SEGMENT – “ESL” & Blinks.
3) ERROR Mode Operation.
REF. S1 - Sensor ERROR : 10min On/20min Off
FRE. S1 - Sensor ERROR : 10min On/6min Off
4) If ERROR is removed – Normal Operation.
※ Types of Sensors
Detected cabinet temperature.
Detected Evaporator Coil temperature to defrost system.
Detected ambient temperature.

2. Check Error
* Errors will be displayed, if there is no error Display "nO".
Disconnected Sensor or Room
temp is under-58℉
Shortage of Sensor or Room
temp is under 149℉
Rt-SENSOR
(Ambient
sensor)
D1-SENSOR
(Defrost -
Sensor)
Disconnected Sensor or Room
temp is under-58℉
Shortage of Sensor or Room
temp is under 149℉
If perform the defrost over 50
min
After pass 30 min from start
working , Defrost sensor
reached 32℉
if cabinet temp is keeping
59℉ for 8 hr

if cabinet temp is keeping
45℉ for 8 hr
E²PROM cannot Read &
Write
if Door S/W is open for 1 Hr
Vapor Fan is not
connected of error
When a combined temperature/amperage value is above the limit specified by
the compressor manufacturer, a protector will operate independently,
turning off the compressor. The compressor will restart when this protector
has reset.
Note :
1. Compressor protector resets automatically.
2. If condenser fan is operating and the compressor is off, it is most likely that
the protector has operated.

Ⅴ. Service Diagnosis
A. Diagnosis Chart
1. Compress will
not
start - no
current
draw.
1. Move to "ON' position.
3. Ground Fault Circuit
interrupter
5. Wiring to Control Board
2. Check continuity
and replace.
1. Check continuity
and replace.
1. Replace control board.
1. Check continuity
and replace.
2. Compressor
will
not run draws
current and
trips
on overload.
3. Compressor
runs
intermittently
and trips on
overload.
2. Refrigerant Line or
Component
1. Plugged or restricted.
1. Clean and replace filter
2. Non-condensible
in system
1. Restricted air flow to
condenser.
1. Move unit or increase
ventilation.

4. Cabinet inside
temperature
too
high;
compressor
will
not start
1. Defective. ( 115V to
relay coil.)
1. Defective. ( Compressor
relay coil not
energized
at 115V.)
5. Cabinet
temperature too
high.
1. Correct setpoint.
Factory defaults :
Freezer -0.4℉(-18℃)
Refrigerator 35℉(2℃)
1. Not sealing, or open
for long intervals.
1. Check for sealing,
check for door open
at time of warm
cabinet temperature.
1. Not enough defrosts
occurring per day.
Operation in humid
conditions.
1. Freezer ; See "C. 1. 5
Defrost System."
2. Refrigerator : "C. 1. 6
Defrost System."
3. Check D-Sensor
position.
1. Repair leak and
recharge
6. Cabinet
temperature dis
- play indicator
does not illumi
- nate properly.
1. Bad connection
between control board
and display board.
7. Cabinet inside
temperature too
low.
1. Defective;
contacts welded.

1. Not enough defrosts
occurring per day.
Operation in humid
conditions.
1. Freezer ; See "C. 1. 5
Defrost System."
2. Refrigerator : "C. 1. 6
Defrost System."
3. Check D-Sensor
position.
1. Freezer : Replace
heaters.
4. Safety Defrost Thermostat
1. Defective, turning off
heaaters prematurely,
or fused open.
1. Freezer : Replace
safety deforst
thermostat.
9. Defrost cycle
lasts too long.
1. Not enough defrosts
occurring per day.
Operation in humid
conditions.
1. Freezer ; See "C. 1. 5
Defrost System."
2. Refrigerator : "C. 1. 6
Defrost System."
3. Check D-Sensor
position.
1. Freezer : Replace
heaters.
4. Safety Defrost Thermostat
1. Defective, turning off
heaaters prematurely,
or fused open.
1. Freezer : Replace
safety deforst
thermostat.
1. Loose fasteners
allow vibration
of part.
1. Properly mount comp ressor. Replace any
missing grommets.
2. Floodback to
compressor.
2. Check for signs of
floodback to compre-

ssor. Evacuate and
recharge if necessary.
Thermistors (semiconductors) are used for the cabinet control sensor and
defrost termination sensor. The resistance varies depending on temperature.
No adjustment is required.
If necessary, check for resistance between thermistor leads and visually check
the thermistor mounting.

Pre-set value
Room Sensor
Pre-set value
■ Set value -1℃↓ : Return Temp' +3℃
Set value 0 ℃↑ : Return Temp' +5℃
* AT <Comp ON Temp : Heater OFF
Comp ON Temp <AT < 26℃ : 10 min. ON / OFF
26 ℃<AT : Heater ON
AT : Ambient Temperature

▲ Set value minus 8℃
● Defrost senser Temp' -10℃
* Default setting 8 hours, adjustable
Pre-set value
Room Sensor
Pre-set value
Pre-set value
Defrost Sensor
No meaning

5. ELECTRONIC CONTROL INSTRUCTIONS
5-2-3. ERROR CODE
- Comp ON : 6 MINUTES
- Comp OFF: 11 MINUTES

115V LED TYPE HE1AN-QDC12V
CONDENSER FAN MOTOR BLADE

EVAPORATOR FAN MOTOR GUARD
AT25℃, 10.75KΩ±1%, -25~25
AT25℃, 10.75KΩ±1%, -25~25

FR1 TM 220V ℃ 냉동
TMF220C-06
FR1 FR1 TM 220V ℃ 냉장
TMR220C-06
ABS/BLACK BM/TM T2*242*72
88 DISPLAY-DP1 기타 BUYER
TM 공용
LIGHT COUNTRY(R19A)
10A/115V
PANASONIC HE1AN Q-DC12V
30A
PANASONIC HE2AN Q-DC12V
25A

Supplier's Compressor Application Model Names
Compressor Set (Total Price)
Compressor Set (Total Price)
Compressor Set (Total Price)
Compressor Set (Total Price)
Compressor Set (Total Price)
S23R,S23F,
S23RG,S49R
STM23R, STM49R
SPT-44,SPT-67,SUSS-48-12/18
SRCB-84/86/96/98(ME)
USCF-27, USC-48/60/72
SUSS-/60-16/24/72-18/30
SBB-60-2B/2S, SBB-70-2B/2S
SBB-90-3B/3S
SBB-60-2BG/SG, SBB-70-2BG/SG
SBB-90-3BG/3SG
SBD-60-2B/2S, SBD-70-2B/S
SBD-90-3B/3S
OVERLOAD PROTECTOR(795 RHB)
RUNNING CAPACITOR 350V15UF
STSRTING CAPACITOR 160V 145UF
Samsung Compressor Set (Total Price)
SRCB-52/70/74(ME)
SUSS-27-8/27-12,USC-27
SBB-24-1B/1S, SBB-24-1BG/SG
SBD-24-1B/S
Overload Protector ( OLP)