Larson Electronics 240 VOLT, 480 VOLT Installation Manual

ALL PURPOSE
CNC/HEAVY DUTY
Rotary Phase Converters
240 & 480 VOLT SERIES
Smart Digital Phase Converter
Operation & Installation Manual
MTPC-DRB-208.240-1P-20HP-3P
DANGER: HIGH VOLTAGE
Electric shock could result in death or injury. Please
DANGER: Risk of Electric Shock
This manual is to serve the purpose of providing recommendations for proper performance,
consult qualified personnel for installation.
Please wait 30 minutes before servicing
but is not to supersede or replace local or national electric codes. Installation should be done
by a licensed electrician who is familiar with phase converter installations.
If this phase converter does not start in less than 2 seconds, TURN IT OFF!
1. Make sure the wire size meets our minimum recommended size.
2. All loads INCLUDING TRANSFORMERS must be DISCONNECTED before starting the phase converter each time. This includes small control transformers that run controls inside your equipment. If you need an
economical 3-phase disconnect switch, please visit for assistance.
www.larsonelectronics.com or call 1-800-369-6671
If your converter still takes more than 2 seconds to start, call our Toll-Free Technical support line 1-800-369-6671. You will be asked to verify conditions 1 and 2 above are met. Failing to meet these two condition account for 99% of starting problems and can result in damage to the starting capacitors.
This converter is quiet. If it does not sound quiet and smooth, TURN IT OFF!
3. Make sure the idler motor is mounted on rubber. DO NOT BOLT THE IDLER MOTOR DOWN! This can cause bearing failure.
4. Make sure the idler motor is wired properly.
For the Larson Electronics soft-start idler motor 240 Volts Input (1, 7, A), (2, 8, B), (3, 9, C), (4, 5, 6 bolted together and insulated). 480 Volts Input (1, A), (2, B), (3, C). The following bolted together and insulated: (4, 7), (5, 8), (6, 9) Do not use wire nuts or ground any of these connections. Use the supplied bolts and make all connections insulated.
* Make sure the Phase Converter Panel, the Idler Motor, and your equipment is grounded!
5. This phase converter does NOT disconnect the single phase power as it passes through the unit, so the single phase legs remain energized even when the rotary phase converter is off. In addition to inst single phase breaker in front of the phase converter, you need to be aware that the single phase power DOES flow through the phase converter whether the unit is on or off.
6. Before connecting load, verify proper function of phase converter. This will ensure the protection of the phase converter and your equipment.
For a stock three-phase motor that uses our Stock Motor Panel, w
the motor according to the diagram for that motor, NOT according to our wiring diagram.
ire
alling a
1. INTRODUCTION
Larson Electronics specializes in converting Single Phase electrical power to Three Phase electrical power. The diagram below provides a very simple view of the layout.
An additional 3-phase breaker panel may be installed on the line between the converter control panel and the 3-phase equipment. This is recommended to protect each piece of equipment and the wire that feeds that equipment.
The two single phase lines pass through the phase converter and are used to manufacture the 3rd line that completes the three phases. The output voltage will alwa If a completely different voltage is needed then a transformer installed in front of the phase converter will be necessary.
The three-phase output is delta configured. This means that voltage measurements between phases will be similar to input voltages. Voltages should only be measured line to line. Do not measure voltages line to ground. Most machinery requires a delta three phase voltag third line voltage to ground should not affect operation. If a piece of equipment requires wye voltage and a neutral connection, the output of the phase converter must be run through a delta -wye transformer to create the neutral. The phase converter must be started before the transformer is connected electrically. This is done with a safety disconnect switch. Larson Electronics can provide these transformers and disconnect switches.
ys be close to the input voltage.
e and this
2.0 INSTALLATION
*Note: Each phase converter comes standard with spare fuses for the ones already installed in the unit.
2.1 PHYSICAL INSTALLATION
All Larson Electronics rotary phase converter units come standard in NEMA 1 indoor rated enclosures. NEMA Type 3R rainproof enclosures are available with the AI series converters.
2.1.1 PHYSICAL INSTALLATION ENVIRONMENTAL CONSIDERATIONS
The unit should be installed in a location free from the following:
Dirt Corrosive gases or liquids Excessive vibration Airborne particles (particularly metal particles) Ambient temperatures exceeding 50 degrees C
High humidity
2.1.2 INSTALLATION GUIDELINES (CONTROL PANEL & IDLER)
Steps to install the control panel and idler:
a. Mount enclosure on a secure wall or on the idler (idler mount
models only.) Attach conduit fittings for single phase input line, 3- phase line to idler and 3-phase line to load.
b. Pull electrical lines into the enclosure. Be sure to pull enough wire
for your load to reach the two terminals on the left side (L1 & L2) plus the terminal on the r
ight side (T3) of the phase converter
controls. Run the ground lines with each circuit.
c. Connect the lines to the idler/generator to the terminals marked A,
B and C.
d. Connect the three phase output lines to the terminals marked
L1/T1, L2/T2, and T3.
e. Connect the single phase input lines to the terminals marked L1
and L2.
The following diagram shows the electrical schematic for the rotary phase converter:
Firmly snap in the green, yellow/white and red switch terminals into the pushbutton switch body. (In the image at right, a clear enclosure cover is used for clarity.)
f. Wire the idler:
240V: Bolt idler leads 4, 5 & 6 together. Insulate this connection with electrical tape or heat shrink tubing. Connect the ground line to the ground screw inside the motor conduit box. Inside the phase converter panel box, connect terminal A to (1,7), terminal B to (2,8) and terminal C to (3,9). Insulate these connections separately. Hardware for these connections is provided.
480V:
4 & 7
5 & 8
6 & 9
3
2
1
1 & 7
3 & 9
2 & 8
4, 5, 6
Bolt idler leads 4 & 7 together, 5 & 8 together, and 6 & 9 together in pairs inside the motor conduit box. Insulate these connections with electrical tape or heat shrink tubing. Connect the ground line to the ground screw inside the motor conduit box. Inside the phase converter panel box, connect terminal A to 1, terminal B to 2, and terminal C to 3. Wiring diagram is listed on the idler motor for your reference.
2.1.3 GENERAL WIRING CONSIDE
- Follow all local, state and national electric codes (NEC) which may supersede
Larson Electronics recommendations.
- T3 is the manufactured line; DO NOT use T3 for any single phase loads.
- Protect all wire and machinery with proper size breakers
- Always make sure rotary phase converter starts before external load(s) are applied.
- A qualified electrician should do all wiring.
- DO NOT assume that a breaker box neutral is a grou
including breaker boxes, phase converter control panel & Idler, disconnect switches, transformers, loads etc.
- Run all control voltage and equipment controls from lines L1/T1 and L2/T2. Terminals A
and B are for the idler only.
RATIONS
nd! Be sure to ground all equipment
- See Wire Sizing Recommendations (section 2.1.4) for wire sizes. This is VERY
IMPORTANT, as under sizing the wire may lead to a phase converter that does not start or work properly.
- To minimize voltage drop, Larson Electronics recommends increasing wire size one size for
every 50 feet of run and rounding up.
2.1.4 WIRE SIZING RECOMMENDATIONS
!
FOR 240V:
FOR 480V:
*For all voltages: Conductors listed are minimum recommended based on largest hard starting & CNC amps. For combined HP’s greater than 50% of maximum total HP listed in the tables above, consult NEC & local codes for conductor sizing. The above charts do not replace or supersede any requirements by local, state, or national electric codes.
ADDITIONAL NOTES ON WIRING:
It is important to have adequate single-phase electrical service. The actual single phase current that will flow through the converter is approximately 1.73 times the three-phase current. The National Electric Code requires 2.5 times the three-phase load current to allow for starting current and a margin of safety. This is a good conservative calculation to determine your single phase branch circuit wire size and breaker size.
The power required to run the phase converter is very small and is negligib le in figuring out the power required. The power required is calculated based on the load only.
Wire can never be sized too large, but too small of wire can impede performance and even keep the converter from starting properly. Increase wire size one size for every 50 feet of run and round up.
3.0 OPERATION & MAINTENANCE
3.1 STARTING & STOPPING
Larson Electronics phase converters are started by turning the rotary switch to the start position. The starting sequence is automatic and the switch needs only to be turned to start and released. The switch should return to the run position on its own. Stopping the phase converter is done in a similar manner, by turning the switch to the stop position. As with most electrical equipment, frequent stops and starts are harder on the rotary phase converter than steady operation. The rotary phase converter is extremely low cost to operate at idle (with no three-phase load), and this is preferable to a high level of stopping and starting. If your load situation dictates that the rotary phase converter must be started and stopped frequently, call us about our On Demand with De
Off kit for optimum product operation.
lay
3.2 CHECKING VOLTAGES
Measuring Voltage is the easiest way to test to see if the phase converter is working properly. When voltages are balanced on the three 3-phase lines, currents are balanced. Measuring
current is more difficult as there are different types of current present in the running phase converter such as regenerative current.
Voltage Measurements:
Measure L1 to L2 This is your single phase voltage as supplied from the utility. To get the
(T1 to T2) most accurate voltage measurements, make sure that the converter is on
and the load is applied.
Measure L1/T1 to T3 This is the voltage between the manufactured line (T3) and one of the
single phase lines. This voltage should be up to 5% higher than the T1 to T2 single-phase voltage.
Measure L2/T2 to T3 This voltage is the least important. It should also be within 5%. This
voltage will drop when a load is applied.
Do not measure line to ground. Voltages will vary widely when doing this.
Frame
HP Range
Hours running
Grease Type
Up to 210
3-5
12,000
Polyrex EM
210-280
7.5-20
9,500
Polyrex EM
280-360
25-50
7,400
Polyrex EM
>360
60 & 75
3,500
Polyrex EM
When the load is applied, this voltage will drop. Ideally it will only drop to 5% below the average of the 3-phase voltages.
If your load motor runs backwards, reverse the two single-phase carry through lines T1 and T2 at the motor that needs reversing. If these lines are switched going to the idler, then the direction of all equipment will be reversed.
3.3 GENERAL MAINTENANCE
The rotary phase converter may operate continuously with or without a load. The converter will run cool and quiet in the no load condition because the voltages are well balanced.
1. Never start the converter with a load applied (including transformers)
2. The converter should start within a second or two. Wait to start loads (including transformers) until the converter reaches full speed. A timer circuit can be used to automatically start loads after the converter reaches full speed.
3.3.1 MAINTENANCE
Keep dust and moisture from the control panel and the idler. Keep dust from accumulating in the motor. Dust can be blown out using compressed air. Keep dust from accumulating on the surface of a TEFC model as this prohibits proper cooling.
3.3.2 LUBRICATION
Larson Electronics rotary phase converter idler/generators are custom made and come with pre- packed bearings using the lubricant specifically designed for this idler.
DO NOT use Lithium based lubricants. These may cause premature bearing failure and will void any warranty.
Be careful not to force so much grease into the bearings that the excess finds its way into the windings of the idler. Some idlers have sealed bearings and will never require greasing. If the idler has grease fittings located on the end bells of the idler, use the chart below for a greasing schedule.
Loading...