1.Make sure the wire sizemeetsour minimumrecommendedsize.
2.All loadsINCLUDING TRANSFORMERSmustbeDISCONNECTEDbeforestarting the phase convertereach time. This includes small control transformers that run controlsinside your equipment. Ifyou need an
economical 3-phase disconnect switch, please visit for assistance.
www.larsonelectronics.comor call 1-800-369-6671
Ifyour converter still takes more than 2 seconds to start, call our Toll-Free Technicalsupport line 1-800-369-6671. You will be asked to verify conditions1 and 2 aboveare met. Failingto meet these two conditionaccount for 99% of starting problems andcan result in damageto the starting capacitors.
3.Make sure the idlermotor ismountedon rubber.DO NOTBOLTTHEIDLERMOTORDOWN!Thiscancause bearingfailure.
4.Make sure the idlermotor iswired properly.
For the Larson Electronicssoft-start idler motor 240 Volts Input (1, 7, A),(2,8, B),(3, 9, C), (4, 5, 6 bolted together and insulated). 480 Volts Input (1, A),(2, B),(3, C). The following bolted together and insulated: (4, 7), (5, 8), (6, 9) Do not use wire nutsor ground any of these connections.Use the supplied bolts and make all connectionsinsulated.
*MakesurethePhaseConverterPanel,theIdler Motor,and your equipmentisgrounded!
5.Thisphase converter doesNOTdisconnectthe singlephase power asitpassesthroughthe unit,so thesinglephaselegsremainenergized even when therotaryphase converterisoff.In addition to instsinglephasebreaker in frontofthephase converter,you need to beawarethatthe singlephasepowerDOES flowthroughthe phase converter whether the unitisonor off.
6.Before connectingload,verifyproperfunction ofphase converter.Thiswillensuretheprotectionofthephase converterand your equipment.
Fora stock three-phase motorthatusesour StockMotor Panel,w
the motor accordingtothediagramforthatmotor,NOTaccordingtoour wiringdiagram.
ire
alling a
1.INTRODUCTION
Larson Electronicsspecializes in converting SinglePhase electrical power to Three Phase electrical power. The diagrambelowprovides a very simple view of the layout.
Anadditional 3-phasebreakerpanel may beinstalledonthelinebetweentheconvertercontrol panelandthe3-phaseequipment.This is recommendedtoprotect eachpieceof equipment andthe wire that feeds that equipment.
The two single phase lines pass through the phase converter and are used to manufacture the 3rdline that completes the three phases. The output voltage will alwaIfacompletely different voltageis neededthenatransformerinstalledinfront of thephaseconverter willbe necessary.
Thethree-phaseoutput is deltaconfigured.This means that voltagemeasurements betweenphases will be similar toinput voltages.Voltages should onlybe measuredline to line.Do notmeasurevoltageslinetoground.Most machinery requires adeltathreephasevoltagthirdlinevoltagetogroundshouldnot affect operation. Ifapieceofequipment requireswyevoltageandaneutralconnection, theoutput of thephaseconvertermust berunthroughadelta-wyetransformer to create theneutral. The phase converter must bestarted before the transformer is connected electrically.This is donewith a safety disconnect switch. LarsonElectronics canprovide these transformers and disconnect switches.
All LarsonElectronicsrotary phase converter units come standard in NEMA 1 indoor rated enclosures. NEMA Type 3R rainproof enclosures are available with the AI series converters.
Boltidler leads 4& 7together,5&8together,and6& 9together inpairsinsidethemotor conduitbox.Insulatetheseconnections withelectricaltapeor heatshrinktubing.Connectthegroundlinetothegroundscrewinsidethemotor conduitbox.Insidethephaseconverter panelbox,connectterminalA to1,terminalB to2,andterminalCto3.Wiringdiagramis listedontheidler motor for your reference.
Itisimportant tohaveadequatesingle-phaseelectricalservice. Theactual singlephasecurrentthat willflowthroughtheconverteris approximately 1.73times thethree-phasecurrent.TheNationalElectricCoderequires 2.5times thethree-phaseloadcurrent toallowforstartingcurrentandamarginof safety.This is agoodconservativecalculationtodetermineyoursinglephasebranch circuit wire sizeand breaker size.
Thepowerrequiredtorunthephaseconverteris very smallandis negligiblein figuringout thepower required. The power requiredis calculated based on theloadonly.
Wirecanneverbesizedtoolarge, but toosmallof wirecanimpedeperformanceandevenkeepthe converter from starting properly. Increasewire size one size for every 50feet of run androundup.
3.0OPERATION&MAINTENANCE
3.1STARTING&STOPPING
LarsonElectronics phase converters are started by turningtherotary switch to thestart position. The startingsequence is automatic and the switch needs only to be turnedto start andreleased. The switch should return to the run position on its own. Stoppingthe phase converter is done in a similar manner, by turningthe switch to the stop position. As with most electrical equipment, frequent stops andstarts are harder on the rotary phase converter thansteady operation. The rotary phase converter is extremely low cost to operate at idle(with no three-phase load), andthis is preferableto a highlevelof stoppingandstarting. If your loadsituation dictates that the rotary phase converter must be started and stoppedfrequently, call us about our On Demand withDe
Off kit for optimum product operation.
lay
3.2CHECKINGVOLTAGES
MeasuringVoltageis theeasiest way totesttoseeif thephaseconverteris workingproperly.Whenvoltages arebalancedonthethree3-phaselines, currents arebalanced. Measuring
current is more difficultas there are different types of current present in the running phaseconverter such as regenerative current.
VoltageMeasurements:
Measure L1 toL2This is your single phase voltage assupplied from the utility. To get the
(T1 to T2)most accurate voltage measurements,makesure that the converteris on
and theloadis applied.
MeasureL1/T1 toT3This is the voltage between the manufacturedline(T3) andone of the
single phaselines.This voltage should be upto 5%higher than the T1 toT2 single-phasevoltage.
MeasureL2/T2 toT3This voltage is theleast important.It should also be within 5%.This
voltage will drop when a load is applied.
Do not measure line toground. Voltages will vary widely when doing this.
Frame
HP Range
Hours running
GreaseType
Up to 210
3-5
12,000
Polyrex EM
210-280
7.5-20
9,500
Polyrex EM
280-360
25-50
7,400
Polyrex EM
>360
60 & 75
3,500
Polyrex EM
When the load is applied, this voltage will drop. Ideally it will only drop to5% below theaverageof the3-phase voltages.
If yourload motor runs backwards, reverse the two single-phase carry throughlines T1 and T2 at the motor that needs reversing. If theselinesare switchedgoing to theidler, then thedirectionof all equipment willbe reversed.
3.3GENERALMAINTENANCE
The rotary phase converter may operate continuously with or without a load. The converterwillrun cool and quiet in thenoload conditionbecause the voltages are well balanced.
1.Never start theconverter with aload applied (including transformers)
2.The converter should start within a second ortwo. Wait to start loads (includingtransformers) until the converter reaches full speed. A timer circuit can beused toautomatically start loads afterthe converter reaches full speed.
3.3.1MAINTENANCE
Keep dust and moisture from the control panel and theidler. Keepdust from accumulatingin themotor. Dust can be blown out using compressed air. Keep dust from accumulating on thesurface of a TEFC modelas this prohibits proper cooling.
3.3.2 LUBRICATION
Larson Electronics rotary phase converter idler/generators are custom made and come with pre-packedbearings using thelubricant specifically designed for this idler.
DO NOT use Lithium based lubricants. These may cause premature bearing failure andwillvoidany warranty.
Be careful not toforce so much greaseinto the bearings that the excess finds its way into thewindings of the idler. Some idlers have sealed bearings and will never requiregreasing. If theidler has grease fittings located on the end bells of theidler, use the chartbelow for agreasingschedule.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.