lapara LA-ITR-800-LCD, LA-ITR-1100-LCD, LA-ITR-2000-LCD, LA-ITR-1500-LCD, LA-ITR-2500-LCD User Manual

...
LA-ITR-800-LCD LA-ITR-1100-LCD LA-ITR-1500-LCD LA-ITR-2000-LCD LA-ITR-2500-LCD LA-ITR-3000-LCD
Line Interactive Pure Sine Wave UPS
EN
________________________________________________________________________________
LA-ITR-LCD
1
Table of Contents
1. Important Safety Warning………………………………………………
2
1.1. Transportation
2
1.2. Preparation
2
1.3. Installation
2
1.4. Operation
2
1.5. Maintenance, Service And Faults
3
2. Installation And Setup……………………………………………………
4
2.1. Rear Panel View
4
2.2. Install The UPS
4
2.3. Setup The UPS
5
2.4. Battery Replacement
7
2.5. Battery Kit Assembly (Option)
8
3. Operations…………………………………………………………………..
10
3.1. Button Operation
10
3.2. LCD Panel
10
3.3. Audible Alarm
11
3.4. LCD Display Wordings Index
12
3.5. UPS Setting
12
3.6. Operating Mode Description
14
3.7. Faults Reference Code
15
3.8. Warning Indicator
15
4. Troubleshooting…………………………………………………………...
16
5. Storage And Maintenance……………………………………………….
18
6. Specifications………………………………………………………………
19
________________________________________________________________________________
LA-ITR-LCD
2
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
1.1. Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1.2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments. Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1.3. Installation
Do not connect appliances or devices, which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them. Do not connect domestic appliances such as hair dryers to UPS output sockets. The UPS can be operated by any individuals with no previous experience. Connect the UPS system only to an earthed shockproof outlet that must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of
the UPS and the connected devices does not exceed 3.5mA.
1.4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
________________________________________________________________________________
LA-ITR-LCD
3
1.5. Maintenance, Service and Faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when working with batteries:
remove wristwatches, rings and other metal objects
Use only tools with insulated grips and handles. When changing batteries, install the same number and same type of batteries. Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and
eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
________________________________________________________________________________
LA-ITR-LCD
4
2. Installation And Setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
2.1. Rear Panel View
LA-ITR-800-LCD / LA-ITR-1100-LCD / LA-ITR-1500-LCD / LA-ITR-2000-LCD
LA-ITR-2500-LCD / LA-ITR-3000-LCD /
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Input circuit breaker
5. Network/Fax/Modem surge protection
6. Emergency power off function connector (EPO)
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
10. External battery connector (only available for L model)
11. External battery pack numbers detection port
2.2. Install the UPS
For safety consideration, the UPS is shipped out from factory without connecting battery wires. Before install the UPS, please follow below steps to re-connect battery wires first.
Step 1
Step 2
Step 3
Remove front panel.
Connect the AC input and re-connect battery wires.
Put the front panel back to the unit.
________________________________________________________________________________
LA-ITR-LCD
5
Rack-mount Installation Step 1 Step 2
Tower Installation
Step 1
Step 2
Step 3
2.3. Setup the UPS Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
Step 2: UPS output connection
There two kinds of outputs: programmable outlets and general outlets. Please connect non-critical devices to the programmable outlets and critical devices to the general outlets. During power failure, you may extend the backup time to critical devices by setting shorter backup time for non-critical devices.
Step 3: Communication connection Communication ports:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring options.
PS. USB port and RS-232 port cannot work at the same time.
Step 4: Network connection Network/Fax/Phone surge port
________________________________________________________________________________
LA-ITR-LCD
6
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line
cable. Step 5: Disable and enable EPO function
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire between pin 1 and pin 2.
Step 6: External battery connection (for long-run models only) Connect one end of external battery cable to UPS unit and the other end to battery box. Use supplied battery detection wire in detection port of UPS unit and plug the other end to battery bank. See below chart for detailed connection.
NOTE: Maximum connected external battery boxes up to 4 units. Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. Please follow steps below to download and install monitoring software:
1. Go to the website http://www.power-software-download.com
2. Click ViewPower software icon and then choose your required OS to download the software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock.
It’s in closed status for UPS
normal operation.
UPS
Battery Box
Battery Box
________________________________________________________________________________
LA-ITR-LCD
7
2.4 Battery Replacement
NOTICE: This UPS is equipped with internal batteries and user can replace the batteries without shutting down the UPS or connected loads (hot-swappable battery design). Replacement is a safe procedure, isolated from electrical hazards.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries. Note: Upon battery disconnection, equipment is not protected from power outages.
Step 1
Step 2
Step 3
Remove front panel.
Disconnect battery wires.
Pull out the battery box by removing two screws on the front panel.
Step 4
Step 5
Step 6
Remove the top cover of battery box and replace the inside batteries.
After replacing the batteries, put the battery box back to original location and screw it tightly.
Re-connect the battery wires.
Step 7
Put the front panel back to the unit.
________________________________________________________________________________
LA-ITR-LCD
8
2.5 Battery Kit Assembly (option) NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select
correct battery kit procedure below to assemble it.
2-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by following below chart.
Step 3: Put assembled battery packs on one side of plastic shells.
Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.
4-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by following below chart.
Step 3: Put assembled battery packs on one side of plastic shells.
Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.
Tapes
Tapes
Tapes
________________________________________________________________________________
LA-ITR-LCD
9
6-battery kit
Step 1: Remove adhesive tapes.
Step 2: Connect all battery terminals by following below chart.
Step 3: Put assembled battery packs on one side of plastic shells.
Step 4: Cover the other side of plastic shell as below chart. Then, battery kit is assembly well.
Tapes
Tapes
________________________________________________________________________________
LA-ITR-LCD
10
3. Operations
3.1. Button Operation
Button
Function
ON/MUTE Button
Turn on the UPS: Press and hold ON/Mute button for at least 2
seconds to turn on the UPS.
Mute the alarm: After the UPS is turned on in battery mode, press
and hold this button for at least 5 seconds to disable or enable the alarm system. But it is not applied to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press and hold ON/Mute button for 5
seconds to enter UPS self-testing while in AC mode
OFF/ENTER
Button
Turn off the UPS: Press and hold this button at least 2 seconds to
turn off the UPS
Confirm selection key: Press this button to confirm selection in UPS
setting mode.
SELECT Button
Switch LCD message: Press this button to change the LCD message
for input voltage, input frequency, battery voltage, output voltage and output frequency.
Setting mode: Press and hold this button for 5 seconds to enter UPS
setting mode when UPS is off.
Down key: Press this button to display next selection in UPS setting
mode.
3.2. LCD Panel
Rack Display Tower Display
Battery info
Load info
Input/output
and Battery
info
UPS status
Warning & Fault info/ Setting operation
Backup time info
Load info
UPS status
Backup time info
Input/output and Battery info
Warning & Fault info/ Setting operation
Battery info
________________________________________________________________________________
LA-ITR-LCD
11
Display
Function
Backup time information
Indicates the backup time in pie chart.
Indicates the backup time in numbers.
H: hours, M: minute
Warning & Fault information
Indicates that the warning and fault occurs.
Indicates the warning and fault codes, and the codes are listed in details in 3.5. section.
Setting Operation
Indicates the setting operation.
Input/Output & Battery information
Indicates the output/input voltage, output/input frequency or battery voltage. V: voltage, Hz: frequency
Indicates the external battery pack numbers.
Load information
Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates overload.
Indicates the load or the UPS output is short-circuited.
UPS status
Indicates that programmable management outlets are working.
Indicates that the UPS alarm is disabled.
Indicates the UPS powers the output directly from the mains
Indicates the battery charger is working.
Indicates the UPS is working in boost mode
Indicates the UPS is working in buck mode
Battery information
Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%.
Indicates low battery.
Indicates there is something wrong with battery.
3.3. Audible Alarm
Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously sounding
________________________________________________________________________________
LA-ITR-LCD
12
3.4. LCD Display Wordings Index
Abbreviation
Display content
Meaning
ENA
Enable
DIS
Disable
ESC
Escape
EP EPO
FA Fan
TP Temperature
CH Charger
RAC
Rack display
TOE
Tower display
SF Site Fault
3.5. UPS Setting
There are two parameters to set up the UPS. Parameter 1: It is for program alternatives. There are 4 programs to set up: output voltage setting, , programmable outlets enable/disable, programmable outlets setting , LCD display direction and exit.
01: Output voltage setting
Interface
Setting
For 208/220/230/240 VAC models, you may choose the following output voltage: 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac 240: presents output voltage is 240Vac For 110/120 VAC models, you may choose the following output voltage: 110: presents output voltage is 110Vac 120: presents output voltage is 120Vac
02: Programmable outlets enable/disable
Interface
Setting
ENA: Programmable outlets enable DIS: Programmable outlets disable
Parameters 1
Parameters 2
________________________________________________________________________________
LA-ITR-LCD
13
03: Programmable outlets setting
Interface
Setting
Setting the backup time limits in minutes from 0-999 for programmable outlets that connect to non-critical devices on battery mode.
04: LCD display direction setting
Interface
Setting
RAC: the LCD display is horizontal. TOE: the LCD display is vertical.
00: Exit setting Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by mode (off-charging) and make sure the battery is connected. The LCD display is shown as right.
Step 2:
Press and hold the Selection button for 5 seconds to enter Setting mode.
Step 3:
Press the Upbutton (ON/MUTE) to switch to "02" of program list. Then press “Enter“ button to enter value setting of parameter 2. Press the “Up” button to change the value to ENA” to enable the programmable outlet function. Then press “Enter” button again to confirm the setting.
________________________________________________________________________________
LA-ITR-LCD
14
Step 4:
Press the Upbutton (ON/MUTE) again to switch to "03" of program list. Then press “Enter“ button for setting programmable outlet time. Push “Up” button to change the value of backup time according your demand. Then press “Enter” to confirm the setting.
Step 5:
Press Upbutton (ON/MUTE) to switch to "00" of program list. Then press “Enter” button to exit setting menu.
Step 6:
Disconnect AC input and wait until the LCD display is off. The new setting will be activated when turning on the UPS again.
3.6. Operating Mode Description
Operating mode
Description
LCD display
ECO mode
When the input voltage is within voltage-regulated range, UPS will power the output directly from the mains. ECO is an abbreviation of Efficiency Corrective Optimizer. In this mode, when battery is fully charged, the fan will stop working for energy saving.
Buck mode when AC is normal.
When the input voltage is higher than the voltage regulation range but lower than high loss point, the buck AVR will be activated.
Boost mode when AC is normal.
When the input voltage is lower than the voltage regulation range but higher than low loss point, the boost AVR will be activated.
Battery mode
When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 seconds, UPS will backup power from battery.
________________________________________________________________________________
LA-ITR-LCD
15
Operating mode
Description
LCD display
Standby mode
UPS is powered off and no output supply power, but still can charge batteries.
3.7. Faults Reference Code
Fault event
Fault code
Icon
Fault event
Fault code
Icon
Bus start fail
01
x
Inverter output short
14
Bus over
02
x
Battery voltage too high
27
x
Bus under
03
x
Battery voltage too low
28
Inverter soft start fail
11
x
Over temperature
41
x
Inverter voltage high
12
x
Over load
43
Inverter voltage Low
13
x
3.8. Warning Indicator
Warning
Icon (flashing)
Alarm
Low Battery
Sounding every second
Overload
Sounding twice every second
Battery is not connected
Sounding every second
Overcharge
Sounding every second
Site wiring fault
Sounding every second
EPO enable
Sounding every second
Fan Failure
Sounding every second
Over temperature
Sounding every second
Charger failure
Sounding every second
Battery Fault
Sounding every second
________________________________________________________________________________
LA-ITR-LCD
16
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table below.
Symptom
Possible cause
Remedy
No indication and alarm even though the mains is normal.
The AC input power is not connected well.
Check if input power cord firmly connected to the mains.
The AC input is connected to the UPS output.
Plug AC input power cord to AC input correctly.
The icon and the warning code flashing on LCD
display and alarm is sounding every second.
EPO function is activated.
Set the circuit in close position to disable EPO function.
The icon and flashing on LCD display and alarm is sounding every second.
Line and neutral conductors of UPS input are reversed.
Rotate mains power socket by 180° and then connect to UPS system.
The icon and flashing on LCD display and alarm is sounding every second.
The external or internal battery is incorrectly connected.
Check if all batteries are connected well.
Fault code is shown as 27, and
the icon is lighting on LCD display and alarm is continuously sounding.
Battery voltage is too high or the charger is fault.
Contact your dealer.
Fault code is shown as 28, and
the icon is lighting on LCD display and alarm is continuously sounding.
Battery voltage is too low or the charger is fault.
Contact your dealer.
The icon and the icon
are flashing on LCD
display and alarm is sounding twice every second.
UPS is overload
Remove excess loads from UPS output.
Fault code is shown as 43, and the icon is lighting on LCD display and alarm is continuously sounding.
The UPS shut down automatically because of overload at the UPS output.
Remove excess loads from UPS output and restart it.
Fault code is shown as 14 and alarm is continuously sounding.
The UPS shut down automatically because short circuit occurs on the UPS output.
Check output wiring and if connected devices are in short circuit status.
________________________________________________________________________________
LA-ITR-LCD
17
Symptom
Possible cause
Remedy
Fault code is shown as 1, 2, 3, 4, 11, 12, 13 and 41 on LCD display and alarm is continuously sounding.
A UPS internal fault has occurred.
Contact your dealer
Battery backup time is shorter than nominal value
Batteries are not fully charged
Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer.
Batteries defect
Contact your dealer to replace the battery.
The icon and the warning code flashing on LCD
display and alarm is sounding every second.
Fan is locked or not working
Check fans and notify dealer!!
________________________________________________________________________________
LA-ITR-LCD
18
5. Storage and Maintenance
5.1. Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer.
5.2 Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.
________________________________________________________________________________
LA-ITR-LCD
19
MODEL
LA-ITR-800-
LCD
LA-ITR-1100-
LCD
LA-ITR-1500-
LCD
LA-ITR-2000-
LCD
LA-ITR-2500-
LCD
LA-ITR-3000-
LCD
CAPACITY
800 VA /
640 W
1100 VA /
880 W
1500 VA /
1200 W
2000 VA /
1600 W
2500 VA /
2000 W
3000 VA /
2400 W
INPUT
Acceptable Voltage Range
81-145 VAC or 162-290 VAC
Frequency Range
60/50 Hz (auto sensing)
OUTPUT
Voltage Regulation (AC Mode)
110/120 VAC or 208/220/230/240 VAC
Voltage Regulation (Batt. Mode)
±3%(before battery alarm)
Frequency Range (Batt. Mode)
50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio
3:1
Harmonic Distortion
8% max @ 100% linear load, 15% max @ 100% non-linear load (before alarm)
Transfer Time
Typical 2-6 ms, 10ms max.
Waveform (Batt. Mode)
Pure Sine Wave
EFFICIENCY
AC Mode
97%
97%
97%
Buck & Boost Mode
90%
90%
90%
Battery Mode
83%
85%
87%
BATTERY
Standard Model
Battery Type & Number
12 V/7 Ah x 2
12 V/9 Ah x 2
12 V/7 Ah x4
12 V/9 Ah x4
12 V/7 Ah x6
12 V/9 Ah x6
Charging Voltage
27.4 VDC ± 1%
54.8 VDC ± 1%
82.1 VDC ± 1%
Recharge Time
4 hours recover to 90% capacity
Long-run Model
Charging Current
N/A
4 A/8A
N/A
4 A/8A
N/A
4 A/8A
Charging Voltage
27.4 VDC ± 1%
54.8 VDC ± 1%
82.1 VDC ± 1%
PROTECTION
Full Protection
Overload, short, discharge, and overcharge protection
ALARM
Battery Mode
Sounding every 10 seconds
Low Battery
Sounding every second
Overload
Sounding every 0.5 second
Battery Replacement Alarm
Sounding every second
Fault
Continuously sounding
PHYSICAL
Standard Model
Dimension, DXWXH (mm)
380 x 438 x 88
480 x 438 x 88
600 x 438 x 88
Net Weight (kg)
12.9
14.23
21.08
23.1
30.65
32.24
Long-run Model
Dimension, DXWXH (mm)
N/A
380 x 438 x 88
N/A
480 x 438 x 88
N/A
600 x 438 x
88
Net Weight (kg)
10.8
14
18
ENVIRONMENT
Operating Humidity
0-90 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 45dB
MANAGEMENT
Smart RS-232/USB
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 80% of capacity when the output voltage is adjusted to 208VAC. **Product specifications are subject to change without further notice.
6. Specifications