LANSITEC Information Technology 100 00193 User Manual

Temperature and Humidity LoRaWAN Sensor
°
Product Part Number: 100-00053
Document Number: 990-00104
Rev. 0.33 12/2017
contact@lansitec.com
Lansitec temperature and humidity sensor is based on the
advanced LoRa modulation and powered by lithium battery
with 5-year operation time. It offers cost effective LoRaWAN
end device for a variety of application. It’s IP64 enclosure and
long operation time offers low maintenance and is ideal for
outdoor use. Sensor work mode can be adjusted via LoRa
network.
Lansitec sensors family is fully compatible and
plug & play for LoRaWAN network operation.
Applications
Weather station
Heating
Drying
Ventilation & air conditioning systems
Smart Agriculture
Building automation
Key features
Powered by lithium thionyl chloride battery: 5 years of
operation for 1 uplink 2 minutes.
Extended industrial operating temperature:-40
Cto+85°C.
Outdoor use: IP64 enclosure.
Accuracy:
±5% RH typically from 20% RH to 80% RH at 25°C.
±0.3°C typically from +5°C to +60°C.
LoRaWAN compatible:
Class A, uplink rate programmable from 10 seconds to 24 hours.
Change uplink cycle via wireless, configurable by server via
downlink command
Operating frequency bands (Option at order):
900MHz, < 25mW radiated power
0/12
Temperature and Humidity LoRaWAN Sensor
°
1. Product specifications
The tables below give the electrical specifications and performance of the temperature and humidity
measurement.
Table 1 General electrical characteristic
ITEMs Parameter Specifications Unit
Structure Size 84X114X55 mm
Electrical
Characteristics
Operating Range Temperature -40 to 85
power supply 3.6V battery V
Sleep current 5uA uA
Transmit current 120mA@17dBm set mA
45mA@14dBm set mA
Uplink cycle 10 minutes in default minutes
Set by downlink command from server
Battery life More than 5 years with 5minute s cycle years
More than 10 years with 10minutes cycle years
Humidity 0 to 100 %RH
Table 2 Temperature measurement performance
Parameter Condition Min Typ. Max Units Resolution 14bit 0.01 °C
Accuracy Typ. +/-0.3 Operating Range Extended -40 85 °C
Long Term Drift Normal <0.04 °C
Table 3 Humidity measurement performance
Parameter Condition Min Typ. Max Units Resolution 12bit 0.04 %RH Accuracy Typ. +/-3.0 %RH Nonlinearity <0.1 %RH
Operating Range Extended 0 100 %RH
Long Term Drift normal <0.5 %RH
C
1/12
Temperature and Humidity LoRaWAN Sensor
2.
Application Information
2.1 Function
The sensor works in OTAA and Class A mode. DEVEUI, APPEUI and APPKEY are stored in the sensor
and is necessary for joining a network. DEVEUI is labeled at the back of the device. APPEUI, APPKEY
should be provided by each application. Lansitec will help to configure this before shipping.
After power on and join the Lora network, sensor will send registration message to Application
Server(AS). If AS doesn’t reply, sensor will retry for 5 times before switching to default mode
(periodically report mode). Configuration information of the sensor is included in this registration
message for AS to validate.
Sensor starts to work after receiving acceptance response or no AS reply after 5 times registration
trial. Temperature and humidity will be reported to AS periodically. The duty cycle is configurable by
commands from AS. Temperature and humidity acquisition and report period is 10 minutes by
default.
According to LoRaWAN specification, downlink response time is decided by uplink duty cycle, user
should refer the needed response time to choose uplink duty cycle. Detailed downlink and uplink
definition are described below.
2.2 Uplink Message
2.2.1 Register
Bytes 1 1 1 1 2 2
Item TYPE SMODE POWER CFG TH CRC
TYPE field
Bit Name Value Description
7~4 TYPE 0x1 Message type. AS can use it to identify different
uplink messages.
3ADR 0:OFF
1: ON
2~0 MODE 0x01~0x07 Current working scheme which should be one of
ADR (Adaptive Date Rate) status
SMODE
SMODE field
Bit Name Value Description
2/12
Temperature and Humidity LoRaWAN Sensor
7~0 SMODE 0x01: AU920
0x02: CLAA
0x04: CN470
0x08: AS923
0x10: EU433
0x20: EU868
0x40: US915
POWER field
Bit Name Value Description
7~3 POWER 0~31 Configured transmit power (dBm)
2~0 Reserved 0x0 Reserved for future use. If MODE is CLAA, it
Data scheme supported by tracker.
This field is preserved by Lansitec and will be
configured before shipping.
)
indicates the frequency sweep mode of the
tracker:
1: A mode
2: B mode
3: C mode
4: D mode
5: E mode
6: All frequency sweep
Refer to CLAA China 470M-510M Band Using
network technology requirements for detailed
information.
CFG field
Bit Name Value Description
7~4 DR 0~15 Data Rate(DR0~DR15).
3 REPTIND 0~1 Indicates whether report the H&T if the value is
the same. Default value is 0, means always
report.
2~0 Reserved 0x0 Reserved for future use.
TH field
Bit Name Value Description
15~0 TH 1~65535 The period of temperature and humidity report,
unit 10s.
CRC field
Bit Name Value Description
15~0 CRC CRC16 of previous fields with TYPE bits set to 0,
the polynomial is . AS only need to compare this
data field with the AS stored one to judge
whether configuration changed.