LANSITEC Information Technology 100 00159 User Manual

LoRa Platinum Temperature Sensor
Document Number: 990-02101
Rev. 1.22 12/2017
contact@lansitec.com
General Description
the advanced LoRa modulation and powered by lithium
LoRaWAN end device for a variety of application. It's long
operation time offers low maintenance and is ideal for
industry use. Sensor work mode can be adjusted via LoRa
network.
Lansitec sensors family is fully compatible and plug & play
for LoRaWAN network operation.
Lansitec sensors can also work with Lansitec Wireless Data
Transfer Unit (P/N: 100-00175) for low cost deployment.
Please contact us for further information.
Applications
Busway temperature monitor
Weather station
Heating
Ventilation & air conditioning systems
Smart Agriculture
Building automation
Key features
Powered by lithium thionyl chloride battery: 5 years of
operation for 1 uplink 5 minutes.
Extended industrial operating temperature:-40°C to +85°C.Accuracy:
±1.5°C typically from -200°C to +200°C.
LoRaWAN compatible:
Class A, uplink rate programmable from 30 seconds to 24 hours.
Change uplink cycle via wireless, configurable by server via
downlink command
Operating frequency bands (Option at order):
900MHz, < 25mW radiated power
0/12
LoRa Platinum Temperature Sensor
1. Product s pecifications
The tables below give the electrical specifications and performance of the temperature and humidity
measurement.
Table 1 General electrical characteristic
Protocol LoRaWan1.0.2
Frequency CN470, EU868, US915, AS923, CLAA
SF=7 ≤ -126dBm
Sensitivity
Operating Current
Tem p e r a t u r e Ra n g e -200~200℃
Accuracy ±1.5℃
Standby Time 6 years @25℃ 17dBm 5 minutes per transmission
Operating Temperature -40~+85℃
Storage Temperature -55~+85℃
Operating Humidity 5%~95%
On/Off Support
Sensor Quantity 4, external, cable length is optional
Antenna External
Dimension Aluminum, 76x46x110mm
Battery Non-chargeable lithium battery 38Ah
Communication Distance >1km in urban area
SF=10 ≤ -136dBm
SF=12 ≤ -142dBm
30uA@sleep mode
Max 138mA@17dBm
1/12
LoRa Platinum Temperature Sensor
2.
Application Information
2.1 Function
The sensor works in OTAA and Class A mode. DEVEUI, APPEUI and APPKEY are stored in the sensor
and is necessary for joining a network. DEVEUI is labeled at the back of the device. APPEUI, APPKEY
should be provided by each application. Lansitec will help to configure this before shipping.
After power on and join the Lora network, sensor will send registration message to Application
Server(AS). If AS doesn’t reply, sensor will retry for 3 times before switching to default mode
(periodically report mode). Configuration information of the sensor is included in this registration
message for AS to validate.
Sensor starts to work after receiving acceptance response or no AS reply after 3 times registration
trial. Temperature will be reported to AS periodically. The duty cycle is configurable by commands
from AS. Temperature acquisition and report period is 5 minutes by default.
According to LoRaWAN specification, downlink response time is decided by uplink duty cycle, user
should refer the needed response time to choose uplink duty cycle. Detailed downlink and uplink
definition are described below.
2.2 Uplink Message
2.2.1 Register
Bytes 1 1 1 1 2 2
Item TYPE SMODE POWER CFG TH CRC
TYPE field
Bit Name Value Description
7~4 TYPE 0x1 Message type. AS can use it to identify different
uplink messages.
3ADR 0:OFF
1: ON
2~0 MODE 0x01~0x07 Current working scheme which should be one of
ADR (Adaptive Date Rate) status
SMODE
SMODE field
Bit Name Value Description
7~0 SMODE 0x01: AU920 Data scheme supported by tracker.
2/12
LoRa Platinum Temperature Sensor
0x02: CLAA
0x04: CN470
0x08: AS923
0x10: EU433
0x20: EU868
0x40: US915
POWER field
Bit Name Value Description
7~3 POWER 0~31 Configured transmit power (dBm)
2~0 Reserved 0x0 Reserved for future use. If MODE is CLAA, it
This field is preserved by Lansitec and will be
configured before shipping.
)
indicates the frequency sweep mode of the
tracker:
1: A mode
2: B mode
3: C mode
4: D mode
5: E mode
6: All frequency sweep
Refer to CLAA China 470M-510M Band Using
network technology requirements for detailed
information.
CFG field
Bit Name Value Description
7~4 DR 0~15 Data Rate(DR0~DR15).
3 REPTIND 0~1 Indicates whether report the temperature if the
value is the same with before. Default value is 0,
means always report.
2~0 Reserved 0x0 Reserved for future use.
TH field
Bit Name Value Description
15~0 TH 1~65535 The period of temperature report, unit 10s.
CRC field
Bit Name Value Description
15~0 CRC CRC16 of previous fields with TYPE bits set to 0,
the polynomial is . AS only need to compare this
data field with the AS stored one to judge
whether configuration changed.
3/12