
Operating and
Installation Instruction
Ultrasonic heating and cooling meter
ULTRAHEAT®T230
13.06.2017
Translation
T230
Landis+Gyr GmbH Subject to change without prior notice 13.06.2017 1
Note: In the following text, the term meter refers to both
the heat meter and the cooling meter unless they are
otherwise differentiated.
1. General
1.1 Use
The T230 is used as a meter for heating or cooling consumption measurement in systems with water.
The meter consists of a high-tech plastic volume measurement
unit, two temperature sensors connected in a fixed position and
an electronic unit that calculates the energy consumption from
the volume and temperature difference.
The meter combines modern microcomputer technology with
innovative ultrasonic measuring technology for which no m echanically moving parts are necessary.
This technology is thus wear free, robust and largely maintenance free. High precision and long-term stability guarantee
precise and equitable cost accounts.
Note: The meter cannot be opened without damaging
the security seal.
1.2 General notes
The meter left the factory in a faultless condition where safety
is concerned. The manufacturer will provide additional technical support on request. Calibration relevant security seals on
the meter must not be damaged or removed. Otherwise the
guarantee and calibration validity of the meter will lapse.
Keep the packaging so that you can transport the meter in
its original packaging following expiry of the calibration validity.
Lay all cables at a minimum distance of 500 mm to high
voltage and high frequency cables.
A relative humidity of < 93% at 25 °C is permissible (without
condensation).
Avoid cavitation in the whole system due to overpressure
i.e. at least 1 bar at qp and approx. 2 bar at qs (applies for
approx. 80 °C).
2. Safety Information
The meters may only be used in building service
engineering plants and only for the applications described.
The local regulations (installation etc.) must be adhered to.
Adhere to the operating conditions according to the
dial plate during use. Non-adherence can cause hazards and the guarantee will lapse.
Do not under any circumstances carrying out welding,
drilling or soldering work close to the meter.
The meter is only suitable for circulating water in
heating systems.
The meter is not suitable for drinking water.
Adhere to the AGFW requirements regarding circulating water (FW510).
Only personnel, trained in the installation and operation of meters in heating and cooling systems, may
install and remove the meter.
Only install or remove the meter when the pipes are
pressure-less.
After installing the meter, check the leak-tightness of
the system.
Guarantee and calibration validity will lapse if the
calibration relevant security seal is broken.
Only clean the meter from outside with a soft, lightly
wetted cloth. Do not use any spirit or cleaning solvent.
As far as disposal is concerned, the meter is a waste
electronic appliance in the sense of European Directive 2012/19/EU (WEEE) and it must not be disposed of as domestic waste. The relevant national,
legal regulations must be observed as the appliance
must be disposed of via the channels provided for this
purpose. The local and currently valid legislation must
be observed.
The meter contains lithium batteries. Do not dispose of
the meter and the batteries with domestic waste.
Observe the local stipulations and laws on disposal.
You can return the lithium batteries to the manufacturer for appropriate disposal following use. When shipping please observe legal regulations, in particular,
those governing the labelling and packaging of hazardous goods.
Do not open the batteries. Do not bring batteries into
contact with water or expose to temperatures above
80 °C.
The meter does not have any lightning protection.
Ensure lightning protection via the in-house installation.
3. Installation
To install the meter proceed as follows:
Determine the place of installation in line with the inscrip-
tion on the meter.
Note: At a heating meter the mounting place of the
flow sensor cold side is equivalent to return .
The mounting place of the flow sensor hot side is
equivalent to flow .
Note: At a cooling meter the mounting place of the
flow sensor hot side is equivalent to the return .
The mounting place of the flow sensor cold side is
equivalent to flow .
Observe the dimensions of the meter and check whether
there is sufficient space available.
Rinse the system thoroughly before installing the meter.
Fit the meter vertically or horizontally between two slide
valves so that the arrow on the housing and the flow direction match. Also observe the installation situations and the
following examples of installation.
Note: Only use the rubber EPDM flat seals that are
supplied.

Landis+Gyr GmbH Subject to change without prior notice 13.06.2017 2
The meter must not be exposed tensions or forces caused
by by pipes or fittings. If this cannot be permanently guaranteed, it is necessary to improve the point of installation or
fix the lines in position, by means of suitable connecting
brackets for example.
Fit the temperature sensors in the same circuit as the me-
ter. Observe the admixtures.
Seal the temperature sensor and the fittings to protect
against manipulation.
If you install the meter for cooling metering, follow the ap-
propriate notes.
Recommendation: If you are installing several meters, the
same installation conditions must be consistent for all meters.
Installation notes
Note: When installing the meter the locally applicable
installation regulations for meters must be observed.
Inlet or outlet sections are not necessary. If you install the
meter in the common return of two circuits, determine a place
of installation with a minimum distance of 10 × DN from the Tpiece. This distance ensures a good thorough mixing of the
different water temperatures. You can install the temperature
sensors in T-pieces, ball valves, directly immersed or in pockets depending on the version. The temperature sensor ends
must reach to at least the middle of the pipe cross section.
Note: Protect the meter against damage through impacts or vibrations at the place of installation.
On activation, open the slide valves slowly.
The meter is made of a robust and very stable material.
Only use open ended spanners to fit the meter. Only insert
the open ended spanner on the holding surfaces provided.
The maximum range of the tightening torque from 15 Nm
for ¾" meter thread or 25 for 1" meter thread must be adhered to during installation. For aligned pipe joints an angle
of rotation of the cupling nut from 120 … 180° (¾") or
90 … 120° (1") from contact of the seal with cupling nut is
sufficient.
Recommendation: Do not install the meter on the pressure
side of a pump. Maintain a minimum distance of 10 x DN on
the pressure side.
Note: During installation it must be ensured that no
water can enter the electronic unit during operation.
Examples of installation (directly immersed sensor)
You can install the meter in any position e.g. vertically or horizontally. In order to avoid accumulation of air and disruption in
operation, fit the meter in a vertical installation position and not
in the uppermost area of a pipeline.
* This position is not permitted for
cold meters and in cases where
moisture can enter the electronic
unit due to condensation (e.g.
during an interruption in the
summer).
Fig.1
Fig. 2
Fig. 3: Installation for circulation with admixing; placement of temperature sensors
Fig. 4: Installation for circulation with throttling configuration for example (flow sensor
in flow direction before control valve / differential pressure regulating valve)
Installation notes for sensor adapter set
A mounting set is included for meters with 5.2 × 45 mm temperature sensor. With this you can fit the temperature sensor
directly immersed into an insert or a ball valve for example.
1. Install with O-ring at the point of installation with the fit-up
aid/pen provided.
2. Place both halves of the plastic bolting round the 3 notches
of the temperature sensor.
3. Press the bolting together and screw the bolting hand tight
into the point of installation until it comes to a stop (tightening torque 3 ... 5 Nm).
Fig. 5: Mounting adapter set
3.1 Installation for cooling metering
Fit the electronic unit separate to the volume measurement
unit, e.g. on the wall for water temperatures below 10° C. Make
a loop downwards in order to prevent condensation running
along the connected lines into the electronic unit. Install the
temperature sensors into the pipe from below.
Note: Wall adapter plates are available as an accessory.
3.2 Electronic unit
The ambient temperature of the electronic unit must not exceed 55 °C. Avoid direct sunlight.

Landis+Gyr GmbH Subject to change without prior notice 13.06.2017 3
Aligning electronic unit
Proceed as follows to align the electronic unit:
Turn the electronic unit to the left or right through 90° or
through 180° as required.
Note: When turning through 45° the electronic unit is
not connected tightly to the volume measurement unit.
Wall fitting (split fitting)
Fit the meter to the wall at water temperatures below 10 °C.
Proceed as follows:
Fit the wall adapter plate (available as an accessory).
Turn the electronic unit through 45°.
Pull the electronic unit away from the volume measurement
unit.
Place the electronic unit on the wall adapter at an angle of
45° and turn it into position.
3.3 Power supply
The meter is equipped with a long life battery for 6 or 11 years
of operation. You can take the operating time from the dial
plate.
Warning: Do not open the batteries. Do not bring
battery into contact with water or expose to temperatures above 80 °C. Dispose of used batteries at suitable collection points.
3.4 Interfaces and Communication
The meter is equipped with an optical interface in accordance
with EN 62056-21 as standard. If the meter is equipped with
the option "M-Bus", it is supplied with a 2-wire cable which you
can extend by fitting a junction box.
3.5 Temperature sensor
Note: Wires must not be separated, shortened or
extended.
Note: Both display range and data displayed can differ
from this description depending on the appliance parameterisation. Certain button functions can also be
blocked.
The meter consists of a 7-digit LCD displaying various values.
Fig.6: LCD
Identification previous year value
Identification previous month value
Switching the display
Proceed as follows to switch between the display values:
Press the button briefly (for less than 2 sec.) to show the
next line of the current loop.
After the last line is displayed, the first line comes up again.
Hold down the button (longer than 3 sec.) in order to dis-
play the next loop.
After the last loop is displayed, the first loop comes up again.
If you do not operate the meter for 30 sec. in the user loop
"LOOP 0", the meter changes to the standard display. If you do
not operate the meter for 30 min. in the loops "LOOP 1 ... 4",
the meter changes to the standard display.
User loop “LOOP 0”
In case of error: message
with error code
Alternate current
temperature hot and
cold side in 2 s cycles
Previous month's values “LOOP 2”
Max. power in 2 s cycles
with date stamp
Energy quantity and
volume on set day
Max. temperature hot
side in 2 s cycles with
date stamp
Max. flow on set day in
2 s cycles with date
stamp
Max. temperature cold
side in 2 s cycles with
date stamp
General/Communication "LOOP 3"
Primary address (only
for M-Bus)
Secondary address
7-digit - for M-Bus
Code entry for test /
para operation

Landis+Gyr GmbH Subject to change without prior notice 13.06.2017 4
4.1 Monthly values
The meter stores the following values for 24 months on the
monthly set day
Missing time
Volume
Energy
and the maxima with date stamp for
Flow
Power
Temperature hot side
Temperature cold side
4.2 Parameterisation
When the LCD displays the code entry, you can call up the
parameterisation operation by inputting the code. You can set
date and M-Bus primary address in the parameterisation operation for example. For more detail see separate parameterisation instruction.
5. Getting started
For activation proceed as follows:
Open the slide valves slowly.
Check the heating system for leak-tightness and bleed air
out carefully.
Press the button on the meter briefly.
The message "F0" disappears after 10 sec.
Check the measured values for flow and temperatures for
plausibility.
Vent the heating system until the flow display is stable.
Fit the user locks to the fittings and the temperature sen-
sors. The scope of supply includes two self lock seals for
sealing a sensor and the connecting fitting.
Read the meter status for energy, volume, operation and
missing time and note the values.
Error messages for incorrect installation:
Error "incorrect flow direction (negative)"
Check that the flow direction arrows on the volume measurement unit
match the flow direction of the system. If the directions do not match,
turn the volume measurement unit through 180°.
Error "negative temperature difference"
Check whether the sensors are installed correctly. If the sensors are
not installed correctly, change the installation position of the sensors.
Heat meter:
Temperature sensor in the flow-pipe with higher temperatures; temperature sensor in return-pipe with lower temperature
Cooling meter:
Temperature sensor in the flow-pipe with lower temperatures; temperature sensor in return-pipe with higher temperature
6. Functional Details
If the respective operation thresholds are exceeded and flow
and temperature difference are positive, the meter summates
the energy and the volume.
If the operate margin is gone below a "u" is displayed at a leading
point for the flow, power and temperature display.
For a positive flow the activity display appears in the user
loop in the LCD.
All segments of the display are switched on for control purposes during the segment test. The flow, power and temperature
difference are recorded with the appropriate +/- signs.
The operating hours are counted from the first connection of
the power supply. The meter saves "operating time with flow"
as soon as a positive flow is recognised. Missing hours are
summated if there is a fault and the meter is thus unable to
take a measurement.
Stored maximum values are marked with an " " in the lower
right hand area of the LCD.
7. Error codes
The meter continuously runs a self-diagnosis and can thus
recognise and display various installation or meter errors:
Check flow or installation direction; correct if necessary
if necessary in exchange with:
Negative temperature difference
Check installation point of the
temperature sensors; exchange if
necessary
if necessary in exchange with:
Air in the measurement unit/pipe,
bleed air from pipe (delivery
condition)
Interruption in the hot side temperature sensor
Inform service department
Interruption in cold side temperature sensor
Inform service department
Electronics for temperature evaluation defective
Inform service department
F4
Inform service department
Short-circuit hot side temperature
sensor
Inform service department
Short-circuit cold side temperature
sensor
Inform service department
Error in the internal memory
holding
Inform service department
Errors F1, F2, F3, F5 or F6 for
longer than 8 hours, recognition of
attempts to manipulate.
No further measurements are
carried out.
Measure dependent on error
code. Error message F8 must be
reset by service department.
Inform service department

Landis+Gyr GmbH Subject to change without prior notice 13.06.2017 5
8. Technical Data
Note: The information on the meter must be observed!
A (EN 1434) for indoor installation
*) according to 2014/32/EU Directive on Measuring Instruments
< 93% rel. humidity at 25 °C, without condensation
Housing protection rating
IP 54 according to EN 60529
Battery for 6 or 11 years
Operation threshold f. T
Temperature difference T
Temperature measurement
range
Always, cable length 1.5 m
Pt 500 according to EN 60751, not detachable
Pt 500, 2 wire technology
Bolb sensor ø 5.2 × 45 mm
IP 65 according to EN 60529
5… 90 °C
National type approvals may be different.
Overall length and connection
9. Asymetric mounting (temperature sensor)
The meter can be mounted asymetric, too. This means one tempera-
ture sensor is directly immersed in the volume measuring tube, where-
as the other temperature sensor is mounted in a protection pocket. For
the lower value of the temperature difference is then 5 K valid at the
respective lower flow limit qi. At this kind of installation the mentioned
protection pockets must be used.
Furthermore the national regulations of the respective country have to
be observered.
Type of protection
pocket
Rack length [mm]
from upper edge
[mm]
*) The sensor pocket must be installed in isolation.

Landis+Gyr GmbH Subject to change without prior notice 13.06.2017 6
10. Declaration of conformity
Landis+Gyr GmbH
Humboldtstrasse 64
90459 Nuremberg
Germany