Lancer 9000, MAX II Service Manual

INSTALLATION AND SERVICE MANUAL
FOR THE
MAX II DISPENSER
LANCER SERIES 9000
REV. 03/22/05 P.N. 28-0564/01
This manual supersedes and replaces 28-0564, dated 12/19/03.
6655 LANCER BLVD. • SAN ANTONIO, TEXAS 78219 USA • (210) 310-7000
"Lancer" is the registered trademark of Lancer
Copyright — 2005 by Lancer, all rights reserved.
SPECIFICATIONS
DIMENSION
Width 16 7/8 inches (429 mm) Depth 24 3/4 inches (629 mm) Height (without legs) 25 1/2 inches (648 mm)
WEIGHT
Shipping 160 pounds (72.5 kg) Empty 146 pounds (66.2 kg) Operating 220 pounds (99.8 kg)
WATER REQUIREMENTS
CAUTION
IF WATER SOURCE EXCEEDS 50 PSIG (3.45 BAR) A RECOMMENDED WATER REGULATOR ASSEMBLY (PN 18-0253/02) MUST BE USED TO LIMIT WATER PRESSURE TO 50 PSIG (3.45 BAR). FAILURE TO USE REGULATOR WILL RESULT IN IMPROPER PERFORMANCE OF DISPENSER.
Minimum flowing pressure of 25 PSIG (1.72 BAR) Maximum static pressure of 50 PSIG (3.45 BAR)
CARBON DIOXIDE (CO2) REQUIREMENTS
Minimum pressure of 70 PSIG (4.92 kg/cm2, 4.83 BAR) Maximum pressure of 80 PSIG (5.62 kg/cm2, 5.52 BAR)
ICE BANK WEIGHT
27 - 30 pounds (12.2 to 13.6 kg)
DRINK CAPACITY
215 – 12 oz drinks under 40°F (4.4°C) at 4 drinks per minute with 75°F (23.9°C) ambient, inlet water, and inlet syrup using 1/3 HP, 115 V, 60 Hz refrigeration system.
Please refer to the Lancer web site (www.lancercorp.com) for information relating to Lancer Installation and Service Manuals, Instruction Sheets, Technical Bulletins, Service Bulletins, etc.
FAX SALES
• NORTH AMERICA – 210-310-7245 • INTERNATIONAL SALES – 210-310-7242 • CUSTOMER SERVICE – 210-310-7242 •
• LATIN AMERICA – 210-310-7245 • EUROPE – 32-2-755-2399 • PACIFIC – 61-8-8268-1978 •
TABLE OF CONTENTS
SPECIFICATIONS ...................................................................................................................................COVER
TABLE OF CONTENTS ......................................................................................................................................i
DISPENSER INSTALLATION HIGHLIGHTS.....................................................................................................ii
1. INSTALLATION ...........................................................................................................................................1
1.1 RECEIVING .......................................................................................................................................1
1.2 UNPACKING ......................................................................................................................................1
1.3 UNPACKING INSTALLATION KITS ...................................................................................................1
1.4 SELECTING A COUNTER LOCATION .............................................................................................1
1.5 MOUNTING THE DISPENSER..........................................................................................................1
1.6 CONNECTING THE DRAIN...............................................................................................................1
1.7 FILLING UNIT WITH WATER ............................................................................................................1
1.8 CONNECTING TO ELECTRICAL POWER .......................................................................................2
1.9 CONNECTING TO WATER SUPPLY.................................................................................................2
1.10 CONNECTING THE CO2 SUPPLY....................................................................................................3
1.11 CONNECTING TO REMOTE BAG-IN-BOX (BIB) SYRUP PUMPS..................................................3
1.12 CONNECTING TO REMOTE PRESSURIZED SYRUP SUPPLY......................................................3
1.13 PURGING THE CARBONATION SYSTEM .......................................................................................3
1.14 ADJUSTING WATER FLOW ..............................................................................................................3
1.15 ADJUSTING WATER TO SYRUP RATIO (BRIX) ..............................................................................3
2. SCHEDULED MAINTENANCE ...................................................................................................................4
2.1 DAILY .................................................................................................................................................4
2.2 WEEKLY.............................................................................................................................................4
2.3 MONTHLY ..........................................................................................................................................4
2.4 EVERY SIX MONTHS........................................................................................................................4
2.5 YEARLY..............................................................................................................................................4
3. DISPENSER CLEANING AND SANITIZING ..............................................................................................4
3.1 GENERAL INFORMATION ................................................................................................................4
3.2 AMBIENT PROCESS.........................................................................................................................5
3.3 ALTERNATE CLEANING AND SANITIZING AGENTS ......................................................................5
4. CONNECTION FOR PLAIN WATER PRODUCT........................................................................................6
5. TROUBLESHOOTING.................................................................................................................................6
5.1 WATER LEAKAGE AROUND NOZZLE .............................................................................................6
5.2 MISCELLANEOUS LEAKAGE ...........................................................................................................6
5.3 INSUFFICIENT WATER FLOW..........................................................................................................6
5.4 INSUFFICIENT SYRUP FLOW..........................................................................................................6
5.5 ERRATIC RATIO ...............................................................................................................................6
5.6 NO PRODUCT DISPENSED .............................................................................................................7
5.7 WATER ONLY DISPENSED, NO SYRUP; SYRUP ONLY DISPENSED, NO WATER .....................7
5.8 NO WATER, JUST SYRUP ................................................................................................................7
5.9 VALVE WILL NOT SHUT OFF ...........................................................................................................7
5.10 SYRUP ONLY DISPENSED. NO WATER, BUT CO2 GAS DISPENSED WITH SYRUP ................8
5.11 EXCESSIVE FOAMING .....................................................................................................................8
5.12 WATER CONTINUALLY OVERFLOWS FROM WATER BATH INTO DRIP TRAY ...........................8
5.13 COMPRESSOR STARTS AND CONTINUES TO RUN UNTIL FREEZE UP AND
WILL NOT CUT OFF..........................................................................................................................8
5.14 WARM DRINKS..................................................................................................................................8
5.15 COMPRESSOR DOES NOT START (NO HUM), CONDENSER FAN MOTOR DOES NOT
RUN AND NO ICE BANK...................................................................................................................8
5.16 COMPRESSOR DOES NOT START (NO HUM), BUT CONDENSER FAN MOTOR RUNS............9
5.17 COMPRESSOR DOES NOT START BUT HUMS .............................................................................9
5.18 COMPRESSOR STARTS BUT DOES NOT SWITCH OFF START WINDING .................................9
5.19 COMPRESSOR STARTS AND RUNS A SHORT TIME BUT SHUTS OFF ON OVERLOAD ...........9
5.20 COMPRESSOR RUNS NORMALLY, BUT WATER LINE IS FROZEN............................................10
5.21 COMPRESSOR CYCLES ON AND OFF FREQUENTLY DURING THE INITIAL PULLDOWN
AND/OR NORMAL OPERATIONS...................................................................................................10
5.22 CIRCUIT BREAKER POPPING .......................................................................................................10
5.23 BIB PUMP DOES NOT OPERATE WHEN DISPENSING VALVE IS OPENED ..............................10
5.24 BIB PUMP OPERATED BUT NO FLOW .........................................................................................10
5.25 BIB PUMP CONTINUES TO OPERATE WHEN BAG IS EMPTY ...................................................10
5.26 BIB PUMP FAILS TO RESTART AFTER BAG REPLACEMENT ....................................................10
i
5.27 BIB PUMP FAILS TO STOP WHEN DISPENSING VALVE IS CLOSED.........................................10
5.28 LOW OR NO CARBONATION .........................................................................................................10
6. ILLUSTRATIONS, PARTS LISTINGS, WIRING DIAGRAMS, AND PLUMBING DIAGRAMS ................11
6.1 MAX II, ASSEMBLY.....................................................................................................................11-12
6.2 REFRIGERATION DECK ASSEMBLY........................................................................................13-14
6.3 CABINET ASSEMBLY.................................................................................................................15-16
6.4 CARBONATOR DECK ASSEMBLY .................................................................................................17
6.5 WATER REGULATOR ASSEMBLY..................................................................................................18
6.6 CARBONATOR WATER/SYRUP LINES ASSEMBLIES.............................................................19-20
6.7 CONTROL HOUSING.................................................................................................................21-22
6.8 WIRING DIAGRAM .........................................................................................................................23
ii
DISPENSER INSTALLATION HIGHLIGHTS
Listed below are ten critical elements which will aid in a successful installation.
1. Fill water bath until water overflows from tank overflow tube.
2. The carbonator pump motor must be disconnected from the power supply (refer to basic manual - Page 2, Section 1.8A) prior to connection to water supply for initial build up of ice bank. Failure to do so will result in automatic shut off of carbonator (see Item 6 below) or damage to the pump.
3. If this dispenser is installed in an area that is susceptible to ±10% variation of the nominal line voltage, consider installing a surge protector or similar protection device.
4. There is a five (5) minute delay which prevents the compressor and condenser fan from starting until the delay has lapsed. If electrical current is interrupted, there is always a five (5) minute delay before the compressor starts.
5. The unit is equipped with a protective timer for the carbonator pump motor, set for three (3) minutes. If the carbonator motor has timed out, it must be manually reset by either momentarily unplugging the unit or switching off the on/off switch (if present). Once power is restored, the five (5) minute compressor delay would be in effect.
6. Supply Water Pressure: Minimum–25 PSIG (1.76 kg/cm
2
); Maximum: 50 PSIG (3.5 kg/cm2) If pressure is over
50 PSIG, a water pressure regulator must be used.
7. On units with the built in water regulator, the regulator must be removed if inlet water pressure is less than 25 PSIG.
8. CO
2 Pressure: Recommend nominal pressure 70 PSIG (4.92 kg/cm
2
, 4.83 BAR).
9. Bag in box syrup packages must be within six (6) feet from unit when internal syrup pumps are being used.
10.Valve Adjustment: Make sure drink temperature is below 40°F (4.4°C) before adjusting brix.
TABLE OF CONTENTS (CONTINUED)
1
1. INSTALLATION
1.1 RECEIVING
Each unit is tested and thoroughly inspected before shipment. At the time of shipment, the carrier accepts the unit and any claim for damages must be made with the carrier. Upon receiving units from the delivering carrier, carefully inspect carton for visible indication of damage. If damage exists, have carrier note same on bill of lading and file a claim with the carrier.
1.2 UNPACKING
A. Cut band and remove. B. Remove top portion of carton by lifting up. C. Remove accessory kit and loose parts from top packaging. D. Remove top inner carton pad and corners. E. Lift unit up by plywood shipping base and remove lower portion of carton. F. Inspect unit for concealed damage and if evident, notify delivering carrier and file a claim against
same.
G. Remove plywood shipping base from unit by moving unit so that one side is off the counter top
or table allowing access to screws on the bottom of the plywood shipping base.
NOTE
If unit is to be transported, it is advisable to leave the unit secured to the plywood base.
H. If unit is to be installed with optional legs, assemble legs to unit by tilting unit. DO NOT LAY
UNIT ON ITS SIDE OR BACK.
1.3 UNPACKING INSTALLATION KITS
A. Inspect kits for concealed damage and if evident, notify delivering carrier and file a claim against
same.
B. Each kit contains a list of the parts and a drawing showing the proper assembly of the parts.
1.4 SELECTING A COUNTER LOCATION
A. Select a location close to a properly grounded electrical outlet and water supply that meet the
requirements as scheduled on the specification page.
CAUTION
FAILURE TO MAINTAIN SPECIFIED CLEARANCE WILL CAUSE THE COMPRESSOR TO OVERHEAT AND WILL RESULT IN COMPRESSOR FAILURE.
B. Condenser air is drawn in the front and sides of the unit, and discharged out the top of the unit.
A minimum of eight (8) inches (203 mm) clearance must be maintained over the top of the unit.
1.5 MOUNTING THE DISPENSER
A. The dispenser is designed to be permanently mounted and sealed to the counter or installed on
4” legs.
B. For permanent mounting use Lancer sealant kit (P/N15-0010) to seal the dispenser to the
counter.
C. For leg mounting, use Lancer leg kit (PN 82-1704).
NOTE
NSF listed units must be sealed to the counter or have four (4) inch legs installed.
1.6 CONNECTING THE DRAIN
A. Remove cup rest. Lift splash plate up and pull out and down on the bottom to remove. B. Remove the drip tray from the unit and connect the drain tube to the drain fitting located on the
back.
C. Route the drain tube to a suitable drain and replace the unit’s drip tray.
1.7 FILLING UNIT WITH WATER
A. Remove the bonnet from the unit. B. Remove the plastic plug (located on the front of the unit’s carbonator deck) from the unit’s fill
hole.
C. Using a funnel or tube, fill the water bath compartment with water until it flows out of the
2
overflow tube into the drip tray.
CAUTION
THE WATER BATH COMPARTMENT MUST BE FILLED WITH WATER BEFORE PLUGGING IN THE UNIT, OTHERWISE THE COMPRESSOR DECK AND CONDENSER FAN MAY NOT OPERATE PROPERLY.
D. Replace the plug.
1.8 CONNECTING TO ELECTRICAL POWER
WARNING
THIS UNIT MUST BE PROPERLY ELECTRICALLY GROUNDED TO AVOID POSSIBLE FATAL ELECTRICAL SHOCK OR SERIOUS INJURY TO THE OPERATOR. THE POWER CORD IS PROVIDED WITH A THREE PRONG GROUNDED PLUG. IF A THREE-HOLE GROUNDED ELECTRICAL OUTLET IS NOT AVAILABLE, USE AN APPROVED METHOD TO GROUND THE UNIT.
DO NOT USE EXTENSION CORDS WITH THIS UNIT. DO NOT “GANG” TOGETHER WITH OTHER ELECTRICAL DEVICES ON THE SAME OUTLET.
CAUTION
FAILURE TO DISCONNECT THE MOTOR POWER SUPPLY WILL DAMAGE THE CARBONATOR MOTOR AND PUMP AND VOID THE WARRANTY.
A. If the unit is equipped with a built-in carbonator, disconnect the power supply to the carbonator
motor by disconnecting the four pin connector located near the top of the electrical control box on the refrigeration deck.
B. Check the dispenser serial number plate for correct electrical requirements of unit. Do not plug
into wall electrical outlet unless the current shown on the serial number plate agrees with local current available.
C. Route the power supply cord to a grounded electrical outlet of the proper voltage and
amperage rating, and plug in the unit. This will turn on the refrigeration system and allow it to start cooling while completing the rest of the installation. The agitator motor will start immediately, but the compressor and fan motor will not start until the five (5) minute delay has elapsed.
1.9 CONNECTING TO WATER SUPPLY
CAUTION
IF WATER SOURCE EXCEEDS 50 PSIG (3.52 KG/CM2) A WATER REGULATOR KIT MUST BE USED TO LIMIT WATER PRESSURE TO 50 PSIG (3.52 KG/CM2). FAILURE TO USE A WATER REGULATOR WILL RESULT IN IMPROPER PERFORMANCE OF DISPENSER.
A. Using tubing and fittings from the installation kit, connect tubing assembly to water source.
DO NOT CONNECT TO DISPENSER AT THIS TIME.
B. Flush water supply line thoroughly.
NOTE
If the water source is above 50 PSIG (3.52 kg/cm2), cut tubing assembly and install Water Regulator Kit (PN 18-0253/02) as shown in kit instruction sheet.
The water supply must be protected by means of an air gap, a backflow prevention device (located upstream of the CO
2 injection system) or another approved method to comply with
NSF standards. A backflow prevention device must comply with ASSE and local standards.
It is the responsibility of the installer to ensure compliance.
C. Route through hole in counter and through opening behind splash plate and connect to
carbonator pump using a flare seal washer (PN 05-0017). Use a back-up wrench to prevent damage to carbonator pump.
D. Leave 12 inches (305 mm) of extra tubing length below the counter for servicing and moving
the dispenser. E. Turn on water supply and check for leaks. F. Using test gauge assembly (PN 22-0138), set regulator at a maximum of 50 PSIG (3.52 kg/cm
2
).
3
1.10 CONNECTING THE CO
2 SUPPLY
A. Connect high pressure CO2 regulator assembly to CO2 cylinder. Use a new CO2 tank washer
if regulator does not have built-in o-ring seal. B. Place CO2 cylinder in service location under counter, etc., and secure it with a safety chain. C. Using tubing and fittings from installation kit connect tubing assembly to tank mount regulator
using flare seal washer (PN 05-0011). Use a back-up wrench to prevent damage to regulator
assembly. D. Route gas line through hole in counter and through opening behind the dispenser splash plate. E. Leave 12 inches (254 mm) of extra tubing length below the counter for servicing and moving the
dispenser. F. Connect tubing directly to the carbonator CO
2 inlet check valve.
W
ARNING
DO NOT TURN ON THE CO2 SUPPLY AT THIS TIME
1.11 CONNECTING TO REMOTE BIB SYRUP PUMPS
A. Locate the remote BIB, syrup supply and pumps in a convenient location. B. Attach the syrup supply tubes to the dispensers syrup inlet fittings (located behind the splash
plate) using a 1/4” Oetiker clamp for each syrup flavor. C. Route the syrup supply tubes to the remote syrup pumps. D. Complete installation of the remote syrup pump system following the manufacturer’s
instructions.
1.12 CONNECTING TO REMOTE PRESSURIZED SYRUP SUPPLY
A. Locate the five gallon syrup containers and the CO
2 cylinder and regulator set in a convenient
location. B. Attach the syrup supply tube assembly to the dispensers syrup inlet fittings (located behind the
splash plate) using a 1/4” Oetiker clamp for each syrup flavor. C. Route the syrup supply tubes to the five gallon syrup containers and attach them to the
appropriate syrup flavor. D. Attach a CO2 supply line from each of the five gallon syrup containers to the low pressure
regulator and pressurize the containers.
1.13 PURGING THE CARBONATION SYSTEM
A. The relief valve for the built-in carbonator is located on the right hand side of the unit’s
carbonator deck. Lift the yellow lever on the top of the relief valve until water flows from the
holes in the relief valve. Then release the relief valve. B. Reconnect the power supply to the carbonator pump. C. Back off on the CO
2 regulator pressure adjusting screw all the way. Open the CO2 cylinder
handle slowly. Turn the CO2 pressure regulator up slowly to 75 PSIG (5.1 bar). D. Open a dispensing valve until water and syrup are flowing steadily from the valve. E. Repeat procedure “D” for each valve. F. Check all of the unit’s syrup, water and CO2 connections for leaks and repair if necessary.
NOTE
To check for CO2 leaks, close the valve on the CO2 cylinder and observe if the pressure to the
system drops with the cylinder valve closed for five (5) minutes. Open the cylinder valve after
check.
G. Replace the unit’s bonnet, splash plate and cup rest.
1.14 ADJUSTING WATER FLOW
A. The refrigeration unit should have been running for a least one hour before you attempt to brix
the valves. The drink temperature should be no higher than 40°F (4.4°C) when the brix is set.
This is best done after the unit has made an ice bank. B. Adjust the water flow for each valve according to the valve manufacturer’s recommendations.
1.15 ADJUSTING WATER TO SYRUP (RATIO) BRIX
Adjust the water/syrup ratio (brix) according to the valve manufacturer’s recommendations.
4
2. SCHEDULED MAINTENANCE
2.1 DAILY
A. Remove the nozzle and diffuser from each valve and wash them in warm water. B. Remove the cup rest and wash in warm soapy water. C. Pour warm soapy water into the drip tray and wipe with a clean cloth. D. With a clean cloth and warm soapy water, wipe off all of the units exterior surfaces. E. Replace the cup rest, valve diffusers and valve nozzles.
2.2 WEEKLY
A. Check the flow and brix of each valve following the brixing instructions given in sections 1.14
and 1.15.
B. Remove the unit’s bonnet and check the level of water in the water bath. Replenish as required,
and replace the bonnet.
2.3 MONTHLY
A. Unplug the dispenser from its power source. B. Remove the bonnet, and clean the dirt from the unit’s condenser using a soft brush. C. Replace the bonnet and plug in the unit.
2.4 EVERY SIX (6) MONTHS
A. Clean and sanitize the unit using the appropriate procedures outlined in Section 3 of this
manual.
2.5 YEARLY
A. Clean water bath interior, including evaporator coils and refrigeration components. B. Clean the entire exterior of the unit. C. Sanitize syrup lines.
NOTE
Because of difficulty in rinsing, detergent solution should not be introduced into the carbonator.
3. DISPENSER CLEANING AND SANITIZING
3.1 GENERAL INFORMATION
A. Lancer equipment (new or reconditioned) is shipped from the factory cleaned and sanitized in
accordance with NSF guidelines. The operator of the equipment must provide continuous maintenance as required by this manual and/or state and local health department guidelines to ensure proper operation and sanitation requirements are maintained.
NOTE
The cleaning and sanitizing procedures provided herein pertain to the Lancer equipment identified by this manual. If other equipment is being cleaned, follow the guidelines established by the manufacturer for that equipment.
IMPORTANT
Water lines are not to be disconnected during the cleaning and sanitizing of syrup lines to avoid contamination.
B. Cleaning and sanitizing should be accomplished only by trained personnel. Sanitary gloves are
to be used during cleaning and sanitizing operations. Applicable safety precautions must be observed. Instruction warnings on the product being used must be followed.
C. Recommended Preparation of Cleaning Solutions.
1. Cleaning solutions (for example, Ivory Liquid, Calgon, etc.) mixed with clean, potable water at a temperature of 90° to 110° Fahrenheit should be used to clean equipment. The mixture ratio, using Ivory Liquid, is one (1) ounce of cleanser to two (2) gallons of water. A minimum of four (4) gallons of cleaning mixture should be prepared.
NOTE
Extended lengths of product lines may require that an additional volume of solution be prepared.
5
2. Any equivalent cleanser may be used as long as it provides a low-sudsing, non-perfumed, easily rinsed mixture.
D. Recommended Preparation of Sanitizing Solutions.
1. Sanitizing solutions should be prepared in accordance with the manufacturer’s written recommendations and safety guidelines. Follow manufacturer’s requirements so that the solution provides 100 parts per million (PPM) (100mg/L) available chlorine at a temperature of 90°F to 120°F. A minimum of four (4) gallons of sanitizing solution should be prepared.
NOTE
Extended lengths of product lines may require that an additional volume of solution be prepared.
2. Any sanitizing solution may be used as long as it is prepared in accordance with the manufacturer’s written recommendations and safety guidelines, and provides 100 PPM (100mg/L) available chlorine.
3.2 AMBIENT PROCESS
A. The ambient process is the most common method for cleaning and sanitizing dispenser
equipment. The detergent should be as recommended and the sanitizer should be low pH (7.0)
chlorine solution. B. Disconnect syrup containers and remove product from tubing. C. Rinse the lines and fittings with clean room temperature water to remove all traces of residual
product. D. Fill lines with a low-sudsing, non-perfumed, and easily rinsed detergent solution. The solution
should be prepared in accordance with the manufacturers recommendations. Make sure the
lines are completely filled and allow to stand for at least 10 minutes. E. Flush the detergent solution from the lines with clean water. Continue rinsing until testing with
phenolphthalein shows that the rinse water is free of residual detergent. F. Fill the lines with a low pH (7.0) chlorine solution containing at least 100 PPM (100mg/L)
available chlorine. Flow sanitizing solution through dispenser until output tests to full 100 PPM
(100mg/L) concentration. Allow to stand for 15 minutes. G. Reconnect syrup containers and ready Unit for operation.
W
ARNING
REMOVE SANITIZING SOLUTION FROM DISPENSER AS INSTRUCTED. RESIDUAL SANITIZING SOLUTION LEFT IN SYSTEM COULD CREATE HEALTH HAZARD.
H. Draw drinks to refill lines and flush the chlorine solution from the dispenser.
NOTE
Please note that a fresh water rinse cannot follow sanitization of equipment. Purge only with the
end use product. This is an NSF requirement.
I. Taste the beverage to verify that there is no off taste.
3.3 ALTERNATE CLEANING AND SANITIZING AGENTS
The above approach to cleaning and sanitizing is strongly recommended. However, the Division Quality Assurance Manager may approve the following cleaning and sanitizing agents.
A. Chlorinated alkaline detergents. These compounds may be used as the cleaning agent, but
may not be used as combined cleaner/sanitizer. B. Iodophors may be substituted for chlorine as the sanitizing agent.
CAUTION
IODOPHORS AND QUATERNARY AMMONIUM COMPOUNDS (QUATS) ARE BROAD CLASSES OF COMPOUNDS. SOME MEMBERS OF EACH GROUP CAN CAUSE SERIOUS PROBLEMS WITH FOAMING, DISTORTION OR DISCOLORATION OF POLYMERIC PARTS, POOR RINSIBILITY, AND OFF-TASTE. THE RINSIBILITY AND OFF-TASTE PROBLEMS HAVE BEEN ESPECIALLY PREVALENT WITH QUATS. BECAUSE OF THE POTENTIAL PROBLEMS, APPROVAL MUST BE GRANTED BY THE DIVISION QUALITY ASSURANCE MANAGER TO SPECIFIC COMPOUNDS. THIS APPROVAL SHOULD BE BASED UPON TESTING IN THE LABORATORY.
6
C. Quaternary ammonium compounds may be used as a combined cleaner-sanitizer but are
generally not recommended. These compounds are not to be utilized at concentrations exceeding 100 PPM (100 mg/L), or that concentration specified in local regulations, which ever is lower.
4. CONNECTION FOR PLAIN WATER PRODUCT
4.1 If plain water product is required, a separate plain water manifold is utilized for easy connection to
any of the three (3) valves on the left side of the dispenser. It may be necessary to loosen the screws on the carbonator pump plate to facilitate this changeover.
4.2 De-pressurize unit by disconnecting the water inlet.
4.3 Remove retaining clip from the fitting behind the faucet plate, and pull the soda line out of the
fitting.
4.4 Remove the cap from the correspondingwater line in the same manner.
4.5 Insert the water line into the fitting behind the water plate and replace the retaining clip.
4.6 Replace the cap onto the soda line and install the retaining clip.
4.7 Repeat for other valves if desired.
4.8 Re-tighten carbonator pump plate screws if loosened (see Step 4.1).
5. TROUBLESHOOTING
TROUBLE
CAUSE REMEDY
5.1 Water leakage around A. Damaged or improperly A. If damaged, replace. If improperly
nozzle. installed o-ring above diffuser. installed, adjust.
5.2 Miscellaneous leakage. A. Gap between parts. A. Tighten appropriate retaining screws.
B. Damaged or improperly B. Replace or adjust appropriate
installed o-rings. o-rings.
5.3 Insufficient water flow. A. Insufficient incoming supply A. Verify incoming supply water
water pressure. pressure is a minimum of 25 PSI.
B. Shutoff on mounting block B. Open shutoff fully.
not fully open.
C. Foreign debris in water flow C. Remove water flow control from
control. upper body and clean out any
foreign material to ensure smooth free spool movement.
D. Foreign debris in water pump D. Remove water pump strainer and
strainer clean.
5.4 Insufficient syrup flow. A. Insufficient CO2 pressure to A. Adjust CO2 pressure to 80 PSI
BIB pumps. (minimum 70 PSI) for BIB pumps.
B. Shutoff on mounting block B. Open shutoff fully.
not fully open.
C. Foreign debris in syrup flow C. Remove syrup flow control from
control. upper body and clean out any
foreign material to ensure smooth free spool movement.
5.5 Erratic ratio. A. Incoming water and/or syrup A. Check pressure and adjust.
supply not at minimum flowing pressure.
B. Foreign debris in water B. Remove flow controls from upper
and/or syrup flow controls. body clean out any foreign material
to ensure smooth free spool movement.
5.6 No product dispensed. A. Water and syrup shutoffs A. Open shutoffs fully. on mounting block not fully open.
B. The key switch on an electric B. Turn key switch to ON position.
valve is in the OFF position.
C. Cup lever arm or ID panel C. Repair.
actuator on electric valve is not actuating the switch.
D. Electric current not reaching D. Check electric current supplied to
electric valve. valve. If current is adequate, check
solenoid coil and switch, and replace if necessary.
E. Improper or inadequate E. Remove valve from mounting block
water or syrup supply. and open shutoffs slightly and
check water and syrup supply. If no supply, check dispenser for freeze-up or other problems.
F. Transformer failure. F. Reset transformer circuit breaker.
If breaker pops again, refer to Section 5.22.
5.7 Water only dispensed, A. Water or syrup shutoff on A. Open shutoff fully.
no syrup; or syrup mounting block not fully only dispensed, no open. water. B. Improper or inadequate B. Remove valve from mounting block
water or syrup supply. and open shutoffs slightly and
check water and syrup supply. If no supply, check dispenser for freeze-up or other problems. Ensure BIB connection is engaged.
C. BIB supply too far from C. Check syrup pump manufactuer’s
dispenser. recommendations for maximum
distance pumps can be located the dispenser.
D. CO2 pressure too low. D. Check the CO2 pressure to the
pump manifold to ensure it is between 70 and 80 PSI.
E. Stalled or inoperative BIB E. Check CO2 pressure and/or
pump. replace pump.
F. Kinked line. F. Remove kink or replace line.
5.8 No water just syrup. A. Low level. A. Add water until it flows from over
flow tube. B. Unit not level. B. Level unit and add water. C. Syrup in water bath. C. Melt ice bank and remove all
water. Refill. Locate possible
syrup leak area and repair. D. Water cage is out of position. D. Reposition water cage. E. PCB relay sticking. E. Check continuity of compressor
relay. Compressor should
time-out in five (5) minutes. F. Refrigerant leak. F. Find leak and recharge unit (if
unit is not frozen). G. Check water supply. G. Turn on water and shut unit OFF,
then ON to reset carbonator. H. Carbonator timed out. H. Turn unit OFF then ON to reset
carbonator. I. PCB malfunctioning. I. Replace PCB.
5.9 Valve will not shut off. A. Cup lever may be sticking or A. Correct or replace lever. binding.
B. Switch not actuating freely. B. Check switch for free actuation.
7
TROUBLE
CAUSE REMEDY
8
5.10 Syrup only dispensed. A. Improper water flow to A. Check for water flow to dispenser No water, but CO
2 gas dispenser. (see Section 5.3).
dispensed with syrup. B. Carbonator pump motor has B. Reset by turning the unit OFF and
timed out. and then ON by using the ON/OFF
switch on top of the unit, or unplugging unit momentarily.
C. Liquid level probe not C. Check connections of liquid level
connected properly to PCB. probe to PCB assembly. D. Faulty PCB assembly. D. Replace PCB assembly. E. Faulty liquid level probe. E. Replace liquid level probe. F. Water bath frozen. F. Thaw water bath and repair faulty
component. (See refrigeration related symptoms.)
G. Water line frozen. G. Refer to 5.13 listed below.
5.11 Excessive foaming. A. Incoming water or syrup A. Correct prior to dispenser. temperature too high. Consider larger dispenser or
pre-cooler.
B. CO2 pressure too high. B. Adjust CO2 pressure downward,
but not less than 70 PSI.
C. Water flow rate too high. C. Readjust and reset ratio. Refer to
Section 1.15.
D. Nozzle and diffuser not D. Remove and reinstall properly.
properly installed.
E. Nozzle and diffuser not clean. E. Remove and clean. F. Air in BIB lines. F. Bleed air from BIB lines. G. Poor quality ice. G. Check quality of ice used in drink. H. High beverage temperature. H. Check refrigeration system.
5.12 Water continually A. Loose water connection(s). A. Tighten water connections.
overflows from water B. Flare seal washer leaks. B. Replace flare seal washer. bath into drip tray. C. Faulty water coil. C. Replace water coil.
5.13 Compressor starts and A. PCB malfunctioning or faulty A. Disconnect ice bank probe from
continues to run until ice bank probe. PCB. freeze up and will not 1. If compressor continues to run, cut off. replace PCB.
2. If compressor stops, replace ice bank probe.
B. Ice bank probe positioned B. Check positioning of ice bank
improperly. probe, and replace if needed.
C. Ice bank probe shorted to ground. C . Replace ice bank probe.
NOTE: First check to ensure that the three (3) minute carbonator timer has not timed out. Turn unit off,
and then on. If the pump shuts off in less than 30 seconds, the dispenser is not frozen.
5.14 Warm drinks. A. Restricted airflow. A. Check clearances around sides, top, and inlet of unit. Remove objects blocking airflow through grill.
B. Dispenser connected to hot B. Switch to cold water supply.
water supply.
C. Refrigeration system not C. Refer to Sections 5.15 - 5.19.
running. D. Refrigerant leak. D. Repair and recharge. E. Condenser fan motor not E. Replace condenser fan motor.
working. F. Dirty condenser. F. Clean condenser. G. Dispenser capacity exceeded. G. Add pre-cooler or replace with
larger dispenser.
5.15 Compressor does not A. There is a five (5) minute A. Allow for five (5) minute delay to start (no hum), compressor and condenser lapse. condenser fan motor fan delay. does not run and B. Ice bank probe not B. Fill water reservoir until water no ice bank. completely submerged. flows from overflow tube.
(Section 5.15 continued on next page)
TROUBLE CAUSE REMEDY
(Section 5.15 continued from previous page)
C. Circuit breaker or fuse tripped. C. Reset breaker or replace fuse.
If problem persists:
1. Determine reason and correct.
2. Electrical circuit overloaded; switch to another circuit.
D. Inadequate voltage. D. Measure voltage across common
and run terminal on compressor. Voltage must not drop below 90%
of rated voltage. E. PCB malfunctioning. E. Replace PCB assembly. F. Incorrect wiring. F. Refer to wiring diagram and
correct. G. Faulty ice bank probe. G. Replace ice bank probe. H. Transformer failure. H. Reset transformer circuit breaker. If
breaker pops again refer to Section
5.25.
I. Ice bank probe not connected I. Connect ice bank probe to PCB.
properly to PCB.
5.16 Compressor does not A. Compressor relay or A. Replace compressor relay or start (no hum), but overload malfunctioning. overload. condenser fan motor B. Inadequate voltage. B. Measure voltage across common runs. and run terminal on compressor.
Voltage must not drop below 90% of rated voltage.
C. Incorrect wiring. C. Refer to wiring diagram and
correct.
D. Compressor malfunctioning. D. Replace compressor or deck.
5.17 Compressor does not A. Inadequate voltage. A. Measure voltage across common start but hums. and run terminal on compressor.
Voltage must not drop below 90% of rated voltage.
B. Incorrect wiring. B. Refer to wiring diagram and
correct.
C. Starting relay malfunctioning. C. Replace starting relay. Be sure to
use correct relay. Failure to use correct relay will cause compressor failure.
D. Compressor malfunctioning. D. Replace compressor or deck.
5.18 Compressor starts but A. Inadequate voltage. A. Measure voltage across common does not switch off and run terminal on compressor. start winding (will run B. Incorrect wiring. B. Refer to wiring diagram and for only a few seconds correct. before internal overload C. Starting relay malfunctioning. C. Replace starting relay. Be sure to switches compressor use correct relay. Failure to use off). correct relay will cause compressor
failure.
5.19 Compressor starts and A. Dirty condenser. A. Clean the condenser. runs a short time but B. Insufficient or blocked air B. Remove all obstructions and allow shuts off on overload. flow. for minimum clearances of eight (8)
inches (203 mm) over top.
C. Inadequate voltage. C. Measure voltage across common
and run terminal on compressor. Voltage must not drop below 90% of rated voltage.
D. Incorrect wiring. D. Refer to wiring diagram and
correct.
E. Defective condenser fan E. Replace condenser fan motor.
motor. F. Refrigerant leak. F. Repair and recharge. G. Compressor malfunctioning. G. Replace compressor or deck.
9
TROUBLE
CAUSE REMEDY
10
5.20 Compressor runs A. Low water level in water A. Add water to water bath until water normally, but water bath. runs out of overflow into drip tray. line is frozen. B. Syrup in water bath. B. Drain water from water bath and
refill with clean water. C. Water cage is out of position. C. Reposition water cage. D. Low freon charge/slow freon D. Find and repair leak. Recharge
leak system.
5.21 Compressor cycles A. PCB malfunctioning A. Replace PCB assembly. on and off frequently B. Defective probe. B. Replace probe. during the initial pulldown and/or normal operations.
5.22 Circuit breaker A. Valve wire harness shorted to A. Detect short by disconnecting input popping. itself or to faucet plate. faston to keylock and single pin
connector. Restore power if breaker doesn’t pop. Then valve wire harness is shorted, if OK, reconnect.
B. PCB is bad. B. Detect short by disconnecting J1
connector (24 VAC input) from PCB. Restore power, if breaker doesn’t pop. Then replace PCB. If breaker does pop, then PCB is OK. Reconnect J1 connector.
C. Secondary wire harness is C. If it does not pop, locate short in
bad. secondary harness between
transformer, PCB and valve wire harness.
D. Transformer failure. D. Detect short by disconnecting both
transformer fastons and restore power. If breaker does pop, replace transformer.
5.23 BIB pump does not A. Out of CO2, CO2 not turned A. Replace CO2 supply, turn on CO2 operate when on, or low CO2 pressure. supply, or adjust CO2 pressure to dispensing valve is 70-80 PSI. opened. B. Out of syrup. B. Replace syrup supply.
C. BIB connector not tight. C. Fasten connector tightly. D. Kinks in syrup or gas lines. D. Straighten or replace lines.
5.24 BIB pump operated A. Leak in syrup inlet or A. Replace line. but no flow. outlet line.
B. Defective BIB pump check B. Replace BIB pump.
valve.
5.25 BIB pump continues to A. Leak in suction line. A. Replace line. operate when bag is B. Leaking o-ring on pump B. Replace o-ring. empty. inlet fitting.
5.26 BIB pump fails to restart A. BIB connector not on tight. A. Tighten BIB connector. after bag replacement. B. BIB connector is stopped up. B. Clean out or replace BIB
connector.
C. Kinks in syrup line. C. Straighten or replace line.
5.27 BIB pump fails to stop A. Leak in discharge line or A. Repair or replace discharge line. when dispensing valve fittings. is closed. B. Empty BIB. B. Replace BIB.
C. Air leak on inlet line or bag C. Repair or replace.
connector.
5.28 Low or no carbonation. A. Low or no CO2. A. Check CO2 supply. Adjust CO2
pressure to 70 PSI.
B. Excessive water pressure. B. Water regulator should be set at
50 PSI.
C. Worn or defective carbonator C. Replace carbonator pump.
pump.
TROUBLE CAUSE REMEDY
6. ILLUSTRATIONS, PARTS LISTINGS, WIRING DIAGRAMS, AND PLUMBING DIAGRAMS
6.1 MAX II, ASSEMBLY
11
16
15
1
5
11
7
12
2
3
18
17
4
19
6
14
15
8
13
SEE SECTION 6.3
9
10
6. ILLUSTRATIONS, PARTS LISTINGS, WIRING DIAGRAMS, AND PLUMBING DIAGRAMS
6.1 MAX II, ASSEMBLY (CONTINUED)
12
ITEM PART NO. DESCRIPTION
1 05-2381 Top Cover, Bonnet
2 05-2384 Back, Bonnet
3 05-2390 Lens, Flavor Label
4 05-2383 Side, Right, Bonnet
5 05-2382 Side, Left, Bonnet
6 05-2385 Trim, Marquee
7 05-2386 Lens, Marquee
8 23-0483 Cup Rest
9 54-2394 Drip Tray Assy
10 05-2388 Base, Wrapper
11 82-3626 Bonnet Assy, Max II
12 04-0406 Screw, 8 - 32 x 0.375
13 04-0074 Nut Clip, 10 - 24
14 04-0236 Screw, 10 - 24 x 0.375
OPTIONAL MERCHANDISING PANELS:
15 05-2389 Lens, Wrapper, Left and Right
16 05-2391 Wrapper, Left
17 05-2393 Wrapper, Back
18 05-2394 Lens, Wrapper, Back
19 05-2392 Wrapper, Right
(Not Shown)
- 05-0786 Plug, Bonnet
- 52-1754/01 PCB Assy, Lamp Driver
- 12-0225 Bi-Pin Lampholder
- 11-0017 Splice, Wire
- 11-0011 Terminal, Female, 18 AWG
- 05-1678 Standoff, PCB
- 12-0047/02 Lamp, F8T5/D
- 04-0429 Rivet, AD-34-BS, for Lampholder
- 52-2113/01 Lead Assy, Extension, Marquee
- 11-0015 Housing, 2 Socket, Male
13
6.2 REFRIGERATION DECK ASSEMBLY
12
10
14
56
16
17
5
39
36
14
11
40
33
14
18
32
37
31
15
30
29
38
28
21
27
14
19
58
20
58
54
60
59
24
25
2
7
4
6
3
55
53
48
60
51
14
8
23
13
22
24
25
49
14
1
9
14
52
50
26
34
35
47
42
43
46
42
43
41
44
44
44
ITEM PART NO. DESCRIPTION
82-1248/02 Deck Assy Refrig, R-134a,
230V/50Hz, Export
82-1428/02 Deck Assy Refrig, R-134a,
115V/60Hz, Domestic
1 51-5107/01 Sub-Assy, Compressor Deck
2 50-0200/01 Insulation, Compressor Deck
3 04-0063 Washer, Flat
4 89-0014 Cover, Hole
5 82-1373/01 Evaporator Coil, R134a
6 52-1773/01 Probe Assy, IBC
7 04-0394 Screw, 6 - 32 x 0.500
8 51-0068 Handle
9 04-0574 Washer
10 52-0903/02 Control Housing Assy
11 30-5118 Cover, Control Housing
12 06-2221 Label, Wiring Diagram
13 02-0032 Washer
14 04-0504 Screw, 8 - 18 x 0.375
15 52-1209 Lead Assy, Ground
16 02-0041 Seal
17 REF Capacitor, Carbonator
26-0374 Capacitor, Carbonator,
115V/60Hz
26-0377 Capacitor, Carbonator,
230V/50-60Hz
18 REF Transformer
25-0047 Transformer, 115V/60Hz
25-0048 Transformer, 230V/50-60Hz
19 REF Motor, Assy
52-1262 Motor, Assy, 230V/50Hz-60Hz
52-1261 Motor, Assy, 115V/60Hz
20 30-5113 Bracket, Agitator
21 05-0495 Propeller, 2.062 Dia.
22 05-0502 Propeller, 2.250 Dia.
23 02-0040 Seal, Extrusion
24 04-0032 Nut, Nylok, 1/4 - 20
25 04-0033 Washer, Flat (0.281 ID)
26 83-0033 Compressor, R-134a,
115V/60Hz, Domestic
83-0034 Compressor, R-134a,
230V/50Hz, Export
27 02-0114 Grommet
28 04-0537 Washer, Flat (0.467 ID)
29 03-0150 Retainer, Clip
30 Ref Relay
12-0005 Relay, 115V/60Hz
12-0031 Relay, 230V/50-60Hz
31 REF Overload
12-0339 Overload, 115V/60Hz
12-0290 Overload, 230V/50-60Hz
32 13-0066 Cover Terminal
33 03-0040 Bale Strap
34 47-0344 Tube, Process
35 47-0718 Tube, Compressor (Hi Side)
36 47-0724 Tube, Return (Lo Side)
37 51-0061 Accumulator
38 50-0211 Boot
30 50-0205 Insulation, Tube
40 50-0159 Insulation, Tube
41 23-0985 Condenser
42 50-0201 Baffle, Condenser
43 30-5112 Plate, Retainer
44 04-0518 Rivet, 0.1250 x 0.328
45 30-5867 Shield, Air,Left
46 30-5865/01 Shroud, Fan Top
47 50-0249 Barrier, long
48 30-5866 Shroud, Fan, Bottom
49 REF Motor, Fan
91-0007 Motor, Fan, 115V/60Hz
91-0009 Motor, Fan, 230V/50-60Hz
50 07-0354 Fan Blade
51 04-0060 Nut
52 02-0413 Silencer
53 30-5864 Bracket, Fan Motor
54 23-0765 Dryer Cap Assy
55 47-0698 Tube, Condenser Out
56 52-2008 Harness Assy, Secondary
57 04-0110 Nut, 8 - 32
58 04-0576 Washer, Int., Tooth
59 06-0877 Label, Ground
60 04-0059 Screw, 8 - 36 x 0.375
14
6.2 REFRIGERATION DECK ASSEMBLY (CONTINUED)
ITEM PART NO. DESCRIPTION
6.3 CABINET ASSEMBLY
15
27
20
21
22
18
25
17
19
23
12
26
3
11
24
10
7
8
3
9
6
26
28
1
2
5
3
4
16
13
3
14
3
3
15
ITEM PART NO. DESCRIPTION
R – 82-3586 Cabinet Assy, Delta II
1 51-0675/01 Wrapper Assy
R 2 07-0347 Cover Plate
R 3 04-0504 Screw, 8 - 18 x 0.375 AB
R 4 07-0405 Plug, Key Lock
R 5 12-0097 Key Switch
R 6 06-0881 Label, Key Switch
R 7 04-0545 Screw, 8 - 16 x 0.780 Plastite
R 8 30-0587 Bracket, Right
9 30-5114/02 Front Plate
R 10 03-0062 Clip, Retaining
R 11 04-0077 Screw, 4 - 20 x 0.250 AB
R 12 06-0851 Label, Overflow
R 13 30-5850 Plate, Bottom
R 14 30-5221/02 Leg Bracket Assy
R 15 81-0112 Legs
R 16 30-0319 Splash Plate
R 17 82-1312 Drain Assy
R 18 04-0068 Screw, 10 - 24 x 0.375 FH,
Machine
R 19 04-0074 Nut, Clip
R 20 11-0015 Socket, Housing
R 21 13-0005 Bushing
R 22 30-5125 Faucet Plate, 6 valve
R 23 52-1214 Harness Assy, 6 valve (6 each,
Item 12 & 13)
R 24 30-0588 Bracket, Left
R 25 50-0248 Insulation, Front
R 26 50-0151 Insulation, Side, Left and Right
R 27 50-0150 Insulation, Rear
R 28 82-3584 Tank Assy, Foamed
R in margin indicates new, changed, or
realigned information
16
6.3 CABINET ASSEMBLY (CONTINUED)
I
TEM PART NO. DESCRIPTION
82-0887/01 Deck Assy, Carbonator,
115V/60Hz
82-0943/01 Deck Assy, Carbonator,
220V/50-60 Hz
1 51-5122 Plate Assy, Carbonator Deck
2 50-0247 Insulation, Carbonator Deck
R 3 05-0435 Sleeve, CO2 In
R 4 06-0877 Ground Label
R 5 05-0436 Sleeve, Probe
R 6 04-0033 Washer, 1/4”
R 7 04-0334 Screw, 1/4 - 20 X 1.000,
Round Head
R 8 04-0711 Caplug
R 9 06-0856 Water Fill Label
R 10 89-0014 Cover, Hole
11 86-0085 Pump, 100 GPH
R 12 07-0017 Clamp with Screw
6.4 CARBONATOR DECK ASSEMBLY
17
R 13 REF Carbonator Motor
91-0063 Carbonator Motor,115V/60Hz
91-0065 Carbonator Motor 220V/50-
60Hz
R 14 04-0061 Screw, 8-18 X 0.500 AB
R 15 01-0987 Elbow, Brass
R 16 02-0194 Grommet,250 OD X 0.156 ID X
0.049 W
R 17 01-1515 Pump outlet Assy
R 18 REF Lead Assy, Ground
(Compressor Deck to Carbonator Deck)
R 19 04-0110 Nut, No. 8 - 32
R 20 04-0576 Washer, No. 8 Internal Tooth
R in margin indicates new, changed, or
realigned information
I
TEM PART NO. DESCRIPTION
14
16
15
13
17
18
To Compressor Deck
12
11
19
20
10
9
8
7
6
5
4
3
1
2
6.5 WATER REGULATOR ASSEMBLY
ITEM PART NO. DESCRIPTION
- 18-0253/02 Regulator Assembly, Water
R 1 18-0252 Regulator
R 2 01-1429 Nut, 7/18 - 18, UNS
R 3 07-0481/01 Bracket, Regulator
4 01-0446 Fitting, Barb
R 5 04-0504 Screw, 8 - 18 x 0.375, AB
R 6 07-0438 Clamp, Oetiker
R 7 08-0264 Tubing, 0.375 ID
R 8 01-0234 Stem, Hose, 3/8
R 9 01-0232 Nut, Swivel, 3/8
R 10 05-0017 Washer, Seal, Flare, Nylon
R in margin indicates new, changed, or
realigned information
18
10
8, 9
6
7
1
2
3
6
4
4
5
6.6 CARBONATOR, WATER/SYRUP LINE ASSEMBLIES
19
19
20
16
15
14
13
12
10
3
4
11
8
9
4
18
4
5
6
17
7
8
9
10
6
17
7
29
19
28
9
2
1
30
21
9
9
7
6
9
7
6
23
8
17
22
4
17
24
8
9
25
27
26
34
35
36
32
33
31
9
ITEM PART NO. DESCRIPTION
R 1 82-3566 Carbonator Assy
2 02-0096 Washer
R 3 52-2892 Probe Assy
17-0469 Fitting Assy, CO2 IN
R 4 05-0011 Flare Seal Washer, 7/16”
R 5 01-1311 Fitting Sub Assy, CO2 IN
R 6 02-0003 O-Ring
7 01-0674 Ball
R 8 01-0689 Sleeve
R 9 02-0005 O-Ring
R 10 01-0669 Body, Check Valve, 7/16”, MF
R – 54-0066 Relief Valve Assy
R 11 02-0023 Seal
R 12 05-0536 Stem
R 13 03-0024/02 Spring
R 14 05-0537 Body, Relief Valve
R 15 05-0525 Lever
R 16 81-0196 Pin
R 17 03-0021 Spring
R 18 48-2374 Manifold Assy, Plain Water Out
R 19 04-0082 Nut, 10-24
R – 23-1388 Water Cage Assy
R 20 23-0767 Cage Assy, Water
R 21 48-2375 Tube Assy, Water
R – 17-0485 Double Check Valve Assy
R 22 01-1466 Fitting, Check Valve
R 23 01-0670 Body, Check Valve, Middle
R 24 01-0673 Body, Check Valve, 3/8, MF
R 25 03-0153 Retainer, Adapter
R 26 05-2256 Adapter, Dole to Dole
R 27 05-1580 Adapter, Cap, Long
R 28 48-2329 Manifold Assy, Carbonated
Water
R 29 05-0017 Flare Seal, 3/8
R 30 30-9435 Bracket, Syrup line
R 31 48-2323 Tube Assy, Syrup, No. 1
R 32 48-2324 Tube Assy, Syrup, No. 2
R 33 48-2325 Tube Assy, Syrup, No. 3
R 34 48-2326 Tube Assy, Syrup, No. 4
R 35 48-2327 Tube Assy, Syrup No. 5
R 36 48-2328 Tube Assy, Syrup, No. 6
R in margin indicates new, changed, or
realigned information
20
6.6 CARBONATOR, WATER/SYRUP LINE ASSEMBLIES (CONTINUED)
ITEM P
ART NO. DESCRIPTION
1/2 A
(SPARE)
F2
2AG
HS1
HYBRID MODULE
C2
RLY2
U1
VR1
J1
_
1
BR1
1
J2
1
J3
RLY1
1
NO TIME
C5
R1
C4
J5
MADE IN U.S.A.
J4
6.7 CONTROL HOUSING (ALSO SEE SECTION 6.8, WIRING DIAGRAM)
21
10
9
8
7
6
11
5
4
3
2
1
20
12
12
19
13
14
15
16
17
18
ITEM PART NO. DESCRIPTION
- 52-0900/02 Control Housing, With ON/OFF Switch
- 52-0903/02 Control Housing, Without Kill Switch
1 30-5109/02 Control Housing
2 52-0868/01 Lead Assy, ON/OFF Switch
3 13-0047 Stand-off
4 52-1423/01 PCB Assy
5 52-2027 Lead Assy, Probe Ground
(Non-Carb Units Only)
6 52-2061 Lead Assy, EIBC
7 12-0190 Terminal Block
8 04-0477 Screw, 8 - 32 X 0.375"
9 04-0504 Screw, 8 - 16 X 0.375"
10 30-5108/01 Cover, Control Box
11 11-0186 Jumper, 4-Position
12 13-0059 Bushing
13 13-0028 Strain Relief
14 52-1219 Power Cord (Pigtail)
15 52-0904 Harness Assy, Trans #1
16 52-0905 Harness Assy, Trans #2
17 52-0906 Harness Assy, Comp #1
18 52-0907 Harness Assy, Comp #2
19 11-0008 Tie Wrap
20 12-0089 Switch
6.7 CONTROL HOUSING (ALSO SEE SECTION 6.8, WIRING DIAGRAM) (CONTINUED)
22
23
6.8 WIRING DIAGRAM
W
IMPORTANT
8
16
15714
PLAIN
AGITATOR
MOTOR
B/WB/W
65
BLK
B
W
TB1
TO PLAIN WATER VALVE
(FIELD INSTALLED OPTION)
BRG
W
J3
IN
TERM2
B
1
OUT
TERM1
2
10 9
W
B
J4
BB
1
J1
TERM4
13
W
IN
BRG
J2
PCB,IBC
OUT
TERM3
B
B
12411
W
3
3
G
GW B
9000 and 9100 Series Only
BWG
G
CARBONATOR
PROBE
W
R
B/W
B
COMPRESSOR
9000 and 9100 Series Only
B
RIBBED
BLK
B
B
CARBONATOR
MOTOR
CAPACITOR
WBWB
1 4
B
WBW
FAN
MOTOR
G
1. WHEN STARTING UNIT OR IF CURRENT IS INTERRUPTED, THERE IS A FIVE (5) MINUTE DELAY BEFORE THE COMPRESSOR/FAN STARTS.
2. THERE IS A THREE (3) MINUTE PROTECTION TIMER ON THE CARBONATOR PUMP MOTOR. IF THE MOTOR HAS TIMED OUT, CHECK WATER SUPPLY AND RESET BY MOMENTARILY DISCONNECTING POWER.
9000 and 9500 Series Only
KEY
V A L V E
S
(5
OR
6)
SWITCH
S1
S2
S3
S4
S5
S6
OPTIONAL MARQUEE
B
B
B
B
B
B
POWER
CORD
BLU BRNG
B
W
W
W
W
W
W
LINE 24 V
B
B
KILL
SWITCH
ELECTRONIC
ICE BANK
PROBE
RIBBED
BLK
RECIRCULATING MOTOR
9100 SERIES ONLY
SYM.
DESCRIPTION CHASSIS GROUND CHAMFER PIN OPTIONAL WATER
BOOST PCB,IBC J4
CONTROL BOX
CARBONATOR
MOTOR
®
LABEL, WIRING DIAGRAM 06-2221
(Continued from previous page)
PromoVen, S.A. - Argentina
Contact: Rafael Mendoza Juncal 858 - Piso 3 Depto. “L” (1062) Buenos Aires Argentina Phone: (54.11)4394.7654 FAX: (54.11)4394.1193 e-mail: promoven@fibertel.com.ar
depositopromoven@fibertel.com.ar
Bras Sulamericana LTDA. - Brasil
Contact: Fabio Queiroz Rua. Dr. Ladislau Retti, 1400 Parque Alexandre Cotia Sao Paulo - Brasil CEP: 06714-150 Phone: 55-11-4612-1122 FAX: 55-11-4612-2219 e-mail: fabio.queiroz@bras.com.br
Lancer Chile Ltda. - Chile
Contact: Heriberto Concha Vicuna mackenna 3019, San joaquin Santiago, Chile Phone: 56-2-5521657 FAX: 56-2-5521961 e-mail: lancerchile@lancer.tie.cl
Lancer Pacific
Australia
Lancer Pacific Pty Ltd 5 Toogood Avenue Beverley 5009 PO Box 331 Welland 5007 South Australia Phone: 61-8-8268-1388 FAX: 61-8-8268-1978 e-mail: joe-thorp@lancer-pacific.com.au
(Managing Director, Lancer Pacific) steve-sotiriou@lancer-pacific.com.au (for Fountain/soft drink) bill-cadd@lancer-pacific.com.au (for Draught Products)
New South Wales / ACT
Lancer Pacific Pty Ltd Unit 8, 2 Holker Street Newington 2127 New South Wales Australia Phone: 61-2-9648-6840 FAX: 61-2-9648-6850 e-mail: john-frize@lancer-pacific.com.au
Victoria / Tasmania
Lancer Pacific Pty Ltd 55 Keele Street Collingwood 3066 Victoria Australia Phone: 61-3-8415-1920 FAX: 61-3-8415-1929 e-mail: hayden-woodall@lancer-pacific.com.au
Queensland / Northern Territory
Lancer Pacific Pty Ltd Unit 31, 284 Musgrave Drive Coopers Plains 4108 Queensland Australia Phone: 61-7-3274-5700 FAX: 61-7-3875-1805 e-mail: brett-thomson@lancer-pacific.com.au
New Zealand
Lancer Pacific Ltd 9 O’Rorke Street Onehunga, Auckland POBox 12-523 Penrose, Auckland New Zealand Phone: 64-9-634-3612 Mobile Phone: 64-21-745-389 FAX: 64-9-634-1472 e-mail: mike-peffers@lancer-pacific.com.au
andrew-nixon@lancer-pacific.com.au
Lancer Authorized Distributors
Indonesia
P.T. Dikarunia Sejahtera - Indonesia JI. Gelong Baru Tengah #1A Tomang, Jakarta, Barat 11440 Indonesia Phone: 62-21-5694-3245 FAX: 62-21-560-6889 e-mail: dikarunia@cbn.net.id
Philippines
RBP Industrial Sales, Inc. - Philippines Unit 20, 2/F, Facilities Centre Bldg. 548 Shaw Blvd 1552 Mandaluyong City Philippines Phone: 632-531-1221/1215/1289 FAX: 632-531-1271 e-mail: rbpsales@pldtdsl.net
rbp@pldtdsl.net
Lancer Asia
International Sales
6655 Lancer Blvd. San Antonio, TX 78219 Phone: (210) 310-7000 FAX: (210) 310-7242 1-800-729-1500 e-mail: asia@lancercorp.com
Hong Kong
Patrick Co - Director Asia Flat A, 24/F., Houston Industrial Bldg. 32-40 Wang Lung Street Tsuen Wan, N. T., Hong Kong Phone: 852-94302585 FAX: 852-24082605 e-mail: patrickco@lancer-asia.com
Lancer Authorized Distributors
Shanghai Freser International Co Ltd. ­China
1856, Hu Tai Road Shanghai, 200436, China Phone: 86-21-5650-3555 FAX: 86-21-5650-2666 e-mail: daniel@freser.com.cn
Freser (HK) Company Ltd - Hong Kong
Flat A, 24/F., Houston Industrial Bldg. 32-40 Wang Lung Street Tsuen Wan, N. T., Hong Kong Phone: 852-2408-2595 FAX: 852-2408-2605 e-mail: freserhk@netvigator.com
Hayakawa Sanki - Japan
Hayakawa Sanki, Inc. 1-13-13, Kayaba-cho Nihonbashi, Chuo-ku Tokyo, 103-0025 Japan Phone: 03-5651-1481 FAX: 03-5651-1445 e-mail: toshi@hayakawa-sanki.co.jp
Tahoe Corporation - Korea
Tahoe Corporation 2FL, 835-66 Yocksam-dong Kangnam-Ku Seoul, Korea Phone: 82-2-557-5612, -5614 FAX: 82-2-557-5615 e-mail: tahoepark@empal.com
Freser (MALAYSIA) SDN. BHD. - Malaysia
No. 31, Jalan TPP 5/13, Taman Perindustrian Puchong, Seksyen 5, 47100 Puchong, Selangor, Malaysia Phone: 60-3-8061-6666 FAX: 60-3-8062-1007 e-mail: freser@tm.net.my
Freser (S) Pte Ltd - Singapore
621 Aljunied Road #02-09 Lipo Building Singapore 389834 Phone: 65-6746-8191 FAX: 65-6746-8196 e-mail: fresersin@pacific.net.sg
Freser International Corporation - Taiwan
No. 76, Gui-Sui Street Taipei 103, Taiwan R.O.C. Phone: 886-2-2553-1555 FAX: 886-2-2553-2742 e-mail: herman@intl.freser.com.tw
Freser Makasan International Co., Ltd ­Thailand
Freser Makasan International Co., LTD. Navanakorn Industrial Estate Zone 4 95/3 Moo 13, Klongnung, Klongluang Patumthani 12120, Thailand Phone: 662 520-3457 (Automatic, 7 lines) FAX: 662 529-3840 e-mail: komsan@makasan.co.th
Lancer - Indian Sub-Continent
India
Shabbir Shafiqui - Area Manager
India and Sub-Continent B-7, Pannalal Silk Mill Compounds 78, LBS Marg, Bhandup (W) Mumbai 400-078, India Phone: 91-22-2561-6665 Cel No.: 91-98-2029-5252 FAX: 91-22-5637-4018 e-mail: shafiquis@vsnl.com
Lancer Authorized Distributors
Western Refrigeration Ltd - India
B-7, Pannalal Silk Mill Compounds 78 L.B.S. Marg, Bhandup (W) Mumbai 400-078, India Phone: 91-22-2561-6665 FAX: 91-22-2562-2257 e-mail: western@bom5.vsnl.net.in
Bengal Marketing Company - Bangladesh
Skylark Point (6th Floor) Room #G-2 24/A Bijoy Nagar, Dhaka-1000, Bangladesh Phone: 880-2-934-2987 FAX: 880-2-935-0127 e-mail: bmc@dhaka.agni.com
Dynamic Equipment - Pakistan
Dynamic Equipment and Controls (Pvt.) Ltd. F-1/23, Canal Cottages, Block-D. New Muslim Town. Lahore. Pakistan. Phone: 0092-42-583-6737
0092-42-583-6787 FAX: 0092-42-586-7924 e-mail: info@dynamic-eqpt.com.pk
m.ateeq@dynamic-eqpt.com.pk
Directory of USA - Canada Offices,
International Offices, and Authorized Distributors
(Continued)
24
Directory of USA - Canada Offices,
International Offices, and Authorized Distributors
Corporate Office
6655 Lancer Blvd. • San Antonio, Texas 78219 • 210-310-7000 • 1-800-729-1500 • FAX 210-310-7250
Lancer USA Manufacturing Locations
Foster Road Facilities
6655 Lancer Blvd San Antonio, TX 78219
Web Site: www.lancercorp.com
Phone: (210) 310-7000 MFG FAX: (210) 310-7088 ENG FAX: (210) 310-7096 ACCT FAX: (210) 310-7091 PURCH FAX: (210) 310-7094
Lancer FBD
5620 Business Park San Antonio, TX 78218 Phone: (210) 666-0544 FAX: (210) 666-2044
Remanufacturing
6655 Lancer Blvd San Antonio, TX 78219 Phone: (210) 310-7256 FAX: (210) 310-7261 1-800-729-1550
Lancer North America
USA - Canada Sales
6655 Lancer Blvd. San Antonio, TX 78219 Phone: (210) 310-7000 SALES FAX: (210) 310-7245 CUSTOMER SERVICE FAX: (210) 310-7250 1-800-729-1500
Georgia Office
1125 Northmeadow Parkway, Suite 116 Roswell, GA 30076 Phone: (770) 343-8828 FAX: (770) 475-8646 1-800-729-1750
Lancer Authorized Distributors
Advanced Beverage Solutions (ABS)
100 N. Gary Avenue, Suite C Roselle, IL 60172 Phone: (847) 524-1707
(877) 814-2271 FAX: (847) 524-1710 www.absone.com
Bevco
6900 Camille Avenue Oklahoma City, OK 73149 Phone: (405) 672-7770
800-460-4238 FAX: (405) 672-7443 e-mail: sales@bevcoinc.com
Joe Kirwan Company
119 White Oak Lane Old Bridge, NJ 08857 Phone: (732) 679-1900 FAX: (732) 679-9236 e-mail: sales@jkirwan.com
L & M Beverage Equipment Co. Inc.
12510 Santa Fe Trail Drive Lenexa, KS 66215 Phone: (913) 888-8988 FAX: (913) 888-9137 e-mail: L7mco@aol.com
Ernest F. Mariani Company
614 West 600 South Salt Lake City, UT 84104 Phone: (801) 359-3744 FAX: (801) 531-9615 e-mail: febell@efmco.com, or
clay@efmco.com
(Update #58 - as of March 08, 2005)
Mark Powers & Company, Inc.
P.O. Box 72 1821 Henry Street Guntersville, AL 35976 Phone: (256) 582-6620 FAX: (256) 582-8533 e-mail: sales@markpowers-and-company.com
Maurer Supply, Inc.
843 Rainier Avenue South Seattle, WA 98144 Phone: (206) 323-8640 FAX: (206) 323-9286 e-mail: maurersupply@qwest.net
Simgo Ltd.
5122 Timberlea Blvd. Mississauga, Ontario L4W 2S5 Canada Phone: 905-602-5800 FAX: 905-602-5804 e-mail: simgo@simgo.com
Simgo (B.C.) Ltd.
16-8125 - 130th Street Surrey, B.C. V3W 7X4 Canada Phone: 604-590-4022 FAX: 604-590-1601
Lancer Europe
Web Site: www.lancereurope.be
Belgium - European Central Office
Lancer Europe, S.A. Mechelsesteenweg 592 B-1930 Zaventem Belgium Phone: 32-2-755-2390 FAX: 32-2-755-2399 e-mail: lancer.europe@glo.be
England
Managing Director Contact: Paul Haskayne Lancer G.B. Llp. Unit 9 Prosperity Court, Midpoint 18 Middlewich CW10 OGD Cheshire, United Kingdom. Phone: 441606837711 FAX: +441606832705 e-mail: phaskayne@lancergb.co.uk
17 Bembridge Gardens Ruislip, Middlesex HA4 7ER, England Phone: 44-1895672667 FAX: 44-1895637537 e-mail: court4lancer@msn.com
Hungary
H-2100 Gödöllõ Isaszegi út 67 Hungary Phone: 36-28-417-179 FAX: 36-28416-881 e-mail: bodolai@compuserve.com
Lancer Authorized Distributors
Complete Beverage Services, Ltd. Republic of Ireland and Northern Ireland
Gortrush Industrial Estate Omagh County Tyrone Northern Ireland Office: 44-1662 250 008 FAX: 44-1662-252-991
Provisiona, S.L. - Spain
Avda. Concha Espina 8 28036 Madrid Spain Phone: 34-91-564 6900 FAX: 34-91-564 3065 e-mail: jmorales@bevserv.com
Lancer Russia
Lancer International Sales, Inc. Representation Office
Kashirskoe shosse, 65 (1), Office 505 Moscow 115583 Russia Mail: Moscow, 115551, Mail Box #2, Russia Mobile Phone: 7-095-991-7778 Office Phone: 7-095-727-4063 Office FAX: 7-095-727-4064 e-mail: vdemkin@ktv.ru
lancer@online.ru
Lancer Middle East / Africa
Elsayed Moniem - Regional Manager Lancer Middle East/Africa 7 Mubarak Street East Ain Shams 11311 Cairo, Egypt Phone: 2-02-49-35-395 FAX: 2-02-49-33-914 Mobile Phone (GSM): 2-010-500-4007 e-mail: elsayed_lancer@msn.com
Lancer Authorized Distributor
DispenseTech - South Africa
P.O. Box 17495 Sunward Park, 1470 South Africa Phone: 27-11-397-7455 FAX: 27-11-397-7648 e-mail: david@dispensetech.co.za
Lancer Latin America
Latin America Sales
6655 Lancer Blvd. San Antonio, TX 78219 Phone: (210) 310-7000
1-800-729-1500 FAX: (210) 310-7245 e-mail: latinamerica@lancercorp.com
Lancer de Mexico, S.A. de C.V.
Contact: Carlos Robles Calle Lerdo De Tejada #544 PTE. Col. Las Villas San Nicolas De Los Garza, N.L. Mexico C.P. 66422 Phone: (52)-81-83-05-81-00 Phone: (52)-81-83-05-81-01 Phone: (52)-81-83-05-81-02 FAX: (52)-81-83-05-81-09 e-mail: Carlos.robles@lancer.com.mx
PEL SudAmerica - Ecuador
Lancer Sales Company Contact: Luciano Lopez Sector Las Acacias Luis De Beethoven #958 Y Capitan Rafael Ramos Quito, Ecuador Phone: 593-22-401-598, 400-937, 406-418 FAX: 593-22-400-535 e-mail: Llopez@ecnet.ec
Lancer Authorized Distributors
Eximport & Barter Co. - Caribbean
2101 S.W. 56th Terrace Hollywood, FL 33023 USA Phone: (954) 967-9999 FAX: (954) 967-9900 e-mail: edbrandao@aol.com
(Continued on reverse)
25
Loading...