Lancaster 7-LXC-50, 7-LXC-75, 7-LX-100, 7-LX-150, 7-LX-200 Installation, Operating And Service Manual

...
INSTALLATION, OPERATING AND
SERVICE MANUAL
ELECTRONIC WATER SOFTENER WITH
THE X-FACTOR CONTROL VALVE
PROGRAMMED FOR PRE-FILL BRINING OPTION
7-LXC-50
7-LXC-75
7-LX-75
7-LX-100
7-LX-150
7-LX-200
7-LX-300
Congratulations on purchasing your new Lancaster Water Softener. This unit is designed to give you many years of trouble free service. When installed in accordance with the following instructions and if given reasonable care, clear-soft water will be the result. For servicing and future inspection
purposes, please le this booklet with your important documents.
In the event that you need assistance for servicing your water softener, please rst contact the
professional contractor who installed the system.
PAGE 1
TABLE OF CONTENTS
Job Specications ......................................................................................................................... 2
Pre-Installation Review ................................................................................................................. 3
General Installation and Service Warnings .................................................................................. 3
Bypass Valve Operation ............................................................................................................... 4
Installation Instructions, Diagrams ................................................................................................ 5, 6
Placing Softener into Service ....................................................................................................... 7
General Operation ........................................................................................................................ 7
Set Time of Day ............................................................................................................................ 8
Adjust Hardness, Days Between Regenerations or Time of Regeneration .................................. 8, 9
Low Battery.................................................................................................................................... 9
Contact Screen Programming ...................................................................................................... 9
Specications ............................................................................................................................... 10-13
Parts Diagrams ............................................................................................................................. 14-21
Service Instructions ...................................................................................................................... 22-24
Troubleshooting ............................................................................................................................ 25-28
JOB SPECIFICATIONS
MODEL NO.
INSTALLATION DATE
SERIAL NUMBER
INSTALLER NAME PHONE
ADDRESS
WATER TEST AT TIME OF INSTALLATION
Hardness CaCo3 (gpg)
Iron (ppm)
pH
SIZING INFORMATION
All Water is Softened Except:
Rear Hose Bib Front Hose Bib Kitchen Cold Toilets All Cold Other
The average family uses 50 gallons per person daily for all water uses in the home.
Daily Water Usage (Gallons/Person)
x Family Size (Number of people in family)
= Total Gallons Per Day
x Grains Per Gallon of hardness
Other:
(Note: Add 4 grains per gallon of hardness for each ppm iron for total compensated hardness)
= Total Grains per Day
PAGE 2
PRE-INSTALLATION
REVIEW
GENERAL INSTALLATION
AND SERVICE WARNINGS
WATER QUALITY: If sand or sediment is present in the
water supply, a sediment lter should be installed ahead
of the water softener. Your water softener has been designed to adequately reduce hardness from levels up to 100 grains per gallon. Ferrous bicarbonate iron levels up to 0.5 ppm can also be reduced. This is iron that is dissolved in water and not visible to the eye in a freshly drawn sample. After standing in contact with air, the ferrous iron will become oxidized to the ferric state and start to
precipitate as a reddish brown oc. It can be seen and may
cause discolored water. Air must not come in contact with water until after it has passed through the water softener. In some cases, additional treatment equipment may be needed to treat water having special characteristics, such as: ferric hydroxide iron, iron bacteria, low pH, tastes and odors, etc. Consult your dealer if you have any questions.
This water softener is not to be used for treating water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after treatment.
WATER PRESSURE: A minimum of 20 pounds of water
pressure (psi) is required for regeneration. Maximum 100 psi. CAUTION: the softener cannot be subject to a vacuum due to loss of pressure (such as a water main
break or submersible well pump check valve failure).
WATER TEMPERATURE: The range of water temperature is 35°F to 100°F. DO NOT install any water softener with less than 10 feet of piping between its outlet and the inlet of a water heater.
AMBIENT TEMPERATURE: DO NOT locate softener where it or its connections (including the drain and
overow lines) will ever be subject to room temperatures
under 33°F.
ELECTRICITY: An uninterrupted 120 volt 60Hz source is required. Make sure electrical source is not on a timer or switch. All electrical connections must be connected according to local codes. The plug-in transformer is for dry locations only. Surge protection is recommended with all electrical connections.
DRAIN: All plumbing should be done in accordance with local plumbing codes. The distance between the drain and the water softener should be as short as possible. The pipe size for the drain line should be a minimum of 1/2” (inside diameter of pipe).
SOFTENING: It is recommended that the softener be installed to soften both the hot and cold water supply. A
separate hard water faucet may be plumbed for drinking
purposes if desired. Outside faucets should be left on hard water.
BYPASS: A bypass valve (optional accessory) should be installed so that water will be available if it should be necessary to shut off the pressure in order to service the softener.
The control valve, tting and/or bypass are designed to
accommodate minor plumbing misalignments but are not designed to support the weight of a system or the plumbing.
Do not use Vaseline, oils, other hydrocarbon lubricants or spray silicone anywhere. A silicone lubricant may be used
on black o-rings but is not necessary. Avoid any type of lubricants, including silicone, on the clear lip seals.
The nuts and caps are designed to be unscrewed or tightened by hand or with the special plastic wrench (V3193). If necessary, pliers can be used to unscrew the nut or cap. Do not use a pipe wrench to tighten or loosen nuts or caps. Do not place a screw driver in the slots on caps and/or tap with a hammer.
Do not use pipe dope or other sealants on threads. Use
Teon tape on the threaded inlet, outlet and drain ttings. Teon tape is not necessary on the nut connection or caps
because of o-rings seals.
After completing any valve maintenance involving the drive assembly or the drive cap assembly and pistons,
unplug power source jack from the printed circuit board (black wire) and plug back in or press and hold
REGEN
and and establishes the service piston position. The display
should ash the software version and then reset the valve
to the service position.
Solder joints near the drain must be done prior to
connecting the drain line ow control tting. Leave at least 6” between the drain line control tting and solder joints
when soldering pipes that are connected on the drain
line control tting. Failure to do this could cause interior damage to the drain line ow control tting.
When assembling the installation tting package (inlet and outlet), connect the tting to the plumbing system rst
and then attach the nut, split ring and o-ring. Heat from soldering or solvent cements may damage the nut, split ring or o-ring. Solder joints should be cool and solvent cements should be set before installing the nut, split ring and o-ring. Avoid getting primer and solvent cement on any part of the o-ring, split rings, bypass valve or control valve.
Install grounding strap on metal pipes.
This water softener is not to be used for treating water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after treatment.
buttons for 3 seconds. This resets the electronics
NEXT
PAGE 3
BYPASS VALVE
The bypass valve is typically used to isolate the control valve from the plumbing system’s water pressure in order to perform control valve repairs or maintenance. The X-Factor bypass valve is particularly unique in the water treatment industry due to its versatility
and state of the art design features. The 1” full ow bypass valve incorporates four positions, including a diagnostic position that allows service personal to work on a pressurized system while still providing untreated bypassed water to the facility or residence. Its
completely non-metallic, all-plastic design allows for easy access and serviceability without the need for tools.
The bypass body and rotors are glass lled Noryl® (or equivalent) and the nuts and caps are glass lled polypropylene. All seals are
self-lubricating EPDM to help prevent valve seizing after long periods of non-use. Internal o-rings can easily be replaced if service is required.
The bypass consists of two interchangeable plug valves that are operated independently by red arrow-shaped handles. The handles
identify the ow direction of the water. The plug valves enable the bypass valve to operate in four positions.
OPERATION:
1. Normal Operation Position: The inlet and outlet
handles point in the direction of ow indicated by the engraved arrows on the control valve. Water ows
through the control valve during normal operation and this position also allows the control valve to isolate the media bed during the regeneration cycle. (see gure
1)
2. Bypass Position: The inlet and outlet handles point to the center of the bypass, the control valve is isolated from the water pressure contained in the plumbing system. Untreated water is supplied to the plumbing system. (see gure 2)
3. Diagnostic Position: The inlet handle points in
the direction of ow and the outlet handle points to
the center of bypass valve, system water pressure is allowed to the control valve and the plumbing system while not allowing water to exit from the control valve to the plumbing. (see gure 3)
4. Shut Off Position: The inlet handle points to the center of the bypass valve and the outlet handle
points in the direction of ow, the water is shut off
to the plumbing system. If water is available on the outlet side of the softener it is an indication of water bypass around the system (i.e. a plumbing connection somewhere in the building bypasses the system).
(see gure 4)
The working parts of the bypass valve are the rotor assemblies that are contained under the bypass valve caps. Before working on the rotors, make sure the system is depressurized. Turn the red arrow shaped handles towards the center of the bypass valve and back
several times to ensure rotor is turning freely.
The nuts and caps are designed to be unscrewed or tightened by hand. If necessary a pliers or the service spanner wrench can be used to unscrew the nut or cap. Do not use a pipe wrench to tighten or loosen nuts or caps. Do not place screwdriver in slots on caps and/or tap with a hammer.
Refer to page 19 for bypass valve parts diagram and service spanner wrench information.
To access the rotor, unscrew the cap and lift the cap, rotor and handle out as one unit. Twisting the unit as you pull it out will help to remove it more easily. There are three o-rings: one under the rotor cap, one on the rotor stem and the rotor seal. Replace worn o-rings. Clean rotor. Reinstall rotor.
When reinstalling the red arrow handles be sure that:
1. The handle pointers are lined up with the control valve body arrows, and the rotor seal o-ring and retainer on both rotors face to the right when being viewed from the front of the control valve; or
2. Arrows point toward each other in the bypass position.
Since the handles can be pulled off, they could be accidentally reinstalled 180° from their correct orientation. To install the red arrow
handles correctly, keep the handles pointed in the same direction as the arrows engraved on the control valve body while tightening the
bypass valve caps.
gure 1 gure 2
gure 3 gure 4
PAGE 4
INSTALLATION INSTRUCTIONS
BRINE LINE FITTING CONNECTIONS
DRAIN LINE FITTING CONNECTION USING 5/8" POLY TUBE
Click to buy NOW!
P
D
F
-
X
C
H
A
N
G
E
w
w
w
.
d
o
c
u
-
t
r
a
c
k
.
c
o
m
(All electrical & plumbing should be done in accordance to all local codes)
1. Place the softener where you want to install it, making sure it is on a clean, level and rm base.
2. Do all necessary plumbing (inlet to inlet, outlet to outlet,
and drain line to drain). The control valve, ttings and/or
bypass are designed to accommodate minor plumbing misalignments but are not designed to support the weight of a system or the plumbing.
3. When assembling the installation tting package (inlet and outlet), connect the tting to the plumbing system rst and then attach the nut, split ring and o-ring. Heat
from soldering or solvent cements may damage the nut, split ring or o-ring. Solder joint should be cool and solvent cements should be set before installing the nut, split ring and o-ring. Avoid getting primer and solvent cement on any part of the o-rings, split rings, bypass valve or control valve.
4. A jumper ground wire should be installed between the inlet and outlet pipe whenever the metallic continuity of a water distribution piping system is interrupted. Install grounding strap on metal pipes.
5. The drain connection may be made using either 5/8” polytube (see below) or a 3/4” female adapter. The polytube insert is shipped attached to the drain line
elbow’s locking clip. Press the insert into the drain line
tubing (tubing not provided). Loosen the nut of the drain line elbow. Press the 5/8” polytube with insert into the
drain line elbow until it seats on the back of the tting.
Tighten the nut. If soldering, joints near the drain must be
done prior to connecting the drain line ow control tting. Leave at least 6” between the drain line control tting and
solder joints when soldering pipes that are connected on
the drain line control tting. Failure to do this could cause interior damage to the drain line ow control tting. Never
insert a drain line into a drain, sewer line, or trap. Always allow an air gap between the drain line and the wastewater
to prevent the possibility of sewage being back-siphoned
into the softener.
6. The brine rell ow control assembly is installed in an easy to access rell elbow located on top of the control valve. The rell ow control assembly is attached to the control valve with a locking clip. The locking clip allows the
elbow to rotate 270 degrees so the outlet can be oriented
towards the brine tank.
7. Connect the brine line polytubing found with the brine
tank to the brine connection on the control valve. The control valve has a standard rell elbow to which a 3/8” exible tube can be connected, see below. Press the polytube into the brine elbow tting. Make sure the oor is clean beneath the brine tank and that it is level and
smooth.
8. A 1/2” (inside diameter, not provided) gravity drain line
should be connected to the overow tting on the side of the brine tank. This overow is in case of a malfunction in
the brine shut off. If the unit is installed where water may
ow in the event of an overow and cause water damage, connect a length of exible tubing and run to a drain below the level of the overow. (Do not connect the tubing to
the drain line on the control valve. Do not run tubing
above overow height at any point.)
POLYTUBE
POLYTUBE
PAGE 5
COLD
Click to buy NOW!
P
D
F
-
X
C
H
A
N
G
E
w
w
w
.
d
o
c
u
-
t
r
a
c
k
.
c
o
m
Click to buy NOW!
P
D
F
-
X
C
H
A
N
G
E
w
w
w
.
d
o
c
u
-
t
r
a
c
k
.
c
o
m
HOT
MINIMUM 10 FEET
BETWEEN
WATER SOFTENER OUTLET
AND
WATER H EATER INLET
A SIX FOOT LENGTH OF 3/8" O.D.
BRINE LIN E POLYTUBE
SUPPLIED WITH BRINE TANK.
LOCATE WATER SOFTENER
AS CLOSE AS POSSIBLE
TO BRIN E TANK.
BYPASS PLUMBING
RECOMMENDED
IF
OPTIONAL BP2000
BYPASS VALVE
IS NOT USED.
TO
OUTSIDE
TAP
LOCATE WATER SOFTENER CLOSE TO A DRAIN. AVOID OVERHEAD DRAIN LINES IF POSSIBLE TO
PREVEN T BACK PRESSURE ON BRINE INJECTOR.
IF OVER HEAD DRAIN LINE IS USED AND EXCEEDS
5 FEET ABOVE CONNEC TION ON CONTROL VALVE
IF DRAIN LINE EXCEED S 20 FEET IN LENGTH,
DRAIN LINE PIPE SIZE SH OULD BE MINIMUM 3/4".
OR
DRAIN LINE
AIR GAP
ADAPTER
WATER
HEATER
TO
DRAIN
CITY WATER
INSTALLATION
WATER METER
BRINE TANK
OVERFLO W GRAVITY DR AIN - ONLY U SED IN CASE O F MALFUNCTION IN THE BRINE SHUTOFF. DO NOT CONNECT TO CONTROL VALVE DRAIN LINE. IF UNIT IS INSTALLED W HERE OVERF LOW COULD CAUSE WATER DAMAGE, CON NECT TU BING AND RUN TO FLOOR DRAIN. DO NOT RUN TUBING ABOVE OVERFLOW HEIGHT.
MINIMUM 10 FEET
BETWEEN
WATER SOFTENER OUTLET
AND
WATER H EATER INLET
COLD
HOT
A SIX FOOT LENGTH OF 3/8" O.D.
BRINE LIN E POLYTUBE
SUPPLIED WITH BRINE TANK.
WATER S OFTENER
BYPASS PLUMBING
RECOMMENDED
IF
OPTIONAL BP2000
BYPASS VALVE
IS NOT USED.
TO
OUTSIDE
TAP
LOCATE WATER SOFTENER CLOSE TO A DRAIN. AVOID OVERHEAD DRAIN LINES IF POSSIBLE TO
PREVEN T BACK PRESSURE ON BRINE INJECTOR.
IF OVER HEAD DRAIN LINE IS USED AND EXCEEDS
5 FEET ABOVE CONNEC TION ON CONTROL VALVE
IF DRAIN LINE EXCEED S 20 FEET IN LENGTH,
DRAIN LINE PIPE SIZE SH OULD BE MINIMUM 3/4".
OR
FROM
WATER MAIN
WATER
HEATER
OVERFLO W GRAVITY DR AIN - ONLY U SED IN CASE O F MALFUNCTION IN THE BRINE SHUTOFF. DO NOT CONNECT TO CONTROL VALVE DRAIN LINE. IF UNIT IS INSTALLED W HERE OVERF LOW COULD CAUSE WATER DAMAGE, CON NECT TU BING AND RUN TO FLOOR DRAIN. DO NOT RUN TUBING ABOVE OVERFLOW HEIGHT.
LOCATE WATER SOFTENER
AS CLOSE AS POSSIBLE
TO BRIN E TANK.
BRINE TANK
PAGE 6
WATER S OFTENER
WELL WATER
INSTALLATION
PRESSURE
TANK
DRAIN LINE
AIR GAP
ADAPTER
TO
DRAIN
FROM
WELL PUMP
PLACING SOFTENER INTO SERVICE
Do not add salt to the brine tank yet. Do not plug the transformer into the receptacle yet. Make sure inlet and outlet valves are to their
closed positions. If using optional bypass, place in bypass position. Turn on main water supply. Open a cold water faucet. This will clear the line of any debris (solder, pipe dope, etc.) that may be in the line. Let water run at faucet for a couple minutes, or until clear. Turn
off faucet. Manually add 1 ½ gallons of water to the brine tank. Now plug the transformer into a 120 volt receptacle (be certain the
receptacle is uninterrupted). Within 5 seconds the control display and buttons will illuminate and the time of day screen will appear.
Press and hold the
REGEN
button for approximately 5 seconds until the motor starts.
Wait until display reads FILL and numbers start counting down.
Momentarily press
Momentarily press
Momentarily press
Momentarily press
REGEN
again. Valve is now in the SOFTENING position.
REGEN
again. Valve is now in the BACKWASH position. (NA for model 7-LXC-50, -100)
REGEN
again. Valve is now in the REGENERANT DRAW position.
REGEN
again. Valve is now in the second BACKWASH position. (NA for model 7-LXC-50, -100)
If using optional bypass SLOWLY turn bypass valve to DIAGNOSTIC position (See gure 3 on page 4) or slowly open inlet valve to allow water to slowly enter Softener.
When water is owing steadily to drain without the presence of air, momentarily press
REGEN
again. Display will read RINSE. Open
the outlet valve of the softener, or if using optional bypass place to NORMAL OPERATION MODE (see gure 1 on page
4). Allow control to nish the RINSE cycle. Allow the control to automatically advance to the SOFTENING position. Now load the brine tank with salt. Solar Salt is recommended. The brine tank salt level should be checked every couple of weeks to determine salt usage. Keeping the brine tank salt level at least 1/2 full is recommended.
SANITIZING: Use 2 oz. of 5 ¼% unscented household chlorine bleach for each cubic foot of resin. Pour bleach directly into the 4”
diameter white brine well located inside the brine tank. Press and hold the system to complete the regeneration automatically. Check for other local and state codes which may also specify sanitation methods.
Note: The rst step of the regeneration process is to ll the brine tank with the proper amount of water. The brine tank will only have a very slight amount of water in it after the regeneration cycles are completed.
REGEN
for 5 - 6 seconds until the motor starts running. Allow
GENERAL OPERATION
Note: As an energy saving feature, the control will automatically turn off all SOLID BLUE or SOLID GREEN display illumination and keypad illumination after about 5 minutes of the last keypad button push. Any further keypad touch will cause the re-illumination of the display and keypad, and re-activate keypad control.
User Displays
When the system is in normal service mode, one of up to ve
available User Displays will be shown. Pressing alternate between the following displays:
• Current time of day
• Treated water ow rate
• Service contact name and phone number (if entered)
• Remaining Capacity of treated water available
• Remaining days to regeneration (if Day Override is
programmed)
Pressing the button while in the Capacity Remaining or Days Remaining displays will decrease the capacity remaining in ten gallon increments or the days remaining in one day increments. To clear the Service Call reminder, press the and buttons simultaneously while the number and banner text screen is displayed. If the system has called for a regeneration that will occur at the preset time of regeneration, the words REGEN TODAY will alternate with the header on the display. Utilizing the control valve’s built-in water meter, a water drop
ashes on the display when water is being treated (i.e. water is owing through the system).
NEXT
will
Drop will ash while water
is being treated.
Contact Screen
NEXT
NEXT
NEXT
NEXT
PAGE 7
SET TIME OF DAY
Current time of day needs to be entered during initial installation, and adjusted when daylight saving time begins or ends. If an extended power outage occurs and depletes the on-board non-rechargeable coin cell battery, when power resumes the time of day should be reset and battery replaced.
STEP 1
STEP 2
STEP 1 – Press
STEP 2 - Current Time (hour): Set the hour of the day using or buttons. AM/PM toggles
after 12. Press
STEP 3
STEP 3 - Current Time (minutes): Set the minutes of the day using or buttons. Press
NEXT to exit Set Time of Day. Press
RETURN TO NORMAL MODE
ADJUST HARDNESS, DAYS BETWEEN REGENERATIONS,
CLOCK
NEXT
to go to Step 3.
to return to previous step.
REGEN
OR TIME OF REGENERATION
STEP 1
STEP 2
STEP 3
STEP 4
STEP 1 - Press
NEXT
and simultaneously for 3 seconds to access Installer Display Settings.
STEP 2 – Hardness: Set the amount of hardness in grains of hardness as calcium carbonate per gallon using the or buttons. The default is 20 with value ranges from 1 to 150 in 1 grain increments. Note: The grains per gallon can be increased if soluble iron needs to be reduced. Press
NEXT
to go to step 3. Press
to exit Installer Display Settings.
REGEN
STEP 3 – Day Override: Set the maximum number of days between regenerations. If value set to
“OFF”, regeneration initiation is based solely on volume used. If value is set as a number (allowable
range from 1 to 28) a regeneration initiation will be called for on that day even if sufcient volume of
water were not used to call for a regeneration. Set Day Override using or buttons:
• number of days between regeneration (1 to 28); or
• “OFF”.
Press
NEXT
to go to step 4. Press
REGEN
to return to previous step.
STEP 4 – Next Regeneration Time (hour): Set the hour of day for regeneration using or buttons. AM/PM toggles after 12. The default time is 2:00 AM. Press
REGEN
to return to previous step.
to go to Step 5. Press
NEXT
PAGE 8
STEP 5
STEP 5 – Next Regeneration Time (minutes): Set the minutes of day for regeneration using
or buttons. Press
NEXT
to return to normal operation. Press
REGEN
to return to
previous step.
RETURN TO NORMAL MODE
LOW BATTERY
A non-rechargeable coin cell battery is located on the circuit board, used only to maintain the time of day during power outages (all other information will be stored in memory no matter how long the power outage). The screen displays LOW BATTERY when the battery needs to be replaced. The screen will remain illuminated solid blue when LOW BATTERY is
displayed. Initially LOW BATTERY display will alternate with the User display, nally displaying only LOW BATTERY. User
displays are still accessible by pressing
NEXT
.
CONTACT SCREEN PROGRAMMING
STEP 1
STEP 2
STEP 3
STEP 4
STEP 1 - Press
NEXT
and simultaneously for 3 seconds to access Installer Display
Settings.
STEP 2 - Press
STEP 3 - Press
NEXT
to go to step 3.
NEXT
to go to step 4.
From Step 4, while hour is ashing, press and hold both the change phone number and banner text.
CLOCK
and button to
Phone Number - Set phone number using the or arrow. Press
to the next digit. Press
Banner Text - Set the banner text up to a maximum of 44 characters. Use the or to select letters of the alphabet, numbers, ampersand (&), or a space in the banner text.
Press
REGEN
to return to previous digit.
NEXT
to forward to the next character or to exit the Installer Display Settings.
PAGE 9
NEXT
to forward
Loading...
+ 21 hidden pages