Lamtec LT 2, KS1-DK Assembly And Commissioning Manual

Assembly and
Lambda Transmitter LT 2/KS1-DK
Commissioning Manual
Lambda­Transmitter LT 2
Combination Probe KS1-DK
Simultaneous measurement of Oxygen (O2)
Combination probe KS1-DK
O
2
CO/H
)
2
2
RS 232
Analogue inputs and outputs
(,
Operation
servicing
)
Option: CANopen Modbus Profibus DP Ethernet
CAN
Field bus
Digital inputs and outputs
to other LAMTEC FMS / VMS / ETAMATIC LT 1 / LT 2
devices
Sensors and Systems for Combustion Engineering
Recording
LAMTEC SYSTEM BUS
Digital inputs and outputs
Opti onal modules
Analogue inputs and outputs
Table of Contents
1 General Information......................................................................................3
1.1 Compliance with the German law on device safety.................................................................. 3
2 Safety Information ........................................................................................4
2.1 Proper use, conditions for use..................................................................................................5
2.2 Permitted users......................................................................................................................... 6
2.3 Safety equipment / protective measures .................................................................................. 7
2.4 Environmentally responsible behaviour, disposal instructions ................................................. 8
3 Introduction...................................................................................................9
3.1 System overview....................................................................................................................... 9
3.2 Theoretical principles of measurement .................................................................................. 13
3.3 Probe method of functioning - O2-sensitive electrode ............................................................ 13
3.4 Probe method of functioning - CO/H2-sensitive electrode...................................................... 14
4 Technical Description ................................................................................16
4.1 Advantages of the LAMTEC measurement principle .............................................................16
4.2 Necessary components ..........................................................................................................16
4.3 Basic design of the LT 2/KS1-DK........................................................................................... 17
4.4 LT 2/KS1-DK........................................................................................................................... 18
4.5 Internal display and control elements of the LT 2/KS1-DK lambda transmitter ..................... 20
4.6 Display and operating unit ......................................................................................................22
4.7 Analogue output...................................................................................................................... 30
4.8 Digital inputs ........................................................................................................................... 31
4.9 LAMTEC SYSTEM BUS ......................................................................................................... 33
4.10 RS 232 interface .....................................................................................................................34
4.11 Cold start delay....................................................................................................................... 34
4.12 Optional extras........................................................................................................................ 35
4.13 Limit values............................................................................................................................. 43
4.14 Analogue inputs ...................................................................................................................... 48
4.15 Device configuration and factory settings............................................................................... 49
5 Installation...................................................................................................51
5.1 General Information ................................................................................................................ 51
5.2 Installing the electronic evaluation unit of the LT 2/KS1-DK lambda transmitter ...................51
5.3 Installing the probe ................................................................................................................. 55
6 Commissioning / Shutdown.......................................................................57
6.1 Switch on measurement ......................................................................................................... 57
6.2 Setting the cell internal resistance R
6.3 Setting the reference air quantity............................................................................................ 59
6.4 Calibration of the probe KS1-DK via menu function .................................................... 60
6.5 Ending calibration ................................................................................................................... 66
6.6 Test report ..............................................................................................................................67
6.7 Probe certificate...................................................................................................................... 68
6.8 Setting service warnings......................................................................................................... 69
6.9 Practical information for operation.......................................................................................... 69
6.10 Taking out of operation ........................................................................................................... 69
............................................................................... 58
I probe
1
Table of Contents
7 Service and Maintenance .......................................................................... 70
7.1 Checking/calibrating the KS1-DK combination probe.............................................................70
7.2 Checking the LT 2/KS1-DK.....................................................................................................71
7.3 Maintenance ...........................................................................................................................72
8 Fault Analysis/Trouble-shooting .............................................................. 75
8.1 Fault indicator via LED line in the LT 2/KS1-DK.....................................................................75
8.2 Warning indicator via LED line in the LT 2/KS1-DK ...............................................................78
8.3 Resetting faults/warnings........................................................................................................82
9 Spare Parts ................................................................................................. 83
9.1 Wearing parts..........................................................................................................................83
9.2 Spare parts .............................................................................................................................84
10 Appendix..................................................................................................... 86
10.1 Technical data of the LT 2/KS1-DK lambda transmitter .........................................................86
10.2 Technical data of the KS1-DK combination probe..................................................................89
10.3 Electrical connection...............................................................................................................90
10.4 Pneumatic connection.............................................................................................................93
10.5 Electrical connection to field bus module................................................................................94
10.6 Fuses ......................................................................................................................................95
10.7 Jumpers ..................................................................................................................................96
10.8 Dimension drawing of KS1-DK combination probe ................................................................97
10.9 Dimension drawing of LT 2/KS1-DK in wall-mounted housing ...............................................98
10.10 Dimension drawing of LT 2/KS1-DK on mounting plate .........................................................99
10.11 Dimension drawing of display and operating unit for panel installation................................100
10.12 Wet/dry measurement – deviation, conversion table............................................................101
11 EC Declaration of Conformity ................................................................. 102
11.1 LT 2/KS1-DK lambda transmitter..........................................................................................102
2
1 General Information
1 General Information
1.1 Compliance with the German law on device safety The German law on device safety stipulates the following:
Note the instructions for use!
Proceed only in compliance with the present technical documentation (Publication No. DLT3015).
Use the devices only for the purpose described in this documentation.
Use by trained personnel only. The device may only be operated and serviced by persons whose knowledge and training qualifies them to do so.
Liability for the function of the device shall be transferred to the owner or plant operator.
Liability for the function of the device shall be borne by the owner or plant operator insofar as the device has been used by persons without the necessary knowledge, has been improperly used, serviced or repaired or has been handled in a manner that does not conform to proper use.
LAMTEC GmbH & Co KG is not liable for damages occurring as a result of non­compliance with the above instructions. Compliance with the above instructions shall not entail any extension to the warranty and liability provisions of LAMTEC GmbH & Co KG’s terms of sale and delivery.
Insofar as reference is made to laws, decrees and standards, the basis for these shall be the law of the Federal Republic of Germany.
3
2 Safety Information
2 Safety Information
The symbols below are used in this Manual as important safety notes for the user. They are located in the sections of the Manual wherever the information is needed. The safety information - and warnings, in particular - must be read and observed.
WARNING This draws attention to possible dangers to persons, particularly from electrical
equipment.
WARNING This indicates possible danger to persons in the event of improper handling of system
parts.
CAUTION! This indicates danger to system parts or possible adverse effects on function.
NOTE: This provides the user with important additional information about the system or
system parts, and supplies more in-depth tips.
This appears in texts containing instructions on how to proceed. In this connection, the plant operator is requested to comply with legal accident
prevention regulations during all work, and to do everything in his power to prevent harm to persons or property, as the situation dictates.
4
2 Safety Information
2.1 Proper use, conditions for use
Use
Proper use
The LT 2/KS 1D lambda transmitter is a universal, microprocessor-based measuring device for the direct measurement of the concentration of O2 and flammable, oxidising gas constituents (CO/H COe ), in the superstoichiometric range in combustion systems ( l >1 ), in
connection with the KS1-DK combination probe. The system is designed for semi-automatic calibration with air and test gas. If you are contemplating employing the measuring system for other purposes, and
cannot assess with certainty whether the device will function without problem in this application, please first contact the manufacturer.
Preconditions The preconditions for use are that system planning, assembly, installation,
commissioning, maintenance and repair work are carried out by adequately trained personnel, and such work is checked by responsible expert members of staff.
Expert handling In particular, please ensure that:
• Use of the device conforms to the technical data and stipulations regarding permitted use and assembly, connection, ambient and operating conditions (contained in the order documents, user information, nameplates, etc.) and the supplied documentation
• Local, system-specific circumstances and risks and regulations pertaining to technical operation of the device are taken into consideration
• All necessary measures to preserve the value of the device, e.g. for transport and storage, maintenance and inspection, are carried out.
The product described herein left the factory in perfect condition, conforming to technical safety regulations and having undergone inspections. In order to maintain this condition, it may only be employed in the manner described by the manufacturer. Likewise, suitable transport, storage and erection and careful operation and maintenance are prerequisites for the perfect, safe operation of the device.
This product must be installed and operated by appropriately qualified personnel, who are familiar with this safety information and warnings and are able to act on them faultlessly. Unqualified tampering with the device or non-compliance with warnings herein or affixed to the device may result in severe bodily harm and/or material damages.
Proper use of the device constitutes its use only for the applications referred to in the technical description. Consequently, additional devices or devices from other manufacturers must be recommended or approved by Lamtec.
Provided that the technical safety instructions and specifications for operation contained in this Manual are observed, in normal circumstances this device does not carry any risk of material damages or harm to health.
), referred to as CO equivalent (
2
5
2 Safety Information
2.2 Permitted users
Qualified personnel
User groups
Staff responsible for safety must ensure that
• Only qualified persons undertake work on system parts. Qualified persons have been authorised by staff who are responsible for the safety of people and equipment to perform the above activities on the basis of their training, experience or instruction pertaining to the device and their knowledge of relevant standards, provisions, accident prevention regulations and system behaviour. The deciding factor is that these persons can recognise and avoid possible dangers in good time when performing the above activities.
Expert staff are persons who conform to DIN VDE 0105 or IEC 364, or directly comparable standards such as DIN 0832.
• The above persons have the supplied manuals and associated order-related documentation at their disposal at all times during their work and heed these documents in respect of the avoidance of risk and damages.
The following three groups of users are permitted to handle the LT 2/KS 1D lambda transmitter:
A Service engineers from LAMTEC or their OEM customers, or trained customer personnel:
• Qualified engineers / technicians
• With very good knowledge of the device.
• “SERVICE” access level - password-protected
B Operators, the customer’s fitters, engineers for measuring and control technology, electrical engineers, electronics engineers
• With introductory knowledge of the device.
• “CUSTOMER” access level – password-protected
C Operating personnel with basic knowledge
• “OPERATION” access level – no password required
6
2 Safety Information
2.3 Safety equipment / protective measures
Danger posed by electrical equipment
Preventive measures to improve operational safety
Avoidance of consequential damages
Protection against escaping gas from the gas-bearing duct
The LT 2/KS1-DK system parts constitute equipment for use in industrial power installations. Switch off the supply voltage to the mains cables when working on mains connections or parts that conduct mains voltage. Refit any protection against electric shock that has been removed before switching on the supply voltage.
Unskilled use or inexpert handling can result in risks to health or material damages. Therefore, always observe the relevant safety notes to prevent damage.
If the LT 2/KS1-DK is employed as a sensor in combination with closed and open­loop control systems, the plant operator must ensure that a failure or fault in the LT 2/KS1-DK cannot result in impermissible damages or dangerous operating states.
In order to prevent faults that may themselves result in direct or indirect personal injury or material damages, the plant operator must ensure that:
• The responsible maintenance personnel can be notified at any time and as quickly as possible
• Maintenance personnel are trained to react appropriately to faults in the LT 2/KS1-DK and associated system malfunctions
• The faulty equipment is switched off immediately in cases of uncertainty
Switching off equipment does not result in direct consequential faults
In order to prevent faults that may themselves result in direct or indirect personal injury or material damages, take care to ensure that qualified personnel evaluate the faults and initiate the appropriate measures.
The KS1-DK combination probe is mounted directly on the gas-bearing duct by means of a counter-flange. If the probe is detached, depending on the system ­and particularly in the case of excess pressure - aggressive and/or hot gas may flow out of the duct and severely harm the health of unprotected operators, if suitable protective measures have not previously been introduced.
WARNING In the event of excess pressure and temperatures higher than 200 °C in the gas
duct, gas escapes when the KS1-DK combination probe is removed.
• Switch off the system before opening; if this is not possible, wear protective clothing and a protective mask.
• Set up warning signs to this effect in the vicinity of the probe mounting point.
• Seal the opening immediately after the work.
7
2 Safety Information
Shutdown / bringing back into service
2.4 Environmentally responsible behaviour, disposal instructions
The LT 2/KS1-DK lambda transmitter and KS1-DK combination probe constitute a high-quality electronic measuring system. Prudent behaviour is therefore essential during all measures, on shutdown, transport and storage.
CAUTION! Do not switch off the LT 2/KS1-DK lambda transmitter while the KS1-DK
combination probe is still mounted, even if the associated system has been shut down. Residual gases lead to corrosion and may damage system parts.
Do not store devices in the open air without protection! Always store in a dry place and, if possible, in the original packaging.
Upon deinstallation, protect cable ends and connectors against corrosion and dirt. Corroded connectors can lead to malfunctions.
Transport in the original packaging when possible
The LT 2/KS1-DK lambda transmitter has also been designed under consideration of ecological aspects. The assemblies can easily be separated from each other into different material types, and therefore put aside for recycling in this sorted condition.
8
3 Introduction
3 Introduction
The LT 2/KS1-DK lambda transmitter is a universal, microprocessor-based measuring device for the simultaneous measurement of the concentration of O constituents (CO/H exhaust gases of combustion systems in the superstoichiometric range ( l >1 ), in
connection with the KS1-DK combination probe.
3.1 System overview
and oxidising gas
), referred to as CO equivalent ( COe ), most commonly in the
2
2
Lambda­Transmitter LT 2
RS 232
(,
Operation
servicing
)
Option: CANopen Modbus Profibus DP Ethernet
Analogue inputs and outputs
CAN
Field bus
Digital inputs and outputs
to other LAMTEC FMS / VMS / ETAMATIC LT 1 / LT 2
devices
Combination probe KS1-DK
Recording
LAMTEC SYSTEM BUS
Digital inputs and outputs
Analogue inputs and outputs
Opti onal modules
O
2
CO/H
2
9
3 Introduction
3.1.1 KS1-DK combination probe
In the version for exhaust gas temperatures up to 450°C
The KS1-DK and KS1-DK-E combination probes enable in situ (directly in the exhaust gas), simultaneous measurement of the concentration of O gas constituents (CO/H gases in the superstoichiometric range (l>1).
), referred to as CO equivalent (COe), in combustion exhaust
2
and flammable, oxidising
2
KS1-DK
With calibrating gas connection for air / test gas – for semi-automatic calibration: Length: 500mm Type 656 R 2030
1000mm Type 656 R 2031 1500mm Type 656 R 2032
In version for exhaust gas temperatures up to 450°C incl. Blow-out device as an additional option
KS1-DK-A
with option
„blow-out device“
With calibrating gas connection for air / test gas – for semi-automatic calibration: Lenght: 500mm Type 656 R 2030A
1000mm Type 656 R 2031A 1500mm Type 656 R 2032A Solenoid valve device 24VDC Type 650 R 2080
See separate publication DLT3018
10
3 Introduction
In ejector version for exhaust gas temperatures up to 1400°C (on request)
With standard GED (stainless steel 1.4571), suitable for exhaust gas temperatures from 400°C...700°C.
With ceramic GED, suitable for exhaust gas temperatures up to 1400°C.
Optional extras: - High dust guard
- Transmitter protective box with housing heater
- Plug & Play
Can only be connected to LT2/KS1-DK-E via probe connection box
See separate publication DLT3010
KS1-DK-E with
standard GED
With option
„high dust guard“
11
3 Introduction
3.1.2 LT 2 lambda transmitter
In the version for KS1-DK
LT 2/KS1-DK lambda transmitter in IP65 wall­mounted housing
• Sheet steel H400 x W300 x D150 mm
• With display and operating unit
• With two analogue outputs 0/4...20mA Type 657 R 1028
• Optionally with integrated reference air pump Type 657 R 1060 This increases the housing size to 500 x 300 x 200 mm (HWD)
• Also see section 4.4.1
Two basic versions are available:
LT 2/KS1-DK lambda transmitter on mounting plate
• 350 x 258 x 132 mm (HWD)
• Without display and operating unit
• Type 657 R 1032
• With two analogue outputs 0/4...20mA
• Also see section 4.4.2
In the version for KS1-DK_E
LT 2/KS1-DK-E lambda transmitter in IP65 wall­mounted housing
• Sheet steel H400 x W300 x D150 mm
• With display and operating unit
• With two analogue outputs 0/4...20mA Type 657 R 1033
• Can only be connected to KS1-DK-E via PCB
• See separate publication DLT3010
12
3 Introduction
3.2 Theoretical principles of measurement
The KS1-DK combination probe basically consists of an electrochemical cell of zirconium dioxide ceramic.
It has three electrodes:
• O
-sensitive platinum electrode
2
• CO/H
Platinum reference electrode
3.3 Probe method of functioning - O2-sensitive electrode
Gas in let
-sensitive electrode of a platinum/precious metal alloy
2
CO/H electrode
2
(Pt / noble metal alloy)
Reference electro de (Pt)
U
S
U
H
Zi rc o niu m oxi de ce r ami c
Protective coating
O-selective
2
reference electrode (Pt)
Ho usin g
Schematic diagram of the structure of the KS1-DK combination probe The O
measuring cell functions as an electrochemical concentration cell and
2
generates a direct voltage, which depends upon the absolute temperature T and the logarithm of the O electrode and O
If specimen gas is fed to the outer electrode and a reference gas with a known O
concentration ratio or O2 partial pressure ratio on the reference
2
outer electrode.
2
2
concentration, such as air (20.96 %), to the inner electrode, at a constant temperature the logarithmic relationship illustrated below occurs between the probe voltage U and the oxygen concentration of the specimen gas.
Sensor characteristic U = f (O2 )
13
3 Introduction
3.4 Probe method of functioning - CO/H2-sensitive electrode
Flammable constituents are, like oxygen molecules, adsorbed on the electrode and diffuse to the “three-phase limit” formed by measuring gas, the electrode and zirconium dioxide. In addition to the Nernst voltage U oxygen content, the flammable constituents in the measuring gas also generate an additional direct voltage U of the two voltages U gases, such as H
= U
S
or CO, the mixed potential is considerably higher than the O2
2
signal. The formation of the mixed potential takes place very rapidly, t are achieved.
through the sensor. The sensor voltage is the sum total
CO/H2
O2
+ U
(Fig. 1). Even at low concentrations of oxidising
CO/H2
determined on the basis of the
O2
times under 2s
60
Sensitivity to O A lower sensor temperature results in greater sensitivity to CO/H to O
(Fig. 2).
2
Likewise, the oxygen concentration has an influence on the sensor voltage U
content increases, the sensor voltage drops off slightly in the high CO range
the O
2
and flammable constituents is influenced by the sensor temperature.
2
and lower sensitivity
2
. As
COe
(Fig. 3). However, the KS1-DK combination probe must never be operated when too cold, as
otherwise the oxidising constituents will influence the O
measurement (falsification of
2
measurement values produces lower values due to the oxidation of unburned flue gas constituents on the O
U
s
(mV ) CO
electrode).
2
Sensor characteristic s (measured)
Nernst characteristic (calc ulated)
incomplete combustion
Fig. 1: Characteristic of a gas burner
complete combustion
Fig. 2: Sensor voltage U
as a function of sensor temperature (heating power)
COe
14
O (%)
2
3 Introduction
If concentrations of O
are higher, more unburned residues (CO/H2 ) oxidise before
2
the 3-phase limit is reached. The graph below shows the influence of the sensor voltage U
as a function of the O2 content.
COe
1000
800
600
e
400
at starting
point with
0% CO
CO
U [mV]
200
9,5 % O 6
% O
2
2
0
0
2000
4000
6000
CO [ppm]
Fig. 3: Sensor voltage U
as a function of O2 content
COe
8000
10000
We therefore recommend calibrating the characteristic in line with the specific system by performing a CO reference measurement.
A further indicator for unburned residues (CO/H
) in combustion systems is the
2
dynamics of the sensor signal (Us). As the content of unburned residues increases, so do the dynamics. Figure 4 below plots the rise of the sensor signal versus the measured O
value in a reference system (12 MW gas combustion) at low load.
2
700
600
500
400
300
Sensor
Signal dynamic > 100 mV+
300
U [mV]
200
100
0
0
small load
1
2
3
O ref. [%]
2
4
56
40
2
CO [ppm]
Fig. 4: Sensor voltage U gas combustion
plotted versus the O2 value of 12MW
COe
15
4 Technical Description
4 Technical Description
4.1 Advantages of the LAMTEC measurement principle
Direct (in situ) measurement of oxygen (O constituents (CO/H
O
measuring range: 0 to 21 vol.% in conjunction with
2
measuring range: 0 to 10,000 ppm LT 2/KS1-DK
CO
e
Uninfluenced by infiltrated air (CO
No treatment of the gas required, measurement directly in the damp flue gas
Setting time to 60 % value (T90 ) <10 seconds with standard sampling
< 2 seconds
CO
e
Measuring gas temperature up to 450°C
Up to 1400°C possible with ejector pump
Low heating power 20...25 watts depending on the exhaust gas temperature
• Universal
Easy to use
• Low-maintenance
) in crude gas up to 450°C
2
)
e
) and oxidising exhaust gas
2
}
4.2 Necessary components
KS1-DK combination probe
• Flange gasket
Internal/external reference air pump or compressed air connection
LT 2/KS1-DK lambda transmitter in IP65 wall-mounted housing incl. display and operating unit, or
on IP00 mounting plate for installation in control cabinet, without display and operating unit
(optional display and operating unit for installation in the control cabinet door,
cable length 1m, Type 657R0831T) or
Remote display software for Windows PCs Type 657R1101
16
4 Technical Description
4.3 Basic design of the LT 2/KS1-DK
Semi-automatic calibration system
Pos.
1
1a
1b
1c
1d
1e
1f
3
2
max. 450°C
1
4
Combination probe KS1-DK with semi-automatic calibration system Type 656 R 2030 / R2031 / R2032
Probe connection box (PCB)
Hose connector „Test Gas” Instrument air for offset calibration or Test gas
- pre pressure 0,3bar Outlet for reference air
Hose connector „reference air”
- Instrument air (pre pressure 0,3bar) or
- Reference air pump **
- Air consumption 40...60l/h Cable glant M16
- Probe heating Cable glant M20
- Absolut pressure sensor
- Difference pressure sensor
- Probe signals
1a
5
6
1b
1c
1d
1e1f
7
Pos.
2
Pre filter Type 650 R 2055
3
Counter flange DN65 Type 655 R 0137 / R 0138
4
Flange gasket Klinger Sil C-4400 Type 655 P 4209
5
Lambda Transmitter LT2-K / KS1-DK with semi-automatic calibration system Type 657 R 1028 / R 1032
6
Display and operation unit
- built-in in LT2
7
Relay module 660R0017 for output of status of operation and limits
- 6 relais with 1 change-over contakt
- built-in in LT2 Type 657 R 0857
To use the semi-automatic calibration system, connect the compressed air (instrument air) for offset calibration and the test gas manually to the probe one after the other and set the required quantity.
** If no instrument air is available for the reference air, an optional pump unit is available.
The pressure sensors are integrated in the probe connection box on the head of the probe. The differential pressure sensor monitors the reference air, the absolute pressure sensor monitors the rise in pressure in the preliminary filter during calibration.
Electrical und pneumatic connections see chapter 10.3 and 10.4.
17
4 Technical Description
4.4 LT 2/KS1-DK
4.4.1 In wall-mounted housing
The LT 2/KS1-DK lambda transmitter is the data interpreting device for the KS1-DK combination probe. It incorporates all the necessary components for the operation of the KS1-DK combination probe and the evaluation of the measurement signal. Furthermore, it features additional analogue inputs and outputs, digital inputs and outputs for process status signals, status signals and limit value signals, as well as serial interfaces and a universal bus interface (optional extra) for connection with the customer’s control systems.
Without reference air pump: Type 657 R 1028
400 x 300 x 150 (HWD)
With reference air pump: Type 657 R 1060
When the optional reference air pump is used, the size of the wall-mounted housing changes
500 x 300 x 200 (HWD)
18
4 Technical Description
4.4.2 On mounting pate Type 657 R 1032
Transformer
for probe and
electronics
Fuses
Supply voltage
commutation
AC115V/AC230V
NOTE Replace fuse
Slot for relay module
657R0857 (optional
extra)
Buffer amplifier for converting the COe signal from mV into mA (no longer required from January
2007)
Connection for remote display software (optional extra)
Probe connection
Protective earth terminal for cable screening
4.4.3 Display and operating unit for panel installation
For use with the LT2-KS1D-K on mounting pate. For installation in the control cabinet door. Max. cable length 1m. Type 657R0831T
Internal display and control elements:
LEDs Maintenance switch Multi-function
19
4 Technical Description
4.5 Internal display and control elements of the LT 2/KS1-DK lambda transmitter
The LT 2/KS1-DK is operated and the measurement values, process status and fault status signals are displayed via the display and operating unit (see section 4.6), or via PC in conjunction with the remote display software. The LT 2/KS1-DK itself features only limited operator controls, which nevertheless permit the initiation or display of all functions necessary for operation, maintenance and service directly on the LT 2/KS1­DK as well.
Warning / Fault display
Operating mode display
Maintenance switch
Multi­function­key
Display- and operating elements on processor card
5.1.3 Display and operating elements
LED 12
LED 6
LED 1
1
LED 5
LED 10
LED 4
Operational display (green) LED 6 Operational status display (green) LED 5 Maintenance switch S 1
Oper ation (lights up) Measurement ( lights up)
- -
-
LED 10
LED 1
LED 12
1
LED 4
LED 5
LED 6
Ma in tenan ce ( or a nge ) LED 1 Warni ng/
Maintenance mode active (lights up)
-
Normal operation (off) No warning / fault
- -
LED 10
LED 11
LED 12
LED 9
LED 3
LED 9
LED 3
LED 9
LED 8
LED 2
LED 8
LED 2
LED 8
LED 7
LED 1
LED 7
LED 1
LED 7
S 1
S 1
LED 7
LED 8
LED 9
LED 10
LED 1
LED 12
1
T 2
2
LED 6
LED 5
LED 4
LED 3
LED 2
LED 1
S 1
T 2
2
LED 12
LED 6
LED 5
LED 4
LED 3
LED 2
LED 1
S 1
LED 7
LED 8
LED 9
LED 10
LED 11
Calibra tion (flashe s) Offset compensation (flashes slowly)
-
With test gas / comparative measurement (flashes rapidly)
-
LED 10
LED 1
LED 12
1
LED 9
LED 8
LED 7
Maintenance mode
-
o ff
T 2
2
LED 5
LED 6
LED 2
LED 3
LED 4
T
S 1
2
2
LED 1
Maintenance mode
­ o n
fault display (red) LED 12
At least one warning present (lights up)
-
At lea st one fa u lt p re sen t (f l as h es)
-
T 2 2
T 2
S 1
2
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
20
4 Technical Description
4.5.1 Multifunction push button T1
NOTE:
Function Button assignment
4.5.2 Monitor output
Processor board micro-switches
Change the displayed warning/fault
Reset the displayed warning/fault
Quick start measuring gas pump, abort cold start
Initiate offset calibration or test gas calibration
Press briefly
Press for more than 3s *
Press for more than 3s **
Press button for more than 3s ** in measurement mode
* Some warnings and faults cannot be reset as long as the fault is still present or the routine is still in progress.
** If at least one warning or fault is present, the button must be pressed for more than 6 seconds.
The monitor output [terminal 31 (-), 32 (+)] allows a multimeter to be connected, for example. Via the monitor output, the following measurement values can be obtained in situ on the LT 2/KS1-DK:
measurement value
• O
2
Probe voltage [U-O2] of O
AC internal resistance [R
sensor
2
probe] of O2 sensor
i
SW 1 SW 2 Function of monitor output
off off
on off
off on
O
measurement value 0...2.5 V ≡ 0…25 vol.% O2
2
Probe voltage (U-O2) of O
Cell internal resistance (Ri probe) of O
Input resistance of connected measuring device > 10 k
sensor 0...2.5 V 0…250 mV
2
sensor 0...2.5 V 0…250
2
21
4 Technical Description
4.6 Display and operating unit
The display and operating unit of the LT 2/KS1-DK consists of an LCD, the cursor keys, the Enter key and the menu keys.
The cursor keys enable you to select measurement values, parameters or functions in the viewing window of the display. These keys also allow you to position the cursor to input and edit (Change) data.
The Enter key activates, confirms and exits Edit mode
The menu keys are assigned to the menu items shown above them in the display.
The screen is divided into three sections:
1. The status bar at the upper edge of the screen. This shows:
Whether Maintenance mode is active (left).
The current operating state (centre). Whether any warnings or faults are
present (right). The status bar also flashes to indicate
faults.
2. The measurement value is shown in the middle of the screen.
3. The menu bar, in which entries are made using the menu key below.
The menu keys feature functions for the LT 2/KS1-DK in abbreviated English:
measurement, calibration Parameter setup, diagnosis
NOTE: The limit values are only displayed if they have been activated via the
parameters 930/940/950/960 ( “Service” access level ) (see section
4.12.8)
22
4 Technical Description
4.6.1 Menu function
When the [meas] key is pressed, the screen switches to a large display of the measurement value, which is selected using the cursor keys (up, down). By pressing the [meas] key several times, you can return to the display of all measurement values.
4.6.2 Menu function
When the [cal] menu key is pressed, “Start calibration” appears in the display. When calibration has been activated, a choice of four calibration functions is available:
Offset calibration on ambient air
Offset calibration with compressed air, open before
Calibration with reference measuring
O2 calibration with test gas, open gas
CO calibration with test gas, open gas
You can select the required calibration function using the cursor keys (up, down). Pressing the ENTER key confirms the selected calibration function and initiates this calibration process.
You can interrupt the calibration modes using the menu function: “Abort calibration, return to measurement mode”.
An O
default value is displayed during the calibration process. It only makes sense to
2
measure or display the O
value in the measuring operating state, that is, when
2
calibration is over. See also chapter 6.5.
23
4 Technical Description
4.6.3 Menu function
Opening the [ par ] menu opens the menu for the parameters.
The Parameter menu is available to the following access levels:
• Operation level
• Customer level
• Service level
(only accessible via password)
• Factory level
NOTE: The password for Customer level can be assigned individually by the customer.
The screen displays the current access level. The menu bar contains a choice of menu functions:
[ exit ] returns to Start menu
[ psw ] changes the access level to enable password entry
[ view ] shows the parameter settings. All parameters are displayed, irrespective of the access level.
[ change ] allows you to change parameters, but here only the parameters available to this access level are displayed.
NOTE: Over 3000 parameters can be changed in the various access levels. To avoid
confusion, we therefore recommend that you use the [ change ] function.
4.6.4 Menu function
[ psw ] opens the sub-menu for password entry, and the Operation* access level is displayed. The functions shown in the menu bar are as follows:
[ exit ] returns to the [ par ] menu
[ clear ] resets the access level to Operation level*
[ ---- ] moves to the previous password input letter of the alphabet.
[ ++++ ] moves to the next password input letter of the alphabet.
The cursor keys (up, down) have the same function as [ ++++ ] and [ ---- ]. Use right and left to move the input sign along the password. If the correct password is entered, the appropriate access level is displayed and is maintained when the menu is exited with [ exit ]. If no keys are pressed for a longer period, the access level resets itself to Operation level.*
* If the password for Customer level is still at the factory setting, the systems goes to Customer level instead.
24
4 Technical Description
4.6.5 Menu function
[ view ] opens the Parameter menu. The functions of the menu bar are as follows: [ exit ] returns to the [ par ] menu function. [ s/l ] changes the display format:
Short: Only the number of the parameter and the current value are displayed.
Medium: A brief description is displayed in addition to the parameter number and the current value.
Long: In addition to the Medium display, a status bar for the parameters is shown.
[ group - ] pages back by one parameter group. [ group+ ] pages forwards by one parameter group.
All the available parameter groups are set out in the appendix. The cursor keys (left, right) correspond to the key function: [ group- ] or [ group+ ]
If not all parameters of a group are displayed in the viewing window, this situation is indicated by flashing arrows in the right-hand margin. You can move and view the parameters using the cursor keys (up, down).
Here is an example of the status bar shown with the Long display:
*kw*_30_[12 ,42 ]_____ The asterisks ‘ * ‘ or ‘__’ are fill characters.
“k” indicates Customer access level (o = Operation, c = Customer, s = Service, f = Factory)
“w” shows the type of parameter (write = can be edited, read = read only)
“30” is the ‘default’ value (basic value in EPROM)
“[ 12 ; 42 ]” is the possible range within which the parameters can be changed
With some parameters, no ‘default’ value or interval is shown!
25
4 Technical Description
4.6.6 Menu function
[ change ] allows you to change parameter values. The sub-menu in the menu bar is
the same as the [ view ] menu. But unlike this, the parameter to be changed is shown inverted (pale font on dark
background). Select the parameter using the cursor keys (up, down). Then press [ENTER] to activate Edit (Change) mode. The parameter value flashes while it is being edited.
A selected parameter is displayed in three ways:
Inverse display
Parameter can be changed
Bordered display
Parameter cannot be changed
Blinking display
Edit (Change) mode is active
You can now change the parameter value using the cursor keys (up, down, and left and right for values with several characters). The functions in the menu bar are as follows:
[ esc ] returns to the [ change ] menu without confirming the
changed parameter.
[ dflt ] resets the ‘default’ (factory-set) value.
[ OK ] confirms the changed value and returns to the [ change ] or [ENTER] menu.
This takes you back to the [ change ] menu. You can then open and change other parameters.
26
4 Technical Description
4.6.7 Menu function
The [diag] key switches the screen to the display of warnings and faults. You can select individual warnings, faults or limit values using the cursor keys (up, down).
NOTE: Limit values are only displayed if they have been activated via the parameters
930/940/950/960 (Service level).
The selected warning or fault, which is displayed inverted, can now be acknowledged or reset with ENTER.
When you select a limit value with the cursor and then press Enter, the display switches to the Limit Value menu.
If you select “maint.”, the LT 2/KS1-DK can be switched to Maintenance mode, as an alternative to using the maintenance switch on the processor board.
If you select “remote”, remote display is possible via LSB with a 2nd LT. To achieve this, the master LT must have the LSB address 10, the slave LT the LSB address 9 (param. 3801).
If you select “hist”, a fault and warning history is displayed. Setting, date and time param. 70...72.
NOTE: Not all warnings and faults can be reset by acknowledging them - the cause of the
warning or fault may have to be corrected first.
27
4 Technical Description
4.6.8 Display parameters 970 / 971 / 972
The ***Display*** parameter group is responsible for the display and operating unit for the LT 2/KS1-DK, with the following parameters:
• P. 970 Contrast
This parameter allows you to adjust the contrast of the display.
• P. 971 Brightness
This parameter regulates the brightness of the display’s background illumination.
• P. 972 Language
With this parameter, you can set the language (English, German) of the displayed texts.
4.6.9 Brightness and contrast
Alternatively, the brightness and contrast can be altered using the Display parameters (see 3.1) or cursor keys as follows:
Contrast + Keys 1 & 2 Contrast - Keys 3 & 4 Brightness + Keys 1 & 4 Brightness - Keys 2 & 3 Press the above keys simultaneously.
28
4 Technical Description
4.6.10 Entering the customer password
The password for Customer level can be assigned individually by the customer. To enter a new password, the Customer access level or higher must be activated. The new password must be entered in parameter 1472, (see figure below).
CAUTION! A few seconds after the password is entered, it is accepted by the device and “####”
is displayed. Thus, once a password has been entered, it can never be read out again.
NOTE: The factory-set password is “0000”. Since this is the default setting for password
entry, you can activate Customer level by changing briefly to password entry and then exiting again without making any changes.
29
4 Technical Description
4.7 Analogue output
Analogue output 1 - terminal 42 (-), 43 (+) Output of O
Analogue output 2 - terminal 44 (-), 45 (+) Output of COe value 0...1000ppm Æ 4...20mA, or alternatively 0/2...10V
Optional modules 3 and 4
Parameters 530 / 540 / 550 / 560 Æ Setting the function:
• OFF /diagnosis
• O
Configured measurement value 1...6
• Ri probe
O2 probe voltage (U-O2)
• COe
• U-COe
Parameters 531 / 541 / 551 / 561 Æ Setting the output value:
4...20mA / error 20mA
4...20mA / error 0mA
• 4...20mA
0...20mA / 0...10V
4…20mA / maintenance 0mA
Parameters 532 / 542 / 552 / 562 Æ Lower range limit Parameters 533 / 543 / 553 / 563 Æ Upper range limit
value 0...10% Æ 4...20mA, or alternatively 0/2...10V
2
measurement value
2
Can be retrofitted at any time by means of plug-in cards on the LT 2/KS1-DK processor board (max. 4)
Type 6 57 R 0050 non-floating Type 6 57 R 0051 floating, maximum possible potential difference ± 20 V (only
possible with outputs 1 and 2)
Floating output card 657R0051
The jumpers only switch between the current and voltage outputs in terms of hardware.
The choice between 0 or 4...20mA is made using the parameters 531/541/551/561.
30
4 Technical Description
4.8 Digital inputs
Eight digital inputs can be configured for the LT 2/KS1-DK lambda transmitter. Depending on the supplied voltage, the digital inputs take on the setting High (supplied voltage 24 V) or Low (input open or supplied voltage 0 V).
Parameter groups 1170...1245 Depending on this setting, the LT 2/KS1-DK lambda transmitter can execute certain
functions. All eight digital inputs are identical in terms of structure and functionality. The digital inputs are configured by means of the parameters listed below.
Factory-set assignment of digital inputs
• Input 1 → Reset fault/warning
• Input 2 → Reset limit value signal (also see 5.4)
• Input 3 → Offset calibration
• Input 4 → PID controller Off
• Input 5 → Maintenance On/Off (ab1v33a)
• Input 6
• Input 7
• Input 8
(1)
Fuel 2 (gas)
(1)
Fuel 3
(1)
Fuel 4
(1)
Parameter 836 – Service level – must be set to “Digital inputs”.
Without preset signal Fuel oil EL
31
4 Technical Description
4.8.1 Parameters of digital inputs
Idle state
Here you can set the idle state of the digital input. If the state differs from the one set
Parameters: 1170/1180/1190/1200/ 1210/1220/1230/1240
Functions A,B,C,D
Parameters: 1171….1244
here, the actions predefined for the functions (A, B, C, D) are executed. If Diagnostic mode is set here, the functions (A, B, C, D) can be initiated for the corresponding digital input by means of the State parameter.
LOW (normal open contacts)
• HIGH (idle)
• Diagnostic mode
The four functions are very similar in structure, but the assignment of the limit values LV 1 - 4 or fuels to the individual functions
(A, B, C, D) is limited. Reset limit value 1 and Fuel 1 are only possible with function A; Reset limit value 2 and Test gas 2 only with function B, etc.
State
The following actions are possible:
• None
Offset calibration Initiates offset calibration.
Fault reset Acknowledges present faults.
Warning reset Acknowledges present warnings.
Reset LV 1 (Function A) resets limit value 1, functions B, C and D reset the limit values 2, 3 and 4 respectively. Therefore, the corresponding LVs must be set to Acknowledge” in Reset mode
• Fuel 1 (Function A only) selects fuel 1, functions B, C and D select fuels 2, 3 and 4 respectively.
• Probe 1 (Function A) selects probe 1, functions B, C and D select probes 2, 3 and 4
No cal. Calibration disabled
PID controller On/Off If the PID controller option is enabled, here you can switch off the PID controller.
Maintenance Switches the device to “Maintenance”
Deactivate Limit value x (also see section 4.13)
Parameters: 1175/1185/1195/1205/ 1215/1225/1235/1245
This parameter indicates the state of the digital input. The three possible states are inactive (idle state) and active; the set functions (A, B, C, D) are initiated. The state of the digital input can be set manually with this parameter, provided that the idle level parameter is set to Diagnostic mode.
32
4 Technical Description
4.9 LAMTEC SYSTEM BUS
NOTE: Data transmission in the LT 2 via the LAMTEC SYSTEM BUS only functions if the
device is set to “MEASUREMENT” and is not in “MAINTENANCE MODE” or “FAULT”.
When communication is taking place correctly, the two LEDs 1 and 2 flash.
For connecting the field bus module, please see section 10.4
4.9.1 Parameter setting (from software version 1V14)
• P3800 Value 1 (default)
LAMTEC SYSTEM BUS – Version 1
P3801 - Devices ID9 (default) If there is more than one LT in a family, they must have different IDs. These are set from ID9...ID16.
• P3802 Device family 1 (default) All devices that exchange values with one another must be set to the same family.
• P3803 O2 OUTPUT VALUE (default) The LT transmits its O2 value for all devices of the same family. NO: The LT does not transmit an O2 value for devices of the family.
P3804 - Transmit CO value for family NO (default): The LT does not transmit a CO value for devices of the family. CO MEASUREMENT VALUE: The LT transmits its CO measurement value for all devices of the same family.
4.9.2 Jumpers, LEDs, fuses and terminals
F6 – T315mA Æ DC5V-LSB
BR12, BR13 Æ setting “C”
BR105 Æ setting 2-3 (clockwise)
LED1 – green Æ RxD of LSB LED2 – yellow Æ TxD of LSB
BR101 Æ setting 1-2 (clockwise) Without LSB termination resistor BR101 Æ setting 2-3 (anti-
clockwise) With LSB-termination resistor
Term.71 Æ CAN-GND Term.74 Æ CAN-H Term.75 Æ CAN-L
33
4 Technical Description
4.10 RS 232 interface
Device address 1 9600 bauds Parity none
4.11 Cold start delay
This function is used to suppress false measurement values while the probe is warming up. A cold start delay is always activated after “Power off” and probe replacement. The cold start delay can be interrupted at any time:
using the multi-function starter
using the display and operating unit
using remote display software, see separate publication During the cold start delay or a fault:
a default value (factory setting) O
In P362 for O in P372 for CO the “Type of default value” can be set:
0 vol. % (P361), COe Æ 0 ppm (P371) can be output.
2
,
2
e
OFF: No default value is output. ON: The default value set in the parameter in front is output. +Maintenance (factory setting): The default value set in the parameter in front is
output during “MAINTENANCE” as well. +Maint.froz.: With this setting, the default value set in the parameter in front is output
during cold start and fault, as before, but in addition the previous measurement value is frozen as long as Maintenance mode is active.
During cold start/fault, the default value has priority over the freezing of the measurement value during maintenance.
After a heating phase of 10 minutes, the probe voltage U-O2 stabilises to values between -20 mV…+20mV and the internal cell resistance Ri settles at values below 100 .
34
4 Technical Description
4.12 Optional extras
Remote display software
• Measurement of flue gas and intake air temperature, and calculation of the efficiency of combustion
Calculation and display of the concentration of CO2, calculated for the specific fuel on the basis of the measured O2 value and the max. CO2 value
Load-dependent and fuel-specific limit values/limit curves
• Integrated PID/O2 controller
(Outputs 1 and 2) max. potential difference 20 V configurable as desired Direct current 0/4...20 mA, burden 0...600W
Digital outputs in conjunction with relay module 657R0857
Field bus connection
Heating for wall mounting case
4.12.1 Remote display software
PC software for configuring the LT 2/KS1-DK as an alternative to the display and operating unit, and for saving and restoring the data record.
Remote display software incl. interface module RS 232 for PC Type 6 57 R 1101
Further licences for remote display software Type 6 57 R 1102
For Windows PCs. Connection to the LT 2/KS1-DK via RS 232 interface. See separate manual DLT1004.
35
4 Technical Description
4.12.2 Measurement of flue gas and intake air temperature and calculation of the efficiency of combustion Type 6 57 R 0895K
NOTE: Since three of the four analogue inputs are assigned in the LT 2 / KS1 DK, the
differential pressure sensor, which monitors the reference air, is removed and replaced with a flow meter with limit value signal. This signal is fed to a digital input and monitored as the warning “No reference air”.
This frees up an analogue input for the intake air temperature. See overleaf for electrical connection diagrams. If the intake air temperature can be set as default beforehand, the above measure is
superfluous.
The calculation is based on the formula: n
= 100 ( qAf + qAg ) %
F
q
= loss of exhaust gas due to free heat
Af
q
= loss of exhaust gas due to latent heat
Ag
q
= ( tA - tL ) * [A2 / 21 – O2 + B]
Af
The calculation of exhaust gas losses is based on the following mean fuel values: Oil A Gas A
= 0.68 B = 0.007
2
= 0.66 B = 0.009
2
It is assumed that the combustion of CO and black smoke takes place freely. The exhaust gas losses due to latent heat Ag are ignored.
Display: Efficiency 0...100% Exhaust gas losses 0...100% Exhaust gas temperature 0...320°C (measuring card at analogue input 3) Intake air temperature 0...320°C (measuring card at analogue input 2) Other ranges on request Measurement accuracy: Temperature better than 2K Efficiency/exhaust gas losses better than 0.2 %
In the 6 57 R 0896 version, the intake air is fixed as default. The intake air temperature is therefore not measured. This is only recommended if the intake air temperature remains virtually constant the entire year round. The average intake air temperature can be defined in parameter 1450.
For electrical connections, see the following two pages.
36
4 Technical Description
w
w
Electrical connection of the LT2/KS1-DK with efficiency calculation
K
K
-D
-D
/KS1
Lambda-Transmitter LT 2
Lambda-Transmitter LT 2/K
with efficiency calculation
Analoge outputs 0/4…20 mA 0/2…10 V (Option)
* on
processor board
S1
*
Module 4
*
Module 3
*
Module 2
*
Module 1
(+)
(-)
(+)
(-)
(+)
(-)
(+)
(-)
49 48
47 46
45 44
43 42
Output 4
Output 3 not connected
Output 2 0...1000ppm COe = 4...20mA
Output 1 0...10% O2 = 4...20mA
80...100% efficiency = 4...20mA (Option)
(reserviert für Option CO2-Berechnung oder Abgastemperatur)
Analoge Inputs
Probe­connection KS1-DK
Module 1
657P0660
Module 2
657P0890
Temperature
Module 3
657P0890
Temperature
Module 4
657P0650 absolut pressure
CO/H2 sensor signal -
O2 sensor signal -
CO/H2/O2 sensor signal +
Sensor heater
sensor heater
Signal input CO/H2-signal
+
internal used
-
18 17 16 15
22 21 20 19
26 25 24 23
PT 100­element
not
iring
PT 100­element
not
iring
Flue gas temperature 0...320°C
Probe Connection Box KS1-DK
26 25 24 23
diameters
12
33
34
35
36
CO/H2 sensor signal -
12
33
O2 sensor signal -
CO/H2/O2
34
sensor signal +
sensor heater
35
sensor heater
36
sensor signals, \ pressure sensors
up to 50 m = 0,8 mm multi cable J-Y(ST)Y-G
diameters sensor heater
up to 20 m = 1,5 mm up to 50 m = 2,5 mm
2
2
2
Relay outpt 1 0- 42V DC 3A
0-230V AC 2A
F1 T1A T2A
/ 250 V [230 V] / 250 V [115 V]
3 2 1
PE N L
For example, combined fault indication (configurable as required) Manufacturer's setting: fault current principle
=
Earth
= Neutral conductor = Phase 230 / 115 V, 48...62 Hz
Line power consumption typically 50 VA Short-term (probe heating phase) ca. 150 VA
To be used only in grounded power line networks !
37
4 Technical Description
-D
-D
S1
Lambda-Transmitter LT 2/K
Lambda-Transmitter LT 2/K
with efficiency calculation
S1
K
K
LAMTEC SYSTEM BUS (floating)
Digital inputs 24 V, ca. 6 mA Bridge BR 106, BR 107 on power electronics
1-2 referenced to (bottom) - instrument potential 2-3 floating potential for (top) - external voltage source
+24 V
Flowmeter of the reference air with limit contactor
40...60l/h
75 74 73 72 71
Fuel 4
69
Fuel 3
68
Fuel 2 (Gas)
67
Maintenance ON/OFF
66
Reference air
65
Calibrat ion
64
Reset limits
63
Reset faults/warnings
62 61 60
CAN Low CAN High not con. not con. CAN-GND
Input 8 Input 7
Input 6 Input 5
Input 4 Input 3 Input 2
Input 1 GND
24 V DC
LAMTEC SYSTEM BUS (CAN-BUS)
Monitor output 0…2,5 V DC
switch over to O , U (only 0 mV)
2S
>
Socket for interface module, 25 pins
(+) (-)
32 31
For example, for connection of a multimeter for service purposes Ri > 10 k
Interface module
RS 232
Only in conjunction with remote display software
RS 422 - 6 63 P 0500
- 6 57 R 1101
38
4 Technical Description
4.12.3 Calculation of the concentration of CO2, calculated for the specific fuel on the basis of the measured O
4.12.4 Load-dependent, fuel-specific limit curves (optional extra) Type 6 57 R 0920
value and the max. CO2 value Type 6 57 R 0910
2
The calculation takes place according to the following formula: CO
= CO2max – (21 % -O2 / 21%)
2
The calculation is based on the following maximum CO
contents at λ = 1 = O2 = 0 vol.
2
% with dry exhaust gas Fuel oil EL 15.4 vol. % Natural gas H 12.0 vol. % Fuel oil S 15.9 vol. % Natural gas L 11.7 vol. % CO
max can be preset individually via the parameters 846, 862, 878 and 894.
2
Output via analogue output 3:
0...20% CO2 = 4...20mA
The load rating (burner load) or another measured variable is activated via analogue input 4 or the LAMTEC SYSTEM BUS. Instead of fixed limit values, fuel-specific curves with two to maximum 18 interpolation points can be entered.
Limit curves (factory setting) parameterised to undershoot, or alternatively two fuels with four limit curves each/two limit values per fuel
4.12.5 Integrated PID/O
controller Type 6 57R1120
2
See separate manual DLT4002.
4.12.6 Output of internal load via analogue output (only in conjunction with ETAMATIC/FMS/VMS) Type 6 57 R 1124
Forwarding of internal load via current input or LAMTEC SYSTEM BUS.
0...1000digits load Æ 0/4...20mA
39
4 Technical Description
4.12.7 Digital outputs
Digital output 1 (standard):
Included as standard in LT 2/KS1-DK basic electronics via internal relay (1 change-over contact) (terminals 1, 2 and 3, also see 10.3).
Switching capacity 230VAC / 2A and 42VDC / 3A
Digital outputs 2 to 7 (optional extra): Via internal relay module Type 657 R 0857 (6 relays - 1 changeover switch) Switching capacity 230VAC / 4A and 48VDC / 3A Digital outputs can be configured as desired using the display and operating unit and
remote display software. Parameter groups 1030 to 1099.
Parameters of digital inputs
Idle state
Parameters: 1030/1040/.../1090
Factory setting:
Relay output 1: Collective fault quiescent current method
Relay output 2: Warning and maintenance
Relay output 3: Measurement
Relay output 4: Limit value 1
Relay output 5: Limit value 2
Relay output 6: Limit value 3
Relay output 7: Limit value 4
Here, the idle state is set. This state is present when none of the functions triggers a switching operation. The Diagnostic mode setting allows the idle state to be changed via the State parameter (see below).
LOW (normal open contacts)
HIGH (idle state)
• Diagnostic mode
40
4 Technical Description
Functions A,B,C,D
Parameters: 1031 to 1034 1041 to 1044 ….. 1091 to 1094
The four functions have virtually the same structure, and an operating state can act as a switching criterion. If a limit value (LV 1-4) is selected as a switching criterion, the output switches when the limit value output is enabled. If, for example, maintenance is chosen as the switching criterion, the output is not in the idle state during maintenance.
Each function (A, B, C, D) may have all operating states as the switching criterion, but the assignment of the limit values LV 1-4 or test gases to the individual functions is limited. Limit value 1 and test gas 1 are only possible with function A, limit value 2 and test gas 2 with function B, etc. Nevertheless, thanks to the OR logic of the four functions, all combinations can be set.
The following operating states can be selected as switching criteria:
• Off
• Warning
• Fault
• Calibration
• Check
• Cold start
• Measurement
• Standby
• Maintenance
Limit values 1 – 4
• Probe 1
• No measurement
• CO signal
State
This parameter indicates the current switching state. Changing the parameter in
Parameters: 1039/1049/…/1099
Diagnostic mode allows the output to be switched manually.
Relay module for the output of the digital outputs
Relay module Type 657 R 0857
For electrical connection diagram, see section
10.3.1.
The following optional equipment is included with delivery:
Load-dependent and fuel-specific limit values/limit curves
• PID/O2 controller
• Blow-out device
• Ejector version
41
4 Technical Description
4.12.8 Field bus connection
For the systems
Profibus DP (Siemens) Type 6 63 R 0401LT
NOTE: PROFIBUS parameters in LT 2: P1300 – P1318. See separate publication, “Profibus for LT”.
Profibus module Electrical connection to LAMTEC SYSTEM BUS via terminal bar. See section 10.4.
Modbus Type 6 63 R 0403LT
CANopen Type 6 63 R 0402LT
Ethernet Type 6 63 R 0406LT For details, see separate publication DLT4002. Dimensions: W130mm x H85mm x D115mm The option „Field bus connection“ (Modbus/Profibus) via communication processor
board is included in LT2 ex software version 1V30 (08.10.2003).
4.12.9 Option “heating for wall mounting case”
For low environment temperatures (<0°C) a heating for the wall mounting case is available.
Type 657 R 0367
230V / 120W
Switching point +15°C
NOTE When option “heating for wall mounting case“ the value of the main fuse F1 is
changing from 1A to 1,6A slow-blow.
42
4 Technical Description
4.13 Limit values
Measurement data can be monitored with the aid of the limit values. The LT 2/KS1-DK is equipped as standard with four fixed limit values, which can be freely configured.
Limit values (factory setting)
Limit value 1: > 400ppm exceeds COe limit
Limit value 2: Disabled
Limit value 3: Disabled
Limit value 4: < -5 mV probe voltage below threshold, 3 seconds trigger delay Reset mode “automatic”, (for monitoring the probe; air value)
Monitoring is effected by comparing the reference value with a lower comparative value (Min. comparative value) or with an upper comparative value (Max. comparative value). If the reference value that you wish to monitor is outside the range (window), this indicates that the reference value is lower than the Min. comparative value or higher than the Max. comparative value, and so the limit value output is enabled. Parameters 910 to 914 indicate whether the limit value is enabled. The relay outputs of the LT 2KS1-DK lambda transmitter can be switched with the aid of limit values 1 - 4. The necessary settings are explained in section 4.13.7. “Digital outputs”. Here, we go on to describe the configuration, display and resetting of limit values. If the display is used, these points can be found in the limit value configuration or limit values parameter groups.
Seven parameters are available for each of the four limit values (e.g. for limit value 1):
1. LV 1 affects:
2. Max. comparative value
3. Min. comparative value
4. Max. LV const.
5. Min. LV const.
6. Reset mode
7. Trigger delay
43
4 Technical Description
Limit value 1 (2,3,4) affects (parameters: 930/940/950/960)
This parameter indicates which reference value is to be monitored. The following reference values are available for monitoring:
Off - The limit value is momentarily not in use.
• O
measurement value
2
Configurable measurement values: one of six possible measurement values defined by the user is monitored.
Probe internal resistance Ri probe
• Probe voltage U-O
Max. comparative value (param. 931/941/951/961) / Min. comparative value (param. 932/942/952/962)
Three possible settings are available for the upper and lower comparative value:
Off:
The comparative value is not active.
Constant value:
Calculated analogue
value:
A constant reference value is chosen as the comparative value. A value calculated from the O
reference value. In the LT 2/KS1-DK lambda transmitter, one of 12 different available reference values may be selected. Configuration of the analogue values to be calculated.
2
actual value or an analogue input is employed as the
2
Max. LV constant (param. 933/943/953/963) / Min. LV constant (param. 934/944/954/964)
If a constant value is selected as the reference value, this constant is defined in Max. or Min. LV. Please note that only integer values can be entered here. If the constant reference value is shown in the display with decimal places, the sequence of numbers in the reference value must be entered with the decimal point omitted.
Example 1:
The O follows: Undershoot at 5.5% and exceeded at 15.6 vol.% O
measurement value is to be monitored, the limit value output must be set as
2
2
A constant value is set as default for the Min. or Max. reference value:
- For the Max. LV constant: 156
- For the Min. LV constant: 55
NOTE: If you wish to monitor the measurement value only for instances where it exceeds or
undershoots the limit values, set the switching threshold in such a way that it never responds. Example: You wish to monitor the O
measurement value only to ascertain if it
2
undershoots the minimum limit. Set max. limit value to 30,0% (300).
Example 2:
You wish to monitor the probe voltage U-O display in mV without decimal places. You must enter the limit values as integers in
. The voltage value is shown in the
2
mV. Thus, entering 100 corresponds to 100 mV.
44
4 Technical Description
Reset mode (param. 935/945/955/965)
If the limit value was enabled by the reference value being undershot or exceeded, this parameter describes the mode for resetting the limit value. There are three possible ways of doing this:
Automatic:
Manual:
Acknowledge:
If the monitored reference value changes so that it reaches the GOOD state once more, the limit value output is automatically reset.
The limit value must be reset manually via the display, via one of the digital inputs or via the remote software. In this Reset mode, limit values can only be reset when the monitored reference value has returned to the GOOD state
The limit value output must be reset manually via the display, via one of the digital inputs (Reset LVx) or via the remote software. If the monitored reference value is still outside the Good range, it is only acknowledged at first, and disappears on reaching the Good state.
Each individual limit value can now be deactivated with the "Deact. LVx" function via the digital inputs ( x = { 1, 2, 3, 4 } ).
Trigger delay (param. 936/946/956/966)
This parameter allows you to set a trigger delay in a time range from 0 to 600 seconds. In this case, the limit value output is only enabled if the monitored reference value remains outside the Min. LV or Max. LV range for longer than the pre-defined time interval. Once the reference value has returned within the limits of Min. LV and Max. LV, the time counter is reset. When the value goes beyond the Min. LV or Max. LV value, the trigger delay starts counting again from the time 0.
Deactivation of limit value (param. 967)
All limit values can be deactivated together depending on the operating mode. Possible settings: Limit values are deactivated in the following states
• 0=Never
1=Cold start (default)
• 2=Coldstart+maintenance
• 3=No measurement. Faults and warnings have no influence on the limit values!
45
4 Technical Description
Display and reset of limit values
The current state of the limit values and resetting them takes place using the display in the Limit Values group.
Parameters: 910 ... 914
Parameters: 914 ... 917
Acknowledged:
Enabled:
The parameters Limit Value 1, Limit Value 2, Limit Value 3 and Limit Value 4 indicate the current settings and state of the limit values. 0 = off, 1 = enabled, 2 = acknowledged, 3 = deactivated. The “Deactivated” state is displayed if the LV has not been parameterised or if it has been deactivated via the digital inputs or an operating mode (param.967). “Off” indicates either that the limit value in question is not being used, or the monitored reference value is within the limits of Min. LV and Max. LV. If “enabled” is displayed for a limit value, the monitored reference value is or was outside the limits of Min. LV and Max. LV.
The parameters Reset LV 1, Reset LV 2, Reset LV 3 and Reset LV 4 enable the limit value output to be reset if Manual or Acknowledge has been selected as the Reset mode. To reset a limit value, you must enter “Reset” in the respective parameter. In Manual reset mode, however, a reset is only possible if the monitored reference value is within the limits of Min. LV and Max. LV.
Off:
This indicates either that the limit value in question is not being used, or the monitored reference value is within the limits of Min. LV and Max. LV.
If “acknowledged” is displayed for a limit value, the monitored reference value is outside the Good range and the exceeding of the limit value has already been acknowledged.
If “enabled” is displayed for a limit value, the monitored reference value is outside the limits of Min. LV and Max. LV.
46
4 Technical Description
Display of excess/undershot limit values
The limit values are displayed by means of the softkey designations. When limit value parameter 930/940/950/960 is activated in the “Service” access level, LV1, LV2, LV3 and LV4 appear on the display, depending on which limit value is currently active.
Exceeded or undershot limits are displayed as follows:
• LV 1
means limit value 1 has been exceeded
• LV 2
Retrieval of limit value settings
Press the "diag" (diagnosis) key
Limit value has been selected
• Press ENTER
means limit value 2 has been undershot
Select the required limit value using the cursor keys The selected limit value is indicated by a border
The limit value setting of the selected limit value is shown in the display, see screenshot
1. Limit value 3 has been parameterised to the O
2. Switching points: Limit exceeded 10.0 vol.% O Limit undershot 3.0 vol.% O
3. Current O
measurement value 6.7 vol.% O2
2
measurement value.
2
2 2
4. Possible states:
enabled Limit value has been triggered
off Measurement value is in Good range
acknowledged Exceeded/undershot limit value has already been acknowledged
47
4 Technical Description
4.14 Analogue inputs
Four analogue inputs via plug-in cards on the LT 2/KS1-DK basic electronics.
Freely configurable using the display and operating unit or remote display software,
parameter groups 570 to 609.
• From January 2007 Analogue input card for voltage -200...1000mV for activating the CO/H2 sensor signal Type 6 57 P 0660
Analogue input card for current 0/4...20mA Type 6 63 P 6001
Analogue input card for current 0/4...20 mA with 24 V DC supply for transducer for LT1 / LT 2 Type 6 63 P 6002
Analogue input card for potentiometer 1...5 k Type 6 57 P 6000
Temperature input for PT 100 Alternative measuring range 0...320 °C
0...850 °C Type 6 57 R 0890
48
4 Technical Description
4.15 Device configuration and factory settings
The configuration and factory setting of the device can be seen from the configuration number. This number is located on the inside of the door of the housing, or on the side in the case of the LT 2/KS1-DK for panel installation. The configuration number has 17 characters and is formulated according to the following code:
Configuration numbers for the LT 2/KS1-DK
a: Display and operating unit
b: Pressure sensor
(via analogue input, see d)
c: Analogue outputs
0 Without
1 With
0 Without
1 Absolute pressure
2 Differential pressure
Output 1 2 3 4
0 Not assigned
1 4...20 mA
2 0...20 mA
3 0...10 V
4 4...20 mA floating
5 0...20 mA floating
6 0...10 V floating
7 Æ 0…100% ejector controlling
8 Æ isolated
Only possible with outputs 1 and 2, maximum potential difference ± 20V
49
4 Technical Description
d: Analogue inputs
Input 1 2 3 4
0 Not assigned
1 Potentiometer 1k
2 Current 0/4...20 mA
3 Three-point step (TPS)
4 Pulse input (Namur)
5 Temperature input PT 100 range 0…320°C
6 Temperature input PT 100 range 0…850°C
7 Current 0/4...20 mA with +24 V DC supply
8 Pressure sensor Type (see b)
9 Voltage -200...+1000mV
e: Digital outputs
f: Not assigned
g: Power supply voltage
(factory setting)
h: Special configurations
0 Open collector
2 2 to 7 relays (1 changeover switch)
1 230 V AC
2 115 V AC
----
50
5 Installation
5 Installation
5.1 General Information
Measuring gas temperature
Fuel
Measuring point
Cable cross-sections
Max. 450°C
Suitable:
• Light hydrocarbons such as natural gas, propane, butane
• Light fuel oil
• Fuel oil S, coal
• Other fuels, such as pyrolysis gases, refuse, etc., to only a limited extent, and with a considerably shorter life
Select the measuring point in such a way that representative exhaust gas (completely mixed) is measured.
Exhaust gas temperature at measuring point max. 450°C
Recommended cable cross-sections between probe connection box (PCB) and data interpreting device (LT 2/KS1-DK)
Measuring cell heater (shielded) Terminal 35 / 36
up to max. 20m 1.5 mm
2
up to max. 50m 2.5 mm2
Other connecting cables (shielded) Probe signals Pressure sensors
0.8 mm
2
Multicable 11 x 0.8 (S-Y(ST)Y..LG)
5.2 Installing the electronic evaluation unit of the LT 2/KS1-DK lambda transmitter
Ambient temperature Operation: - 20 °C to + 60 °C Transport and storage - 40 °C to + 85 °C
NOTE: Cold electronics = good electronics! This maxim is crucial when determining the installation location for the LT 2/KS1-DK
lambda transmitter.
51
5 Installation
5.2.1 LT 2/KS1-DK wall-mounted housing
Mount the LT 2/KS1-DK lambda transmitter in a suitable location. For electrical connections and the probe connection, see below.
Ensure a suitable spot for wall mounting. Ensure that the wall has a sufficient load­carrying capacity and that the measuring system is easily accessible.
For electrical connection, see section 10.3.
Without reference air pump With reference air pump
350 350
300
Housing depth: 150mm
Weight: approx.10kg
455
LAMBDA TRANSMITTER LT2
500
Housing depth: 200mm
Weight: approx.13kg
52
5 Installation
5.2.2 LT 2/KS1-DK mounting plate
For installation in the control cabinet (protection class IP00). Ensure sufficient ventilation, provide forced ventilation if necessary. Internal control cabinet temperature max. 60°C. For electrical connections and the probe connection, see below.
For electrical connection, see section 10.3.
131.5
258
16.5 16.5
225
Ø13
12
325
350
Ø13
Weight: approx. 6kg
53
5 Installation
5.2.3 Electrical connection of the LT 2/KS1-DK lambda transmitter
DANGER Before all work on electrical equipment, switch off the power supply voltage to the
equipment and check that it has been isolated. Compliance with the relevant safety provisions is essential.
1
Mains connection
1 - L
2
2 - N 3 -
34
4 - PE
Fitting cable coupler
Cable cross-sections
For electrical connection, see section 10.3.
Recommended cable cross-sections between probe connection box and LT 2/KS1-DK
Probe heater (shielded) Terminal 35 / 36
up to 20m 1.5 mm up to 50m 2.5 mm
2
2
Other connecting cables (shielded) Probe signals Pressure sensors
0.8 mm
2
Multicable 11 x 0.8 (S-Y(ST)Y..LG)
WARNING Take care to ensure that cable routing and screening confirms to regulations. Probe connection: The signal line of the LT 2/KS1-DK, terminals 12, 33 and 34, must not be routed
together with mains cables, particularly cables of frequency converters for speed control. Any connection with the power circuit must be avoided.
Lines may be routed together with pressure sensor cables, however.
DANGER A faulty probe connection may result in the probe being damaged beyond repair.
Before commissioning, check probe connection terminals 12 to 36
12 (-) Probe signal CO/H 33 (-) Probe signal O 34 (+) Probe signal CO/H
2
2
/ O2 (shared inner electrode)
2
35 Probe heater 36 Probe heater
54
5 Installation
5.3 Installing the probe
CAUTION: The first commissioning / first calibration must be carried out in environment
temperatures of -20...+40°C with air (offset calibration). If this should not be ensured in the inserted condition, the first caliration of the probe
must be carried out in developed condition and may be inserted thereafter. A first calibration uring too high flue gas temperatures is leading to storing wrong
datas of the probe, which can be affected the accuracy and the durability of the probe.
Bevor calibration, after setting the internal cell resistance (chapter 6.2), you have to trigger an exchange of the probe via parameter 109. So all stored datas of the probe will be deleted and uring offset calibration be refreshed.
CAUTION: When installing the probe and during subsequent operation, take care to ensure that
the probe does not come into contact with oil, grease or boiler cleaning agents. Contaminated or dirty probes can be recognised by their potential difference across
air gap U-O2 of <–20mV, or >+20mV. Furthermore, the probe must always be kept in operation once installed. This prevents humidity from settling on the measuring cell, which in certain circumstances may lead to measurement errors and the destruction of the probe!
Install and align the probe Counter flange standard DN65 Counter flange in version “blow-out device” DN80
CAUTION! Don’t forget the seal between the counter-flange and the probe flange.
55
5 Installation
Connect the probe electrically (wiring diagram chapter 10.3)
Connect the probe pneumatically (connecting diagram chapter 10.4)
NOTE: In the PCB of the probe there is a shut-off plug valve, Which must be opened uring
calibration with compressed air or test gas. Should be the probe installed in a inaccessibly location, a additional shut-off plug valve can be installed in the near of the LT2.
In such a case, the internal valve can be always opened.
CAUTION! After calibration, the compressed air or test gas must be closed. The reference air must be always connected and be opened.
56
6 Commissioning / Shutdown
6 Commissioning / Shutdown
The commissioning relates to the software version 1V52 in the LT2, recognizeable at the indentification plate of the LT2.
6.1 Switch on measurement
Maintenance switch S1
- Maintenance mode off
- Maintenance mode on
LED 9
LED 10
LED 11
LED 12
LED 3
LED 4
LED 5 Measurement
LED 6 Operation
LED 8
LED 2
LED 7
LED 1 Maintenance
S 1
T 2 2
• Switch on the LT2
• You can switch to maintenance either using the display and operating unit under “diag” or using the maintenance switch S1. Maintenance switch S1 always has priority over the software switch under “diag”.
• “Maintenance” is displayed (LED1 lights up orange)
• The probe heats up (10 min.)
• “COLD START” is displayed (LED 5 “Measurement” off)
• “Operation” is displayed (LED 6 lights up green)
NOTE: During “COLD START”, “MAINTENANCE” or “FAULT”, a default value is displayed:
• (Factory setting) O
0 vol. % (P361)
2
• (Factory setting) COe Æ 0 ppm (P371)
In P362 for O
, P372 for CO, the type of default value can be set:
2
OFF: No default value is output. ON: The default value set in the parameter in front is output. +Maintenance (factory setting): The default value set in the parameter in front is
output during “MAINTENANCE” as well. +Maint.froz.: With this setting, the default value set in the parameter in front is
output during cold start and fault, as before, but in addition the previous measurement value is frozen as long as Maintenance mode is active.
During cold start/fault, the default value has priority over the freezing of the measurement value during maintenance.
During cold start, the cell internal resistance R
of the O2 electrode is displayed
I probe
or output on the display and operating unit or the monitor output. The cold start delay can be interrupted by pressing the “cal” button of the display
and operating unit, then proceeding according to the menu guidance, or by pressing multi-function pushbutton T2 (for more than 3 seconds, or for more than 6 seconds if a warning or fault is present).
57
6 Commissioning / Shutdown
6.1.1 Possible warning / faults
Warning “Internal resistance of probe 1 too high” Fault “Probe broken wire/faulty probe”
Trigger of the Warning: The internal cell resistance has the limit of 200 Ohm exceeded (in mode “MEASURE”)
Trigger of the fault: The internal cell resistance has the limit of 300 Ohm exceeded (in mode “MEASURE”)
Possible causes:
Aborting cold start uring heating up phase
Cable diameter of the probe heating to small
• Probe aged Æ use a replacement probe and exchange it
Fuse F2 defective
6.2 Setting the cell internal resistance R
Note the cell internal resistance R these alternatives:
Display and operating unit
Remote display software
• Monitor output
When heated to operating temperature (approx. 30 minutes after switch-on), the measured internal resistance R ohms). If the measured internal resistance is higher, increase the power of the probe heater by 0.5 watts (parameter 180). If it is lower, reduce the heating power by 0.5 watts. Repeat this process until the internal resistance reaches 18 ohms (+/-5 ohms). Wait approx. 10 minutes before repeating the process, to allow time for the internal resistance to adapt to the new heating power.
The probe voltage U-O2
NOTE: To read off the cell internal resistance R
“meas”.
I probe
and read off the probe voltage U-O2 using
I probe
of the O2 electrode should equal 20 ohms (+/-5
I probe
stabilises to values between -20...+20mV.
and the probe voltage U-O2 press
I probe
LT2 display
P180 is only available in the service level.
If it is not possible to get an internal cell resistance lower then 25 Ohm, check the cabel diameter aof the probe heating (see chapter 5.2.3).
58
6 Commissioning / Shutdown
6.3 Setting the reference air quantity
NOTE: Only compressed air that is free from oil and water may be used as reference air. We
recommend using instrument air, where this is available. If neither compressed air nor instrument air is available, an optional pump unit can be
employed in the external housing Type 657 R 1061. This pump unit cannot be retrofitted in the LT 2 housing
NOTE: The reference air is monitored continuously by a differential pressure sensor, which is
installed in the probe connection box of the KS1-DK. The reference air is monitored with the fault “No reference air”. Initiation time: 1 hour
1.) Calibrate the differential pressure sensor to 0. To do so, close the reference air throttle completely and set parameter 108
in the LT 2/KS1-DK to “initiate”.
2.) Next, open the reference air throttle until a differential pressure of 2 to 3 mbar is reached (see display in the LT2 “P ref.air”).
2.) Check calibration after a few hours of operation, maybe repeat it.
LT2 display
Differential pressure sensor
Absolute pressure sensor
Electr.
connections
Pressure sensors
Electr.
connections
Probe
Air
outlet
Throttle
Test gas
Throttle
Reference
air
Shut-off plug
valve
Test gas
PCB interior view of
KS1-DK probe
Hose connection for reference air (instrument air pre-pressure 1bar)
Hose connection for test gas (instrument air or calibrating gas pre-pressure 1bar)
59
6 Commissioning / Shutdown
6.4 Calibration of the probe KS1-DK via menu function
Note: The pressure increase of the calibration with compressed air or testgas is monitored
by a absolut pressure sensor. Befor starting calibration, the value of the absolute pressure must be adjusted to the actuell environment pressure.
Via a zero point offset in parameter 412 the value of the absolut pressure can be increased or decreased.
CAUTION! Befor first calibration, the probe must be at least 30 minutes operated in „MEASURE“
without a fault, otherwise the new probe datas will not be refreshed. Trigger parameter 109 „exchange probe“. Stored datas of the probe will be deleted.
Several possibilities exist for calibrating both sensors of the probe.
Offset calibration on ambient air Æ chapter 6.5.1 The probe must be located at ambient air
alternativ
Offset calibration with compressed air, open before Æ chapter 6.5.2
- pre pressure compressed air 0,3bar
- Pressure increase “dP” 2…3mbar
Calibration with reference measuring Æ chapter 6.5.3
- Reference measuring device
alternativ
• O2 calibration with test gas, open gas Æ chapter 6.5.4
- Test gas containing O
, pre pressure 0,3bar
2
- Pressure increase “dP” 2…3mbar
CO calibration with test gas, open gas Æ chapter 6.5.5
- Test gas containing CO, pre pressure 0,3bar
- Pressure increase “dP” 2…3mbar
With param. 270, you can define which access level is required in order to initiate calibration. The following settings are possible:
• “Off” (default):
• “Customer”, “Service”
“Maintenance”, “Customer+Maintenance”
• “Service+Maintenance”
60
6 Commissioning / Shutdown
6.4.1 Offset calibration of both sensors on ambient air
The first commissioning / first calibration must be carried out in environment temperatures of -20...+40°C with air (offset calibration).
If this should not be ensured in the inserted condition, the first caliration of the probe must be carried out in developed condition and may be inserted thereafter.
A first calibration uring too high flue gas temperatures is leading to storing wrong datas of the probe, which can be affected the accuracy and the durability of the probe.
Uring offset calibration in ambient air the
• O
sensor will be calibrated to 21%
2
U-COe voltage will be calibrated to “0”
NOTE: Offset calibration on ambient air only works with O2 values > 18%.
Menu function
When you press the [cal] menu key, “Start calibration” appears in the display. After you have activated calibration select:
Offset calibration on ambient air
• Uring calibration LED 5 is flashing slowly
• Length of calibration time max. 5 minutes
Possible warning / faults
Offset voltage outside the limits Probe voltage U-O
< -20mV
2
Trigger of the warning:
- Probe voltage U-O
in ambient air is outside the range of -20…+20mV
2
• Resolution:
- Probe is not in ambient air
- Reverse polarity swap probe connection terminals 33-34
- Change the probe / sensor
61
6 Commissioning / Shutdown
6.4.2 Offset calibration of both sensors with compressed air
Uring offset calibration compressed air air the
value will be calibrated to 21%
• O
2
U-COe voltage will be calibrated to “0”
NOTE: Offset calibration on ambient air only works with O2 values > 18%.
For offset calibration, compressed air with a pre-pressure of 0,3bar must be connected to the “Test gas” hose connection on the PCB.
Menu function
When you press the [cal] menu key, “Start calibration” appears in the display. After you have activated calibration:
• Open the shut-off plug valve in the PCB
• Set the pressure rise “dp” to 2...3mbar via the test gas throttle in the PCB
• Start calibration
• Following successful calibration, close the shut-off plug valve
62
6 Commissioning / Shutdown
Possible warning / faults
Offset voltage outside the limits Probe voltage U-O
< -20mV
2
Trigger of the warning:
- Probe voltage U-O
in ambient air is outside the range of -20…+20mV
2
• Resolution:
- Probe is not in ambient air
- Reverse polarity swap probe connection terminals 33-34
- Change the probe / sensor
D-P offset calibration too low, not enough gas (compressed air)
Trigger of the warning: Rise in pressure in preliminary filter during offset calibration with insufficient compressed air (<0.5mbar).
• Possible causes:
- There is no instrument air (compressed air) at the test gas connection of the probe, or inadequate pre-pressure (0,3bar)
- The shut-off plug valve in the PCB is not open.
- The test gas throttle in the PCB is not open sufficiently.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter cracked or broken (replace)
D-P offset calibration too high, dirty preliminary filter
Trigger of the warning: Rise in pressure in preliminary filter during offset calibration with excessive compressed air.
• Possible causes:
- Instrument air (compressed air) at the probe test gas connection has excessive pre-pressure.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter is dirty (clean it)
63
6 Commissioning / Shutdown
6.4.3 Calibration of the O2 value with reference measurement
Menu function
Alternatively, calibration may also be performed with test gas.
NOTE: During reference measurement, take into consideration whether the measuring
device is measuring wet or dry. In devices with an upstream measuring gas cooler, the measurement is always dry. The same applies to devices that draw out the humidity using a chemical substance. The KS1-D probe measures damp. The difference between wet and dry measurement can be seen in the graph in the appendix.
NOTE: The calibration/check with reference measurement only works with O2 values < 18%.
When you press the [cal] menu key, “Start calibration” appears in the display. After you have activated calibration, select Calibration/check with reference measurement
• When calibration with reference measurement starts, there is a waiting time of 5
seconds before the values are displayed.
• Change the O2-value with the cursor keys
• Press OK
- O2 + O2
Change the values using the Right and Left keys.
CAUTION:
If you are calibrating the measurement value using the display and operating unit cal, you must confirm the new calibration value with “ENTER” or “OK”. Otherwise, the menu ends automatically after 15 seconds, and the new calibration value is rejected.
NOTE: If there is no possibility for a reference measurement or for tes gas, you have to enter
the probe temperature of the test report in parameter 141,to get a correct measurement value.
But this method functions only with a new probe / sensor.
64
6 Commissioning / Shutdown
6.4.4 O2 calibration with test gas
Connect test gas at the hose connector “test gas” of the PCB, with a prepressure of 0,3bar.
Menu function
Example for test gas: 3 Vol.% O
in N2
2
NOTE: The calibration/check with O2- test gas only works with O2 values < 18%.
When you press the [cal] menu key, “Start calibration” appears in the display.
• Open the shut-off plug valve in the PCB
• Set the pressure rise “dp” to 2...3mbar via the test gas throttle in the PCB
• Start calibration
• When calibration starts, there is a waiting time of 5 seconds before the values are
displayed.
• Change the O2-value with the cursor keys
• Press OK
• Following successful calibration, close the shut-off plug valve
- O2 + O2
CAUTION:
If you are calibrating the measurement value using the display and operating unit cal, you must confirm the new calibration value with “ENTER” or “OK”. Otherwise, the menu ends automatically after 15 seconds, and the new calibration value is rejected.
NOTE: If there is no possibility for a reference measurement or for tes gas, you have to enter
the probe temperature of the test report in parameter 141,to get a correct measurement value.
But this method functions only with a new probe / sensor.
65
6 Commissioning / Shutdown
6.4.5 CO calibration with test gas
Connect test gas at the hose connector “test gas” of the PCB, with a prepressure of 0,3bar.
Menu function
Example for test gas: 3 Vol.% O A test gas CO in N
is not suitable for calibration. A test gas must always contents O2
2
, 100ppm CO, 100ppm H2, in N2
2
in the range of %.
NOTE: The calibration/check with CO- test gas only works with CO values > 0ppm.
When you press the [cal] menu key, “Start calibration” appears in the display.
• Open the shut-off plug valve in the PCB
• Set the pressure rise “dp” to 2...3mbar via the test gas throttle in the PCB
• Start calibration
• When calibration starts, there is a waiting time of 5 seconds before the values are
displayed.
• Change the COe-value with the cursor keys
• Press OK
• Following successful calibration, close the shut-off plug valve
- CO + CO
CAUTION:
If you are calibrating the measurement value using the display and operating unit cal, you must confirm the new calibration value with “ENTER” or “OK”. Otherwise, the menu ends automatically after 15 seconds, and the new calibration value is rejected.
NOTE: The KS1-DK combination probe does not measure CO selectively, but measures the
sum total of oxidising exhaust gas constituents (CO/H composition of which remains constant, the CO content in the exhaust gas can be estimated with limited accuracy (+/- 25% of the respective measurement value, not better than +/-20ppm ) on the basis of the oxidising exhaust gas constituents..
6.5 Ending calibration
Leave the menu with EXIT
Switch off MAINTENANCE
). In the case of fuels the
2
66
6 Commissioning / Shutdown
6.6 Test report
A test report is supplied with each probe. It is therefore possible to compare the current measurement values with the values from the test stand.
O2-sensor temperature 953 Kelvin
67
6 Commissioning / Shutdown
6.7 Probe certificate
Every probe comes with a passport, which must be filled out during commissioning. The probe passport must always be enclosed in the case of complaints and repairs.
NOTE: The settlement of problems on the basis of goodwill requires the submission of the
passport.
68
6 Commissioning / Shutdown
6.8 Setting service warnings
Service warnings 1 and 2 draw attention to the need for regular servicing. The plant operator can define service warnings as required, e.g.
• Service warning 1 → Check probe
• Service warning 2 → Remove and clean probe
The appropriate cycle times can be pre-defined in the range of 1 to 65535 hours by means of parameters 1260 and 1261.
The factory setting is with service warnings deactivated.
6.9 Practical information for operation
6.9.1 Measurement with pronounced pressure surges at the measuring point
If the display jumps dramatically, damping can be increased (i.e. by increasing the time constant of measurement value integration) and the display settled using the display and operating unit or the remote display software (optional extra) parameter 360 for O down the rate at which the display reaches a final value.
NOTE: Increased damping also results in the artificial slowing down of the measurement
signal.
display, P370 for COe display - Operation access level. However, this slows
2
6.9.2 Shutdown, switching on and off
In the case of longer shutdowns of approx. three months or more, we recommend switching off the measurement. To prevent damage to the probe, it must be removed. For shorter shutdowns, however, we recommend that you leave the measurement running.
6.10 Taking out of operation
To reliably exclude the possibility of damage to the KS1-DK combination probe, the latter must be removed before taking the measurement out of operation, or immediately after the mains voltage is switched off.
CAUTION: Remove the probe before taking the measurement out of operation.
Danger, hot!
NOTE: Once removed, the KS1-DK combination probe can be stored for an unlimited
duration. The zirconium dioxide measuring element only becomes worn during operation (measuring cell at operating temperature). This is also the case if the probe has already been in operation.
69
7 Service and Maintenance
7 Service and Maintenance
If the boiler is to be wet-cleaned, please note the following: Only carry out wet cleaning after the probe has been removed. If wet cleaning is
performed with the probe installed, it will be damaged. Trouble-free operation is then no longer possible.
NOTE: The probe must always be removed before wet cleaning. Wet
cleaning with the probe installed causes damage to the probe.
7.1 Checking/calibrating the KS1-DK combination probe
Checking/calibration (when installed in an appropriate location) should be carried out at normal operating temperature and under operating conditions.
Recommended intervals (cycles):
6 hours after commissioning
3 to 6 months for natural gas combustion
See section 6 “Commissioning the measurement”
CAUTION: Don’t forget! After replacing the probe, perform a new offset calibration in air and a new test gas
calibration.
Limit value 4 is factory-set in such a way that an automatic check of the probe is possible when the system is stationary and during pre-ventilation.
Limit value 4 -5 mV U-O2 undershoot, automatic reset trigger delay 3 seconds ­20mV undershoot is monitored by fault 1
Fault 1 must never be triggered when the probe is inactive. If fault 1 " Probe voltage <
-20mV " is triggered, it must be reset manually.
NOTE: After a power failure (and thus the failure of the probe heater), the probe voltage U-
O2 may briefly drop below the value -20 mV while the probe is heating up again.
We recommend that you retain the factory setting of limit value 4 for safety reasons.
70
7 Service and Maintenance
7.2 Checking the LT 2/KS1-DK
7.2.1 Checking the measurement input of the LT2/KS1-D
Connect a digital voltmeter to terminals 33 (-) and 34 (+) parallel to the probe. Compare the measured O
Range: -20 mV … +300 mV. If the deviation is less than 1 mV, the LT2/KS1-D is in good working order. If the deviation is greater than 1 mV, repeat the measurement with another digital voltmeter.
Connect a digital voltmeter to terminals 12 (-) and 34 (+) parallel to the probe. Compare the measured CO/H2 voltage with the displayed CO/H2 voltage ( U-CO/H2).
Range: -50 mV … +950 mV. If the deviation is less than 10 mV, the LT2/KS1-D and the buffer amplifier are in good working order. If the deviation is greater than 10 mV, repeat the measurement with another digital voltmeter.
CAUTION:
Check the measurement accuracy of the connected digital voltmeter.
voltage with the displayed probe voltage (U-O2).
2
If there is still a deviation check the buffer amplifier or replace the device. Measuring range of buffer amplifier: Input -50...+950mV, output 0...20mA
From January 2007, the buffer amplifier is no longer installed and is replaced by a special input card. Measuring range -200...+1000mV.
7.2.2 Checking the probe: internal resistance measurement Ri probe
Only possible with probe simulator LS 2 Order No. 655 R 1030. Connect the probe simulator to terminals 33 (-) and 34 (+).
With the R
probe potentiometer, set an internal resistance of < 200 Ω.
I
Check using the voltmeter as follows: Measure the alternating voltage between terminals 33 (-) and 34 (+). The display in mV roughly corresponds to half the probe internal resistance. If R
- >200 , a warning “LS 2 internal resistance too high” is displayed after 10
I
seconds, if R
> 300 , a fault
I
”Probe broken wire/faulty probe” appears Example: 75 mV = 150
NOTE: Probe internal resistance monitoring is deactivated during “cold start”.
71
7 Service and Maintenance
7.3 Maintenance
Due to the extensive self-diagnosis, the LT2/KS1-DK measurement system is largely maintenance-free. Maintenance is restricted to calibration and, when necessary, cleaning the preliminary filter from dust and other deposits, and the replacement of the ZrO
measuring element at the given intervals.
2
7.3.1 Checking the measurement
Check the measurement monthly, quarterly or six-monthly, depending on the application, see section 7.1
7.3.2 Wearing parts
KS1-DK combination probe Average service life 3-5 years (depending on the fuel).
72
7 Service and Maintenance
7.3.3 Cleaning the sintered metal preliminary filter
Cleaning the filter is only necessary if permeability is impaired. In this case, one of the two following error messages is displayed: “Delta-P offset calibration too high, dirty filter” “Delta-P offset calibration insufficient, not enough gas” This fault is also noticeable in the sluggish response of the probe to changes in
measurement values during offset calibration, and in a sharper rise in pressure (absolute pressure) during calibration.
To clean the filter, you will need the CO/H
measuring cell repair kit
2
Type 656 R 2060...2062. To replace the CO/H
measuring cell, dismantle the probe as follows:
2
Detach the baffle plate
To do so, slacken the two Allen screws
Carefully pull the baffle plate to the front and off, as the preliminary filter is inserted in the plate. If you cannot loosen the two Allen screws, cut off the heads and knock the pins out. The repair kit contains new screws and anti-seize paste. Clean the sintered metal preliminary filter: Brush and blow out. On installation, ensure that the baffle plate is oriented so that it is against the flow of exhaust gas.
7.3.4 Replacing the CO/H
measuring cell
2
To do this, you will need the CO/H2 measuring cell repair kit Type 656 R 2060…2062
Disconnect the gas lines and electric cables of the KS1-DK combination
probe and remove it
Replace the CO/H
measuring cell. To do so, detach the probe as follows
2
1. Disconnect the probe (terminals 12/33/34/35/36)
2. Remove the baffle plate (section 7.3.3)
3. Remove the probe head by slackening all six Allen screws
If you cannot loosen the Allen screws, cut off the heads and knock the pins out. The repair kit contains new screws and anti-seize paste.
4. Pull the probe head and probe to the front and out
5. Unscrew the probe from the probe head
6. Remove the metal O-ring and discard it, the repair kit contains new metal O­rings.
7. Install in reverse order
Don’t forget anti-seize paste! Ensure that the baffle plate is against the flow!
73
7 Service and Maintenance
31
5 6
4
element pieces description item-no. material
6 1 metal O-ring 650 P 2057 Inconell 600 5 1 metal O-ring 650 P 2058 Inconell 600 4 1 CO/H2 sensor incl. adapter 656 P 2030 ZrO2-ceramic 3 1 filter 650 P 2055 SIKA H 20 2 6 hex-nut 650 P 2066
1.4571
1 6 hexagon socket head screw 650 P 2065 1.4571
3.) Reinstall the KS1-DK combination probe and connect up the gas lines and electric cables. Don’t forget the seal
4.) Commission the measurement as described in section 6.
measuring cell repair kit 500 mm 656 R 2060
CO/H
2
1000 mm 656 R 2061 1500 mm 656 R 2062
74
8 Fault Analysis/Trouble-shooting
8 Fault Analysis/Trouble-shooting
Messages in plain text:
Via display and operating unit, under “diag”
Via remote display software (optional extra)
Indication via LED line, LEDs 7 to 12, on the processor board in the LT 2/KS1-DK
8.1 Fault indicator via LED line in the LT 2/KS1-DK
Indication via LED line, LEDs 7 to 12, LED 12 flashes (faults flash)
LED
12 11 10 9 8 7 Faults
No fault active Probe voltage U-O2 < -20mV Faulty probe heater Probe broken wire/faulty probe No probe dynamics Fault in analogue outputs
– Only relevant when used with integrated O2 control
(1)
8.1.1 Probe voltage U-O
2
8.1.2 Faulty probe heater
< -20mV
Probe + / - reversed polarity swap probe connection terminals 33-34
• Probe contaminated replace
NOTE: Probe voltage U-O
in air -20 to +20 mV
2
Check fuse F 5 (see section 10.6)
Inspect the probe heater. If the heater is intact, measure between the two pins of the probe heater connector (recognisable by the two white wires), approx. 2 ohms cold, approx. 10 ohms at operating temperature. If this is not the case (infinite resistance) Æ faulty heater - replace probe.
If the measurement is successful, check the power supply voltage (with an effective measuring device or oscilloscope). The probe heater should be supplied with approx. 13 V DC with cyclical polarity reversal.
Electromagnetic disturbance through wrong cable routing. Maybe parallel to frequency converter, actuators, gates.
NOTE: The probe heater receives power in the form of a direct voltage of approx. 13V, with
cyclical polarity reversal. Measurement with a multimeter is therefore problematic.
If the above voltage is not received, check the wiring terminal connections and tighten if necessary.
NOTE: The current heater data can be read out via the operating data parameters 41/42/43.
75
8 Fault Analysis/Trouble-shooting
8.1.3 Probe broken wire/faulty probe
This message appears if the AC internal resistance (RI) of the ZrO2 measuring cell exceeds the permitted limit value of 300 in measurement mode. The warning “Internal resistance too high” generally appears before or after the above message.
• Possible causes:
The probe (measurement signal terminals 33 – 34) has been disconnected
• Loose contact → check terminal connections, tighten if necessary
Check the wiring, if it is OK replace the probe
8.1.4 No probe dynamics
No probe dynamics were registered. Check the probe
NOTE: The test is disabled on delivery.
Activate it via parameter groups 1330 to 1334. A check takes place to determine whether the measurement value changes by more than the parameterised threshold value within a time that is to be defined.
8.1.5 Fault in analogue outputs
8.1.6 Incorrect O
value
2
Check the parameter assignments of the analogue outputs (P530...P569).
Check the computer electronics of the analogue outputs and replace if necessary. It is possible that an analogue output that is not installed has been activated (check installed outputs)
See sections 4.7 and 10.7
Influence exerted upon the ribbon cable of the display due to electromagnetic interference (order a ferrite core)
If a control measurement produces a different O2 value from the one displayed
Have you taken the wet/dry measurement factor into consideration? See graph in section 10.14. of the appendix
Check/calibrate the O
Replace the CO/H
measuring probe, see 7.1
2
measuring cell, see section 7.3.4
2
Commission the new probe as described in 6
Measurement value too high? Infiltrated air - check tightness of seal and hose connections.
NOTE: During counter-measurement, take note of whether the measuring device is
measuring wet or dry. In devices with an upstream measuring gas cooler, the measurement is always dry. The same applies to devices that draw out the humidity using a chemical substance. The combination probe measures damp. The difference between wet and dry measurement can be seen in the graph in the appendix (section 10.14).
76
8 Fault Analysis/Trouble-shooting
8.1.7 No reference air (can be output as a warning via P395, initiation time 1 hour)
This fault also appears if the reference air is monitored by a flow meter with limit transducer (e.g. with the efficiency calculation optional extra 657R0895K, see section
4.12.2) The reference air does not reach the quantity required for flowing around the
reference electrode. This can result in the falsification of the measurement value.
Possible causes:
There is no instrument air (compressed air, reference air pump) at the reference air connection of the probe.
The reference air throttle is not open sufficiently.
The signal from the differential pressure sensor has drifted.
Measures:
Check electrical and pneumatic connections
Reset the reference air quantity, see 6.1.2
Faulty differential pressure sensor? replace
Faulty pressure input card replace
77
8 Fault Analysis/Trouble-shooting
8.2 Warning indicator via LED line in the LT 2/KS1-DK
As a rule, warnings do not have any influence on measurement function. Indication via LED line, LEDs 7 to 12, LED 12 lights up
12 11 10 9 8 7 Warnings
LED
No warning active Internal resistance too high Offset outside limits No reference air
D-P offset calibration too low, not enough gas
D-P offset calibration too high, dirty filter
D-P test gas calibration too low, not enough gas
D-P test gas calibration too high, dirty filter
Insufficient quantity of calibrating gas Probe absolute pressure too high/too low Probe temperature too high/too low Faulty probe temperature sensor Invalid test gas calibration Implausible test gas calibration, repeat Analogue input 1: Input value too high/too low Analogue input 2: Input value too high/too low Analogue input 3: Input value too high/too low Analogue input 4: Input value too high/too low Analogue outputs configuration error Service warning 1 Service warning 2 No probe dynamics Dynamics test initiated
(1)
(2)
(2)
(2)
(2)
(1)
– Only relevant when used with integrated O2 control
)
(1
– Not relevant to the version described here
(2)
8.2.1 Internal resistance of probe 1 too high
This message appears if the AC internal resistance (RI) of the ZrO2 measuring cell exceeds the permitted limit value of 200 in measurement mode.
Possible causes: Probe has aged (worn) purchase replacement probe and replace old probe Measurement can only continue to operate with reservations. Check measurement
accuracy, see section 7.
- Check F2 fuses, see section 10.6 of appendix
- Fault in power pack electronics replace
Checking the LT 2K electronics: Measure the alternating voltage over terminals 33-34 of the LT 2 using a multimeter.
The display in mV roughly corresponds to the display of half the AC internal resistance
78
8 Fault Analysis/Trouble-shooting
8.2.2 Offset voltage outside the limits
An impermissible voltage U-O2 was discovered during offset calibration. Check whether the O
- Sufficient flow of compressed air/instrument air
- Cracked filter insert?
8.2.3 No reference air (can be output as a fault via P395, initiation time 1 hour)
This warning also appears if the reference air is monitored by a flow meter with limit transducer (e.g. with the efficiency calculation optional extra 657R0895K, see section
4.12.2)
The reference air does not reach the quantity required for flowing around the reference electrode. This can result in the falsification of the measurement value.
Possible causes:
- There is no instrument air (compressed air, reference air pump) at the
- The reference air throttle is not open sufficiently.
- The signal from the differential pressure sensor has drifted.
Measures:
- Check electrical and pneumatic connections
- Reset the reference air quantity, see 10.4
- Faulty differential pressure sensor? replace
- Faulty pressure input card replace
measuring cell has been supplied with air.
2
Pressure rise greater than 1...2 mbar; see 6.1.2
If OK, check the probe voltage U-O
in air.
2
Permitted voltage range -20…+20mV. Reversed polarity of probe terminals 33/34
reference air connection of the probe.
8.2.4 D-P offset calibration too low, not enough gas (compressed air)
Rise in pressure in preliminary filter during offset calibration with insufficient compressed air (<0.5mbar).
Possible causes:
- There is no instrument air (compressed air) at the test gas connection of the
probe, or inadequate pre-pressure (0,3bar)
- The shut-off plug valve in the PCB is not open.
- The test gas throttle in the PCB is not open sufficiently.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter cracked or broken (replace)
8.2.5 D-P offset calibration too high, dirty preliminary filter
Rise in pressure in preliminary filter during offset calibration with excessive compressed air.
Possible causes:
- Instrument air (compressed air) at the probe test gas connection has
excessive pre-pressure.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter is dirty (clean it)
79
8 Fault Analysis/Trouble-shooting
8.2.6 D-P test gas calibration too low, not enough gas
Inadequate rise in pressure in preliminary filter during test calibration (<0.5mbar). Possible causes:
- There is no test gas at the test gas connection of the probe, or inadequate
pre-pressure (0.3bar)
- The shut-off plug valve in the PCB is not open.
- The test gas throttle in the PCB is not open sufficiently.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter cracked or broken (replace)
8.2.7 D-P test gas calibration too high, dirty filter
Excessive rise in pressure in preliminary filter during test gas calibration. Possible causes:
- Test gas at the probe test gas connection has excessive pre-pressure.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter is dirty (clean)
8.2.8 Insufficient quantity of calibrating gas
An insufficient rise in pressure is discovered during manual offset or test gas calibration of the KS1-DK.
Possible causes:
- There is no test gas or compressed air at the test gas connection of the probe,
or inadequate pre-pressure (0,3bar)
- The shut-off plug valve in the PCB is not open.
- The test gas throttle in the PCB is not open sufficiently.
- The signal from the differential pressure sensor has drifted (recalibrate to “0”).
- Probe preliminary filter cracked or broken (replace)
8.2.9 Implausible test gas calibration, please repeat
This message occurs when the probe temperature calculated from the probe voltage and the concentration of gas lies outside the range of 800° - 1200° Kelvin.
Possible causes:
- The O
concentration entered under parameter 301 does not correspond to
2
that of the connected calibrating gas
- Ageing/contaminated sensor? replace.
- Infiltrated air - check tightness of seals and hose connections.
8.2.10 Analogue input 1/2/3/4 input value too high/too low
The input value at the analogue input in question is outside the permitted range. Range limits: parameters 574/584/594/604 (min. value) and 578/585/595/605 (max. value). The current input value can be read out via parameters 570/580/590/600.
Measures:
- Check wiring reversed polarity?
- Check source (connected device)
- Faulty input card? replace
80
8 Fault Analysis/Trouble-shooting
8.2.11 Analogue outputs configuration error
Analogue outputs are parameterised that cannot physically be found. Check parameters 539, 549, 559, 569 and 530, 540, 550,560 and compare with the inserted cards. If necessary, replace analogue output cards and/or the processor board.
8.2.12 Service warning 1 / service warning 2
The service warning draws attention to the need for regular servicing. The user can define service warnings as required, e.g.
Service warning 1 check probe Service warning 2 replace probe The appropriate cycle times can be configured as desired by means of parameters
1260 and 1261.
81
8 Fault Analysis/Trouble-shooting
8.3 Resetting faults/warnings
Menu-guided via “diag” in the display and operating unit (optional extra)
Menu-guided via “Status” using remote display software The [diag] key switches the screen to the display of warnings and faults. You can
select individual warnings, faults or limit values using the cursor keys (up, down). The selected warning or fault, which is displayed inverted, can now be acknowledged
or reset with ENTER.
Via digital inputs - input 1
By pressing the multi-function pushbutton T2 (for more than 3 seconds for each fault)
If several faults are present at the same time, you must press the multi-function pushbutton T2 several times.
NOTE: Not all warnings and faults can be reset by acknowledging them - the cause of the
warning or fault may have to be corrected first.
82
9 Spare Parts
9 Spare Parts
Below is a list of the relevant spare parts. We recommend that you stock up on wearing parts. The stocking of spare parts with footnote The stocking of spare parts with footnote
system is equipped with the optional extra in question.
9.1 Wearing parts
1 CO/H
Length 500 mm Type 6 56 R 2060
1 CO/H
Length 1000 mm Type 6 56 R 2061
1 CO/H
Length 1500 mm Type 6 56 R 2062
1
Sintered metal filter repair kit Type 6 50 R 2065
measuring cell repair kit
2
measuring cell repair kit
2
measuring cell repair kit
2
(1)
is a matter for your own judgement.
(2)
only makes sense if the measurement
1 Assembly paste (anti-seize paste) 5-pack Type 6 50 R 1090
1
1
1
1
1
Flange gasket DN65 3mm Klinger Sil C-4400 Type 6 57 P 4209
Assorted small accessories box KS1-DK Type 650 R 2070
Shut-off valve, Type 6 57 P 0556
Absolute pressure sensor on board Type 650 R 2066
Differential pressure sensor on board Type 650 R 2067
83
9 Spare Parts
9.2 Spare parts
Probe KS1-DK
(1)
1 Replacement probe complete, average service life approx. 2...5 years
(depending on fuel) for measuring gas temperatures up to 450°C Length 500 mm Type 6 56 R 2030
(1)
1 Replacement probe complete, average service life approx. 2...5 years
(depending on fuel) for measuring gas temperatures up to 450°C Length 1000 mm Type 6 56 R 2031
(1)
1 Replacement probe complete, average service life approx. 2...5 years
(depending on fuel) for measuring gas temperatures up to 450°C Length 1500 mm Type 6 56 R 2032
(1)
1 Test gas throttle Type 6 57 P 0525
(1)
1 Reference air throttle Type 6 57 P 0436
(1)
1 PUN hose 6x1 black Type 6 57 P 0547
84
9 Spare Parts
LT2
(1)
1 Mainboard LT2
Type 6 57 R 1882
(1)
1 Processor board LT2 LT2
Type 6 57 R 1874
(1)
1 isplay and operating unit LT2
Type 6 57 R 0833
(1)
1 power pack (transformer) LT2
Type 6 57 P 0342
(1)
1 Spare fuse box LT 2
Type 65 7 R 1310
(1)
1 Analogue input card -200...+1000mV (from January 2007)
Type 6 57 P 0660
(1)
1 Analogue output card 0/4...20 mA; 0...10 V (1 channel) LT2
Type 6 57 R 0050
(1) 1
Pressure sensor input card LT2 Type6 57 R 0650
(2) 1
Analogue input card 0/4...20 mA LT2 Type 6 63 P 6001
(2) 1
Analogue output card 0/4...20 mA; 0...10 V floating, LT2 Max. potential difference ± 20 V Type 6 57 R 0051
(2) 1
Analogue input card LT1/LT 2 potentiometer 1...5 k LT2 Type 6 57 P 6000
(2) 1
Analogue input card 0/4...20 mA Type 6 63 P 6001
(2) 1
Analogue input card 0/2...10 V LT2 Type 6 57 P 6005
(2) 1
Temperature input for PT 100 LT2 Type 6 57 R 0890
(2) 1
Relay card 660R0017 for digital outputs, 6 relays each with 1 changeover switch LT2
Type 6 60 R 0857
(2) 1
Pump for reference air Type 6 57 R 1062
85
10 Appendix
10 Appendix
10.1 Technical data of the LT 2/KS1-DK lambda transmitter
Version:
Housing:
Protection class to DIN 40050
Dimensions (HxWxD) mm
Colour Weight
plus display and operating unit
Ambient temperature: Operation Transport and storage
Power supply voltage:
Power consumption:
Display:
Resolution:
Measurement accuracy: (with KS1-DK combination probe)
Setting time (60 % time):
Time until ready for operation with KS1-DK (cold start)
Wall-mounted housing Type 657 R 1028
Wall-mounted housing with reference air
Mounting pate
Type 657 R 1032 pump Type 657 R 1060
Sheet steel, powder-coated surface-mounted housing
Electrogalvanized sheet steel
Electrogalvanized sheet
steel
IP 65 IP 65
400 x 300 x 150 500 x 300 x 200
IP 00
350 x 258 x 131.5
Grey RAL 7032 ----- ----­approx. 10 kg
approx. 0.5 kg
approx. 13 kg
approx. 0.5 kg
approx. 6 kg
approx. 0.5 kg
-20 °C ... + 60 °C
-40 °C ... + 85 °C 230 V AC and 115 V AC
+ 10 % / -15 %, 48 Hz...62 Hz
To be used only in grounded power line networks !
Typically 50 VA, briefly 150 VA (probe heating-up phase)
Graphic LCD 100 x 80 mm (W x H)
O2: 0.1 vol. % O 1 vol. % O
in the range 0...18 vol. % O2
2
in the range 18...30 vol. % O2
2
CO: 1ppm in CO range
O2: ± 10 % of measurement value No better than ± 0.3 vol. % O
2
CO: ± 25 % of measurement value No better than +/- 10 ppm in exhaust gases from natural gas combustion following previous calibration under operating conditions with a CO reference measurement in the measuring range 0...100 ppm :. 10 ppm
O2: T 60 < 10 s COe: T 60 < 2 s
Approx. 10 minutes after “POWER ON”
86
10 Appendix
Analogue outputs:
Monitor output Accuracy 2 % of measurement value, no better than 0.2 vol. % O Resolution 10 mV Factory settings Can be switched to probe voltage U-O2
1...4 current / voltage
outputs 2 standard, 3...4 optional
Accuracy: Measuring ranges and physical size can be configured
Resolution: 0.1 vol. % O2 Factory setting: Output 1 0...10 vol. % O
Analogue input: 2
• Analogue input card voltage -200…+1000mV
Control elements:
• Multi-function pushbutton, maintenance switch and 2 LED lines each
Interface:
0...2.55 V DC, burden > 10 kΩ, ≤ 100nF
2
0...2.55 V DC 0...25.5 vol. % O
0...2.55 V DC 0...255mV U-O2 using DIP-switches
2
Direct current 0 / 4...20 mA (default) Burden 0...600
Direct voltage 0...10 V Burden 10 k
Not floating (optional electrical isolation)
0.5 % output value, no better than 0.01mA
Æ 4...20 mA,
2
Output 2 0…1000ppm Æ 4…20mA
Optional Via plug-in cards on the LT 2/KS1-DK power pack electronics
6 57 P 0660
• Analogue input card potentiometer 1...5 k
6 57 P 6000
• Analogue input card current 0 / 4...20 mA 6 63 P 6001
• Analogue input card 0 / 4...20 mA with 24 V DC supply for transducer 6 57 P 6002
• Temperature input for PT 100 sensor 6 57 R 0890 Temperature range 0...320°C / 0...850°C Resolution 1°C
Wall-mounted housing/mounting plate
with 6 LEDs
• Display and operating unit with graphic LCD
• Remote display software (optional extra)
• LAMTEC SYSTEM BUS
• RS 232 only in conjunction with interface module 6 63 P 0500
87
10 Appendix
Digital outputs:
Digital inputs:
Calculation options:
Field bus connection:
Conformity with the following European Directives:
1 as standard Relay output (collective fault indicator )
0...230 V AC, 4A / 0... 42 V DC, 3A
Optional extra: Relay module with 6 relays (1 changeover switch) Switching capacity
0...230 V AC, 4A / 0... 48 V DC, 3A 657 R 0857
Configurable as desired for process status, status and limit value signals
8 inputs – configurable as desired Factory settings: 24 V DC based on device potential Can be switched over for external voltage sources (floating) via jumper
• Calculation of efficiency of combustion Range 0...100%, resolution 0.1%
• Calculation of concentration of CO2 Range 0...20%, resolution 0.1 %
• PID controller
• Customised measurement values Fuel quantity, steam pressure, etc.
Optional for the systems:
• Profibus DP (Siemens)
• Modbus
• CANopen – on request
• Ethernet – on request
89 / 336 / EEC Electromagnetic Compatibility 73 / 23 / EEC Low Voltage Directive
88
10 Appendix
10.2 Technical data of the KS1-DK combination probe
Measuring range:
Measurement accuracy:
Probe output voltage:
Error-influencing factors:
Cross-sensitivity:
Probe internal resistance of ZrO
2
measuring cell in air and 22W heating power:
Permitted fuels:
Permitted continuous exhaust gas temperature:
Life:
Heating power:
Heating current:
Insulation resistance between heater and probe connection:
Mounting position:
Protection class:
Counter flange:
: 0...18 vol. % O2
O
2
with limitation 0...21 vol. % O
2
COe: 0...1000ppm COe
O2: ± 10 % of measurement value No better than ± 0.3 vol. % O
2
CO: ± 25 % of measurement value No better than +/- 10 ppm in exhaust gases from natural gas combustion following previous calibration under operating conditions with a CO reference measurement in the measuring range 0...100 ppm :. 10 ppm
electrode: -100mV...+1000mV
O
2
Resolution: 0.1mV CO/H
electrode: -50...+950mV
2
Resolution: 1mV
Temperature Other unburned hydrocarbons
To SO
, NH3, NO, propane, aromatic hydrocarbons
2
15...25 ohms
Residue-free, gaseous hydrocarbons Light fuel oil Coal Wood
< 450 °C
3 years with natural gas
20...25 watts, depending on the version and the measuring gas temperature
Approx. 1.3 A
> 30 M
Horizontal to vertical
IP42
In version standard Æ DN65 In version blow.out device Æ DN85
89
10 Appendix
10.3 Electrical connection
K
K
-D
-D
/KS1
Lambda-Transmitter LT 2
Lambda-Transmitter LT 2/K
Analoge outputs 0/4…20 mA 0/2…10 V (Option)
* on
processor board
S1
*
Module 4
*
Module 3
*
Module 2
*
Module 1
(+)
(-)
(+)
(-)
(+)
(-)
(+)
(-)
49 48
47 46
45 44
43 42
Output 4 not connected
Output 3 not connected
Output 2 0...1000ppm COe = 4...20mA
Output 1 0...10% O2 = 4...20mA
Analoge Inputs
Probe­connection KS1-DK
Module 1
657P0660
Module 2
not occupied
Module 3
657P0650 difference pressure
Module 4
657P0650 absolut pressure
CO/H2 sensor signal -
O2 sensor signal -
CO/H2/O2 sensor signal +
Sensor heater
sensor heater
Signal input CO/H2-signal
+
internal used
-
18 17 16 15
22 21 20 19
26 25 24 23
Probe Connection Box KS1-DK
22 21 20 19
26 25 24 23
diameters
12
33
34
35
36
CO/H2 sensor signal -
12
33
O2 sensor signal -
CO/H2/O2
34
sensor signal +
sensor heater
35
sensor heater
36
sensor signals, \ pressure sensors
up to 50 m = 0,8 mm multi cable J-Y(ST)Y-G
diameters sensor heater
up to 20 m = 1,5 mm up to 50 m = 2,5 mm
2
2
2
Relay outpt 1
0- 42V DC 3A 0-230V AC 2A
F1 T1A T2A
/ 250 V [230 V] / 250 V [115 V]
3 2 1
PE
N
L
For example, combined fault indication (configurable as required) Manufacturer's setting: fault current principle
=
Earth
= Neutral conductor
= Phase 230 / 115 V, 48...62 Hz
Line power consumption typically 50 VA Short-term (probe heating phase) ca. 150 VA
To be used only in grounded power line networks !
90
10 Appendix
Lambda-Transmitter LT 2/K
Lambda-Transmitter LT 2/K
S1
S1
-D
-D
K
K
LAMTEC SYSTEM BUS (floating)
Digital inputs 24 V, ca. 6 mA Bridge BR 106, BR 107 on power electronics
1-2 referenced to (bottom) - instrument potential 2-3 floating potential for (top) - external voltage source
+24 V
Monitor output 0…2,5 V DC
switch over to O , U (only 0 mV)
2S
>
(+)
(-)
75 74 73 72 71
Fuel 4
69
Fuel 3
68
Fuel 2 (Gas)
67
Maintenance ON/OFF
66
Reference air
65
Calibration
64
Reset limits
63
Reset faults/warnings
62 61
60
32 31
CAN Low CAN High not con.
LAMTEC SYSTEM BUS (CAN-BUS)
not con. CAN-GND
Input 8 Input 7
Input 6 Input 5
Input 4 Input 3 Input 2
Input 1 GND
24 V DC
For example, for connection of a multimeter for service purposes Ri > 10 k
Socket for interface module, 25 pins
Interface module
RS 232
Only in conjunction with remote display software
- 6 57 R 1101
RS 422 - 6 63 P 0500
91
10 Appendix
10.3.1 Relay module for digital outputs (optional extra)
Lambda Transmitter LT 2/KS 1DK
Relay Module 660 R 0857
Terminal strip x2
15 13 14
12 10 11
18 16 17
9 7 8
6 4 5
3 1 2
Relay­outputs
2-7
Max. 230 VAC/4A 48VDC/3A
d
6
d
5
d
4
d
3
d
2
d
1
10.3.2 Analogue input 2 terminals 15...18 - connection variations
Output 7
Output 6
Output 5
Output 4
Output 3
Output 2
92
10 Appendix
10.4 Pneumatic connection
Probe Connection Box
after releasing an automatic offset calibration or a calibration with Testgas, set the increase of the difference pressure (dp) with the throttle to 2...4 mbar.
Throttle for
Testgas
to the
probe
Set difference pressure to
2...4 mbar
Throttle for
Shut off plug
valve Testgas
Reference air
Hose connector
Reference air
(Pressure air
pre pressure 0,3bar)
Air outlet
Hose connectors
4/6mm
Hose connector
Testgas
(Pressure air or
Testgas
pre pressure 0,3bar)
Differential pressure sensor
Absolute pressure
Throttle
Test gas
Shut-off plug
valve
Test gas
Throttle
Electr. connections
Pressure sensors
Electr.
connections
Probe
Reference air
Air
outlet
Hose connection for reference air (instrument air pre-pressure 0,3bar) Hose connection for test gas (instrument air or calibrating gas pre-pressure 0,3bar)
93
10 Appendix
NOTE: In the PCB of the probe there is a shut-off plug valve, Which must be opened uring
calibration with compressed air or test gas. Should be the probe installed in a inaccessibly location, a additional shut-off plug valve can be installed in the near of the LT2.
In such a case, the internal valve can be always opened.
CAUTION! After calibration, the compressed air or test gas must be closed. The reference air must be always connected and be opened.
10.5 Electrical connection to field bus module
LT2/KS 1DK
PE-bar
Term.75 CAN-L
Term.74 CAN-H
Term.60 +24V
Term.61 0V
shield
LAMTEC SYSTEM BUS
4
2 3
shield
termination resistor for LSB enable
Term.71 CAN-GND
1056789
shield
ENTER
with termination
resistor for LSB
PB X1
Profibus DP
PB X2
Profibus DP
X2
PROFIBUS
without function
X3
94
10 Appendix
10.6 Fuses
Fuses: F1 1A slow-blow for 230 V,
Designation Value Function
Primary fuse
2A slow-blow for 115 V 1,6A slow-blow for 230V
when option “heating for wall mounting case”
F2 0.4A slow-blow Probe measurement electronics
F3 1A slow-blow 12 V for display background illumination
F4 1.25A slow-blow
± 5 V supply for processor board
F5 4A slow-blow Probe heater and 24 V supply
F6 0.315A slow-blow LAMTEC SYSTEM BUS
95
10 Appendix
10.7 Jumpers
LAMTEC SYSTEM BUS BR101 on mainboard: Selection of LSB termination resistor :
1-2 disable 2-3 enable
BR12 and BR13 on processor board: to position “C”
Digital inputs: BR106, 107: Setting 1-2: Digital inputs based on device
potential. Setting 2-3: Digital inputs electrically isolated.
96
10 Appendix
10.8 Dimension drawing of KS1-DK combination probe
element pieces description item number material
a 1 Probe head 650 P 2055 1.4571
b 1 Reception tube with housing 650 P 2050...2052 1.4571
c 1 Probe connection box (PCB) 656 P 2034…2054 Die-cast AL
d 1 KS 1D probe 656 P 2030…2032
e 1 Filter insert 650 R 2055 Hastelloy X
f 1 Baffle plate
97
10 Appendix
10.9 Dimension drawing of LT 2/KS1-DK in wall-mounted housing
55
45
Type 657 R 1028 without pump for reference air
35
22.5
35.5
300
175
LAMBDA TRANSMITTER
LT2
Type 657 R 1060 with integ. pump for reference air
6
30
85115
55
45
35
150
400
300
175
LAMBDA TRANSM ITTER
LT2
22.5
35.5
30
6
180115
200
500
98
Loading...