Lamtec FMS, FMS 4, FMS 5, VMS Series, VMS 4 Series Manual

...
Commissioning FMS Firing Management System
TÜV type-approval
0085 AS 0254
DIN DVGW Test mark NG-2510 AS 0324
Sensors and Systems for Combustion Engineering
2
Access levels 19
General Information 5 - 15
Entering the password 19
Validity of these instructions 5
Changing password 20
Standards 5
Changing parameters 20
For your safety 6
List of parameters
Follow the legislation on safety of appliances 6
(level 0 and 1 parameters only) 21 - 29
Purpose 7 - 8
Leakage test 30 - 31
Intended purpose of FMS 4 / FMS 5 7 - 8
Mode of operation
Application-internal output regulator (optional) 8
Integrated leakage test (option)
Application-internal O regulator (optional) 10
2
Leakage test flow chart 30
Integrated leakage test (option) 30
Using these instructions 9 - 10
Purpose of these instructions 9
Venting
Preliminary clarification 9
Leakage test line over-roof 31
Finding the appropriate section 9
Calculation formula 31
Conventions 9 - 10
Suggested circuit for venting the gas line
Fault correction 10
over-roof in conjunction with the combustion management system 31
FMS Operating principle 11 - 15
FMS digital inputs 11
Output regulator (optional) 32 - 38
FMS operating sequence 11 - 12 Pre-ventilation suppression
Method of operation 32 - 34
through an external signal 12
Procedure description 32
Automatic pre-ventilation suppression 12
Weather control 32
Setting the pilot burner, serving mode 13
Set-point switch-over 33
Program monitoring time 13
Startup circuit 33
Restarting 13
Thermostat and control region 34
Leakage test (option) 13
Manual control 34
4 curve sets (option) 13 Flying curve change (option) 13
Setting the regulator 35 - 38
Automatic fuel change 13
Interpreting the display 35
Range limits 13
Control region 35
Internal load 14
Regulator behaviour 36 - 38
Manual operation 14
Examples 38
Parameterisation 14 Correction 14
Before commissioning 39
Facility for direct connection of Namur transmitter (option) 14
Adjusting motor limit switch 39 Freedom from error of feedback signals 14 Pre-ventilation limit 14
FMS Commissioning 40 - 72
Energy-saving mode for running text display 15
Function test 40 - 41
Separate ignition point 15
Significance of FMSdigital input display 41
Integrated power control unit (option) 15 Integrated O regulation 15
2
Setting control elements 42
Operation of control elements for potentiometer
Settings 16 - 30
adjustment and limit switch settings 42
Inputs 16 - 18
Programming curves 43 - 48
Significance of ID number 16
Programming the compound 43
Inputs 16
Entirely new curve, clear memory 43
Configuration sticker 16
st
Programming 1 point
Configuration number 16
(separate ignition point) 44
Condition on delivery 17 - 18
Programming with burner running 44 - 45 Assignment of sockets to inputs 17
Programming with burner stationary 45 Configuration cards (examples) 17
nd th
Programming 2 to 19 point 45 Processor card 18
Programming last top point 46 Power supply card 18
Store curve 46 Plug-in p.c. card for a continuous output 18
Check monitoring values 46
Adding points 47
Parameters 19 - 20
Changing curve point 48 Parameter setting 19
Table of Contents
3
Instrumentation for commissioning 72
O regulation 49 - 62
2
Adjusting load ratings individually 73
Automatic functions control
Entering an initial curve 73
during operation 49 - 50
Approaching control elements from one side 74
Adjusting the integrated O regulator (optional) 49
2
Entering settings 74
Checks during burner start-up 49
Entering top setting 74
O monitoring bands 49
2
Ignition delay when setting 74
O boundary curves 49
2
Pre-setting load automatically 74
Dynamic probe test 50
Entering the compound curves
Probe blockage 50
with the burner stationary 75
Correction output monitoring 50
Keeping the re-circulation damper
Regulation strategy 51 - 53
closed in pre-ventilation 75
With pre-setting for load changes 52
Setting the pilot burner (servicing mode) 75
Extended regulation strategy (air shortage) 53
Switching the burner on again via the target value 75
Connection to O meter 54
2
Via analogue interface 54 Operator controls and display 55 - 56
System Operation 76 - 89
Mode switching 55
Mode display 76 - 78
Calling up O regulation text messages 56
2
Significance of modes on the FMS 76 - 77 O regulator modes 77
Commissioning 57 - 61
2
"ES" Mode progress (set-control) 78
Setting the correction range 57
Continue programming 78
Inputting the O target value curve 58
2
Calling up the correction range set 59 Calculation and setting of
4 Curve sets FMS (option) 79
control parameters-(manual) 59
Interconnection with 4 curve sets option 79
Lag time (parameters 898/900) 60 P-factor (parameter 899) 60
Checksums
Setting base value for "Deactivated
Running time meter 80
control” and "Air shortage” 61
Recalling the checksums
Calling up the base value for O regulation
2
and the safety times 80
deactivated/air shortage 61
Calling up running time meter 80
Automatic 61 Operation 62
Messages / Faults 81 - 89
The meaning of the additional modes 62
What happens in the event of FMS fault 81
Calling up O regulation text messages 62
2
Reading off a fault 81 Resetting a fault 81
Correction 63 - 66
Calling up fault history 81
Set correction input 63 - 65
O regulation perturbed 82
2
Setting the correction range 65
Air shortage perturbation 82
Recall set correction range 65
Resetting O errors 82
2
Altering the correction range 66
Calling up O regulation error history 82
2
Correction modes 66
Fault codes 83 - 89
Run to shut-off limits 67 - 70
FMS Fault Correction
Run to shut-off limits 67
Aids 90 - 115
Checking the shut-off limits at the
General Faults (A) 90 - 94
three/point step output of the FMS 67
Three-point step control output (B) 95 - 96
Checking the shut-off limits at continuous output of the FMS 68
Continuous output (C) 97
Tolerance limits direction air deficiency 69
Load signal (D) 98 - 99
Indication for an example protocol 69
Feedback (E) 100 - 103
Checking the O influence 69
2
Correction input (F) 104 - 105
Example protocol 70
Digital inputs (G) 106 Control unit faults (H) 107
Tips & Tricks 71 - 75
Leakage test 108
Programming 1st point (ignition load point) 71
Parameters (P) 109 - 118
Programming with burner running 71 - 72 Programming with burner stationary 72 Reversing the programming 72
Table of Contents
4
with leakage test 131
FMS Fault Correction
Oil operation with pilot burner
Aids O regulation 117 - 118
and ignition flame monitor 132
2
Oil poeration without pilot burner 133
Parameter (P) 117 - 118
Relay module R16 134 - 137
Servicing 119 - 120
Circuit diagram type 660 R 0016 V3 134
Changing EPROMs 119
Block diagram type 660 R 0016 V4 135 Changing a data EPROM
Contact plan, relay module type 660 R 0016 V3 136 or a program EPROM 119
Contact plan, relay module type 660 R 0016 V4 137 Re-entering range limits 119
Installing new software version 120
Safety interlock chain 138
Example safetz interlock chain 230V 138
Procedure for installation of
Wiring of the analogue inputs 139
new software in the FMS 120 Replacing the relais module 660 R 0016 120
FMS 4 / FMS 5
Connection diagram 140 - 144
Appendix 121 - 147
Type 664 F 0010 / Type 665 F 0010 140
EMC of wiring 121
Type 664 F 0020 / Type 665 F 0020 141 Connection of screening 121
Type 664 F 0030 / Type 665 F 0030 142 PE bus bar 121
Type 664 F 0040 / Type 665 F 0040 143 Switch cabinet wiring 121
Type 664 F 0050 / Type 665 F 0050 144 Screening of leads from the field 121
FMS 4 / FMS 5 Feedback on TPS channels 122
Connection diagram
Positive connection 122
with output regulator 145
Example of positive potentiometer connection 122
Direct connection of
Error-proof feedback 122 Examples of potentiometers 122
Namur transmitter (option) 146 - 147
Examples of servomotors 122
Extract from circuit diagram 146 External switching of the fuel control element 123
Technical data 146
Selecting a suitable sensor
for rev. speed monitoring 147
Replacing a servomotor, replacing a potentiometer 124 - 125
Relay module
Replacing a servomotor with LAMTEC
connection diagram 148
precalibration 124
Type 660 R 0013 / Type 660 R 0131 148 Replacing a complete servomotor 125
Type 660 R 0019 148 Replacing the potentiometer in a servomotor 125
Connection diagram Switch and key combinations
Modem for remote control 149 on the VMS / FMS front panel 126
Switch and key combinations
General Notes 150
O regulation 127
2
Technical data 151 - 152
Notes on air pressure monitor
Accessories
Not on operation with
and Spare Parts 156 - 157
re-circulation control elements 128
Accessories and Spare Parts for
Interconnection of the air pressure monitor 128
FMS Combustion Management System 156 - 157
Paramterisation of the re-circulation pre-ventilation time 128 Interconnection of monitors
Declaration of Conformity 158 - 159
of the re-circulation ducts 128
EC Declaration of Conformity 158 Notes on start without pre/ventilation 129
Appendix to the EC Declaration of
Conformity or EC Manufacturer's Declaration 159
Process sequence charts 130 - 133
Gas operation with pilot burner,
Protocol example 160
leakage test and ignition flame monitor 130
O target value curves 161
2
Gas operation without pilot burner
5
General Information Validity of these Instructions
Validity of these instructions These instructions apply to the FMS 4 and FMS 5 Combustion Management
System in any configuration.
The software-related information relates to the software version V3.1 (recognisable from the sticker inscription on the program EPROM).
Standards The units conform to the following standards and regulations:
FMS EN 298
EN 230
where applicable where applicable where applicable
where applicable EMC Directive, Low Voltage Directive Gas Appliance Directive
Integral leakage test:
EN 1643
Test mark gas side DIN DVGW PÜZ NG-2510 AS 0324
CE-0085 AS 0254
EN 676 EN 267 EN 12 952-8 u.-11 EN 12 953-7 u.-9
6
General Information For your safety
Follow the legislation The legislation on safety of appliances states: on safety of appliances Follow the instructions !
Proceed only in accordance with this FMS commissioning supplement (booklet No. D LT 6079)
Use the appliance solely for the specified purpose. It must be operated only by trained personnel. The appliance must be operated and serviced only by persons with the required knowledge and training. Follow the burner manufacturer's safety rules.
Associated automatic flame guard The unit is approved for use only with an external automatic flame guard. The automatic flame guard type F 250 made by Hartmann & Braun is used for testing purposes. However, any other automatic flame guard tested in accordance with DIN EN 298 and/or DIN EN 230 and approved for continuous operation may be used instead of this.
Electrical connection to appliances not mentioned in these instructions Only after consultation with the manufacturers or a qualified expert.
If an automatic flame guard not approved for continuous operation is connected, approval of the system for continuous operation will lapse.
Liability for proper functioning of the appliance passes to the owner or operator. Liability for correct functioning of the appliances in every case passes to the owner or operator, should the appliance be incorrectly operated, serviced or repaired by persons without the requisite knowledge, or if operation is inconsistent with the specified intended purpose.
In the event of modifications to the unit the type approval lapses. The unit's inputs and outputs and associated modules must only be wired according to the specifications in these instructions.
LAMTEC GmbH & Co KG will not be liable for damage or injury arising out of a failure to observe the instructions above. The warranty and liability provisions of the terms and conditions of sale and supply of LAMTEC GmbH & Co KG shall not be extended by virtue of the instructions above.
Where reference is made to legislation, government regulations and standards, these are based on the legal system of the Republic of Germany.
To be used only in a grounded power line network!
7
General Information Purpose
Intended purpose The FMS 4 / FMS 5 Combustion Management System is a control unit for FMS 4 / FMS 5 combustion systems.
Brief description
The FMS 4 adjusts up to four control elements as a function of a control variable (generally the burner load) according to freely programmable curves.
The FMS 5 adjusts up to 5 control elements as a function of a control variable according to freely programmable curves).
2 sets of curves (e.g. for oil or gas) can be filed as standard, with the option for 4 or 8 sets of curves.
Examples of possible control elements:
- Combustion air damper - Re-circulation fan
- Combustion air fan - Flue gas damper
- Fuel quantity - Flue gas fan
- Atomiser steam
Up to 20 points can be programmed for each channel. The display is relative between 0 and 999.
The FMS has two correction inputs for shifting the setting curves, allowing a feedback control (e.g. O control unit) to be connected up.
2
Each output is freely configurable, either three-point step control element output for direct actuation of a motor or constant output (on the FMS 5
th
the 5 channel is always constant). The constant output can be set to any of the following variables:
- Current signal 0 … 20 mA
- Current signal 4 … 20 mA
- Voltage signal 0 … 10 V
The FMS 4 also has a so-called monitor output. In addition an internal value (such as the load position of the burner or position of the gas control element) can be outputted by means of 4 … 20 mA signal).
The FMS has one serial interface for remote control/ display via PC (Windows software available separately) and for connection to other system components via BUS (e.g. fault message system, O control).
2
Connections for Interbus-S, Profibus, Modbus and CAN­BUS are available as options. Other BUS systems on request.
The FMS constantly monitors its own functioning and that of the control elements connected.
Each analog input (control variable and feedback or correction) is freely configurable via plug-in cards.
Alternatively:
- Potentiometer (1 5kS) - Step input (DPS)
- Current signal 0/4 … 20 mA - Namur transmitter as a two-wire system
- PT 100 - inductive sensor with switch terminals in three-wire system
The unit is of error-proof construction.
General Information Purpose
Application - internal output regulator (optional)
Application - internal O regulator
2
(optional)
The FMS contains a burner control unit with process control program.
Outputs:
- actuation of gas valves
- actuation of oil valves
- actuation of the ignition valve and ignition transformer
- fan release
- oil pre-heating
- fault signal
- signal outputs for oil and gas operation
(in the off condition, oil operation is always indicated)
The external signals to the control unit are via floating contacts or chains of contacts.
The following signals can be pre-set:
- 3 separate safety interlock circuits
- fault unlocking
- air pressure monitor
- gas pressure monitor (min.)
- flame signa
This software option makes it possible to calculate the burner's required load setting continuously for a specified target value (referred e.g. to temperature or pressure), through comparison with the actual value. This load setting can be notified internally to the electronic compound as the specified value.
This software function makes it possible to regulate one or several actuators independently of a switched-on O actual value. By using a self-optimising
2
regulator strategy, it is also possible to regulate burners with frequent load changes.
l (pilot flame monitor and ignition flame monitor)
- pre-ventilation and ignition release
- pre-ventilation suppression
- control release
- re-circulation release
- burner on
- fuel selection
8
9
General Information Using these instructions
Purpose of these instructions These instructions are concerned exclusively with commissioning and
servicing.
Further information, for example design examples, possible uses, software settings etc., is given in separate booklets.
Special information dealing with optional equipment on this unit is explained in separate booklets.
Preliminary clarification To make the best use of these instructions, proceed as follows:
Check whether the settings of your FMS meet the system requirements. You will find the settings on the sticker on the unit.
- Which physical quantities (current, resistance) and values does your FMS need on its inputs?
- Which physical quantities (current, voltage, relay signal) and values does the system expect on the outputs of the FMS ?
- Do the settings of the FMS match your requirements with regard to operating behaviour (pre-ventilation, feedback etc) ?
Should these matters not be clear, please read the section "Settings” (page 16-29)
Finding the appropriate section Determine what operation you wish to perform on the FMS.
When initially putting into operating or tracing the cause of a fault, a function test is first recommended. You must then decide whether you wish to program with the burner stationary or running and whether or not an entire curve is to be programmed.
Identify your current requirement from the table of contents and turn to the appropriate page.
Conventions Sub-headings
Serve as a guide if you can already handle the FMS and merely want to refer to certain information again.
Lines in italics after the sub-headings
describe what the current state of the system should be. If this is not the case, the subsequent operations will not show the desired result.
Lines in bold type indicate an action which you are to perform.
10
General Information Using these instructions
The figures and letters in brackets (1), (2), (3), (4), (5), (6), (7), (8), (A) and (B) relate directly to the picture of the front panel. They identify the part on which the specified action is to be performed or on which a reaction can be seen.
The lines in ordinary typeface below the procedural instruction describe the reaction of the system or unit following the operation.
The figures at the right-hand margin denote a paragraph in the "Fault Correction” section of these instructions. If the reaction indicated does not occur, please refer to this. It describes the possible causes of faults and how to rectify them.
___________________________________________________________________
The word in italics between two lines and the sign
are notes for a better understanding of the operation or notes on how to avoid incorrect operation.
___________________________________________________________________ ___________________________________________________________________
The lines in bold italics between two lines and the triangle
draw attention to dangers. The instructions given there must be followed. ___________________________________________________________________
If you now follow the operations step by step, paying attention to the instructions, you will automatically be working correctly. If any of the reactions indicated do not occur, there is a fault with the unit or the system. You should correct the fault first before proceeding.
Fault correction Follow the instructions identified by the figures given after the fault codes
and after the procedural instructions. You may find the solution to your problem there.
This section, however, makes no claim to completeness. Should the actions described there not have the desired effect, the unit or parts of the unit (e.g. front panel etc.) must be changed. If the fault still occurs you are dealing with a fault specific to the system.
___________________________________________________________________ Tip: You can download the up-to-date version of these instructions from
http://www.lamtec.de as PDF File. You will find the version from the letter of the booklet no. (see the backside of this document). Example:
DLT 6066 cD
booklet No. version language
___________________________________________________________________
CHANNEL 1 CHANNEL 2 CHANNEL 3 CHANNEL 4
ENTER
POWER OIL GAS ALARM
SETPOINT
FEEDBACK
SETPOINT
FEEDBACK
ACTUAL VALUE
FEEDBACK
ACTUAL VALUE FEEDBACK
SETPOINT
CHANNEL 5
xxx
xxx
xxx
5
4
6
A B
7 8
3
SETTING
AUTOMATIC
CLEAR MEMORY
O -CONTROL
2
PARAMETERISATION
MONITORIN
DISPLAY
FEUERUNGS-MANAGEMENT-SYSTEM FMS
LAMTECLAMTEC
xxx
2
1
DISPLAY CHANNEL 5 (DIGITAL INPUTS)
LOAD RATING
(CORR. INPUT)
STATUS
(CORR. RANGE)
SETPOINT
ii
i
!
i
11
General Information FMS Operating Principle
FMS Digital Inputs For the FMS to function according to the requirements of a combustion
system, the condition signals from the system must be relayed to the FMS.
These signals include:
Pre-ventilation suppression Air pressure monitor Gas safety interlock circuit Gas pressure > min. Oil safety interlock circuit Ignition flame Boiler safety interlock circuit Burner on Ignition position acknowledgement Fault reset High firing rate acknowledgement Re-circulation On Fuel selection Control release Flame signal Set-point switch over
(only with integral load control unit)
For use in burner control, the FMS emits 9 digital signals, which are converted by relay module (type 6 60 R 0016) into twelve output signals for 230 V:
Main gas 1 Ignition valve Main gas 2 Ignition transformer Oil Release ignition gas line Heated oil distribution Fan Oil operation signal Pre-ventilation / post-ventilation Gas operation signal Fault signal
___________________________________________________________________
FMS operating sequence The operating sequence described relates to a usual configuration of the (for diagram of example, unit. The various parameter settings can result in a somewhat different see appendix) sequence.
___________________________________________________________________
A signal is first sent to terminal 2 (burner ON), indicating when the burner is to start. The FMS then interrogates the safety interlock chain for the selected fuel and the air pressure monitor contact. If the fuel is selected via the fuel safety interlock circuits, the FMS performs a plausibility check. If it does not detect a satisfactory condition, a corresponding text message is emitted and the process control stops. If all signals are OK, the fan output is activated and the ducts run to their bottom stop as a check. The "pre-ventilation/post-ventilation” output is activated. Once all ducts have reached their bottom stop, they open for aeration. Any leakage test configured runs in parallel.
In the case of control elements, aeration is used to enter and to check the range limits. The fuel control element, after reaching its top position, runs back into the ignition position. All other ducts remain in the open position. The FMS now interrogates the high firing rate acknowledgement and the air pressure monitor. If these signals are OK, the parameterised aeration time runs. If a duct is configured for re-circulation, this opens with a time delay. On reaching the parameterised re-circulation delay time, the pre-ventilation time stops. As soon as the re-circulation duct has reached the aeration position, the aeration time continues. Once this time has elapsed the ducts run into the programmed ignition position (re-circulation fully closed). Once all ducts have reached ignition position, the FMS interrogates the ignition position acknowledgement. In gas operation the gas pressure monitors must also be in a satisfactory condition prior to ignition. The ignition transformer is now activated alone for the duration of the pre-ignition time (transformer start-up time).
12
General Information FMS Operating Principle
Start without pilot burner: The main valves open and remain activated together with the ignition transformer for the duration of the safety period. During this time the flame signal appears.
Start with pilot burner: The ignition valve and main gas 1 are opened. The pilot flame forms and
st
the flame signal appears. Once the 1 safety period has elapsed, the pilot burner burns on its own. The main gas 2 then opens and remains activated
nd
in parallel with the ignition valve for the duration of the 2 safety period. When this period has elapsed the ignition valve closes again.
When ignition is completed the re-circulation duct and the flue gas damper run to the programmed point. Correction is activated. All ducts may run to the programmed base load point (depending on the setting selected). The FMS remains in the base load position until control release (terminal 4) is given.
Following control release the FMS follows the prevailing external load. A current signal proportional to the position of the compound is emitted as internal load (not on FMS 5). Withdrawal of the signal/control release during operation allows the compound to run at base or ignition load (configurable).
Withdrawal of the terminal 2 signal is followed by shutting off. The main valves close. (In gas operation, main gas 1 first, followed by main gas 2 with an approx. 5-second delay, in order to allow the monitoring line between the solenoid valves to burn out. In the event of a fault shut-off, however, they both close immediately). If configured for post-ventilation, the air ducts open again for this period. After the configured after-burning time the FMS again checks for a period of 5 seconds whether the flame has gone out. If not, a fault shut-off occurs. The FMS then goes into "OFF” mode.
Pre-ventilation suppression The pre-ventilation range can be skipped by means of the pre-ventilation through an external signal suppression signal (terminal 1). If the signal is present straight away at
burner start-up (terminal 2 signal), the control elements run directly to the ignition position. In order to enter the range limits, however, pre-ventilation should be performed once after "Clear Memory”. Pre-ventilation suppression can only occur, however, if this function is activated via parameters.
Automatic pre-ventilation When activated by parameters, the FMS starts after regulator switch-off suppression automatically without pre-ventilation. Pre-ventilation is only carried out now after
fault switch-off or power failure. Using this function is subject to the regulations applicable to the facility.
13
General Information FMS Operating Principle
Setting the pilot burner, servicing mode
Program monitoring time
Restarting
Leakage test (option)
4 curve sets (option)
Automatic fuel change
Flying curve change (option)
Range limits
A so-called servicing mode can be set via parameters. The control unit then runs until the stabilisation period. In this mode 5 successive starts are possible without the need for pre-ventilation and without a leakage test.
th
The 5 start is automatically followed by pre-ventilation and/or a leakage test.
It can be determined by way of parameters how long the FMS may take after a start signal (terminal 2) until ignition occurs. If this length of time is exceeded, a fault shut-off occurs. If the content of the parameter is set to 0, no fault occurs (= program monitoring time = T).
Automatic restart can be activated via parameters. The control unit attempts a one-off restart in the event of any fault marked with * after a factory-set period (standard: 10 sec). This restart can be prevented by setting the period to 0.
n the case of firing systems according to EN 676 the parameter must
be set to "0”.
The standard setting is without restart.
The control unit may optionally also perform the leakage test on the gas valves. The leakage test can per performed before ignition and/or after shut-off
The leakage test is performed by way of the main valves. The use of filling and discharge valves is also possible by means of relay switching.
The FMS offers the facility for using two curve sets for each fuel (e.g. summer/winter operation) or a mode with and without speed.
When using Option 4: Curve sets, it is possible to switch within one fuel selection from one curve-set to the other (flying curve change). Fuel change can only be performed via "Off”.
When switching the fuel selection switch over (terminal 75), the FMS first moves automatically to the base load position. Then the system switches off. Only then are the fuel selection and thus the curve set changed over. If the "Burner on” signal is still present, the burner starts with the new fuel. (This function is not available with Option 4: Curve sets).
st
In the 1 pre-ventilation after "Clear memory”, the FMS determines the maximum range of travel for each control element and stores this automatically. If no ranges limits have yet been determined, the setting (in the case of constant outputs the feedback setting) in pre-ventilation stands at 0 and 999 points respectively. At all further starts a check is made to see that these range limits are correct. Should the limit switches be shifted or the frequency converter setting changed after programming, the range limits must be re-entered.
If the range limits cannot be determined automatically, they can also be entered manually by way of parameters. If the FMS has no existing range limits, it automatically takes the top and bottom point of the curve as the limit. It then does not go beyond this.
____________________________________________________________ I
____________________________________________________________
!
14
General Information FMS Operating Principle
The internal load is the load value at which the compound currently stands. It therefore corresponds indirectly to the output of the burner. The internal load is displayed in addition to the external load signal. In the "load value” position therefore both the external load (left-hand) and the internal load (right-hand) are displayed.
The value of the internal load can be outputted via the monitor output, in order to connect further units (e.g. O control, only on FMS 4). When
2
connecting other units, it must be remembered that the signal in itself is not error-proof.
When switching over to "Load value” with the burner running the burner load can be set via the FMS. The load value can then be adjusted with the channel 1 toggle switch. The system follows this load value in the compound. Operating a switch other than channel 1 causes the unit to exit manual mode again.
The person commissioning the unit can adjust various functions of the
FMS
by way of parameters (e.g. post-ventilation time). The parameters are classified into various safety levels. With the exception of the lowest safety level these are accessible only with a password. The parameterisation can be undertaken both on the unit itself and by means of a PC and Windows software.
The FMS has 2 correction inputs. An analog signal (0/4 … 20 mA) can be connected to these for shifting the set curves (e.g. for O correction or air
2
temperature correction). The assignment of the correction to the individual output channels and the mode of operation can be adjusted via parameters.
If the FMS cannot perform a correction because a control element stop has been reached, it adjusts the internal load and hence the compound until the correction can take effect as required.
An output for controlling the speed of a combustion air fan or a re-circulation fan etc. can be monitored by switching the pulse output of a Namur transmitter directly to the FMS.
Continuous outputs and three-point step outputs have different feedback requirements. In the case of continuous outputs comparisons are made between output and feedback values in or to check the plausibility. The units therefore do not have to be intrinsically error-free in order to form the feedback signal. For availability reasons (minimisation of interference) the reproducibility of the values should be as good as possible.
For technical reasons this method cannot be used in the case of three-point step outputs. For this reason TÜV approved potentiometers must be connected directly as feedback to the FMS. These potentiometers must positively render the position of the damper.
Normally during pre-ventilation each control element runs as far as ist uppermost stop. Now, by means of parameters, a limit can be set for each channel that is not exceeded during pre-ventilation.
Internal load
Manual operation
Parameterisation
Correction
Facility for direct connection of Namur transmitter (option)
Freedom from error of feedback signals
Pre-ventilation limit
15
General Information FMS Operating Principle
Energy-saving mode for The brightness of the display can be adjusted to the ambient light running text display conditions by means of parameters.
In addition the display can be set to automatically revert to the lowest brightness level if not operated within a given period of time.
Separate ignition point In the standard version the ignition point is situated outside the accessible
range in order to set a separate fuel/air ratio. By means of parameters, however, the ignition point can be adjusted so that it lies on the compound curve.
Integrated power control unit An integrated power control unit is also available as an option. Where this (option) is used the actual temperature or the actual pressure is directly switched
instead of the load signal. The control parameters are adjusted via parameters. It is also possible to change the setting (daytime/night time
The integral output regulator is a PID controller with special combustion technology functions. It can be used as a fixed-value regulator or as a weather-dependent regulator. The following signals can be set:
- Actual value (analogue)
- External temperature or some other analogue signal for target value shifting
(only in weather-dependent regulators)
- Target value switching (via zero-potential contact)
Combustion enabling by the output regulator takes place internally in the FMS Boundary values that switch the burner on and off, need to be set via parameter
regulation - optimises combustion systems
2
- saves fuel
- minimises pollutants
The main purpose of O regulation is to compensate for perturbations that
2
affect combustion. In addition, the O regulation system monitors the
2
combustion's fuel/air ratio. A message is output at once if it strays outside the permitted limits. The following are the main perturbing factors that affect combustion:
Air: Temperature Contamination: Burner
Pressure Boiler Humidity
Fuel: Calorific value Mechanical systems:
Temperature Mechanical Viscosity hysteresis Density (free play) Gas pressure fluctuations
The O control unit is implemented as a free-standing software module.
2
The unit compares the residual oxygen content in the exhaust gas of a
combustion system measured by means of the LT1/LT2 Lambda transmitter (actual value) with the optimum residual oxygen content (target value). The target values are stored in the instrument in the form of an installation-specific curve. The control unit applies a correction until the actual value corresponds to the target. The calculated output value of the O control module is transmitted to the compound module as a correction
2
input signal.
operation) and to control the atmospheric conditions by switching in the outside temperature.
setting. In this case, the startup signal is removed internally from the FMS via the output regulator module. The operator is alerted by the display (running text) that the output regulator refuses to enable a startup.
Integrated O
16
Settings Inputs
Significance of ID number The ID number comprises 8 characters, e.g. 664 V 0010
The two figures before the letter denote the unit, in this case a FMS 4. The letter denotes whether the unit is a VMS or a FMS. The penultimate figure provides information on the unit hardware. It also determines which connection diagram applies (see appendix).
Inputs The inputs can be configured on the backplane by means of plug-in
configuration cards. Any of the following can be connected up to each input:
- a potentiometer in the range from 1-5 kS
- a current signal 0 … 20 mA or 4 … 20 mA
- a step signal ("OPEN CLOSE" commands)
- a frequency signal (Namur transmitter), for details see appendix
- a PT 100 element
- flame sensor module (in preparation)
- a potentiometer module (in preparation) There is a plug-in card for each configuration. This is inserted into the
respective socket in order to configure the input.
Configuration sticker The factory setting is entered on a sticker on the side of the unit.
This corresponds either to the customer data or, if nothing was specified, the standard setting (see condition on delivery).
The EEPROM checksums and thereby the software version are also entered on this sticker, together with the configuration number and hence the hardware setting.
Configuration number The configuration number is a 15-digit number, constructed according
to a fixed code.
BUS-card input voltage
Channel 1 assignment
red. feedback channel 4 red. red. red.
Correction input 1
Channel 5 feedback
Load input
Channel 2 assignment Channel 3 assignment Channel 4 assignment Channel 5 assignment
feedback channel 3 feedback channel 2 feedback channel 1
Correction input 2
Channel 4 feedback Channel 3 feedback Channel 2 feedback Channel 1 feedback
a x b x x x x x c x x d x x x x e x f x K y y y y y
BUS-card
x = 1 ^ Interbus-S 2 ^ SUCOnet K-Bus 3 ^ 4 ^ Profibus 5 0 ^ not present
CAN-Bus
^ Modbus
K = Channel assignment
y = 1 ^ Recirculation 2 ^ Fuel 3 ^ Air 4 ^ Flue gas 5 ^ mech. Compound 6 ^ Steam
a, b, c or d = Feedback, correction and load
x = 1 ^ Potentiometer input 1kW...5kW 2 ^ continuous signal 0/4...20mA 3 ^ TPS input 4 ^ Pulse input (Namur) 5 ^ PT 100-input 6 ^ Flame sensor input (only on red. feedback channel 4) 7 ^ continuous signal 0/4...20mA potential separated 8 ^ 0 ^ unoccupied
constant signal with 24 V supply
Input voltage
x = 1 ^ 230 VAC 2 ^ 115 VAC 3 ^ 24 ACV 4 ^ 24 VDC 5 ^ Special voltage
Settings Condition on delivery
Condition on delivery All units are set according to the order. Settings not evident from the
ID number or configuration number must be indicated separately. In particular:
Outputs
- whether continuous or three-point step
- whether 0 … 10 V, 0/4 … 20 mA
- position of the outputs in the event of fault Inputs, load, feedback
- Whether potentiometer or 0/4 … 20 mA or step
- Whether inputs are used doubled (redundant) and if so, which (possible only if the integrated power control unit is not used)
- Whether special plug-in configuration cards (PT 100, Namur transmitter) are used
Correction input
- Whether 0 … 20 or 4 … 20 mA or direct temperature connection
- Mode of operation, on which channel, upward or downward shift (modifiable only via software)
Assignment of Backplane sockets to inputs
Configuration cards (examples)
Feedback 1
Corr. Input 1
Corr. Input 2
Load input or load control unit value
Feedback 2
Feedback 3
Feedback 4
Feedback 5
Red. Feedback 1
Red. Feedback 2
Red. Feedback 3
Red. Feedback 4
or atmosphere control
or flame sensor module
17
R4 = 0W
R4 = 0W
R4 = 0W
R8 = 2K2
R10 = 2K2
R15 = 0W
R12 = 0W
R12 = 0W
R11 = 0W R16 = 0W
R17 = 0W
R15 = 0W
Potentiometer Configuration
TPS configuration
0/4 … 20mA configuration
TM1
R17
R18
R16
R13
R14
R15
R5
R11
R12
R10
R7
R9
R8
R4
D1
T1
C1
R6
R2
R3 D2
R1
D2
D1
R10
R12
R16
R4
R15
R8
R11
R18
R9
R7
R13
R14
R17
R1
R3
R5
R2
R6
C1
TM1
T1
TM1
R10
R12
R11
R5
R16
R18
R17R13
R15
R14
R9
R7
R4
R8
R2
R6
C1
T1
D1
D2
R3
R1
Settings Condition on delivery
Processor card
Note: Continuous channels must all be fitted with additional cards from channel 1 onwards
Power supply card
Plug-in p.c. card for The standard control outputs are three-point step a continuous output (except for a possible 5-channel. This is always continuous).
Each TPS output can be reconfigured to make it continuous by plugging in an additional card.
The jumpers serve only for hardware switching between current output and voltage output. The selection of 0 or 4 … 20 mA is done through the software by means of parameters.
18
T 902
EEprom for curves
and parameters
Monitoring processor
EEprom for curves
and parameters
Main processor
Program processor
Main processor
Program EPROM
Over-voltage
processor
Sockets for contiuous additional cards
TPS Configuration
Channel 1
Transformer
Fuse 2 1 AT mA
80 C 537
Channel 2 Channel 3 Channel 4
Bridge voltage output 0 … 10V
Bridge current output 0/4...20mA
T 902
Settings Parameters
Parameter setting The parameter level can be accessed by turning to the "Parameter”
selector switch position. When working on level 1-4, this works only with the burner stationary (i.e. no signal on the digital inputs). Only level 0 is accessible with the burner running.
___________________________________________________________________
As a rule, the factory parameter settings are precisely tuned for the installation for which the unit has been designed. Therefore, it is only necessary to change parameter settings in exceptional cases.
___________________________________________________________________
Access levels The parameters are divided into four different access levels according to
function and safety classification:
Operating level (Level 0)
! Accessible without password, non-critical parameters that may possibly
have to be altered during operation.
Customer level (Level 1)
! Accessible with modifiable password (on delivery set at "0000”), access
to parameters, adjustment of which calls for technical knowledge, which are tailored to the system and which are not altered during operation.
Service level (Level 2)
! Accessible with a fixed password, but only to personnel specially trained
in parameterisation. Access to all parameters that are not fixed on the basis of standards and technical regulations.
Production levels (Levels 3 and 4)
! Access to all parameters (only possible through LAMTEC)
Each parameter level is protected by its own checksum. This checksum serves to show that no changes have been made (see page 78).
Entering the password Selector switch (1) to status
Push switch (4), channel 2 and 3, up
and at the same time
push switch, channel 4, down
- the input field for the password appears on the display.
Set the appropriate password via the switch.
Acceptance key (3) Parameters on the corresponding level are released.
Selector switch (2) to parameterisation
xxx
LAMTECLAMTEC
xxx
xxx
xxx
2
3
4
1
19
!
!
!
i
Settings Parameters
Changing the password ____________________________________________________________
Only possible at customer level (level 1)
____________________________________________________________
From level 1, once accessed: Turn selector switch (1) to Status Simultaneously push keys (4) channel 2 and 3 upwards and channel 4 downwards
- the display shows the password input field Set the new password for the level Turn selector switch (1) to Digital inputs Press the Acceptance key (3)
- new password is set
Changing parameters Select the required parameter with Channel 3 key
Change its value with Channel 4 key
- The values are accepted immediately without further confirmation
An explanatory text for the parameters can be called up by pressing the Acceptance key (3)
____________________________________________________________ For larger values, changes can be in x100 steps with Channel 1 key and
in x10 steps with Channel 2 key. ____________________________________________________________
xxx
LAMTECLAMTEC
xxx
xxx
xxx
3
4
1
20
i
xxx
LAMTECLAMTEC
xxx
xxx
xxx
3
i
Settings List of Parameters
(Level 0 and 1 parameters only)
_____________________________________________________________________________________________________
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
Pre-ventilation
346 VO LimK1 1 0 999 Limit to which pre-ventilation can be 999 P4
terminated, Channel 1
347 VO LimK2 1 0 999 Limit to which pre-ventilation can be 999 P4
terminated, Channel 2
348 VO LimK3 1 0 999 Limit to which pre-ventilation can be 999 P4
terminated, Channel 3
349 VO LimK4 1 0 999 Limit to which pre-ventilation can be 999 P4
terminated, Channel 4
350 VO LimK5 1 0 999 Limit to which pre-ventilation can be 999 P4
terminated, Channel 5
Running direction
374 Laufr.K1 1 0 999 Channel 1 running direction in event or fault 2 P6
375 Laufr.K2 1 0 15 Channel 2 running direction in event or fault 2 P6
376 Laufr.K3 1 0 15 Channel 3 running direction in event or fault 2 P6
377 Laufr.K4 1 0 15 Channel 4 running direction in event or fault 2 P6
378 Laufr.K5 1 0 15 Channel 5 running direction in event or fault 2 P6
427 Vodel R 1 0 999 750 P71
When changing the parameters via interface (by means of optional PC software) a check must then be made on the spot to ensure that the changes have been properly accepted. This can be done by reading out the parameters on the unit or by comparing the unit's checksums. See page 78 .
0 = OFF (control element stops) 1 = Control element runs OPEN 2 = Control element runs CLOSED 3 = Control element runs to the setting 6 = Control element runs to its ignition point 8 = Control element runs to base load
Re-circulation delay time (on FMS) No. of air duct points (VMS)
21
22
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
Correction 433 K1 Spreiz 1 0 999 10 P22
434 K2 Spreiz 1 0 999 10 P22
517 KB11.1 0 0 999 0 P7
597 KB21.1 1 0 999 0 P7
Monitor output
677 Moni.1 1 0 23 0 P8
678 Moni.2 1 0 25 0 P9
679 Moni.3 1 0 25 0 P9
3
680 Moni.4 1 0 25 0 P9
4
681 Moni.5 1 0 25 0 P9
5
682 Moni.6 1 0 25 0 P9
6
683 Moni.7 1 0 25 0 P9
7
684 Moni.8 1 0 25 0 P9
8
685 Unt.Mo1 1 0 999 0 P10
686 Unt.Mo2 1 0 999 2: 0 P10
687 Unt.Mo3 1 0 999 3: 0 P10
688 Unt.Mo4 1 0 999 4: 0 P10
Spread factor for correction input (00.0 99.9) 01.0 = no expansion
Spread factor for correction input (00.0 99.9) 01.0 = no expansion
Correction range, correction input 1
Correction range, correction input 2
Definition of the monitor output with curve set 1
0= internal load 14= channel 4 actual value 1= channel 1 setting 15= channel 5 actual value 2= channel 2 setting 21= external load 3= channel 3 setting 22= correction input 1 4= channel 4 setting 23= correction input 2 5= channel 5 setting 24=O -actual value
2
11= channel 1 actual value 25=O -setpoint
2
12= channel 2 actual value 26=Flame intensity 13= channel 3 actual value
Definition of the monitor output with curve set 2
Definition of the monitor output with curve set
Definition of the monitor output with curve set
Definition of the monitor output with curve set
Definition of the monitor output with curve set
Definition of the monitor output with curve set
Definition of the monitor output with curve set
Monitor output, curve set 1: 4 mA correspond to X points
Monitor output, curve set 4 mA correspond to X points
Monitor output, curve set 4 mA correspond to X points
Monitor output, curve set 4 mA correspond to X points
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
689 Unt.Mo5 1 0 999 Monitor output, curve set 5: 0 P10
4 mA correspond to X points
690 Unt.Mo6 1 0 999 Monitor output, curve set 6: 0 P10
4 mA correspond to X points
691 Unt.Mo7 1 0 999 Monitor output, curve set 7: 0 P10
4 mA correspond to X points
692 Unt.Mo8 1 0 999 Monitor output, curve set 8: 0 P10
4 mA correspond to X points
693 Ob.Mo1 1 0 999 Monitor output, curve set 1: 999. P10
20 mA correspond to X points
694 Ob.Mo2 1 0 999 Monitor output, curve set 2: 999 P10
20 mA correspond to X points
695 Ob.Mo3 1 0 999 Monitor output, curve set 3: 999 P10
20 mA correspond to X points
696 Ob.Mo4 1 0 999 Monitor output, curve set 4: 999 P10
20 mA correspond to X points
697 Ob.Mo5 1 0 999 Monitor output, curve set 5: 999 P10
20 mA correspond to X points
698 Ob.Mo6 1 0 999 Monitor output, curve set 6: 999 P10
20 mA correspond to X points
699 Ob.Mo7 1 0 999 Monitor output, curve set 7: 999 P10
20 mA correspond to X points
700 Ob.Mo8 1 0 999 Monitor output, curve set 8: 999 P10
20 mA correspond to X points
Flying curve change
702 Luftvor 1 0 999 Air advance with flying 0 P11
curve change in points
703 Dauer LV 1 0 999 Duration of air advance with flying 0 P11
curve change in seconds
704 Wirku LV 1 0 999 Effect on air advance 1 P11
0-Load / 1-Setting
Band shift
707 Wirk.Bve 1 0 1 Effect on band shift 0 P2
0-Load / 1-Setting
708 BandV K1 1 0 50 Band shift 4 P3
Channel 1
709 BandV K2 1 0 50 Band shift 4 P3
Channel 2
710 BandV K3 1 0 50 Band shift 4 P3
Channel 3
23
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
711 BandV K4 1 0 50 Band shift 4 P3
Channel 4
712 BandV K5 1 0 50 Band shift 4 P3
Channel 5
Compound 718 Laufz L 1 0 65535 Running time in pts./min for TPS 9999 P12
Load input In the event of load via current or pot, the value must be 0
719 Laufz K1 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 1
720 Laufz K2 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 2
721 Laufz K3 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 3
722 Laufz K4 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 4
723 Laufz K5 1 0 65535 Running time in pts./min 9999 P13
for continuous output channel 5
729 stopVERB 1 10 100 Minimum compound running time 10 P15
in seconds
730 minTAKT1 1 1 100 Minimum cycle length for channel 1 1 P16
in 20ths seconds per digit (50 ms)
731 minTAKT2 1 1 100 Minimum cycle length for channel 2 1 P16
in 20ths seconds per digit (50 ms)
732 minTAKT3 1 1 100 Minimum cycle length for channel 3 1 P16
in 20ths seconds per digit (50 ms)
733 minTAKT4 1 1 100 Minimum cycle length for channel 4 1 P16
in 20ths seconds per digit (50 ms)
734 minTAKT5 1 1 100 Minimum cycle length for channel 5 1 P16
in 20ths seconds per digit (50 ms)
740 PauseT1 1 1 100 Minimum pause between channel 1 cycles 2 P27
in 20ths seconds per digit (50 ms)
741 PauseT2 1 1 100 Minimum pause between channel 2 cycles 2 P27
in 20ths seconds per digit (50 ms)
742 PauseT3 1 1 100 Minimum pause between channel 3 cycles 2 P27
in 20ths seconds per digit (50 ms)
743 PauseT4 1 1 100 Minimum pause between channel 4 cycles 2 P27
in 20ths seconds per digit (50 ms)
744 PauseT5 1 1 100 Minimum pause between channel 5 cycles 2 P27
in 20ths seconds per digit (50 ms)
24
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
754 ES aktiv 1 10 100 ES is activated when load 40 P17
falls by X points
755 Verz. ZÜ 1 0 999 Delay time of 0 P19
ignition position relay
756 Verz. GL 1 0 999 Delay time for base load 0 P20
with sep. ignition point
757 Verz. RG 1 0 999 Delay time for control release 0 P21
758 ZEIT NA 1 0 999 Post-ventilation time 0 P18
759 Verz. ZÜ 1 0 30 Ignition delay when setting 0 P29
after actuation of the ignition point
Control unit
768 KuerznLE 1 0 15 Delay time for "Damper open" 5 P72
after fan on
769 D.n.Abs 1 0 1 Leak test 0 P53
0 = Off, 1 = On
772 Dicht Zü 1 0 1 Leak test before starting 1 P53
0 = Off, 1 = On
777 Prgüzeit 1 0 9999 Program monitoring time 4 P40
With content 0 no monitoring occurs
782 VorZüdel 1 2 40 Transformer pre-energise time 3 P51
(pre-ignition time)
783 Stab.zei 1 3 100 Stabilisation time 3 P52
785 ZEIT VO 1 30 999 Pre-ventilation period 30 P54
787 Wartung 1 0 1 Service mode, control unit runs 0 P60
only until stabilisation time
789 Nachbr.z. 1 0 30 Post-combustion time (flame signal 10 P62
irrelevant) in seconds
Power control unit (option)
790 Lasttyp 1 0 2 Load control type 0 P80
0 = off 2 = Atmosphere-controlled unit 1 = Fixed value (possible only where there is control unit hardware provision for this)
791 Anf.Temp. 0 0 999 Starting maximum temperature 0 P81
792 Anf.Leis 0 0 999 Starting power 0 P82
793 Anf.Zeit 0 0 32767 Starting time in minutes 0 P83
794 ext.Lgre 0 0 1000 External power limit 0 P84
after switching off
25
26
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
795 SoftStop 0 0 100 D
796 Soll1min 0 0 1000
797 Soll1max 0 0 1000
798 Soll2min 0 0 1000
799 Soll2max 0 0 1000
800 Obergren 0 0 1000
801 Untergren 0 0 1000
802 Regelb.U 0 -999 +999
803 Regelb.O 0 0 999
804 Bren.AUS 0 0 200
805 P-Faktor 0 0 999
806 I-Faktor 0 0 999
807 D-Faktor 0 0 999
808 Nachst.z 0 0 60
809 L-Einheit 1 0 3 0 P94
810 min.Einh. 1 0 999 0 P95
811 max.Einh. 1 0 999 Upper limit 0 P95
Soft stop time Burner after running 0 P85
Control unit setting 1 minimum with P86 atmosphere control/control unit setting 1
Control unit setting 1 maximum P86 with atmosphere control
Control unit setting 2 minimum with P86 atmosphere control/control unit setting 2
Control unit setting 2 maximum P86 with atmosphere control
Load regulator: upper limit P87 with atmosphere control
Load regulator: lower limit P87 with atmosphere control
Control range, bottom P88
Control range, top P89
Burner off P90
P-factor of control unit 3 P91
I-factor of control unit 4 P91
D-factor of control unit 50 P91
Rest time 10 P92
Load regulator actual value input and setting representation
0 = Display in digits 1 = Display in °C 2 = Display in bar (XX.X)
Lower limit Pressure (4 mA) correspond to X bar
Pressure (4 mA) correspond to X bar
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
814 Leist. 1 1 0 1000 1 P91
815 Leist. 2 1 0 1000 2 P91
816 Leist. 3 1 0 1000 3 P91
817 Leist. 4 1 0 1000 4 P91
Interface
822 BaudS 1 1 0 5 4 P23
823 BaudS 2 1 0 5 2 4 P23
0 = 1200 3 = 9600 1 = 2400 4 = 19200 2 = 4800 5 = 38400
826 Adr.S 1 1 0 31 0 P24
827 Adr.S 2 1 0 31 2 0 P24
Display
831 Helligkt 1 0 6 5 P25
0 = 100 % … 6 = 13 %
832 DispOFF 1 0 65535 15 P26
833 Sprache 1 0 6 0
0 = German 4 = Swedish 1 = English 5 = 2 = French 6 = Dutch
3 =
838 Int.L.AU 1 0 999 200
839 LastTotb 1 0 15 10 P14
850 1 0 3 0 P55
851 1 0 3 0 P55
Power output of burner with curve set
Power output of burner with curve set
Power output of burner with curve set
Power output of burner with curve set
Baud rate of serial interfac
Baud rate of serial interface
Network address VMS / FMS se
Network address VMS / FMS ser.
Brightness of display in steps
Display switch-off time in minutes (0 = none) i.e., time after operation until switched back to lowest brightness level
Selection of language display
not assigned
not assigned
Value of internal load in AU mode (for external power display)
Dead band definition +/- this value does not alter load
Represented unit
steam,
rev speed, quantity
Represented unit channel 2
e 1
r. 1
Einh. Kan.1 channel 1
0 = digits 2 = pressure, 1 = °C (temp.) 3 = mA
Einh. Kan.2
27
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
852 1 0 3 0 P55
853 1 0 3 0 P55
854 1 0 3 0 P55
860 1 0 999 0 P55
861 1 0 999 0 P55
862 1 0 999 0 P55
863 1 0 999 0 P55
864 1 0 999
0 P55
871 1 0 999 0 P55
872 1 0 999 0 P55
873 1 0 999 0 P55
874 1 0 999 0 P55
880 1 0 3 0 P55
881 1 0 3 0 P55
882 1 0 999 0 P52
883 1 0 999 0 P52
0 P52
0 P52
Einh. Kan.3
Einh. Kan.4
Einh. Kan.5
R4mA K1
R4mA K2
R4mA K3
R4mA K4
R4mA K5
R20 mA K2
R20 mA K3
R20 mA K4
R20 mA K5
Einh. K01
Einh. K02
4mA KOK 1
4mA KOK 2
884 20mA KOK 1 1 0 999
885 20mA KOK 2 1 0 999
Represented unit channel 3
Represented unit channel 4
Represented unit channel 5
4 mA feedback corresponds to x units channel 1
4 mA feedback corresponds to x units channel 2
4 mA feedback corresponds to x units channel 3
4 mA feedback corresponds to x units channel 4
4 mA feedback corresponds to x units channel 5
20 mA feedback corresponds to x units channel 1
20 mA feedback corresponds to x units channel 2
20 mA feedback corresponds to x units channel 3
20 mA feedback corresponds to x units channel 4
20 mA feedback corresponds to x units channel 5
Represented unit correction input 1
Represented unit correction input 2
4 mA feedback correspond to X of correction input 1
4 mA feedback correspond to X of correction input 2
20 mA feedback correspond to X of correction input 1
20 mA feedback correspond to X of correction input 2
0 P55
870 R20 mA K1 1 0 999
28
Settings List of Parameters
(Level 0 and 1 parameters only)
Para- Short Safety Lower Upper meter- design- level limit limit Standard No. nation Description values Aids
_____________________________________________________________________________________________________
1 P30
897 O2Stoer 1 0 2 O
2
0 P31
898 O2-TotZ 0 3 20 15 P32
899 O2-P-Fak 0 1 50 O P-factor 5 P32
2
900 O2 TZ - 0 0 5 O
2
3 P32
901 O2Neutr1 1 0 1000 Correction value output on deactivated
O regulation. Fuel 1 300 P31
2
902 O2Neutr2 1 0 1000 Correction value output on deactivated
O regulation. Fuel 2 300 P31
2
903 O2FWZeit 1 0 9999 O deactivated after fuel
2
change in sec.. 30 P33
904 O2WarteZ 1 0 9999 O regulation active after
2
ignition in sec. 90 P34
910 O2Totbnd 2 0 10 O lag band in 0.1% 2
2
914 O2Aktiv 0 0 999 Activate O regulation from
2
load position X (in pts) 0 P35
915 O2Deakti 0 0 999 Deactivate O regulation from
2
load position X (in pts) 999 P35
917 LftmKor1 1 0 999 Air shortage correction value, fuel 1 150 P31
918 LftmKor2 1 0 999 Air shortage correction value, fuel 2 150 P31
919 O2 4mA 1 0 999 O value 4mA 0 P36
2
920 O2 20mA 1 0 999 O value 20mA 250 P36
2
931 O22UBU1G 1 0 250
100 P37
932 O22UBU1V 1 0 250
100 P37
933 O22UBU2G 1 0 250
100 P37
934 O22UBU2V 1 0 250
100 P37
936 O2SOWert 0 0 65535 2 P38
Parameter for O regulation
2
896 O2Regler 0 0 9 O -Regulator
2
0 = O regulator off 8 = Only display, base value
2
1 = Standard regulator for deact. O regulator
2
2 = Without lag time 9 = Only display, base value 3 = only display for air shortage neutral value
Error shut-down by regulator permitted (0=No, 1=on air shortage)
Lag time of the O regulation section
2
Lag time shortening of the regulation section with full load
Lower 2nd monitoring band, fuel 1 in % of target value, base load
Lower 2nd monitoring band, fuel 1 in % of target value, full load
Lower 2nd monitoring band, fuel 2 in % of target value, base load
Lower 2nd monitoring band, fuel 2 in % of target value, full load
Probe dynamic test
29
30
Leakage Test Mode of Operation
Integrated Leakage Test (option)
Leakage test flow chart
Integrated leakage test The leakage test checks whether the main gas valves are leak-tight. (option) The supply gas pressure is used for this purpose. Since the leakage test line
(space between the two main valves) burns empty in the event of a shut-off, this part is normally pressureless when starting (gas pressure > min. = 0). The FMS checks this. Main gas 1 is then briefly opened and gas flows into the test line (gas pressure > min. changes from 0 to 1). This pressure must then subsist for 30 seconds. The leakage test is then deemed to be completed. If the leakage test line is not empty at the start (e.g. as a result of a fault shut­off previously), main gas valve 2 is opened first. The leakage test line is thus vented (into the combustion chamber or over the roof, depending on the system, for suggested circuit see next page). A check is then conducted to see whether the line remains pressureless for 30 seconds. Otherwise the procedure is as described previously.
The leakage test can be performed before ignition and/or after shut-off. Selection via parameters.
The pressure monitor for the leakage test line must be connected to "Gas pressure >min” input (terminal 73). It also monitors the minimum pressure during operation. If another minimum pressure is to be monitored during operation, however, the pressure monitor is, for this purpose, to be looped into the gas safety interlock circuit.
The test line, however, must be designed so as to ensure that the test time of 30 sec. per valve is sufficient to reliably detect a leak of 0.1% of the fuel gas
3
consumption at maximum firing heat output, but at least 50 dm /h.
Flow chart
Start
Leak Test
Leak
test line
under pressure
Gas > min = 1
Gas valve 1
(gas line side)
open for 2 sec.
Yes
Yes
1
1
1
1
Pressure
drops again
1
No
No
No
Pressure rises again
No
Wait 30 sec
and
test pressure
Leak test
successfully
completed
Leak
test line
pressureless ?
Gas > min = 0
Leak
test line
pressureless ?
Parameter
770 = 1
Wait 30 sec
and
test pressure
Fault shut-off
1
Gas valve 2
(burner side)
open for 2 sec.
Yes
Yes
Loading...
+ 132 hidden pages