Lamtec F130I User Manual

Manual
Flame Monitoring Device
F130I
Sensors and Systems for Combustion Engineering
www.lamtec.de

Table of Contents

Table of Contents
1.1 Purpose/Applicability of the Document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Safekeeping of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Target Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 General Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Classification of the Safety Instructions and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Product-specific Dangers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4 Mounting Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.5 Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.6 Information about connecting the flame sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3 Product Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Proper Use - Conditions of Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Life Cycle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Rating Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Design and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.1 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
4.2 Flame Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.3 Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.4 UL Listed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.5 Control Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1.1 Safety When Putting the Device Into Operation . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2 Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.1 Electrical Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
5.2.2 Installation and positioning of the optical flame sensor . . . . . . . . . . . . . . . . . . . 23
5.2.3 Aligning the optical flame sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.2.4 General information about ionisation flame monitoring . . . . . . . . . . . . . . . . . . . 24
5.2.5 Positioning of the ionisation electrode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3 Putting the Device into Operation for the First Time . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3.1 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3.2 Acceptance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.1 Maintenance Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Customer Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.3 Warranty and Delivery Terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7 Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
8 Correcting Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.1 Fault Finding and Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
8.2 Information About the Repair Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
9 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10 Disposal Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2
Table of Contents
11 Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.1 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.1.1 F130l evaluation device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
11.2 Connecting Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
11.2.1 F130I connection diagram 230V device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
11.2.2 F130I connection diagram 120V device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.2.3 Application Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
11.2.4 F130I terminal connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
11.3 List of Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
11.4 Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
11.5 Order Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3

1 Important Information about the Manual

1 Important Information about the Manual

1.1 Purpose/Applicability of the Document

These instructions facilitate the safe and efficient handling of the flame monitor consisting of the evaluation device F130l and the approved flame sensors in the flame sensors chapter 4.2
Flame Sensors
The specifications in the document refer to the following device version:
SW: 1.2.0.0
HW: 1.0.0.0 If you utilise a different version, this can lead to other effects to your device than those de-
scribed here. The flame monitor F130I complies with the following standards and directives:
DIN EN 298:2012
DIN EN 60730-2-5:2015
DIN EN 50156:2016, chapter 10.5
DIN EN 746-2:201 1 (Industrial thermoprocessing equipment – Part 2: Safety requirements for combustion and fuel handling systems)
DIN EN 61508:2011, Ed.2 Part 2 (Requirements SIL 3)
DIN EN 60730-1:2012
DIN EN 50581:2013
2014/68/EU (Pressure Equipment Directive)
2009/142/EC (Gas Appliances Directive)
EU/2016/426 Gas Appliance Regulation (GAR)
2014/35/EU (Low Voltage Directive)
2014/30/EU (EMC Directive)
2011/65/EU (RoHS2 Directive)
UL372 (in preparation)

1.2 Safekeeping of the Manual

Look after the manual and all the associated documents carefully. The manual is part of the product and must be kept safe and be accessible to personnel at all
times. Moreover, it is important that the manual:
Is available when required.
Is kept for the entire service life of the device.
Is available to its next operator.
4
1 Important Information about the Manual

1.3 Target Group

These instructions must have been read carefully and completely before commencing with any work. The basic prerequisite for working safely is compliance with all the specified safety instructions.
NOTICE
All assembly , commissioning, troubleshooting and maintenance work may only be carried
out by authorised and trained personnel.
The device may be operated and maintained only by those who are capable of doing so
in terms of their level of knowledge and training.
Opening the devices is not permitted under any circumstancesFor safety reasons, access to parameterisation must be restricted to authorised
personnel.
5

2 General Safety Instructions

2 General Safety Instructions

2.1 Classification of the Safety Instructions and Warnings

The following symbols are used in this document to draw the user's attention to important safe­ty information. They are located at points where the information is required. It is essential that the safety information is observed and followed, and that applies particularly to the warnings.
DANGER!
This draws the user's attention to imminent danger. If it is not avoided, it will result in death or very serious injury. The plant including its surroundings could be damaged.
WARNING!
This draws the user's attention to the possibility of imminent danger. If it is not avoided, it may result in death or very serious injury. The plant including its surroundings could be damaged.
CAUTION!
This draws the user's attention to the possibility of imminent danger. If it is not avoided, it may result in minor injuries. The plant including its surroundings could be damaged.
NOTICE
This draws the user's attention to important additional information about the system or system components and offers further tips.
The safety information described above is incorporated into the instructions. Thus, the operator is requested to: 1 Comply with the accident prevention regulations whenever work is being carried out. 2 Do everything possible within his control to prevent personal injury and damage to prop-
erty.
6
2 General Safety Instructions

2.2 Product Safety

WARNING!
This product is state-of-the-art technology and complies with the generally accepted safety-related rules and regulations. Every device is tested before delivery to ensure that it is working properly and safely.
Only use this product when it is perfect condition and in accordance with the manual, the
prevailing regulations and guidelines and the applicable safety and accident prevention regulations.
WARNING!
The risk of danger in the event of external fire, traffic and wind, flood waves and earthquakes depend on the installation situation and the installation site to be assessed separately where appropriate.
7
2 General Safety Instructions

2.3 Product-specific Dangers

Electrical coupling with devices that are not mentioned in these instructions may only occur after consulting with LAMTEC or with an expert.
WARNING!
The Gerät is not provided with a direct switch-off of the fuel valves. The subsequent signal processing must be carried out in the control system, which is
adapted to suit the combustion plant.
The device may only be used with burner controllers that work according to DIN EN 298.
NOTICE
This product is state-of-the-art technology and complies with the generally accepted safety­related rules and regulations. Every device is tested before delivery to ensure that it is working properly and safely.
Only use this product when it is perfect condition and in accordance with the manual, the
prevailing regulations and guidelines and the applicable safety and accident prevention regulations.
WARNING!
The F130I is a safety device. Only specialist staff of the manufacturer or people approved by the manufacturer may intervene. No interventions by anyone else are permissible. This ap­plies, in particular, in the event of a defective fuse.
WARNING!
Please observe the safety instructions to avoid personal injury and damage to property and the environment!
Qualified specialist staff are required to carry out all activities (assembly, installation, ser-
vicing, etc.).
When installing the electrical accessories, do everything necessary to provide shock pro-
tection.
Make sure that the power cables are not interchanged between L and N.The plug connectors X13, X14, X15 and X16 do not have a secure disconnection from the
mains voltage. To replace or disconnect the plug connectors, all poles of the plant must be disconnected from the mains.
To ensure the electrical safety, the flame signal output and the alarm relay output on X11
must be supplied with the same potential.
Measuring circuits must feature a secure disconnect according to
EN 61140 "Protection against electric shock ..." for active parts; for this reason, use only measurement and evaluation devices which have a double or reinforced insulation.
After each activity (e.g. assembly, installation, servicing, etc.), check the wiring and para-
metrisation to make sure it is in good working condition.
If the equipment is dropped or suffers impact, you should no longer commission it. The
safety functions may also be impaired but fail to show any obvious external damage.
The manufacturer of the burner or boiler ensures that the protection class/category IP40
or IP54 (for outdoor use) is achieved for the F130l during installation or where applicable
8
2 General Safety Instructions
the requirement for enclosure type 3 (NEMA). The device is designed for installation in switch cabinets.
These operating instructions describe many possible applications and functions and
should be used as guidelines. Carry out functional tests on the test bench and/or in the plant application to ensure correct functioning and document the results.
Check all safety times during the commissioning.In order to provide for operating safety , make sure when installing the output contacts that
the circuitry of the radio interference suppression to be provided by the user is carried out in such a way that there is no risk of shorting out the relay contact output (flame signal) by defective component parts of the suppressor circuitry.
NOTICE
Follow the additional instructions to guarantee safety and reliability when working with the F130l:
Prevent effects of condensation and humidity . If necessary , make sure that the installation
is sufficiently dry before you switch it on.
Avoid static charge because This is has a destructive effect when it comes into contact
with the device's electronic components
Ensure that the maximum permitted operating temperature (refer to this in table 11.1
Technical Data), particularly due to radiant heat, is not exceeded at the installation loca-
tion.
Take action to ensure sufficient cooling.
NOTICE
LAMTEC recommends that you use ESD equipment when working on the electrics/electron­ics!
9
2 General Safety Instructions

2.4 Mounting Notes

NOTICE
Please observe the following warnings to avoid personal injury and damage to property and the environment:
Compliance with national safety regulations and standards is required at all times.Note that approvals for accessories, in particular the optical flame sensor, are not part of
the approval of the F130I.
During the assembly and installation process, you must meet the requirements of stand-
ards DIN / VDE 0100, 0550 and DIN / VDE 0722.
Although the device exceeds the requirements of the applicable EMC standards, in some
cases by a considerable amount, proper wiring is the prerequisite for ensuring that the de­vice and thus the entire plant operates without problems in all cases.
Run the sensor connection cable including its extension physically separate from the
mains and control cables (do not run them parallel to each other).
Avoid running sensor cables near the following components:
- ignition cables
- ignition transformer and electric motors
- contactors resp. switches and frequency transformers, which switch high inductive or capacitive loads.
Run the supply and signal cables of the flame monitor physically separated from each
other. Take measures to prevent short circuits between the cables.
10
2 General Safety Instructions

2.5 Installation Notes

WARNING!
Please observe the following warnings to avoid personal injury and damage to property and the environment:
Tighten the screw terminals of the F130l using a sufficient tightening torque.Supply the feed cable with L, N and FPE only. The neutral conductor may not have any
potential difference to FPE.
Phase and neutral conductors may not be interchanged (this would lead to dangerous
malfunctioning, loss of protection against contact, etc.).
The supply cable of the F130l must absolutely be fused with a 4A (slow) fuse.
The minimum fusing amounts to 0.5A.
The strain relief for the connected cables must comply with standards (e.g. according to
DIN EN 60730 and DIN EN 60335).
Make sure that no spliced strands can come into contact with any of the adjacent connec-
tions. Use appropriate end sleeves.
Before working in the connection area, switch off the power supply to the plant from all
poles. Ensure that it cannot be switched back on and that the plant is voltage-free. There is a risk of electric shock when the plant is not switched on.
The device may only be opened by qualified personnel. Disconnect the device from the
supply voltage at all poles before opening.
Apply shielded cables directly (without any intermediate terminals if at all possible). If in-
termediate terminals are necessary , take the shortest route to applying the shielding to the terminal.
Avoid long connecting wires without shielding.In order to provide for operating safety make sure when installing the output contacts that
the circuitry of the radio interference suppression to be provided by the user is carried out in such a way that there is no risk of shorting out the relay contact output by defective com­ponent parts of the suppressor circuitry.
11
2 General Safety Instructions

2.6 Information about connecting the flame sensor

WARNING!
It is important that signal transmission be as free of interference and loss as possible
Do not lay the sensor lead with other leads – lead capacities decrease the size of the flame
signal – use a separate cable.
Observe the permitted length of the sensor leads.The mains-operated ionisation flame sensor is not protected against contact but does
need to be protected against accidental contact.
Earth the burner as prescribed in the regulations – it is not enough to earth the boiler on
its own!
Position the ignition electrode and the ionisation flame sensor where the ignition spark
cannot arc over to the ionisation flame sensor (risk of electrical overloading)
Make sure that the functional earth ground (FPE) is connected properly. A missing or in-
correctly connected cable will not be able to protect the ionisation input in the event of a malfunction or from external overvoltage and other EMC influences.
Depending on the flame sensor input, only one sensor each may be connected.Please observe the requirements and specifications of the flame sensor manufacturer.
12

3 Product Description

3 Product Description
The flame monitor F130l is a safety device for the monitoring of flames (ignition or main flame) using the ionisation method. In addition, it is also possible to connect it to optical sensors.
The flame monitor is used in combustion plants to record the burner flame in the combustion chamber and signal the flame signal to the downstream burner control system by means of a safety-oriented, potential-free relay output.
1 F130I housing 2 LED display 3 Device connector 4 Top-hat rail mounting

3.1 Proper Use - Conditions of Use

The flame monitor is preferably intended for use in stove systems. The evaluation device may only be operated with the flame sensors approved in 4.2 Flame Sensors. The monitoring of the following fuels is possible:
Fuel Ionisation Optical Oil - X Gas X X Biomass - X Solid matter (wood, powdered coal...) - X Chemical and other waste products - X Combined fuels - X
The flame scanner is not designed to switch off the fuel valves. The subsequent signal pro­cessing must be carried out in the control system, which is adapted to suit the combustion plant.
Please observe the following information when operating the flame monitor:
The safety information in this manual
Chapter 11.1 Technical Data in this manual. Any other usage going beyond this is considered to be improper use. The plant operating com-
pany is liable for any damages that resulting from this.
13
3 Product Description

3.2 Life Cycle

The device is designed to have a service life of Gerät 10 years or 250,000 cycles. The obser­vations about likelihood of failure are based on these values.
The actual service life of the Gerät depends on the ambient temperature among other factors. In particular, operation at high temperatures reduces the actual service life.
The design service life applies for a use of the device in accordance with the specifications of the documentation. The device must be replaced by authorised personnel when the service life with regard to the number of burner cycles or the corresponding usage time has been reached.
Please observe the specified duration of service for the flame sensor. These can be found in the specifications of the respective manufacturer.

3.3 Rating Plate

Type plate example:
NOTICE
The flame monitoring device is only available in the 120V version with UL approval.
UL approval in preparation
14

4 Design and Functions

4 Design and Functions

4.1 Design

Fig. 4-1 Flame monitoring
The flame monitor consists of the F130l evaluation device and the flame sensors from chapter
4.2 Flame Sensors The F130l evaluation device is connected by pluggable screw terminals. The following connection terminals are available:
Supply of auxiliary power (mains voltage)
Connection for LDR sensor
Connection for ionisation electrode
Connection for UV tubes
Measurement output for ionisation current measurement
0/4..20mA analogue output for flame intensity
Alarm relay output
Flame signal output The arrangement of the control and operating elements is shown in chapter 4.5 Control Ele-
ments. The connection and terminal connection diagram can be found in chapter 1 1.2 Connecting Di-
agrams.
15
4 Design and Functions

4.2 Flame Sensors

The evaluation device has three flame sensor inputs:
Ionisation input (ION)
UV input
LDR input
The sensor inputs can be used individually or in combination. If one of the flame sensors de­tects a flame, the flame relay output is switched on and flame signalled.
Depending on the spectral sensitivity of the flame sensors, these are differently suited for spe­cific fuels. The following table lists all approved flame sensors for the device and their appli­cation areas.
The suitability of the device types may differ from that indicated in the table depending on par­ticular circumstances.
Sensor type
QRA2 /2M Siemens UV tubes UV Gas / oil No 190...270 nm normal
QRA4.U QRA2 housing
QRA10/ 10M
QRB1A Siemens LDR,
QRB1B
QRB1C*
QRB3 / 3S MZ770S* Satronic/
Ionisation electrode
Manufac­turer
Honeywell
-
Sensor type
visible
LDR, visible
Ionisation ION Gas Yes
F130I input For fuel Con-
tinu­ous opera­tion
LDR Öl No
LDR Öl No 400 … 800nm
Wavelengths range
450…800nm
Comment
Sensitivity m ... high Sensitivity
version QRA2 housing
versionm … high sensitivity
normal Design
sensitive design
high-sensitivity design
S ...high sensitivity
-
--
NOTICE
Observe the respective national approvals of the flame sensors, e.g. exists for * no UL ap­proval.
NOTICE
LAMTEC guarantees that the flame monitor is in perfect working order but cannot offer any guarantees if it is used improperly.
Continuous operation capability is provided only for sole use of ionisation electrode. When
connecting a UV/LDR sensor the F130I should be used for intermittent operation.
Please observe the specific requirements of your plant when selecting the flame monitor.
We will be pleased to answer any questions you may have about LAMTEC products.
16
4 Design and Functions

4.3 Functional Description

Flame monitoring
The flame sensors listed in chapter 4.2 Flame Sensors are intended for connection to the flame sensor inputs. Depending on the flame sensor, dif ferent properties of the flame are used in order to determine the status of the flame as well as its intensity and to convert it into elec­trical signal that can be evaluated. Thus, the ION input utilises the rectifying property of the flame, the UV tubes on the UV input the ultraviolet (UV) radiation and the LDR input the radiant energy of the visible light spectrum. The connection of the flame sensor is approved individu­ally or in combination, whereby the evaluation device F130l reports a flame as soon as one of the inputs detects a flame. The evaluation of the flame signals and the enabling of the flame relay output is 2-channel. The flame signal is reported via a safety-oriented, potential-free re­lay output.
Self-monitoring function
The correct functioning of both processing channels is monitored by a separate monitoring unit. The output relays are switched off by this in the event of a fault and the fault relay is switched on.
Status information
One LED display , as shown in chapter 3 Product Description, indicates the state of the flame monitor. The following LEDs are present:
LED Explanation
PWR Green
ON - device voltage present
ERR Red
ON - device starting
OFF - fault-free operation
Flashing 1 Hz - fault
FSB Yellow
No function
0 Red
flame OFF
1 Green
flame ON
Flame intensity output
The flame intensity is provided by a parametrisable 0/4...20 mA analogue output (current loop) as not error-free information. The following variables of the flame sensor are utilised here:
ION input- 0..30 ADC ionisation current >= 1 A Flame ON
UV input- 0..100% flame intensity > 75 % Flame ON
LDR input- 0..100% flame intensity > 15% Flame ON The parametrisation on the 0..20 mA or 4..20 mA output is possible via the configuration
switches inside the device or the FSB communication interface. Please refer to chapter 4.5 Control Elements for the assignment of the configuration switches.
If the flame sensor inputs are activated simultaneously, the following priority order for the in­tensity output on the analogue output applies:
17
4 Design and Functions
1 ION 2 LDR 3UV The amount of the ionisation current can also be determined via a shunt measuring principle
using a multimeter. The measured voltage is to be converted as follows into the ionisation cur­rent:
10 mVDC = 1 ADC
WARNING!
Both analog outputs have mains voltage reference. Protecting against contact is to be noted.
Measuring circuits need to hazardous active parts safe isolation to EN 61 140 "Protection
against electric shock ..." have, so please only use measurement and Evaluation units which have a double or reinforced insulation.

4.4 UL Listed

In preparation
NOTICE
For applications within the scope of the UL Listed certification procedure, it must be ensured that the components used are "Listed" certified. That is, in addition to the flame detector used must also be the connection cable and if used the power supply "Listed" certified. The applicable installation rules according to NFPA70 (NEC) must be observed.
18
4 Design and Functions

4.5 Control Elements

Configuring the device via configuration switches
There are 8 DIP switches inside the F130l for making parameter settings to the device.
WARNING!
Observe the safety instructions when working on the housing.
Fig. 4-2 Opening the housing
NOTICE
To open the housing, first remove all connectors. Then using a flat, pointed object (e.g.
screwdriver) carefully pry off the upper cover of the housing (see figure).
WARNING!
When opening the housing there is direct access to dangerous parts.
Opening the device is permitted only with all-pole disconnectionWhen closing, make sure the cover is seated flush with the housing and that all detent
points firmly fixed. If the cover is not mounted properly , it can have a negative influence on the mechanical and electrical properties of the product.
19
4 Design and Functions
To activate the configuration switches UP1 to HP3, switch HP4 must be set to 1.
Fig. 4-3 DIP switches on the F130l
The following settings can be made using the configuration switches:
Switch no. Setting
UP 1 No Function UP 2 free UP 3 Selection FFDT
1 - FFDT 1 s in combination with HP 3 - 0
0 - FFDT 3 s in combination with HP 3 - 1 UP 4 free HP 1 Mode current loop
1 - 4..20 mA active
0 - 0..20 mA active HP 2 free HP 3 Selection FFDT
0 - FFDT 1 s in combination with UP 3 - 1
1 - FFDT 3 s in combination with UP 3 - 0 HP 4 DIP switch enable
1 - DIP switch active/parametrisation via FSB inactive
0 - DIP switch inactive/parametrisation via FSB active
NOTICE
Set the FFDT parameters by a combination of HP3 and UP3 switches before commissioning. The device must be disconnected from power while setting the parameters. Setting the FFDT parameters during operation is not permitted. A non antivalent switch position causes a safety shutdown. Follow the safety instructions in chapter 2
20

5 Commissioning

5 Commissioning

5.1 Safety

5.1.1 Safety When Putting the Device Into Operation

WARNING!
Observe the safety instructions from chapter 2.
Disregard for these safety instructions can result in severe injuries or significant physical dam­age.
DANGER!
Danger if shock protection is not provided
There is a risk of death or very serious injury from electric shock. When installing the electrical accessories, do everything necessary to provide shock pro-
tection.
NOTICE
Exceeding the maximum permissible operating temperature
Ensure that the maximum permitted operating temperature (refer to this in table in chapter11.1 Technical Data), particularly due to radiant heat, is not exceeded at the installation location.
Take action to ensure sufficient cooling.
NOTICE
Laying of cables
Warning to avoid damage to property Lay the connecting cable including its extension apart from the mains and control cables
(don't lay them parallel to each other).
Avoid laying cables near the following components:
- ignition cables
- ignition transformer and electric motors
- contactors resp. switches and frequency transformers, which switch high inductive or ca­pacitive loads.
Although the device exceeds the requirements of the applicable EMC standards, in some
cases by a considerable amount, proper wiring is the prerequisite for ensuring that the de­vice and thus the entire plant operates without problems in all cases.
21
5 Commissioning
NOTICE
Shielding/extension of connecting cables
Warning to avoid damage to property
Apply shielded cables directly (without any intermediate terminals if at all possible).If intermediate terminals are necessary, take the shortest route to applying the shielding
to the terminal.
Avoid long connecting wires without shielding.Use a separate, shielded extension cable to implement an extension on site.
NOTICE
High electromagnetic interference
Excessive electromagnetic interference can lead to sporadic problems with flame detection and even prevent it.
In individual cases, a connection between device ground and functional earth ground
(FPE) can remedy this.
NOTICE
EMC emission testing
It was ascertained during the type test that the device meets the EMC emissions require­ments. A separate EMC emissions test is not necessary after installation.

5.2 Setup

The following sections provide information on:
What prerequisites have to be met to install the product properly
How you have to position the product
How you have to secure the product

5.2.1 Electrical Connection

You can find connection and terminal connection diagrams in the appendix, 11.2 Connecting Diagrams
NOTICE
A conversion to the respective mains frequency is not necessary.
The device functions in the frequency range specified in chapter 11.1 Technical Data.
22
5 Commissioning

5.2.2 Installation and positioning of the optical flame sensor

Observe the following points when installing and positioning the optical flame sensor:
NOTICE
Mounting location
Ensure that the mounting location is easily accessible. During operation of the combustion
plant, you should have the possibility to check the alignment of the flame monitor.
Ensure that the burner flame is clearly visible in the entire "colour range of the combustion
plant" for the optical flame sensor.
NOTICE
Mounting the device using a holder
If at all possible, mount the optical flame sensor to the burner/boiler viewing opening using
a holder optimised by LAMTEC for use with flame sensors.
The flame sensor is now mounted. Please observe the following instructions about aligning the optical flame sensor.

5.2.3 Aligning the optical flame sensor

Observe the following points when aligning the optical flame sensor:
In the axially parallel arrangement, it can be difficult to detect that the flame has gone out. Avoid aligning the flame sensor in an axially parallel arrangement with the flame.
The correct positioning (alignment) of the flame sensor is decisive for a high availability and achievable selecting quality

5.2.4 General information about ionisation flame monitoring

Observe the following items for ionisation flame monitoring:
The functionally secure monitoring of a gas flame will be achieved when the flame moni­toring is able to be optimally adapted according to the conditions of the gas-fired genera­tion plant.
Take into account that with the ionisation method, the flame and burner are also utilised as part of the electrical conducting circuit for the formation of an optimal ionisation DC cur­rent, therefore, it is essential that the boiler and burner be grounded properly.
Fuel, burner setting and the arrangement of electrodes are crucial for the amount of the achievable ionisation DC current.
The ionisation DC current also increases with the heating value of the gas. The require­ment for the formation of optimal values is provided if "based on the setting of the burner":
a "rigid" flame arises, – the burner is operated with a low excess of air so that an optimal combustion arises.
23
5 Commissioning

5.2.5 Positioning of the ionisation electrode

Observe the following points when positioning the ionisation electrode (lance):
Select a position so that the sensor electrode as well as the counter electrode (burner noz­zle possibly with additional electrodes for increasing the effective area) remain in contact with the flame in the entire control range of the burner.
The sensor electrode should immerse into the hot part of the flame, however, the temper­atures prevailing there should not exceed the lance specifications.
To check the optimal electrode position, the ionisation DC current is measured via the shunt measuring principle at X14 or the 0/4..20mA output on terminal X14. For further in­formation, see chapter 4.3 Functional DescriptionFlame intensity output.
24
5 Commissioning

5.3 Putting the Device into Operation for the First Time

5.3.1 Requirements

WARNING!
Observe the safety instructions in chapter 2. Disregard for these safety instructions can result in severe injuries or significant phys­ical damage.
Initial start-up requirements:
The F130l evaluation device, as well as the corresponding flame sensor are mounted ac­cording to the specifications from chapter 5.2 Setup.
The flame sensor is positioned according to the specifications from chapter 5.2.3 Aligning
the optical flame sensor5.2.5 Positioning of the ionisation electrode
All electrical installations must have been tested.
All terminal and plug-in connections must have been tested.
The parameterization of the FFDT via the DIP switches was carried out according to chap­ter 4.5 Control Elements
NOTICE
Putting the device into operation
T o ensure a safe operation of the flame monitor , comply with the following sequence when
placing into operation for the first time:
Switch off the burner
Check the positioning of the flame sensor resp. the ionisation electrode again to make sure it is correct. Take the information given in chapter 5.2.3 Aligning the optical flame sensor5.2.5 Positioning of the ionisation electrode into account.
Check the proper parameterization of the FFDT via the DIP switches, according to chapter 4.5 Control Elements
The ionisation current and the flame intensity can be determined at terminal X14. For fur­ther information, see chapter 4.3 Functional DescriptionFlame intensity output.
The device is operationally ready approx. 10s after switching on the supply voltage. The operational readiness is indicated by the LEDs, as described in chapter 4.3 Functional De- scription.
The F130l must signal "Flame off". To do this, observe LEDs and switch state of the flame relay output at X11.
Switch on burner and preferably bring to base load.
Now position the ionisation electrode resp. the optical flame sensor optimally . A change of the position can influence the monitoring properties of the flame monitor.
The F130l must signal "Flame on". To do this, observe LEDs and switch state of the flame relay output at X11. The flame intensity resp. the ionisation current must also be checked. This must be stable over the entire working range of the system.
Switch-off test Simulate the flame going out or "tearing off". To do this, shut off the fuel supply of the burner being monitored by the flame sensor. Check that after the extinguishing of the flame in the safety time parameterized according to chapter 4.5 Control Elements, the
25
5 Commissioning
flame relay output opens and the signal to close the safety shut-off valve has triggered. The shut-off test in the relevant power range and all relevant operational modes of the fir­ing must be carried out.
For each change of the position or configuration of the flame monitoring, the switch-off
time must be reverified.

5.3.2 Acceptance

NOTICE
Obligation to provide evidence
Due to the obligation to provide documentary evidence to testing authorities, for quality man­agement systems or to clarify liability issues and so on, we urgently recommend that you doc­ument your checks of the parameter settings. This documentary evidence can be included in the burner's settings log.
WARNING!
26

6 Maintenance

6 Maintenance

6.1 Maintenance Tasks

NOTICE
The F130l evaluation device is maintenance-free.
However, you should at intervals – that depend on the operating conditions of the plant – clean the aperture of the flame sensor and the associated viewing opening on the furnace.
NOTICE
The service life of the flame sensor is limited. Refer to the manufacturer's specifications for the respective service life of the flame sensor. An operation of the flame monitor outside of its specification is not permitted. Replace faulty or aged flame sensors with new ones of the same type.
Observe the following general information:
The isolation of the ionisation electrode is subject to a contamination and the electrode a loss of contact material. Clean the ionisation sensor at regular intervals and check for an unpermitted loss of contact material (burn-up).
The optical sensors age and are subject in part to high environmental influences. There­fore, clean the sensors at regular intervals and check for proper functioning.
Perform the following activities to the system during regularly scheduled maintenance:
Check of all electrical plug connections.
Place burner into operation.
Check flame monitor for proper function.
Check reaction time for flame failure (switch-off test) analogue to commissioning. Is there a correct switch-off within the safety time parameterized according to chapter
4.5 Control Elements ?
Create a log for the measurements and tests that have been performed. This must also be confirmed by signature of the operator, if necessary.

6.2 Customer Service Information

Please contact LAMTEC Service/Support if you have any questions.
LAMTEC GmbH & Co.KG Sensors and Systems for Combustion Technology
Wiesenstraße 6 D-69190 Walldorf Hotline: +49 (0) 6227 / 6052-33 email: support@lamtec.de
27
6 Maintenance

6.3 Warranty and Delivery Terms

The manufacturer's warranty conditions apply. Warranty claims are refused if changes have been made to the flame scanner or it has been interfered with in any way during the warranty period.
The device is shipped as specified in the purchase order information. LAMTEC's terms and conditions of delivery and service and the general terms and conditions of delivery and service of the electrical and electronic engineering industry apply.
28

7 Repairs

7 Repairs
WARNING!
Observe the safety instructions in chapter 2. Disregard for these safety instructions can result in severe injuries or significant physical damage.
When replacing the F130l or a flame sensor, it must be replaced by a device with the same identification information.
Perform the following activities after replacing an evaluation device or a sensor:
Check all electrical plug connections.
Place burner into operation
Check flame monitor for proper function
Check reaction time for flame failure (switch-off test) analogue to commissioning.
Is there a correct switch-off within the safety time according to chapter 4.5 Control El- ements ?
Create a log for the measurements and tests that have been performed. This must also be confirmed by signature of the operator, if necessary.
29

8 Correcting Faults

8 Correcting Faults

8.1 Fault Finding and Troubleshooting

There is a fault present if the "ERR LED" flashes or lights up continuously. In the event of a fault, the alarm relay output is closed.
A fault is not reset automatically . To reset a fault, the device supply must be disconnected. To do this, disconnect the F130l for at least 5 seconds from the mains and then switch it on again.
NOTICE
Check the settings and connections
Check the input and output terminals of the flame monitor for proper configuration and
connection.
Check inputs and outputs for short-circuit and interruptions.
NOTICE
Permanent fault
If a fault cannot be reset, please contact the LAMTEC maintenance and repair department
for assistance.
Only the maintenance and repair department may perform repairs.

8.2 Information About the Repair Service

Please contact LAMTEC Service/Support if you have any questions.
LAMTEC GmbH & Co.KG Sensors and Systems for Combustion Technology
Wiesenstraße 6 D-69190 Walldorf Hotline: +49 (0) 6227 / 6052-33 email: support@lamtec.de
30

9 Decommissioning

9 Decommissioning
Put the plant in the safe state in order to decommission it. De-energise the device and its components. Heed the information provided by the burner/boiler manufacturer during disassembly. LAMTEC Leipzig GmbH & Co KG is to be informed of the decommissioning. The type and se-
rial number of the decommissioned device must be provided.
31

10 Disposal Notes

10 Disposal Notes
NOTICE
Improper or inadequate recycling harms the environment. Please observe the regional dispos­al regulations.
The device itself is to be recycled as electronic waste to returned to the burner or boiler
manufacturer.
32

11 Appendix

11 Appendix

11.1 Technical Data

11.1.1 F130l evaluation device

Fig. 11-1 F130I
Fig. 11-2 dimensions F130I
Housing material: Plastic The right to make technical changes is reserved.
Input parameters Auxiliary power/device supply
Supply voltage
1
Factory setting 230 VAC +10 % -15 % or 120 VAC +10 % -20 %
Mains frequency
1
47 Hz ... 63 Hz Power consumption  10 VA Internal device fusing 50 mAT for 230 V device
100 mAT for 120 V device External device fusing
(mandatory)
min. 500 mAT
max. 4 AT
Ionisation input
Supply voltage
1, 2
(Auxiliary power) Device supply voltage Ionisation current from 1 ADC Flame ON Mode Continuous operation capable
1
The product may not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-related functions lose their valid-
ity.
2
The attainable ionisation current at the plant is dependent on the supply voltage. The higher the supply voltage, the higher the sensitivity of the Ionisation lance.
The min. sensitivity of the device of 1 uA is independent on the supply voltage. See also Chapter F130I connection diagram 120 V device.
33
11 Appendix
Input parameters
Connection cable for ionisation electrode < 10 m/32,8 ft
Connection cable for auxiliary power < 3 m/9.8 ft
UV input
Sensor voltage supply (Auxiliary power) > 200 VAC- lead mains potential Permitted external input voltage to
X16/1 for connection of a switch contact Input current in the ON state I Mode Intermittent operation
Connection cable < 10 m/32.8 ft
LDR input
Sensor voltage supply (Auxiliary power)  42 V - lead mains potential Detectable sensor resistance range 220  ... 220 K Flame ON Sensor current  100 A Mode Intermittent operation
Short-circuit detection Yes Connection cable < 10 m/32.8 ft
230 VAC 50/60 Hz
= 100 A
min
Burner restart every 24 h necessary
Burner restart 24 h necessary
Output parameters Output contact status signal
Contact Not safety-oriented, floating contact Contact type NO, in the event of a malfunction, the contact is closed. Protection class SKII, base isolation for the flame signal Permissible switching voltage
1
230 VAC cos   0.3 Contact fusing (internal) 1 AT Specified external contact fusing
1
0.5 AT
Flame signal output contact
Contact Safety-oriented, floating contact Contact type NO, for "flame ON", the contact is closed Protection class SKII, base isolation for the status signal Permissible switching voltage Permissible switching current
1 1
230 VAC 48 VDC
Max. 0.5 A cos  0,4 Min. 10 mA
provide external spark suppression for inductive loads,
do not switch capacitive loads. Contact fuse (soldered) 0.5 AT Safety time (FFDT) Response time in the event
of the flame going out Switch-on time t
t
configurable to 1 s or 3 s (standard 1 s) by using the DIP
V Off
switch
 1 s
V On
Analogue output (current loop) - Leads mains potential not safety oriented Current 0/4 20 mA
34
11 Appendix
Output parameters
Load max. 240 Intrinsic error ± 2 % from 1/3 of the value range Connection cable Connection cable 10 m/32.8 ft must be shielded and
applied one side to FPE.
Shunt measuring
Transmission ratio ionisation current to voltage to be measured
Intrinsic error  2 % Electrical safety Contact protection by means of protective impedances Min. impedance of the connected
measuring device Connection cable < 1 m/3.3 ft
Technical capacity
Connection cross section flexible 0.25 ... 2.5 mm2/24 AWG ... 14 AWG
Mode Continuous operation for:
Safety integrity level DIN EN 61508 Part 2 - SIL 3 Overvoltage category DIN EN 60730-1, ÜK III Susceptibility to interference DIN EN 298 Emitted interference DIN EN 55022, Class B
10 mV (DC) = 1 A (DC)
1 M
rapid 0.20 ... 2.5 mm2/24 AWG ... 14 AWG
Ionisation flame monitoring Intermittent operation for:
Ionisation flame monitoring
Optical monitoring
Environmental capacity
Protection class DIN EN 60529, IP20 Ambient temperature
1
-20 °C +60 °C/-4 °F ... 140 °F
Environmental category D according to GL VI Part 7 Relative humidity 3K5, 5 % ... 95 % as per DIN EN 60721-3-3 Vibration and oscillation GL, VI Part 7, Para. 9, characteristic 1 (0.7g/1.54 lb)
Storage/transport conditions
Storage location Enclosed spaces Air temperature
1
-20 °C +80 °C/-4 °F ... 176 °F
Relative humidity According to DIN EN 60721-3-3:
Transport 2K3, up to 95 %
Storage 1K3, 5 % ... 95 %
Weight approx. 0.5 kg/1.1 lb
1
The product may not be transported, stored or operated outside the specified range. If it is, any guarantees with regard to safety-
related functions lose their validity.
35
11 Appendix

11.2 Connecting Diagrams

11.2.1 F130I connection diagram 230V device

Fig. 11-3 F130I connection diagram 230V device
* FSB currently no funktion
36
11 Appendix

11.2.2 F130I connection diagram 120V device

Fig. 11-4 F130I connection diagram 120V device
*FSB currently no function ** or without transformer, such as 230V device
37
11 Appendix

11.2.3 Application Example

Brahma Type AR1 Series 01
Code 18211002
0,5 VA
Connection via flat connector 6.3 x 0.8 mm
Fig. 11-5 Brahma transformer 120 V Type AR1 Series 01
Connection on F130I
Fig. 11-6 F130I Connection diagram Brahma transformer
*FSB currently no function
38
11 Appendix
Connection of several F130I
Fig. 11-7 Application example F130I Brahma transformer 120V
39
11 Appendix

11.2.4 F130I terminal connection diagram

The sockets have a slot coding. This largely prevents the sockets from being swap.
Terminal Description of
terminal
X23 FSB 1 FSB - Vcc 6
(currently no function)
X13 Mains 1 - 0
X11 Störmeldung 1 Fault output 0
(potential-free) 2 Fault input Flame signal 3 Flame input (potential-free) 4 Flame output
Operation Problem ILSB/FSB Flame OFF Flame ON
PIN Description of PIN Coding
2 FSB - GND 3 FSB - H 4 FSB - L
2N 3 FPE 4L
X14 Ionisation current 1 ION-Measuring - 6
2 ION-Measuring +
Current loop 3 0...20 mA -
4 0...20 mA +
X15 Ionisation input 1 ION-N 1
2 ION-L* 3 Supply Ionisation lance* 4 Ionisation lance
X16 UV-input 1 UV - 0
2 UV +
LDR-input 3 LDR +
4 LDR -
40
11 Appendix

11.3 List of Abbreviations

Abbreviation Explanation
SIL The safety integrity level serves for the assessment (according to IEC 61508) of the elec-
tric/electronic/programmable electronic (E/E/PE) systems in relation to the reliability of safety functions, i.e. the reporting of a flame signal.
ESD Electrostatic discharge is a spark or disruptive charge that is created due to large differ-
ences in potential that can cause a short, high electrical voltage pulse on an electrical device.
FPE A functional earth ground is used for trouble-free function of electrical systems and
devices.
FFTD The flame failure detection time is (according to DIN EN 298) the reaction time of an
independent flame monitor between the flame detection and the flame signal that indicates
the flame failure. PWR Power (supply voltage) ERR Error FSB Flame Scanner System Bus is a communication interface developed by LAMTEC that
works with a protocol of the same name LDR A light dependent resistor or a flame sensor input for this type of flame sensor. UV Is a flame sensor input for the connection of UV tubes which utilise the ultraviolet wave-
length range of the flame for flame detection. ION Is an ionisation input which utilises the rectifying properties of the flame in order to detect
it. HP The main processor is one of two controllers within the double-edged system structure of
the flame monitor. This chiefly takes over the control of the device. Peripherals which are
connected to this are designated with HP. UP The monitoring processor is one of two controllers within the double-edged system struc-
ture of the flame monitor. This chiefly takes over the monitoring of the main processor.
Peripherals which are connected to this are designated with UP, if necessary.
41
11 Appendix

11.4 Declaration of Conformity

42
11 Appendix
43
11 Appendix

11.5 Order Information

Flame monitor F130I Order number
Flame monitor F130I supply voltage 230 VAC 659G1001 Flame monitor F130I supply voltage 120 VAC 659G1002
44
The information in this publication is subject to technical changes.
LAMTEC Meß- und Regeltechnik für Feuerungen GmbH & Co. KG
Wiesenstraße 6 D-69190 Walldorf Telefon: +49 (0) 6227 6052-0 Telefax: +49 (0) 6227 6052-57
info@lamtec.de www.lamtec.de
Printed in Germany | Copyright 2019
Print no. DLT7669-19-aEN-006
Loading...