These instructions apply to the ETAMATIC and ETAMATIC S in any configuration.
This devices conform to the following standards and regulations:
EN 230
EN 267 (where applicable)
EN 298
EN 676 (where applicable)
EN 746-2 (where applicable)
EN 12952 -8 u.11 (where applicable)
EN 12953 7 u. 9 (where applicable)
TRD411
TRD412
TRD604
EMC - Directive, Low-Voltage Directive
Pressure equipment directive
Gas Appliance Directive
Test symbols: CE-0085 AU 0207
The ETAMATIC is a control unit for combustion systems.
7
1 General Information
1.2Variants - Device Configuration
The variant number describes the device's variant. You will find the variant number on the side
of the housing. The variant number is based on the following key:
Serial number
Example: ETAMATIC in variante no.: 0 0 001 r0 AM S AP
ETAMATIC00001r0AMSAP
abcde f g
a: Flame monitoring
1Flame monitoring 50Hz
2Flame monitoring 60Hz
b: Control by atmospheric condition for PCU / standby operation
1cont.by atmospheric condition PCU current 4...20 mA passive
2cont.by atmospheric condition PCU PT100 up to 320°C
3cont.by atmospheric condition PCU poti 5 kOHM
4Current correction
5STANDBY-operation if load controller integrated
6STANDBY-operation, activation via fieldbus
7STANDBY-operation, activation via LSB
c: Analogue in-/output
04x three-point-step output
13x DPS and 1x continues output 4...20 mA, FB 4...20 mA
42x DPS and 2x continues output 4...20 mA, FB 4...20 mA
54x DPS and output of the internal load
104x DPS with type switchover channel 1
113x DPS & 2x continuous.and with type switchover channel1
213x DPS and 1x continuous output 4...20mA, FB RPM-2L, 300-3600 I/min
223x DPS and 1x continuous output 4...20mA, FB RPM-2L, 600-7200 I/min
233x DPS and 1x continuous output 4...20mA, FB RPM-2L, 30-300 I/min
243x DPS and 1x continuous output 4...20mA, FB RPM-2L, 60-600 I/min
APOutput relais fault normally open
RPOutput relais fault normally closed
9
2 Safety
2Safety
2.1German Law on Device Safety
The legislation on safety of appliances stat es:
Follow the instructions!
Proceed only in accordance with this ETAMATIC commissioning supplement (print no
DLT2001-11-aEN-184)
Use the equipment for the purpose described!
Operating by trained personnel only.
The appliance may only be operated and serviced by personnel with the required knowledge
and education to do so on the conditions and safety rules.
Follow the safety instructions of the burner manufacturer.
To be used in grounded power line network only!
If a flame monitor, which is not approved for continuous operation, is connected up, the approval for continuous operation of the system will be rendered invalid.
The unit is approved for use only with an external automatic flame guard. The automatic flame
guard type F 250 made by LAMTEC is used for testing purposes.
The following flame monitoring systems / flame sensors are applicable for use
(see the print no. of the associated documents in brackets behind the devices):
Compact flame detector F200 K1 and F200 K2(DLT 7620)
Flame monitoring system F150 (DLT 7521) and F250 (DLT 7540) in conjunction with the flame
sensors FFS05 / FFS05 Ex / FFS05 ExII (DLT 7501 and DLT 7503) and FFS06 (DLT 7502)
Any other automatic flame guard tested in accordance with DIN EN 298 and/or DIN EN 230
and approved for continuous operation may be used instead of this.
Before using a flame sensor / flame monitoring system you have to study the associated manual. Pay attention to the specifications and observe the instructions.
Electric connection to devices, which are not mentioned in these instructions only after consultation with the manufacturer or a qualified expert. If an automatic flame guard which is not
approved for continuous operation is connected, the system will loose the approval for continuous operation. Liability for proper functioning of the appliance passes to the owner or operator. Liability for correct functioning of the appliances in every case passes to the owner or
operator, should the appliance be incorrectly operated, serviced or repaired by persons without the requisite knowledge, or if operation is inconsistent with the specified intended purpose.
In the event of modifications to the unit the type approval lapses. The unit's inputs and outputs
and associated modules must only be wired according to the specifications in these instructions.
LAMTEC GmbH & Co KG will not be liable for damage or injury arising out of a failure to observe the instructions above. The warranty and liability provisions of the terms and conditions
of sale and supply of LAMTEC GmbH & Co KG shall not be extended by virtue of the instructions above.
LAMTEC GmbH & Co KG will not be liable for damage or injury arising out of a failure to observe the instructions above. The warranty and liability provisions of the terms and conditions
of sale and supply of LAMTEC GmbH & Co KG shall not be extended by virtue of the instructions above.
Where reference is made to legislation, government regulations and standards, these are
based on the legal system of the Republic of Germany
10
2 Safety
2.2For Your Safety
In this operating instructions, the following symbols are used as important safety instructions
to the user. These symbols appear wherever there is a need for this information in a particular
section.
It is essential to note and comply with the safety instructions, particularly the warnings.
DANGER!
Indicates possible danger to personnel, particularly with regard to electrical equipment
WARNING!
Indicates possible danger to personnel if the system components are not handled correctly.
CAUTION!
Indicates danger to system components or possible impairment of functionality.
NOTICE!
Contains important additional information for the user concerning the system or system com-
ponents and provides helpful tips
Contained in texts that provide information on how to perform tasks.
In performing all tasks, the operator is requested to observe all statutory safety regulations
and to do everything possible, according to the circumstances, to prevent injury to persons or
damage to equipment
11
2 Safety
2.3Associated Automatic Flame Guard
The unit is available with and without an integral flame guard. Sensor types FFS 06, FFS 05
and FFS 05UV can be connected to the integral flame guard. When used without integral
flame guard, any tested flame guard in accordance with DIN EN 298 and/or DIN EN 230 and
approval for continuous operation may be connected to terminal 53 like the following (document no. in brackets):
Compact flame detector F200 K1 and K2 (DLT7620) or the flame guards F150 (DLT7521) and
F250 (DLT7540) with the flame sensors FFS05 / FFS05 EX / FFS05 ExI (DLT7501 and
DLT7503) and FFS06 (DLT7502)
WARNING!
If the ETAMATIC is used with an integral flame guard, terminal 53 must not be connected to
any other components.
WARNING!
Electrical connection to appliances not listed in these instructions: only after consultation with
the manufacturers or a qualified expert.
If a flame guard, which is not approved for continuous operation, is connected, the approval
of the system for continuous operation expires.
Liability for proper functioning of the unit passes to the owner or operator.
If the unit is incorrectly operated, serviced or repaired by unqualified personnel, or if operation
is inconsistent with the specified intended purpose, liability for the unit’s correct functioning in
each case passes to the owner or operator.)
WARNING!
The type approval lapses in the event of modifications to the unit. The unit's inputs and outputs
must only be wired according to the specifications in these instructions.
LAMTEC GmbH & Co KG will not be liable for damage or injury arising out of a failure to observe the instructions above. The warranty and liability provisions contained in LAMTEC
GmbH & Co KG’s terms and conditions for and Supply, shall not be extended by virtue of the
instructions above.
Where reference is made to legislation, government regulations and standards, these are
based on the legal system of the Federal Republic of Germany.
12
3 Brief Description
3Brief Description
The ETAMATIC regulates up to 4 control elements as a function of a control variable, in accordance with freely programmable curves. The ETAMATIC has 4 three-point step control outputs. The ETAMATIC S has 3 three-point step control outputs and one 4-20 mA output.
Examples of possible control elements:
•combustion air damper
•combustion air fan (ETAMATIC S only)
•fuel valve
•recirculation damper
Up to 20 points (usual 11) can be programmed per channel. The Display is relative between
0 and 999.
The ETAMATIC has a 25-pole Sub-D connector with serial interface for remote operation / re-
mote display via a PC (Windows software available separately). Connections for Interbus-S,
PROFIBUS-DP, CANopen, TCP/IP (Modbus TCP) and Modbus are available as optional
equipment. Other BUS-systems available on enquiry. The connection of other plant components, e.g. fault signal systems and O
9-pole Sub-D connector.
Operation is via a front panel laminated keyboard. The parameters are displayed on a 2-row
LCD screen.
The ETAMATIC is also available as a special version without a front panel. In this case, operation is via optional PC software or programming unit. As display for end-user, a customers
interface is connectable via LAMTEC SYSTEM BUS.
The ETAMATIC continuously monitors its own functions and those of the connected control
elements.
230-V outputs:
•Actuation of the gas valves
•Actuation of the oil valves
•Actuation of the oil pump
•Actuation of the ignition valve and the ignition transformer
•Fan release
•Fault message
•Open/Close control signals for the valve/damper motors
External signals to the ETAMATIC are transmitted via floating contacts or chains of contacts.
The following signals can be pre-set:
•3 separate safety interlock circuits
•fault release
•air pressure monitor
•control release
•min. gas pressure monitor (for leakage test)
•flame signal
•ignition position acknowledgement
•re-circulation on
•burner on
•select fuel
•set-point switching (for load regulator)
trim, is via the LAMTEC SYSTEM BUS interface to a
2
13
3 Brief Description
3.1Display and operational controls
Select operating modes:UEAN PARA O
Select operating parametersStatus Firing-rate rating Setpoint Actual value feedback Setpoint
feedback
2)
digital inputs
1)
AUTO SPLO *
2
Changing display
–compound
–O
2
–flame in-
tensity
*UEAN =Display of monitoring processor
PARA=Parameterisation
AUTO =Automatic
EINS=Set
SPLO=Clear memory
1)
only if activated in the parameter section
2)
only in ETAMATIC S
14
4 Operating Description
4Operating Description
(for specimen diagrams, see Appendix 9.8 Process Sequence Charts)
A signal is first fed to terminal 58 (Burner On) indicating when the burner is to start.
The ETAMATIC then interrogates the boiler safety interlock circuit or the common safety interlock chain (ETAMATIC) and the contact of the air pressure monitor. If it does not detect an
"OK" condition, the text of a corresponding message appears and the operating control stops.
If all signals are OK, the fan output is activated and the ducts run to their bottom stop as a
check.
Once all channels have reached their bottom stop, they open for aeration. The leakage test
runs in parallel (gas operation only).
In the case of control elements the aeration is used to enter and/or test the range limits. After
reaching its top position, the fuel control element runs back into the ignition position. All other
channels remain in open position. The ETAMATIC then interrogates the air pressure monitor.
If this signal is OK, the parameterised aeration time runs. If a channel is configured for re-circulation, it opens with a time-delay. On reaching the parameterised re-circulation delay time,
the aeration time stops. As soon as the re-circulation channel has reached the aeration position, the aeration time is resumed. When this time has expired all the channels run to the programmed ignition position (re-circulation fully closed). After the lapse of the aeration time, all
channels run to the programmed ignition position (recirculation closed)
4.1Starting without pilot burner
The main valves open and together with the ignition transformer remain activated for the duration of the safety time. During this time the flame signal appears.
4.2Starting with pilot burner
The ignition valve and main gas 1 (in gas operation) or the ignition valve alone (in oil operation)
run open. The pilot flame forms and the flame detection detects the flame. The flame detection
sends the signal to the burner control device.
On expiry of the 1
time) the pilot burner burns alone. Then main gas 2 or the oil valve opens and remains activated in parallel with the ignition valve for the duration of the 2
closes again at the end of this period.
3 seconds after ignition, all channels run to the programmed base load point. The ETAMATIC
remains in base load position until control release is given.
After control release the ETAMATIC follows the power control unit’s default setting.
A shut off follows the cancelling of the signal of the terminal 58. The main valves close. In gas
operation, first main gas 1 and second main gas 2 closes with a delay of approx. 5 sec., in
order to allow the test line between the solenoid valves to burn out. In the event of a fault shutdown, both close immediately.
If configured for post-ventilation, the air channels open again for this period.
Thereafter the ETAMATIC is in the "OFF" mode.
st
safety time, the ignition transformer switches off. For 3 sec. (stabilisation
nd
safety time. The ignition valve
15
5 Commissioning
5Commissioning
5.1Before Commissioning
5.1.1Basic Settings
First you must configure the device (ETAMATIC) for the requirements of the system.
Therefore, you have to set some parameters.
The factory standard settings are indicated by *.
We recommend to use the LAMTEC PC software for Windows (available separately).
Press keys 2 to 9 to enter the password (condition on delivery 0000)
Press key 11 (ENTER)
LED between the keys 13 and 14 is on ( i.e. keys are working).
Press keys 13 or 14 to set the display to "Parameters".
Press keys 6 or 7 to select the required parameter.
Press keys 8 or 9 to change the content.
There are only 5 languages available in a single EPROM. The availability of languages depends on the version of the EPROM. For more information refer to the parameter list
(DLT1045).
16
5 Commissioning
5.1.4Character of the Output Channels
Select parameter 356 - 359 (channel 1 to channel 4).
Enter the type of control element which is connected.
NoFMSETAShort TextDescriptionMinMaxDefault
35622Fkt. KFunction definition channel106
Category = channel configuration and broken wire
detection
In this parameter you define the type of actuator the
respective output channel controls. This indirectly determines the channel’s behaviour at pre-ventilation, at
band shifting, at changes of the burner-firing rate and at
drift compensation. This possibly may, affect special
functions (e.g. if the channel is configured to recirculation or flue gas).
0 = Channel OFF (broken wire monitoring and
indication in the display are active further on /
channel switch off with P 366 - P 373)
1 = recirculation
2 = fuel
3 = combustion air
4 = flue gas
5 = mechanic compound
6 = atomizer steam (like fuel, but without pre-ventila-
tion of the channel: switch off determination
of range limits)
Behaviour of the actuators with FMS:
steam = Remains CLOSE until the pre-ventilation time
has expired. After that the actuator runs to
ignition position.
REZI = Runs OPEN after the configured pre-ventila-
tion time, even if terminal 6 has a signal. In reg-
ular operation terminal 6 must have a signal.
flue gas = Runs completely open in BE and remains
open until ignition. Then the actuator runs to
compound. At start without VO, ignition starts
not until flue gas is completely open.
mech. compound = Acts like air in VO.
Behaviour of the actuators with VMS:
steam = Remains CLOSE until the pre-ventilation time
has expired. After that the actuator runs to
ignition position.
REZI = runs open to the configured number of points
in VO = position, which the allocated air actua-
tor must have reached (terminal 6 has signal).
flue gas = Runs completely open in BE and remains
open
until ignition. Then the actuator runs to com-
pound. At start without VO, ignition starts not
until flue gas is completely open.
mech. compound = Acts like air in VO.
Select parameter 366 and 367 (curve set 1 and 2).
Controller release with bit pattern.
NoFMSETAShort TextDescriptionMinMaxDefault
36622K Enb. 1Channel enable for curve set 103115/31
This parameter defines, which channel is active with
which curve set. All channels are active by default (content 31, for ETAMATIC 15). The following function may
be realised. Example:
changing channel activities with fuel oil/gas
emergency operation with or without frequency converter
Selection per binary pattern:
decimal 15, all 4 channels are released for operation
decimal 31, all 5 channels are released for operation
Example:
Channel 1, 2 and 5 are released
Default settings at delivery:
curve set 1 (oil) = 1001
curve set 2 (gas) = 1101
18
5 Commissioning
5.1.5Start with or without pilot burner
Select parameter no. 774 and 775 (oil operation, gas operation).
NoFMSETAShort TextDescriptionMinMaxDefault
77411ZüBr. ÖLStart with (1) or without (0) pilot burner for oil, (2)=oil
with continuous ignition flame
0 = start without pilot burner - oil operation
1 = start with pilot burner - oil operation
2 = pilot burner also active in burner operation with
continuous monitoring of the ignition flame.
Therefore P 788 has to be set to 1
3 = start with pilot burner - oil operation,
only the ignition flame may be present during ignition
(until the 2
4 = pilot burner also active in operation with continuous
operation monitoring of the ignition flame, only the
ignition flame may be present during ignition
(until the 2
(from v. 5.4/510 on)
9 = start with pilot burner - oil operation
You may start the pilot burner with terminal 70 dur-
ing operation.
11 = start with pilot burner - oil operation
only the ignition flame may be present during igni-
tion (until the 2
You may start the pilot burner with terminal 70 dur-
ing operation.
17 = start with pilot burner - oil operation
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
19 = start with pilot burner - oil operation,
only the ignition flame may be present during igni-
tion (until the 2
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
25 = start with pilot burner - oil operation,
You may start the pilot burner with terminal 70 dur-
ing operation.
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+oil), the pilot burner starts
to ignite oil.
27 = start with pilot burner - oil operation,
only the ignition flame may be present during igni-
tion (until the 2
You may start the pilot burner with terminal 70 dur-
ing operation. Before curve set change from solo
operation (gas/fuelA) to mixed mode (+oil), the pilot
burner starts to ignite oil
nd
safety time)
nd
safety time)
nd
safety time).
nd
safety time).
nd
safety time).
041
NOTICE!
2 to 4, 9, 11, 17, 19, 25, 27 The ignition flame input must monitor the ignition flame sep-
arately and P 788 must be set to 1.
9, 11 FMS only
17, 19, 25, 27 FMS with mixed fuel firing only
19
5 Commissioning
NoFMSETAShort TextDescriptionMinMaxDefault
77511ZüBr.GasStart with (1) or without (0) pilot burner for gas, (2)=gas
with continuous ignition flame
0 = start without pilot burner - gas operation
1 = start with pilot burner - gas operation
2 = pilot burner also active in burner operation with
continuous monitoring of the ignition flame.
Therefore set P 788 to 1
3 = start with pilot burner - gas operation,
during the ignition (until the 2. safety time) only the
ignition flame may be present
4 = pilot burner also active in operation with continuous
operation monitoring of the ignition flame.
During ignition (until the 2. safety time), only the
ignition flame may be present.For this purpose P
788 has to be 1
(since v. 5.4/5o210)
9 = start with pilot burner - gas operation
You may start the pilot burner with terminal 70 dur-
ing operation.
11 = start with pilot burner - gas operation
only the ignition flame may be present during igni-
tion (until the 2
You may start the pilot burner with terminal 70 dur-
ing operation.
17 = start with pilot burner - gas operation
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
19 = start with pilot burner - gas operation,
only the ignition flame may be present during igni-
tion (until the 2
Before curve set change from solo operation (oil/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
25 = start with pilot burner - gas operation,
You may start the pilot burner with terminal 70
during operation.
Before curve set change from solo operation (gas/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
27 = start with pilot burner - gas operation,
only the ignition flame may be present during igni-
tion (until the 2
You may start the pilot burner with terminal 70 dur-
ing operation.
Before curve set change from solo operation (oil/
fuelA) to mixed mode (+gas), the pilot burner starts
to ignite gas.
nd
safety time).
nd
safety time).
nd
safety time).
041
NOTICE!
2 to 4, 9, 11, 17, 19, 25, 27 The ignition flame input must monitor the ignition flame sep-
arately and P 788 must be set to 1.
9, 11 FMS only
17, 19, 25, 27 FMS with mixed fuel firing only
20
5 Commissioning
5.1.6Pre-ventilation period
Select parameter no. 785
If an output channel is set to flue gas re-circulation, attention must still be given to P 427.
NoFMSETAShort TextDescriptionMinMaxDefault
78511ZEIT VOPre-ventilating time in seconds099930
Set the duration of pre-ventilation in this parameter.
The commissioning engineer sets this value.
P784 sets the lower limit of the pre-ventilation.
5.1.7Recirculation Delay
Select parameter no. 427
NoFMSETAShort TextDescriptionMinMaxDefault
42711VO Del RNumber of points of air channel of recirc. (VMS)/delay
time (FMS)
Number of points of an air channel for recirculation
(VMS) / delay time (FMS) in seconds.
With VMS it is necessary to couple the recirculation flap
delay with an air channel during pre-ventilation. Therefore an air channel is assigned to the recirculation flap
(see P 428). The opening of this air channel now determines the moment, when the recirculation flap shall
open. Set in this parameter the number of digits the air
channel has to reach, before recirculation becomes
active.
If the device is an ETAMATIC or a FMS, set the delay
time in seconds before the recirculation flap opens,
i. e. during this period only the boiler is ventilated.
The total pre-ventilation duration (P 785) has to be
greater than the value in this parameter.
- VMS opening of the air channel for delay of the
recirculation channel (in digit)
- FMS delay time (in seconds)
0 = recirculation channel remains closed during pre-
ventilation
1... = Delay/delay time of the recirculation channel
0999750/10
21
5 Commissioning
5.1.8Deactivate load control unit
Select parameter no.790 (type of burner-firing-rate controller)
NoFMSETAShort TextDescriptionMinMaxDefault
79011LasttypType of output regulator. 0-OFF / 1-constant regulator /
2-weather-controlled regulator
Switch on or set the type of internal firing rate controller
0 = OFF
1 = constant burner sequencer
2 = control by atmospheric condition 1
3 = control by atmospheric condition 2
For ETAMATIC, P 809 selects from which input the
actual value signal should be taken. If the parameter is
set to 1, the integrated PT100 input is used, otherwise
the firing rate input.
If the ETAMATIC uses the PT100 input as the actual
value signal for the internal firing rate controller, you
may deactivate the firing rate controller with a bridge
between terminals 19 and 20. The firing rate input
occurs via terminals 3-6.
NOTICE!
These parameters (P 356 - P 359, P 366, P 367, P 427, P 774, P 775 P 785, P 790, P 833)
must be adjusted to the system before commissioning. Further parameters which, although
you can alter them, only need to deviate from the standard setting in exceptional cases, are
given below.
5.1.9Running Time of the Regular Firing Rate Input with TPS-Input
030/1
Select parameter no. 718.
If the load default is not provided via analogue signal, the parameter must be set to „0“
NoFMSETAShort TextDescriptionMinMaxDefault
71811Laufz LRunning time in points/mins. for DPS load input (in digit/
min)
Set how fast the signal of the external firing-rate should
change if the firing-rate input is provided via the TPS
signal.
A counter generates the external firing rate with a TPS
signal. It counts up or down, depending on the contact.
This parameter sets the speed of the counter. Set the
parameter to 0, if the firing-rate input is not TPS.
With manual mode the load default via redundant feedback channel 2 is treated as TPS load, if TPS load is
configured (P 718 0).
0 = load default current or potentiometer
500 = load default TPS
012000/500
5.1.10Minimum Running Time of the Compound
Select parameter no. 729
22
5 Commissioning
NoFMSETAShort TextDescriptionMinMaxDefault
72912stopVERBMinimum running time of compound 1099910
Minimum running time of the compound (in seconds)
Set the minimum running time of the compound in seconds. This parameter slows down the ramp-up time or
ramp-down time of the burner from base firing-rate to
high firing-rate.
5.1.11Post-ventilation time
Select parameter 758
NoFMSETAShort TextDescriptionMinMaxDefault
75811ZEIT NAPost-ventilating time010000
Post-ventilation time (in seconds)
0 = no post-ventilation
1000 = continuous ventilation (from 5.0 on)
Set the duration, how long the VMS/FMS/ETAMATIC
ventilates after a switch OFF. The air flaps were open
for this purpose. A fan output runs to 20mA. The FMS/
ETAMATIC holds the release signal of the fan.
No post ventilation occurs if the parameter content is 0
and in the case of a fault shutdown.
The actuators are not monitored in post ventilation
mode! The actuators only open when the flame is extinguished. The time begins to run immediately with closing of the magnetic valves. It may be necessary to add
this post burn time to the required post ventilation time
23
5 Commissioning
5.1.12Delaytime of the Air Dampers During Pre-ventilation
Select parameter no. 768.
NoFMSETAShort TextDescriptionMinMaxDefault
76812KverznLEDamper delay after fan ON in seconds 0155
Delay time for flaps after switching ON the fan in seconds (only for FAT)
Enter a delay time for opening of the flaps with respect
to the ventilator release. This prevents from increasing
the power consumption of the ventilator motor in the
star/delta starting phase (only effective for FMS and
ETAMATIC).
(from 5.4 / 52201 on)
This parameter affects even with continuous ventilation.
24
5 Commissioning
5.1.13Parameters of the Interface
NOTICE!
These parameters have to be equal to the settings of the remote control software.
Otherwise no communication is possible.
NoFMSETAShort TextDescriptionMinMaxDefault
82222Baud S1Baud rate of serial interface 1054
This parameter sets the baud rate for the serial interface. The standard value is parameter content "4"
(19,200 baud). If the display shows problems with the
serial transmission (especially with long serial connections), it may be helpful to drop the baud rate. This must
be carried out on the VMS/FMS/ETAMATIC as well as
on the operating device e.g. laptop.
82422Par. S1Parity check for serial transfer (ser.1)1021
This parameter sets the parity bit for interface transmission. Standard is even (parameter content: EVEN=0,
NONE=1, ODD=2).
0 = even
1 = none
2 = odd
82622Adr. S1Network address VMS/FMS (ser.1)10311
Network address VMS / FMS (serial Interface 1)
Enter the network address for the serial interface. Fac-
tory status for the network address is "1". Only if several
devices are connected via an RS422/RS485 bus, this
network address has to be changed.
5.1.14Deactivate leakage test
Select parameter no. 772
NoFMSETAShort TextDescriptionMinMaxDefault
72214Laufz KRunning time in points/mins. for continuous output
channel 4
see P 719
25
0
65535
9999
5 Commissioning
5.1.15Set pilot burner (maintenance mode)
Select parameter no. 787
NoFMSETAShort TextDescriptionMinMaxDefault
78711WartungMaintenance mode (control unit only until stabilization
time)
0 = maintenance mode on (main valves are opened)
1 = maintenance mode active
2 = curve set switch allowed in set mode
Set the maintenance mode with this parameter. The
maintenance mode sets the pilot burner or the ignition
flame monitor. It enables to do 5 consecutive ignition
attempts without restarting with pre-ventilation and the
leakage test. The burner sequencer only steps up to the
flame stabilisation time. You may not open the main
valves before the reset of this parameter.
After the 5
automatically.
Note:
A "Total Reset" resets the counter for maintenance
mode automatically i.e. the next cycle is treated as the
first and pre-ventilation and the leakage test are running.
Therefore, reset faults with a "Partial Reset" wherever
possible (selection switch on "Status", first channel key
2 upwards, then in addition channel key 1 downwards). Attention: You may not use a partial reset for some
faults.
th
attempt pre-ventilation and leakage start
020
26
5 Commissioning
5.1.16Automatic Restart after Failure
Respect the directives for combustion plants, if you set this parameter.
NoFMSETAShort TextDescriptionMinMaxDefault
83622AutStartAutomatic restart after fault 0300
Delay in seconds
Automatic restart of the burner on fault condition. In the
case of a fault for which the standards permit an automatic restart for FMS/ETAMATIC, this parameter initiates the restart. Set to 0 for VMS.
0 = no restart of the burner
1 = automatic restart of the burner for faults, which are
marked in the list of faults
Selection of the standard with P 425:
0 = TDR
1 = no restart of the burner
2 = EN676
27
5 Commissioning
5.1.17Burner Firing Rate Controller
Enter Set Point Values
Select parameter 796 and 798 (setpoint value 1 and setpoint value 2).
With control by atmospheric condition select additionally parameter 797 and 799.
NoFMSETAShort TextDescriptionMinMaxDefault
79600Soll1minController setpoint 1 minimum 099990
Firing-rate controller setpoint 1 minimum (setpoint 1) in °
C or bar (xx.x)
Set the minimum value for the first controller setpoint
(active if input "set point switching" = 0) (weather guided
controller) in this parameter. If the firing rate controller is
configured as a constant controller, the set point is set
here.
"Set point input via front panel"
1.Selection switch: firing-rate value
2.Display: controller setpoint, controller actual value,
firing-rate setpoint, internal firing-rate
3.Channel key 3 down and channel key 4 up at the
same time
4.Controller setpoint starts to flash and the setpoint can
be changed with channel key 2
5.Do not save value: channel 3 up and channel 4 down
at the same time or switch off burner
6.Save value: save the setpoint to the minimum value
parameter with the Enter key (in P 796 / P 798
depending on the setpoint switching input)
Saving is only possible with constant controller.
With control by atmospheric conditions you may set the
firing-rate controller setpoint value default manually
Activation of the controller setpoint modification is disabled when operating mode is OFF. You may not trigger
the burner start by shifting the switching point.
refer to figure "Control by Atmospheric Conditions / Setpoint Switching of the Firing-rate Controller"
Firing-rate controller set point 2 minimum (set point 2)
in ° C or bar (xx.x)
Enter the minimum value for the second controller set
point (active if input "set point switching" = 1) (control by
atmospheric condition). Enter the setpoint in this parameter, if the firing-rate controller is configured to constant
controller,
see P 796
refer to figure "Control by Atmospheric Conditions
/ Setpoint Switching of the Firing-rate Controller"
Control Range
Select parameter no. 802 and 803
NoFMSETAShort TextDescriptionMinMaxDefault
80200EinschPtBurner start point 9999991
Enter the switching point of the firing-rate controller as
the difference to the set point.
[Switching point] = [setpoint] - [parameter content]
e. g. : burner should switch on at 110.
setpoint = 120, parameter content = 10,
110 = 120 - 10
If the burner shall start above the setpoint,
you may enter negative values as well.
Therefore the following values correspond:
-1 = 65535 and -999 = 94537
Parameter content = 65536 - difference
i. e.: burner shall switch on at 125.
set point = 120, parameter content = 65536 - 5 = 65531
switching point value= 120 - (-5) = 125
80300Regelb.Oupper Control range 099910
(difference to the set point 1/2) in ° C or bar (xx.x)
Enter the upper control range limit.
The entered value corresponds to the difference
between the actual setpoint and the upper limit of the
control range.
Depending on the content of Parameter 809, the content of this parameter is interpreted as ° C (directly without decimal point) as bar (resolution 0.1 bar, i.e. range
from 0.1 to 99.9 bar) or in digit.
see figure "Control range of the Firing-rate Controller"
29
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.