10. When de-aeration has been completed turn the motor protection
switch QM1 off and also manual control function off.
11. Open shut-off valve (1) at the back of the group of ll valves.
12. Close both ball valves (3) and (4).
13. Remove the ll hoses.
14. Fasten the expansion vessel back in its place in the foremost ball
valve (3) in the group of ll valves.
15. Remove the safety valve on the expansion vessel.
16. Fill ¾ of the expansion vessel with water/ethanol or water/glycol
mixture.
17. Fasten the safety valve to the expansion vessel.
18. Open the foremost shut-off valve (3) in the group of ll valves.
19. Remove and clean the net strainer (5) on the mud separator,
repeat this several times, if necessary. The red-handled valves (1)
and (2), as well as the valve under the ll container (3) must be
closed in order to prevent uids from running out.
Filling and de-aeration have now been completed.
4.2.3. Heating and domestic
hot water connections
Remove the crown panel from the
geothermal heat pump’s upper part
for the duration of installation works
by undoing the two screws shown in
the picture. Pull the crown panel directly forward and lift it off the heat
pump. Make the heat distribution and domestic water connections as
shown in the picture below.
1
2
3
4
5 6
7
8
10
9
11
1213
1. Lämmönjako 1, meno Heating flow 1 22 mm
2. Lämmönjako 1, paluu Heating return 1 22 mm
3. Lämmönjako 2, meno Heating flow 2 22 mm
4. Lämmönjako 2, paluu Heating return 2 22 mm
5. Kylmä vesi Cold water 22 mm
6. Lämmin vesi DHW flow 22 mm
7. Paisunta Expansion ¾”
8. Maapiiri, meno Collector circuit, flow 1”
9. Maapiiri, paluu Collector circuit, return 1”
10. Jäähdytys, meno Cooling, flow 1”
11. Jäähdytys, paluu Cooling, return 1”
12. Aurinkoyhde, meno Solar connection, flow ¾”
13. Aurinkoyhde, paluu Solar connection, return ¾”
14. Kv-kierto Hot water circulation ½”
Varaajan täytön yhteydessä varaajassa olevan ilman on päästävä vapaasti
poistumaan. Huom! Ei ilmaventtiilin tai varoventtiilin kautta.
While lling the storage tank outgoing air has to be freely deated.
NB! Not via air valve or safety valve.
14
Heating connection
Heat distribution circuit surface sensors located on top of the storage tank
must be installed to the distance of approx. 0.5 m from the three-way or
four-way valve. Circuit HD1 is always the main heating circuit (rooms, for
example); it is used for higher temperature (radiator heating, for example). In
case of compressor malfunction, the electric heating element heats the circuit HD1 more efciently. Circuit HD2 is used in radiator-heated buildings for
the possible oor heating share or for other purposes (e.g., humid rooms).
Speed controlling of the heat circulation pumps
Grundfos UPM3 AUTO heat circulation pump which is used in a HD circuit can be set in three different controlling modes: proportional pressure
mode, constant pressure mode, constant curve mode. Factory setting is
proportional pressure mode 3. In radiator network constant pressure
mode 1 or 2 can be used if sound of the ow water is disturbingly high.
Proportional pressure mode LED1
green
LED2
yellow
LED3
yellow
LED4
yellow
LED5
yellow
Proportional pressure mode 1
Proportional pressure mode 2
Proportional pressure mode 3
Auto
Adapt
Constant pressure mode LED1
green
LED2
yellow
LED3
yellow
LED4
yellow
LED5
yellow
Constant pressure mode 1
Constant pressure mode 2
Constant pressure mode 3
Auto
Adapt
Constant curve mode LED1
green
LED2
yellow
LED3
yellow
LED4
yellow
LED5
yellow
Constant curve mode 1
Constant curve mode 2
Constant curve mode 3
Constant curve mode 4