Lampoassa ESI 6-17, EMI 22-43, ELI 60-90 User Manual

Page 1
100% GEOTHERMAL HEAT
LÄMPÖÄSSÄ 10/2016
LÄMPÖÄSSÄ GROUND SOURCE HEAT PUMP
ESI 6-17 / EMI 22-43 / ELI 60-90
INSTRUCTIONS
FOR USE,
AND MAINTENANCE
Page 2
2
100% GEOTHERMAL HEAT
Foreword
We thank you for your condence in our products and congratulate you on making an excellent choice! You have selected a long-lasting and environmentally friendly Lämpöässä geothermal heat system. We hope that you will enjoy the trouble-free heating provided by Lämpöässä for many decades to come. Please familiarize yourself with these instruc­tions for use and maintenance. Keep the instructions for future use and reference should problems occur.
These instructions consist of three manuals drawn up with consideration of different user groups. The instructions for use include manuals inten­ded for users, installers, and maintenance personnel. The instructions also separately contain warranty conditions, technical specications, and connection diagrams.
Page 3
3
100% GEOTHERMAL HEAT
Contents
1. Safety 4
2. Geothermal heating system operation 4
2.1. Lämpöässä structure and operating principle 4
2.1.1. Heat collection circuit 4
2.1.2. Compressor unit 4
2.1.3. Hot water storage tank 5
2.2. ÄssäCooling cooling system 7
3. How to use the equipment 7
3.1. Control system functioning 7
3.2. Touch screen functioning 7
3.3. Setting the time and date 8
3.4. Function shortcuts 8
3.4.1. Room temperature adjustment 8
3.4.2. Room temperature adjustment by room temperature measurement 8
3.4.3. Domestic water boost 9
3.4.4. Home/Away function 9
3.4.5. Measurements 10
3.4.6. Timer functions 10
3.4.7. Heating curves 10
3.4.8. Storage tank settings 11
3.4.9. Optional equipment 11
3.5. Menu functions 11
3.5.1. Storage tank settings 11
3.5.2. Heating curves 12
3.5.3. Other set values 13
3.5.4. Measurements 16
3.5.5. Optional equipment 17
4. INSTALLATION WORKS 18
4.1. Before installation 18
4.1.1. Transport 18
4.1.2. Ground source heat pump installation area 18
4.1.3. Removing the packaging 18
4.1.4. Space requirements 19
4.2. HVAC installation 19
4.2.1. Heatcollectioncircuitandllgroupinstallation 19
4.2.2. Filling and de-aeration of the heat collection circuit 20
4.2.3. Connections between heat pump and storage tank 20
4.2.4. Heating and domestic hot water connections 20
4.3. Electrical installation and outdoor sensors 22
4.3.1. Outdoor sensor 22
4.3.2. Storage tank and heat distribution sensors 23
4.3.3. Room sensor (optional) 23
4.3.4. Current monitor 23
4.4. Commissioning 24
5. MAINTENANCE 25
5.1. Maintenance and care 25
5.2. Possible problems occurring during use 25
5.3. Alarms 26
5.4. Maintenance procedures 26
5.4.1. Manual control 27
5.4.2. Input and output statuses 27
5.4.3. Running information 28
5.4.4. Heat distribution circuit quantity 28
5.4.5. Domestic hot water temperature limit 28
5.4.6. Positioning valve control 28
5.4.7. Part-power / Full power 29
5.4.8. Immersion control 29
5.4.9. Temperature gauges 30
5.4.10. External alarm 30
5.4.11. Soft starter alarms 30
5.4.12. Super heat valve control 30
5.4.13. Boiler maximum limits 31
5.4.14. Cooling 31
5.4.15. Return factory settings 31
6. WARRANTY CONDITIONS 32
7. TECHNICAL SPECIFICATIONS 33
8. ENERGY LABEL 35
9. HVAC SCHEMES 43
10. ELECTRICITY SCHEMES 46
Page 4
4
USER MANUAL
100% GEOTHERMAL HEAT
2.1. Lämpöässä structure and operating principle
The Lämpöässä ESi/EMi/ELi series are especially suitable for use as the primary heating system of new and renovated residential buildings and secondary residences. In order to ensure trouble-free operation, all Lämpöässä geothermal heat pumps have been test-run, set up and tested by the manufacturer. If a geothermal heat pump is being used in the part-power conguration, for example, because high temperature is required in the radiator system, the heating system must be dimensioned and adjusted so that the return water temperature is always below +55 °C. By part-power we hereby mean that the electric heating element (immersion heater) is allowed to switch on if necessary.
Because Lämpöässä ESi/EMi/ELi series doesn’t include integrated sto­rage tank, it needs a separate storage tank to function. The size and structure of the storage tank can be chosen due to the need for hot domestic water. For the operating principle and main components of Esi/ Emi series, see the picture on page 6. The picture has also been dis­cussed in Sections 2.1.1-2.1.3.
2.1.1. Heat collection circuit
The geothermal heat system circulates water/ethanol mixture protected against freezing in the heat collection circuit in order to collect thermal energy accumulated in soil through solar radiation. The heat collection piping used comprises a bore hole or plastic pipe (PEM 40/10) placed at least 1-1.2 metres deep in soil or at least 3 metres deep in water. The circulating mixture warms up by a few degrees and delivers this thermal energy to the geothermal heat pump’s EVAPORATOR (1), i.e., the heat exchanger. The temperature of the heat collection uid arriving from the soil to the evaporator is approx. 0 ºC.* This temperature can be lower in winter and higher in summer. At the evaporator, the energy of the heat collection uid is transferred to the low-pressure refrigerant circulating inside the heat pump. The refrigerant is evaporated using the thermal energy.
2.1.2. Compressor unit
From the evaporator, refrigerant vapour is transferred to COMPRESSOR (2) for ramping up the pressure. This is accompanied by steep tempera­ture rise. In the course of the heat pump process, the refrigerant tem­perature is the highest after the compressor, in excess of 100 ºC, and the refrigerant is referred to as ’hot gas’.
1. Safety
In order to ensure trouble-free operation of the Lämpöässä geothermal heating system and achieve the best efciency, the system must be transported and installed in accordance with the manufacturer ’s instruc­tions. After performance of installation works, the installation checklist must be reviewed in order to minimise the risk of potential errors. The manufacturer shall not accept any responsibility for equipment defects or related expenses caused through installation faults.
The pipe and electrical installations for the Lämpöässä geothermal heat­ing systems can only be installed by qualied persons. If problems should occur during installation, we recommend that you contact your dealer or consult with Lämpöässä maintenance specialists by phone.
If the fault symbol is displayed on the touch screen, a system malfunction has occurred. Press this button to display infor­mation on the cause of the malfunction.
Press this button for additional information on the touch screen data.
2. Geothermal heating system operation
A geothermal (or ground source) heat pump can extract geothermal heat from soil, water bodies or a bore hole. For an overview of the heat pump and its operating environment, see the picture below. Of the total thermal energy required for heating, Lämpöässä collects more than 75% from natural sources. For thermal energy collection, approx. 25% of electrical energy is required for running the various system components.
The geothermal heating system consists of heat collection piping, water/ ethanol (ethyl alcohol) mixture circulating within the piping, and a ground source heat pump unit. The ground source heat pump unit com­prises an integrated hot water storage tank, compressor, heat exchang­ers, and closed refrigerant circuit, i.e., compressor unit. The heat collec­tion uid in the ground circuit, the refrigerant and the water in the heating network never mix at any stage of the process. Heat is transferred between uids using plate heat exchangers.
i
Page 5
5
USER MANUAL
100% GEOTHERMAL HEAT
The hot refrigerant is transferred from the compressor to heat exchangers (condenser and superheater), through which it releases its thermal energy into the heating water storage tank (6). The heat in the storage tank is used for heating and hot domestic water production purposes. When heat is extracted from the refrigerant vapour, a point is reached where the vapour begins to revert into liquid – i.e., is condensed. This point is close to temperature required for heating (in general, approx. 35-55 ºC). Since the refrigerant gas leaves the compressor at approx. 120 ºC, it cools rst and liquees later. The energy released in the course of such cooling is referred to as superheating energy. The superheating energy can be efciently utilised in nal heating of domestic water, by using a superheat exchanger (3).
After the superheater, the refrigerant is transferred to CONDENSER (4), where it is transformed from vapour to liquid, releasing the heat to the heating water storage tank and from there to the heating network. Emi 22P- and Emi 43P -models with separate storage tank has no separate superheater heat exchanger. All thermal energy is conceded through condenser heat exchanger to the separate storage tank. Having conceded its thermal energy, the liquid refrigerant is transferred through dehydra­tion lter to EXPANSION VALVE (5), where the pressure of the liquid refrigerant drops and a new cycle from the evaporator can commence.
2.1.3. Hot water storage tank
It is possible to connect multiple storage tanks to ESi/EMi/ELi -models to store the thermal energy created. These storage tanks can vary in size. Lämpöässä Esi and Emi utilises carefully designed superheating technol­ogy allowing advantageous generation of heating and domestic hot water. The objective is to maximise the share of geothermal heat in over­all heating. A two-sectioned HEATING WATER STORAGE TANK (6) equipped with partition enhances utilisation of superheating energy. The coefcient of performance remains at a high level, since the energy-ef­cient superheating mixture involves heat transfer between two tank sec­tions using two different heat exchangers (condenser and superheater). Water from the hot water storage tank is circulated in the heat distribu­tion piping consisting of 1-3 loops.
The top part of the storage tank, i.e. the UPPER STORAGE TANK (6a), is heated by using superheat removal heat exchanger (superheater 3) by the extremely high thermal energy acquired from the compressor. Hot superheating energy is stored for nal heating of domestic hot water. If required, the high thermal energy can also be transferred to the heating system from the top storage tank.
The LOWER STORAGE TANK (6b) stores the thermal energy required for central heating from the condenser (4) at heating network-adjusted tem-
HEAT DISTRIBUTION CIRCUIT
HEAT COLLECTION
COOLING
GEOTHERMAL HEAT PUMP
Bore hole
Horizontal piping
in soil
Piping in water
Compressor unit
Two-sectioned storage tank
Heat collection
circuit
Heating water
Domestic water
Compressor
Evaporator
Superheater
Condenser
Page 6
6
USER MANUAL
100% GEOTHERMAL HEAT
peratures lower than those of domestic hot water. The storage tank temperature levels are controlled by an adjustment curve – thus, at ordi­nary heating circumstances, the temperature varies depending on the heating need. In such cases, the system operates in so-called ‘oating condensing’ mode. Heat distribution can be arranged using water circu­lation-based oor heating, hot water radiators or air heating. The best coefcient of performance is achieved by oor heating, since the lower is the temperature of heat release, the better is the coefcient.
Domestic water is heated within a COIL (7) inside the storage tank, which is divided into two parts. The domestic water is pre-heated in the coil located at the storage tank’s lower part, while nal heating takes place inside the coil located at the tank’s upper part. In general, domes­tic water temperature must exceed that of the heating water. Owing to the two-stage heat release of the superheating technology, the larger storage tank section heating the supply water can be kept at a lower temperature, since nal heating of the domestic water takes place using the upper storage tank section of higher temperature. In such a case, the
Solution with separate storage tank with intermediate oor:
Solution with separate storage tank:
Condenser Superheater
Evaporator
6a.Upper storage tank
6b. Lower storage tank
7.DHW coils
Heating circulation
Separate storage tank Ground source heat pump
2. Compressor
5. Expansion valve
Brine
circuit out
Brine circuit in
4.
3.
1.
Heating circulation
Ground source heat pump
Brine
circuit out
2. Compressor
5. Expansion valve
Separate storage tank
Brine circuit in
Condenser Superheater
Evaporator
6. Storage tank
7.DHW coils
4. 3.
1.
Page 7
7
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
process operation temperatures remain as low as possible, which improves the system’s annual efciency. Division of the coil into two parts allows heating of the domestic water circulation only using the upper storage tank coil, so that blending of the storage tank temperature stratications is avoided.
Lämpöässä ESi/EMi/ELi are well suitable for pieces of real estate with especially high hot domestic water consumption. In renovated residential buildings Lämpöässä Esi/Emi can be connected to existing separate sto­rage tank as well if the storage tank is in good condition and is suitable for geothermal heating. In this case Lämpöässä ESi/EMi/ELi can be con­nected without the superheating feature and separate storage tank is used. In case the building includes previously installed water tank that is suitable for geothermal heating, it can be connected to Lämpöässä ESi/ EMi/ELi.
2.2. ÄssäCooling cooling system
A passive cooling system can be installed into the heat collection circuit, in which case the uid in the circuit is circulated through an additional heat exchanger. The heat exchanger releases cooling energy to indoor air. Such exchangers include radiant cooling units provided within the venti­lation system or fan coils installed indoor. Lämpöässä offers multiple solutions for control of the cooling with ÄssäControl control system. These are available as accessories.
The Lämpöässä product family includes wall and ceiling-mounted fan units for cooling, complete with installation set. Passive cooling is a favourable approach to cooling, since the only running costs are associ­ated with water circulation pump and cooling fan operation. In Esi/Emi series cooling is connected externally to the device through heat collec­tion circulation.
3. How to use the equipment
3.1. Control system functioning
ÄssäControl by Lämpöässä is a logic-based control system. It considers the conditions prevailing in the premises and the surrounding environ­ment with improved precision. ÄssäControl control system adjusts the heating network supply water temperature proceeding from the storage tank and outdoor temperature based on a seven-point adjustment curve, so that the room temperature remains pleasantly even regardless of out­door temperature variations.
Depending on the connections, the control system controls 1-3 heat distribution circuits or 1-2 heat distribution circuits and domestic hot water temperature. With the help of the ÄssäControl control system, it is also possible to control a heat source external to the geothermal heat pump unit.
These instructions contain a user manual and a manual for equipment installer. Maintenance functions are password-protected.
3.2. Touch screen functioning
After unit start-up the display goes into basic mode, displaying on the two-part ÄssäControl home screen function shortcuts (8 pc.), time, date, and outdoor temperature. To switch between the two home screens, use the arrow buttons in the bottom right corner. To access the Functions screen, press the symbol in the top left corner.
Page 8
8
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
The function shortcuts displayed on the rst home screen include room temperature adjustment, domestic water boost, home/away function, and measurements.
The function shortcuts displayed on the second home screen include timer functions, adjustment curve set values, storage tank set values, and optional equipment.
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar. Alarms are described more in chapter 5.3.
3.3. Setting the time and date
The time and date can be adjusted by pressing the date/time displayed on the home screen top part.
3.4. Function shortcuts
For user convenience, shortcuts have been provided to functions used most often. Use home screen shortcuts to access the respective functions.
3.4.1. Room temperature adjustment
The heat distribution circuit/circuits’ heat curve setting can be adjusted by using the home screen shortcut Room temperature adjustment to achieve room temperature increase or decrease. The setting can be adjusted between -3...+3 °C by using the ‘plus’ and ‘minus’ buttons. The function Room temperature adjustment is intended for quick tempera­ture increase. Choose the heat distribution circuits to be inuenced by
the adjustment by buttons HD1, HD2 (optional equipment) and HD3 (optional equipment). To restore the original setting, change the value to 0 °C. The original heating curve and heating curve adjusted by this func­tion are visible on the Heat adjustment curve screens.
3.4.2. Room temperature adjustment by room temperature measurement (optional equipment)
As an option, the room temperature measurement function can be acquired for the system. In such a case, the room temperature is also displayed on the home screen and the screen Room temperature adjust­ment includes information on current/target room temperatures. Adjust­ment of room temperature now takes place by comparing the target and current room temperatures. By adjusting the target temperature higher or lower than the room temperature at the time, the unit adjusts the heat curve in the desired direction. Choose the heat distribution circuits to be inuenced by the adjustment by buttons HD1, HD2 (optional equip­ment) and HD3 (optional equipment).
Page 9
9
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
The rate of the function Room temperature adjustment can be increased
1...7 times by compensation. The compensation function is included under additional room temperature settings, which can be accessed by pressing the button at the bottom centre of the screen. In case of compen­sation value 7, the adjustment is seven times faster than in case of value
1. Large compensation values can cause room temperature uctuations.
3.4.3. Domestic water boost
The storage tank can be set to function at maximum thermal output in order to meet transient needs, for example, if the need for domestic hot water increases temporarily. For domestic water boost, press the Max button. Return to the normal mode by pressing the Eco button. Choose the domes­tic water boost period (1...24 h) using the ‘plus’ and ‘minus’ buttons.
3.4.4. Home/Away function
The home/away function shortcut can be used to save energy when the residents are away for a long holiday trip, for example. The function Away changes the heat distribution circuit and storage tank temperature settings until the set date and time; after that, the original set values are automatically restored (i.e., the normal mode Home is reactivated).
The system’s normal mode is Home. To activate the Away function, press the button Away and set the date and time of your return for restoring the mode Home (default value: 24 h). The changes in room and storage tank temperatures can also be programmed. In order to ensure restoring of the normal temperatures by the time of your return from the holiday trip, the day preceding the actual return date, for example, could be programmed as the return date.
Set the desired heat distribution circuit temperature adjustment under Room temperature adjustment; values between -10...+10 °C are possi­ble. Set the desired storage tank temperature adjustment value under Storage tank temperature adjustment. This setting inuences domestic water temperature. Values between -10...+10 °C are possible. If any of these temperatures is not to be changed, keep 0 °C as its value. When leaving for a holiday trip, for example, both of the values might be low­ered by approx. 5 degrees by setting -5 °C as the room/storage tempera­ture adjustment value.
Page 10
10
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
On the following screens, the target weekdays for timed temperature changes are selected. On the screens, the temperature change beginning and end times (in full hours) can be set in weekday-specic manner, as well as the change in degrees. Temperature change values between
-10...+10 °C are possible.
The last timing column consists of symbols describing the state of timing. A white symbol means that there is no active timer setting for the weekday. A yellow symbol means that time and temperature have been set, but the timer function has not been activated. A green symbol means that time and temperature have been set and the timer function has been activated.
3.4.7. Heating curves
This shortcut allows accessing the Heating curves menu, which will be discussed in more detail in the Section on menu functions.
The function can be activated only if the end date or time is in the future. If the end date is set into the past, the mode Home is activated and the mode Away cannot be activated.
3.4.5. Measurements
This shortcut allows accessing the Measurements menu, which will be discussed in more detail in the Section on menu functions.
3.4.6. Timer functions
Timer functions can be utilised, for example, in secondary residences or to benet from off-peak electricity rates, in which case weekday-specic modication of temperature levels is advantageous. The values once set are saved in the memory and can be modied as necessary. The timer function can be activated or removed from use through the Timer func- tions shortcut.
On the Timer functions screen, the timing target (storage tank or heat distribution circuit) is selected and the timer function activated/ deactivated.
Page 11
11
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
3.4.8. Storage tank settings
This shortcut allows accessing the Boiler settings menu, which will be discussed in more detail in the Section on menu functions.
3.4.9. Optional equipment
This shortcut allows accessing the Optional equipment menu, which will be discussed in more detail in the section on menu functions.
3.5. Menu functions
Menu functions can be accessed by pressing the menu button on the home screen.
3.5.1. Storage tank settings
Storage tank set values are used to adjust the storage tank top and bot­tom section temperature limits to meet the site’s domestic hot water consumption. The system includes a function that automatically elevates storage tank temperature if the heat distribution circuit adjustment curves are set higher than the storage tank temperature. Factory settings for the storage tank bottom section are 40 °C (min) and 45 °C (max). Factory settings for the storage tank top section are 50 °C (min) and 55 °C (max).
The difference between Min and Max values can be 2...10 °C. The maxi­mum allowed storage tank top and bottom section temperature set value is 60 °C in case of full power geothermal heat pumps and 60 °C (bottom section) / 85 °C (top section) in case of part-power geothermal heat pumps. In Esi, Emi 22P-Emi 43P or ELi 60P-90P model with separate storage tank are the temperature sensors installed in the same water space on the top section of the storage tank. In such case same tempera­ture settings are used for the top and lower sections of the storage tank.
The value Correction indicates the temperature as corrected by the Timer function, Home/Away function, Domestic water boost function, or auto­matic heat distribution circuit correction.
The storage tank temperature is a decisive factor in compressor starting and stopping. The minimum value programs compressor starting at the storage tank’s target temperature. The maximum value programs com­pressor stopping at the storage tank’s target temperature.
The storage tank is heated by the compressor. If the target temperature cannot be reached in a certain time (1...24 h), it is presumed that there is something wrong with the compressor and the compressor is turned off. In such cases, the storage tank is heated by the electric heating ele­ment. The default set value for this function is 12 h. If the electric heat­ing element is switched on, the following warning is displayed on the
Page 12
12
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
control panel display: Storage tank temperature not achieved in set time. Electric heating element has been switched on. For more information on programming the time, see menu Set values. NOTE! Electric heating is used only as back-up!
Maximum annual ground source heat pump efciency can be achieved if the storage tank temperature is kept at an optimal level. The ground rule is that the storage tank set values must be kept at the lowest possible level, since it allows the best annual efciency.
In winter, when the need for heating is larger, the set value for the storage tank bottom section should be programmed in relation to the supply water temperature. The temperature of the storage tank upper part increases after a long period of use and the threshold value for the com­pressor to run is 90 °C. This is due to the superheating properties of the storage tank structure. Because of this, the domestic hot water tempera­ture limiting function (option) can be used in order to avoid potential hot water-related hazards. In general, the compressor is controlled according to the minimum setting of the storage tank lower part.
In summer, when there is no need for heating (with the exception of humid rooms), the compressor is seldom on and there is less superheat­ing for domestic hot water production. In such a case the storage tank upper part and lower part temperatures are close to each other.
3.5.2. Heating curves
Heat distribution circuits (HD) are controlled by a seven-point adjust­ment curve. Depending on the connections, the control system controls 1-3 heat distribution circuits or 1-2 heat distribution circuits and domes­tic hot water temperature. In the Heating curves menu, the values of all heat distribution circuits can be changed separately to meet the heating water temperature (supply water) at a certain outdoor temperature.
Exemplary oor heating adjustment curve (factory setting) °C*
Outdoor temperature -20 -13 -7 0 +7 +13 +20 Heating water temperature +32 +31 +29 +27 +25 +23 +21
Exemplary radiator heating adjustment curve °C*
Outdoor temperature -20 -13 -7 0 +7 +13 +20 Heating water temperature +53 +48 +42 +36 +30 +25 +21
The factory-set heating curve is suitable for oor heating. The adjust­ment curve values should be specied during the rst year; they could be changed as follows, for example: If the indoor temperature feels too chilly while the outdoor temperature is -10 °C, the supply water set value can be increased a little at the outdoor temperature points -13 °C and -7 °C. Monitor the inuence of the adjustment on room temperature for at least 24 hours before making any further modications in adjustment curve set values. When using radiator heating temperature change is quicker.
For the temperature correction caused by Home/Away or Timer func­tions, see the bottommost line.
Maximum domestic water temperature can be limited by adjusting the Domes­tic water temperature limit value between 0...90 °C (factory setting: 55 °C).
* Conditions in Finland.
Page 13
13
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
3.5.3. Other set values
The menu Other set values allows circuit-specic programming of maxi­mum and minimum heat distribution circuit supply water values, as well as programming of the safety device-heating element activation time.
3.5.3.1. Language
The Language menu allows choosing between Finnish, Swedish and English for the user interface language.
3.5.3.2. Screen settings
On screen settings -page it is possible to adjust the brightness of the screen and also the time after the screen goes off.
3.5.3.3. Min and max temperature of HD circuits
Set values are minimum possible values (min) and maximum possible values (max). Heat distribution circuits 2 and 3 are optional.
Factory settings for heat distribution circuits are as follows:
Set value and setting range
Meaning Factory
setting
Supply water1 max 0…90 °C
Maximum value of heat distribution circuit 1 heating supply water.
60°C
Supply water1 min 0…90 °C
Minimum value of heat distribution circuit 1 heating supply water.
5°C
Supply water2 max 0…90 °C
Maximum value of heat distribution circuit 2 heating supply water.
60°C
Supply water2 min 0…90 °C
Minimum value of heat distribution circuit 2 heating supply water.
5°C
Supply water3 max 0…90 °C
Maximum value of heat distribution circuit 3 heating supply water.
60°C
Supply water3 min 0…90 °C
Minimum value of heat distribution circuit 3 heating supply water.
5°C
Page 14
14
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
3.5.3.4. Safety device settings (in monovalent devices)
This screen allows programming activation of the safety device-heating element if the storage tank target temperature is not achieved by the compressor during the dedicated period (from 0 to 24 hours, factory setting: 12 hours). The setting is applicable in full-power systems only.
3.5.3.5. Bivalent settings (in bivalent devices)
In bivalent system the immersion heater and compressor can be on at the same time. In bivalent settings -page can be set the heating time before additional heating goes on.
3.5.3.6. Summer functions
In this screen months when function is valid and circulation pumps active are selected. To avoid circulation pumps to be stucked they auto­matically start up every week for 30 seconds. Here you can also validate heating circuits where summer function is effecting. Circuit can be active during a whole summer when it is controlling bathroom area for example.
3.5.3.7. Brine circuit circulation pump control
This screen allows adjustment of the ground circuit uid ow rate. If the setting is 100%, the ow speed is maximal. If the setting is 0%, the ow speed is minimal. Factory setting: 80%.
3.5.3.8. External heating source controlling (accessory)
It is possible to connect a variety of additional external heat sources to the ground source heat pump, such as electricity or oil boiler. In the menu, Additional heat source control, the heating time is determined before the additional heat source is activated, as well as the time between the addi­tional heat sources. This setting is only in bivalent mode. In monovalent mode the additional heat source can be used as a safety device. As stan­dard the system comprises a control of one heating source. Control of (2 ... 4) additional heating sources, can be purchased as an accessory.
Settings Options Factory
settings
Number of immersion heaters
1…4 1
Resistor control Analog / digital Digital
Analog Control (only if the control mode analog)
0 ... 10 V, The four-stage voltage amount by which the additional heat sources are triggered.
0, 0, 0, 0
Locations of the additional heat sources
Upper / lower tank Upper
Page 15
15
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
3.5.3.9. ÄssäControl-cooling, free (accessory)
To the heat pump collector can be installed a cooling system, where the heat transfer uid is circulated in the building. If the system is tted with a room temperature sensor, cooling circuit temperature is automati­cally adjusted to the desired room temperature. Without the room sensor, the system is cooling at maximum power. Free cooling is an energy-ef­cient way to cool the property, as the operating cost only consists of a circulating pump and energy consumption of the cooling fan motor. The cooling setting values can be modied under Other settings and Cooling (Note! The cooling-function is acquired).When taking the cooling system into use, the cooling control mode is set in the service menu. In the service there is following selectable control modes: Room temperature, External and Manual.
Room temperature
Room Temperature menu provides the cooling temperatures, which deter­mines when the cooling system is running. In addition, the menu will display the current room temperature, coolant temperature, humidity, and dew point value, as well as system status heating / cooling / off).
External
When the control mode is External, cooling is controlled by an external thermostat, which is connected according to the wiring diagram.
Manual control
When the control mode is set to Manual, this menu can be used to switch to active cooling. The system tries to keep the coolant tempera­ture at a minimum of one degree above the dew point. From the menu coolant temperature can be set to be constant, where the dew point effect is not taken into account.
3.5.3.10. ÄssäControl-cooling, exible (accessory)
Flexible cooling allows for a more versatile and more efcient cooling. In the exible cooling, there are six different control modes:
1. Heating
Ground source heat pump uses the ground loop by transferring energy to the storage tank for heating or hot water.
2. Heating and cooling
Ground source heat pump heats the boiler by transferring heat from the refrigerant circuit and ground loop to the storage tank. This function is available when heating and cooling is needed simultaneously.
3. Passive cooling
Ground source heat pump cools the cooling circuit by transferring heat to the ground loop. If the coolant circuit temperature has not reached the set value, in the time available (the display section Delay), becomes passive cooling automatically active cooling
Page 16
16
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
4. Active cooling
The ground source heat pump uses the compressor to cool the cooling circuit by transferring heat to the accumulator tank
5. Unloading the extra heat
If the temperature in the accumulator rises to high, the extra heat is unloaded via an exchanger to the ground loop or air.
6. Switched off
The control of cooling is based on the machine’s control modes, and control of magnetic valves and the circulating pumps. The position of the magnetic valves in different modes are determined in the service menu. In the service menu there is available control mode Control of the room temperature and External, which acts as free cooling.
3.5.3.11. Linkin several ground source heat pumps
Determing the master device
If the system contains more than one geothermal heat pump, one has to be chosen as master device. All the sensors are connected to the master device. Program settings are dened in the factory and the master device is marked with the MASTER-marking and other devices with SLAVE­marking. All heat pumps can be monitored and controlled from each heat pumps control screen.
The compressors rotation extra accessory can be enabled when the sys­tem contains more than one geothermal heat pump. However, all the linked ground source heat pumps have to be equipped with ÄssäControl
Compressor rotation
If multiple ground source heat pumps are used in the building, they can be connected to each other with compressor rotation (optional equip­ment). In such cases should be noted that all connected ground source heat pumps are equipped with ÄssäControl control system. Compressor rotation evens the operating hours of compressors. In the Compressor rotation menu can the start and shutdown intervals be modied. Possible values are for start interval values between 1...240 min (factory setting 1 min) and shutdown interval 1...240 s (factory setting 10 s).
3.5.4. Measurements
Ground source heat pump operation can be monitored using various dif­ferent measurement data. Use the screen numbering in the bottom bar for navigating between the Measurements screens.
Measurements screen values describe heat pump operation under vari­ous conditions and the values shown cannot be modied. The left-hand column indicates current measurement values and the right-hand col­umn the respective set values. Measurement results from all sensors, compressor running times, and electric heating element operation times can be browsed.
Page 17
17
USER MANUAL
100% GEOTHERMAL HEAT
Use the button in the bottom left corner to return to the home screen. Use the arrow button in the bottom right corner to return to previous screen. For
instructions screen, press the ‘i’ button in the top right corner. In case of operation faults, an alarm button is displayed on the top bar.
3.5.5. Optional equipment
In addition to the standard delivery, all of the additional features acquired are displayed on the Optional equipment screen.
Possible optional equipment includes:
Optional equipment For more information, see
Heat distribution circuit 2 Adjustment curves, Timer functions
Heat distribution circuit 3 or Domestic water temperature limit
Adjustment curves, Timer functions Adjustment curves
Room temperature measurement Shortcut functions, Adjustment curves
External heat source controlling Other set values
ÄssäControl-Cooling free Other set values
ÄssäControl-Cooling exible Other set values
Compressor rotation Other set values
Page 18
18
100% GEOTHERMAL HEAT
INSTALLATION
4. INSTALLATION WORKS
4.1. Before installation
Pipe assemblies for the installation of the Lämpöässä system may only be installed by qualied and trained persons. The equipment must be installed in compliance with instructions provided; after performance of installation works, the installation checklist must be reviewed in order to minimise potential errors. The manufacturer shall not be responsible for any equipment defects or related expenses caused through installation faults.
Check that:
• all the necessary hoses and sensors have been delivered
• the ground source heat pump has been correctly tted
• the connections on top of the geothermal heat pump are intact
• the fuse size is correct for the master fuse and the ground source heat pump (see technical specications)
• the ground circuit collection piping and supply piping have been installed properly
4.1.1. Transport
The Lämpöässä geothermal heat pump must always be transported in a vertical position. If tilting the equipment is unavoidable, for example, to pass through a doorway, the maximum tilting angle allowed is 45°. In other cases, the machine’s compressor unit must be detached during tilting. The equipment may be moved from beneath using a fork lift, for example. Do not go underneath the equipment while it is being lifted!
A transportation platform has been fas­tened on both sides of the ground source heat pump using screws. The ground source heat pump’s accessory package includes adjustable feet to be screwed into the unit bottom (see picture). After that, remove the wooden platform elements and their xation screws (4 pc). To remove the platform, lift the equipment by a fork lift, for example.
4.1.2. Ground source heat pump installation area
We recommend that the Lämpöässä ground source heat pump be installed in a warm room with oor drain. During installation, when lling the ground circuit, some water/ethanol or water/glycol mixture may be splashed onto the oor. The chosen area does not have to be reproof. Approx. 50 cm of installation space should be reserved above the equipment.
The oor must be able to withstand the weight of the ground source heat pump carrying a full storage tank. The oor must also be sufciently even, because the ground source heat pump must be installed as level as possible. Final adjustments can be made using the adjustable feet under­neath the equipment.
4.1.3. Removing the packaging
Remove the plastic wrapping and corner padding from around the prod­uct. Check that the pump has not suffered any transportation damage. If the heat pump is found to be damaged, the transport company must be immediately notied. We recommend photographing the damages.
Also check the contents of the delivery immediately. The Lämpöässä ESi/ EMi/ELi-series accessory package includes the following components:
• valve motor
• 4-way valve (GSHP with separate storage tank with intermediate oor) OR 3-way valve (GSHP with separate storage tank)
• heat distribution pump
• outdoor sensor
• heating circuit temp. sensor
• storage tank temp. sensor (2 pc.)
• adjustable foot (4 pc.)
• lling group
• lling bottle (packaged inside the product)
• safety valve
If some of the accessories specied in the order are not included in the delivery, notify the equipment dealer within ve days.
The plastic roof of the product is removed by lifting it from the edges.
Page 19
19
100% GEOTHERMAL HEAT
The front door is opened by sliding it upwards. Before this two screws in the front panel must be removed (as shown in the picture on right).
4.1.4. Space requirements
Lämpöässä ESi/EMi/ELi series ground source heat pump can conveniently be placed into a technical or utility room. The oor space to be reserved between the machine and storage tank must be adequate for pipe con­nections. Considering possible equipment maintenance, there must be approx. 70 cm of free space in front of the geothermal heat pump.
The height of a Lämpöässä ESi/EMi/ELi series ground source heat pump (including adjustable feet) is at least 145 cm. The transport platform adds some 8 cm. At the back section of the machine are the ground circuit connections that rise some 5 cm above the roof. Approx. 50 cm of free space must be reserved for connections on top of the machine. This should be kept in mind when installing the equipment into a low room, such as basement.
ESi EMi ELi
O
STORAGE
TANK
Y
B
A V
X
C
GSHP
F
O
A
400 400 400
B
50 50 50
C
50 50 50
O
700* 700* 700*
X
2300 3200 3600*
F
700 700 700
Y
1500 1500 2500*
V
200 200 200 * Min. width depends on the size of the selected storage tank
4.2. HVAC installation
4.2.1. Heat collection circuit and ll group installation
The connections for heat collection circuit are located on the top of the device. Install the heat collection circuit pipes to exible hoses on the top of the device pursuant to the picture below. Install the ll and deairing group to the returning line from the heat collection circuit.
Esi
1. Lauhduttimelta meno
2. Lauhduttimelle paluu
3. Tulistimelta meno
4. Tulistimelle paluu
5. Maapiiriin meno
6. Maapiiristä paluu
1 2 3
4
5
6
1. Flow from the condenser
2. Return into the condenser
3. Flow from the superheater
4. Return into the superheater
5. Collector circuit, flow from the evaporator
6. Collector circuit, return into the evaporator
¾” ¾” ½” ½” 1” 1”
¾” ¾” ½” ½” 1”
1”
Emi
1. Lauhduttimelta meno 1½” sk
2. Lauhduttimelle paluu 1½” sk
3. Tulistimelta meno ¾” sk
4. Tulistimelle paluu ¾” sk
5. Höyrystimeltä maapiiriin 2” sk
6. Maapiiristä höyrystimelle 2” sk
1. Flow from the condenser 1½” IT
2. Return into the condenser 1½” IT
3. Flow from the superheater ¾” IT
4. Return into the superheater ¾” IT
5. Collector circuit, ow from the evaporator 2” IT
6. Collector circuit, return into the evaporator 2” IT
12
3
4
5
6
ELi
1. Lauhduttimelta meno 2” sk
2. Lauhduttimelle paluu 2” sk
3. Tulistimelta meno ¾” sk
4. Tulistimelle paluu ¾” sk
5. Höyrystimeltä maapiiriin 2” sk
6. Maapiiristä höyrystimelle 2” sk
1. Flow from the condenser 2” IT
2. Return into the condenser 2” IT
3. Flow from the superheater ¾” IT
4. Return into the superheater ¾” IT
5. Collector circuit, ow from the evaporator 2” IT
6. Collector circuit, return into the evaporator 2” IT
12
3
4
5
6
NOTE! Insert the electricity plug of the superheat pump
into the connector box if superheat circuit connected.
If cooling equipment is located higher than the ground source heat pump is connected to the pump, a membrane expansion vessel must be included in the system. In such cases, a de-aeration connection must be installed to the highest point of the system and the ll container removed from use by closing the shut-off valve underneath it (see the annexed HVAC connections diagram).
Page 20
20
100% GEOTHERMAL HEAT
INSTALLATION
4.2.2. Filling and de-aeration of the heat collection circuit
Accessories required for the lling and de-aeration of the ground circuit:
• mixing tank, 60 litres
• submersible pump tted with a lter, lifting height approx. 30m
• water/ethanol or water/glycol mixture (1:1) with a frost resist­ance of -16 °C
• reinforced hose 1” (2 pc.), length approx. 3 m
• connector 1” (1 pc.) (female)
• connector 3/4” (1 pc.) (female)
WORK STAGES
Please check that the ground circuit has been correctly connected.
NOTE! The following instructions are for ESi series. The lling and de-
airing is done similarly to EMi/ELi series but the valve gropup is built
during installation.
1. Remove the styrox packaging protecting the group of ll valves.
2. Detach the expansion vessel from the foremost ball valve.
3. The foremost shut-off valve (2) of the group of ll valves must always be open.
4. Attach the submersible pump reinforced hose to the foremost ball valve (3) in the group of ll valves and open the ball valve.
5. Attach a reinforced hose from the ball valve (4) at the back of the group of ll valves to the ll container and open the valve.
NOTE! The ow direction has to be correct since there is a one
way valve installed between the cooling connections.
6. Fill the container with water/ethanol or water/glycol (frost r. -16 °C) mixture (ratio 1:1).
7. Bleed air from ll hoses by activating the submersible pump and keeping the valve (1) open. When air has escaped, close the valve (1) to start actual uid circulation through the ground circuit.
8. Add uid until the piping is full. Upon de-aeration, the unit’s own brine circulation pump can be used to speed up uid circulation.
Check that the motor protection switch (QM1) is not on.
Turn master switch (Q1) and control current switch (F10) on.
The forced control of gound circuit pump can be activated from the maintenance manual of ÄssäControl. Go to manual control and choose manual control on and ground circuit 1 on.
Turn the motor protection switch (QM1) on.
NOTE! When using the system’s own brine circulation pump for
1
2
4
5
3
de-aeration purposes, check that the ow direction of the separate submersible pump is always the same as that of the unit’s pump.
9. Keep the submersible pump running until the uid is clear and no gurgling can be heard from the pipes. NOTE! De-aeration usually takes several hours and helps to ensure that all the air is remove from the system and will not cause any malfunctions once the system is started. Leave no pressure in the network! Remove any air from the evaporator through the de-aeration connection of the pipe located between the ground circuit and the evaporator.
10. When de-aeration has been completed turn the motor protection switch QM1 off and also manual control function off.
11. Open shut-off valve (1) at the back of the group of ll valves.
12. Close both ball valves (3) and (4).
13. Remove the ll hoses.
14. Fasten the expansion vessel back in its place in the foremost ball valve (3) in the group of ll valves.
15. Remove the safety valve on the expansion vessel.
16. Fill ¾ of the expansion vessel with water/ethanol or water/glycol mixture.
17. Fasten the safety valve to the expansion vessel.
18. Open the foremost shut-off valve (3) in the group of ll valves.
19. Remove and clean the net strainer (5) on the mud separator, repeat this several times, if necessary. The red-handled valves (1) and (2), as well as the valve under the ll container must be closed in order to prevent uids from running out.
Filling and de-aeration have now been completed.
4.2.3. Connections between heat pump and storage tank
The storage tank is connected to the ground source heat pump pursuant to the connection diagram at the end of this manual. The connections for the ground source heat pump are shown in the picture found in chapter
4.2.1. The factory setting for super heat valve can be found in the technical specications table. The setting can be adjusted in the mainte­nance menu.
4.2.4. Heating and domestic hot water connections
Connect the heating and domestic hot water connections pursuant to connection diagrams in the chapter 8. Connection diagrams.
Page 21
21
100% GEOTHERMAL HEAT
Heating connection
Heat distribution circuit surface sensors located on top of the storage tank must be installed to the distance of approx. 0.5 m from the three­way or four-way valve. Circuit HD1 is always the main heating circuit (rooms, for example); it is used for higher temperature (radiator heating, for example). In case of compressor malfunction, the electric heating element heats the circuit HD1 more efciently. Circuit HD2 is used in radiator-heated buildings for the possible oor heating share or for other purposes (e.g., humid rooms). In these cases the circuits can be con­trolled individually. The heat distribution circuits can be unconnected through Summer Fuctions for summer. In this case e.g. HD2 in humid rooms can only be used.
The pipes in the heating network are connected to the ground source heat pump using either textile hoses (network of radiators) or using a xed piping network (oor heating). These connections prevent sound from passing into the network. All heating connections (for example, a heating radiator for an air conditioner or a heated towel rail) must be made to the heat distribution circuits, not domestic hot water. When the network piping is in place, lling may commence.
NOTE! Maximum storage tank pressure is 1.5 bar!
NOTE! If renovating, ensure that the heat distribution piping has been properly rinsed before connecting the geothermal heat pump. If renova­ting, installing a mud separator to the heat ditribution circuit is recommended.
Speed controlling of the heat circulation pumps of Esi series
Heat circulation pumps with EMi/ELi-series determined by demand of the heatable estate. Heat circulation pumps will be adjusted according to manufacturer’s instructions.
Grundfos UPM3 AUTO heat circulation pump which is used in a HD circuit can be set in three different controlling modes: proportional pressure mode, constant pressure mode, constant curve mode. Factory setting is proportional pressure mode 3. In radiator network constant pressure mode 1 or 2 can be used if sound of the ow water is distur­bingly high.
Proportional pressure mode LED1
green
LED2
yellow
LED3
yellow
LED4
yellow
LED5
yellow
Proportional pressure mode 1
Proportional pressure mode 2
Proportional pressure mode 3
Auto
Adapt
Constant pressure mode LED1
green
LED2
yellow
LED3
yellow
LED4
yellow
LED5
yellow
Constant pressure mode 1
Constant pressure mode 2
Constant pressure mode 3
Auto
Adapt
Constant curve mode LED1
green
LED2
yellow
LED3
yellow
LED4
yellow
LED5
yellow
Constant curve mode 1
Constant curve mode 2
Constant curve mode 3
Constant curve mode 4
Storage tank and heating system lling and de-aeration
The storage tank is to be lled with special care through the group of ll valves included in the system so that the storage tank pressure never exceeds 1.5 bar. While lling the storage tank, the air inside it must be allowed to escape freely and not through air valve or safety valve, for example. Suomen Lämpöpumpputekniikka Oy cannot be held respon­sible for any expenses resulting from storage tank breakage in situations where the tank has not been lled with water pursuant to the above instructions.
There must be a de-aeration valve in the same branch with the group of ll valves. The expansion vessel may be in the same branch as well. The pipes in the network are lled with water.
Page 22
22
100% GEOTHERMAL HEAT
INSTALLATION
Filling and de-aerating a heating system tted with a pressure gauge:
• Open the ll valve on the heating network.
• Fill the network with water.
• De-aerate the storage tank and network until all the air has been
removed and leave the pressure at 1-1.2 bar (max. 1.5 bar).
• Maximum pressures:
• Heating network storage tank – 1.5 bar
• Domestic hot water circuit – 9 bar
Domestic hot water connections and circulation of water
If there is no domestic hot water circulation at the site, make connections pursuant to HVAC diagrams annexed to these instructions. Domestic water is connected to the ground source heat pump pursuant to the picture in Section 4.2.1. The same picture is provided on top of the unit, under the roof. The mixing valve is tted to the hot water pipe in order to prevent burns. The overow pipe is joined to the oor drain as instructed or to an overow funnel if the distance to the oor drain is more than two metres. The overow funnel must be directed down towards the oor drain. The backpressure valve is tted to the cold water joint on the input side (see the annexed HVAC connections diagram).
NOTE! External radiators or dryers may not be connected to domestic hot water circulation!
If the heatloss of the DHW circuit is considerd great it is recommended to install an ÄssäStream heater (see more in the ÄssäStream brochure).
HVAC checklist
Check that
• the joints are tight and there are no leaking valves
• the expansion vessel on the heating system and ll side is prop-
erly installed
• the overow pipe on the safety valve and the pressure gauge on
the heating system have been properly installed
• the heating system has been lled and de-aerated appropriately
• the ground circuit has been installed, lled and de-aerated
appropriately
4.3. Electrical installation and outdoor sensors
Only qualied electricians are permitted to carry out electrical work on the heat pump according to general regulations.
GSHP
El.network Fuse size slow, A (*bivalent models)
Esi 6
400V 3N~ 3x10 (*16)
Esi 9
400V 3N~ 3x16 (*20)
Esi 11
400V 3N~ 3x16 (*20)
Esi 14
400V 3N~ 3x16 (*20)
Esi 17
400V 3N~ 3x16 (*20)
Emi 22/22P
400V 3N~ 3x25 (*always congure separately)
Emi 28/28P
400V 3N~ 3x25 (*always congure separately)
Emi 43/43P
400V 3N~ 3x50 (*always congure separately)
ELi 60/60P
400V 3N~ 3x63 (*always congure separately)
ELi 90/90P
400V 3N~ 3x100 (*always congure separately)
The Lämpöässä heat pump is connected to a 400 V (50 Hz) electrical network. The Lämpöässä heat pump has been tted with an integrated electrical switchboard which is permanently powered. The location of the protection switch for the motor and other tripping devices are in the electrical switchboard that is inside the heat pump. The electrical switchboard is located at the top of the heat pump, under the plastic roof. The plastic roof of the product is removed by lifting it from the edges. A plastic-coated wire is used as a supply line, which wire travels to the master switch in a casing pipe. The electrical switchboard cover can be removed by undoing four screws on top of the switchboard.
While using the superheat function in Esi-model the connection plug (XP11) of superheat circuit pump (P11) needs to be mounted to the connection box. The connection box can be found from behind of the heat pump front plate. More details can be found from the annexed electrical connections diagram.
In the electrical connection of heat distribution pump (P12/P13) must be used plug-ins included in the package. See the annexed electrical con­nections diagram.
4.3.1. Outdoor sensor
In order for the outdoor sensor to recognise weather conditions as effec­tively as possible, it must be placed in the correct location. The outdoor sensor should be placed on the north-western or northern side of the building to avoid the effects of the morning sun. If the sensor cannot be placed as recommended, ensure that this is protected from direct sun light.
Page 23
23
100% GEOTHERMAL HEAT
The sensor is placed approximately 2/3 of the way up to the wall of the building near the corner. A sensor should not be placed under a roof, in a place protected from the wind or over a vent, doors or windows where the temperature is not the normal outdoor temperature.
Device Terminal Block No. Conductor Type
Outdoor sensor NTC X 1/10 and X 1/2 2 X 0,7 mm
2
4.3.2. Storage tank and heat distribution sensors
In Esi/Emi model with separate storage tank are the temperature sensors installed in the same water space on the top section of the storage tank. In such case same temperature settings are used for the top and lower sec­tions of the storage tank. The connections diagrams for cases where the ground source heat pump is connected to a Lämpöässä storage tank are found at Lämpöässä website. Heat distribution circuit sensors must be installed to the distance of approx. 0.5 m from the three-way or four-way valve to the owing line of the heat distribution circuit.
4.3.3. Room sensor (optional)
In order for the room sensor to detect average indoor temperatures as reliably as possible, it must be placed in a central and open location, for example a hallway between several rooms or the staircase. String a bipo­lar electrical line (at least 0.5 mm2) from the heat pump to the room sensor. Position the room sensor approximately 2/3 of the way up the wall. Connect the room sensor lead to the heat pump.
Device Terminal Block No. Conductor type
Room sensor NTC X 1/4 and X 1/2 2 X 0,7 mm
2
4.3.4. Current monitor
If the equipment has been installed in the part-power conguration, load limiting relays must be installed to the building’s master electrical switch­board, if necessary. These relays are intended to reduce the power of the ground source heat pump’s electric heating element by phases if the phase current passing through the building’s master fuses approaches the master fuse nominal current.
Current monitoring relay installations and connection
Load limiting relays are connected downstream of the master electrical switchboard’s master fuse so that the entire building’s main current passes through the relays. Contact data of load limiting relays are wired by quadrupole cable from the master switchboard to the ground source heat pump electrical switchboard, where they are connected to the con­trol circuit diagram.
These settings are initial and may require changing. Relays must always be adjusted in a case-specic manner.
• Choose correct current range
• Turn switch 2 to position
ON (if master fuse size is less than 50 A)
• Other switches 1, 3-6 to
position OFF.
• Adjust hysteresis, cur­rent % and delay using screws in the front part (master fuses 25 A)
• Hysteresis 21
• Current 25 - 28 %
• Delay 1s
• The relay requires external voltage 24-240 V/AC.
• External supply is con­nected to terminals A1 and A2.
• Terminals 15 and 16 are connected to geothermal heat pump and interrupt the heating element’s supply with respect to the phase the current value of which is exceeded.
• Each phase must be lead through the relay using the dedicated hole inside it.
• L1 for relay 1
• L2 for relay 2
• L3 for relay 3
No other connections with relay are necessary.
Page 24
24
100% GEOTHERMAL HEAT
INSTALLATION
Electrician’s checklist
Check that
• all phases going to the switchboard are in the correct phase sequence
• the master fuse is of sufcient size
• the ground source heat pump’s fuse size is correct, type: slow (C curve)
• if necessary, current monitor has been installed to the building’s master electrical switchboard (part-power models)
• the main cable is of sufcient size
4.4. Commissioning
Before commissioning, check that:
• the heating system has been connected, lled and de-aerated appropriately
• the ground circuit has been installed, lled and de-aerated appropriately
• electrical connections have been made appropriately and the outdoor sensor (and optional room sensor) has been installed
• after preventing the compressor from starting, water in the stor­age tank has been heated by the electric heating element for at
least 6 hours
If the ground source heat pump is started for the rst time without pre-heating, compressor will be damaged. Fill the storage tank with water and prevent the compressor from starting by pressing down the red compressor motor circuit breaker. Switch on the ground source heat pump’s power supply, the electric heating element begins to heat the water contained in storage tank. A regulator alarm goes on and the text “Compressor 1 circuit 1 some motor protection gone off. Check motor protection F1, F2 or F3” appears on the display. Later another regulator alarm goes on and the text “Resistor functioned in full power system” appears. These alarms do not require taking any measures. Starting of the compressor is allowed after six hours of pre-heating.
NOTE!
A compressor started without pre-heating
is not covered by warranty!
Possible problems during startup
Problem Cause Solution
Fuses always blow when the compres­sor is started.
You are using the wrong type of fuse.
Check that the fuse is auto­matic: C or D / ceramic fuse: SLOW or with a snail icon.
Temporary connections at the site are causing an overload of the fuses
Reduce load.
The heat collection circuit pump does not start.
The regulator may not be getting any power.
Check the regulator fuse.
The regulator is not au­thorised to start the pump.
Check the measured/set values.
The shut-off valves are in the ll position.
Check that the de-aeration and ll valves are in the closed position and that the intermediate valve is open.
The plug-ins of heat collection pump are unconnected from the swithboard.
Connect the plug-ins.
Control system is on manual control.
Remove manual control from the maintenance menu or switch off the ground source heat pump’s power supply for a moment.
The compres­sor runs for a little while and the evaporator pressure switch goes off.
There may still be air in the heat collection circuit.
De-aerate the heat collection circuit.
There may be a leak in the refrigerant circuit.
Contact the equipment installer or dealer.
There may be dirt in the mud separator.
Check the mud separator and clean as required.
The level of uid in the heat collection circuit. may be too low.
Check the level of the ll container and ll as required (de-aeration of groun circuit may be necessary as well).
Some valve in the heat collection circuit may be closed.
Check all valves and open if closed.
The compres­sor runs for a little while and the condenser pressure switch goes off.
There may be air in the condenser circuit or charge pump.
De-aerate charge circuit net­ween the device and storage tank. Open the charge pump and chech that the pump is operating.
The uid level in the heat collection circuit ll container drops suddenly after startup.
There is a leak in the system (the smell of ethyl alcohol or glycol is strong), there is a leak in the heat collection circuit or there is still air in the circuit.
Check the condition of valves in the de-aeration group, air valve and the shaft seal on the ground circuit pump, check the condition of heat collection circuit extension joints, or de-aerate.
Motor protection switches go off when starting.
The compressor or the ground circuit pump is short-circuited or one of the phases is not activated.
Check electrical connec­tions.
The fuses in the master switchboard of the build­ing have blown or are faulty.
Check and replace fuses as required.
The maintenance menu section Manual control allows manual control of compressors, pumps and valves. This facilitates troubleshooting process and may be of help in case of starting problems.
Page 25
25
100% GEOTHERMAL HEAT
5. MAINTENANCE
5.1. Maintenance and care
The Lämpöässä ground source heat pump is an easy-care and reliable heating system that does not require regular maintenance. If the instal­lation is carried out with care and in accordance with the instructions provided, there is usually no need for maintenance. The ll container and mixture circuit lter should be checked every couple of weeks during the rst few months and afterwards approximately once a month for the rst year of use thereafter. Also in pressurized systems it should be checked regularly that the pressure stays at approx. 1 bar.
Lämpöässä heat pumps which includes 3-6 kg refrigerant are hermati­cally sealed and therefore annual inspection is not required. You are offered the possibility of concluding an agreement on periodic inspec­tions, in connection with which the operation of the Lämpöässä heat pump is covered stage by stage. The observations are registered in the inspection record and necessary measures taken (such as adjustments, for example). For additional information on the periodic inspection agree­ment, visit huolto@lampoassa..
5.2. Possible problems occurring during use
Problem Possible cause Solution
The compressor does not start.
The water tank temperature is adequate and in accordance with the regulator.
No action re­quired.
The compressor has been stopped for less than 1 minutes.
No action re­quired.
Fuse problem. Check the condi-
tion of the fuses in the master switchboard.
Incorrect power supply phase se­quence.
Contact an electri­cian.
The compressor does not start and the display reads “Incorrect phase sequence” or “Motor protec­tion switch gone off”.
Incorrect power supply phase se­quence.
Contact an electri­cian.
The motor protection switch has gone off.
Check the motor protection switch adjustment val­ues, set the motor protection switch to Start position and acknowledge the alarm text displayed. If the fault is not cleared, contact an electrician.
The compressor does not start and the display reads “Low pres­sure switch gone off” or “High pressure switch gone off”.
The low pressure switch has gone off. Check functional-
ity of the brine circuit pump by running it through the mainte­nance menu and acknowledge the alarm text displayed.
The high pressure switch has gone off. Check func-
tionality of the condenser pump by running it through the main­tenance menu and acknowledge the alarm text displayed.
The compressor does not start and the display reads “Compres­sor 1 circuit 1 some motor protection gone off. Check motor protection F1, F2 or F3.”
The motor protection switch has gone off.
Press down the motor protection switch.
The suction pressure switch on the pressure switch has gone off.
Set off the switch.
No text is visible on the display.
The device is not getting any power. Check that that
the control cur­rent and master switches are on.
A fuse has blown. Check the build-
ing’s master fuse and heat pump supply fuse.
The display is damaged or the display cable loose or damaged.
Contact mainte­nance.
The system does not produce enough heat.
A sudden drop in outdoor temperature may temporarily cause inadequate heating power in new buildings, because moisture contained in the structure takes up a lot of heat when it dries.
No action re­quired.
During the rst year, the ground circuit may not produce heat at full power because the earth around the ground circuit pipes has not yet become more solid.
No action re­quired.
In the Measure- ments screen, the set value and measured value do not match.
Some active correction function (for example, timer or home/away) is adjusting the original set value.
The active correc­tion function can be deactivated, if required.
A spiking over-voltage caused by a lightning strike has caused a fault in the regulator (not under warranty), causing the temperature to drop from the actual values.
Replace the regu­lator (not under warranty).
The regulator motor has been set on manual and the regulation does not take place.
Return the heat distribution circuit adjustment motor to automatic mode.
In summer, when the building indoor temperature exceeds the value ad­justed, the supply water temperature sensor indicates higher readings as compared to the adjustment curve, due to rise in the heat distribution circuit temperature.
No action re­quired.
Page 26
26
100% GEOTHERMAL HEAT
MAINTENANCE
Etusivulle palataan näytön vasemmassa alakulmassa olevasta painikkeesta. Edelliselle sivulle palataan näytön oikeassa alakulmassa olevasta nuolipai-
nikkeesta. Oikean yläkulman i-painikkeesta avautuu ohjesivu. Toimintahäiriössä yläpalkkiin ilmestyy hälytyspainike.
The compres­sor is on all the time or for long periods of time.
A lot of heat is needed, for example the outdoor temperature is very low or the structure is drying during the rst year’s use of the building.
No action requi­red.
Lack of refrigerant. Can be detected from bubbles in the liquid container even after some minutes of use.
Contact a refrig­eration supplier or maintenance.
If these instructions do not help, please contact the equipment installer or your local dealer. If necessary, contact the Lämpöässä maintenance call centre at +358 40 841 8340.
5.3. Alarms
There are two ways to examine the alarms with ÄssäControl.
• You can see the active alarms if you press the alarm bell on front page. You can check out the alarms by pressing the check out alarms -button. You can go to alarm history from active alarms page by pressing the button at the bottom of the page.
• You can see earlier alarms by pressing the alarm history -button at the menu functions.
The software automatically stores the newest 100 fault messages. This menu allows resetting the fault log data stored. Possible alarms in Esi ground source heat pump:
• Compressor 1 circuit 1 some motor protection gone off. Check motor protection F1, F2 or F3.
• Compressor 1 internal heat protection gone off. Wait 45 min.
• Low pressure pressostat of circuit 1 functioned. Accept presostat.
• High pressure pressostat of circuit 1 functioned. Accept presostat
• Incorrect phase order. Change feed phase order.
• Temperature did not rise in pre set time. Resistance enabled.
• Outside temperatur sensor fault.
• Hot gas sensor 1 fault.
• Low boiler sensor fault.
• Top boiler sensor fault.
• Heating circuit 1 sensor fault.
• Heating circuit 2 sensor fault.
• Heating circuit 3 sensor fault.
• Hot water temperature sensor fault
• Room temperature sensor fault.
• Alarm of liquid circuit (optional)
• External alarm
• Resistor functioned in full power system
5.4. Maintenance procedures
NOTE! Access to the maintenance menu is password-protected. Access to the maintenance menu is restricted to Lämpöässä installer training graduates and certied installers. Status data can be monitored through the maintenance menu. The monitoring options include digital inputs and outputs, analog inputs and outputs, and variables.
Page 27
27
100% GEOTHERMAL HEAT
Etusivulle palataan näytön vasemmassa alakulmassa olevasta painikkeesta. Edelliselle sivulle palataan näytön oikeassa alakulmassa olevasta nuolipai-
nikkeesta. Oikean yläkulman i-painikkeesta avautuu ohjesivu. Toimintahäiriössä yläpalkkiin ilmestyy hälytyspainike.
5.4.1. Manual control
This screen allows bypassing automatics and controlling compressors, pumps, and valves manually. Control has been divided between digital outputs and analog outputs.
5.4.2. Input and output statuses
For the purpose and function of digital inputs and outputs, see the annexed equipment electrical diagrams.
Digital inputs
This screen allows checking digital input statuses.
Digital Input (ID)
1 Compressor 1 Motor protection 10 Low pressure alarm circuit 1
2 Not in use 11 High pressure alarm circuit 1
3 Brine pump 1 Run indicator 12 Compressor 1 Run indicator
4 Not in use 13 Not in use
5 Not in use 14 Soft Starter
6 Not in use 15 External Alarm
7 Compressor 1 internal alarm 16 Not in use
8 Not in use 17 Flow Sensor
9 Phase failure detector 18 Not in use
Digital outputs
This screen allows checking digital output statuses.
Digital Output (NO)
1 Brine circuit 1 10 Not in use
2 Not in use 11 Not in use
3 Alarm signal 12 Immersion heater 4
4 Compressor 1 13 Immersion heater 1
5 Condenser pump 1 14 Heating circuit pump 1
6 Magnetic valve 1 15 Heating circuit pump 2
7 Immersion heater 2 16 Heating circuit pump 3
8 Immersion heater 3 17 Not in use
9 Not in use 18 Pressure equalizing valve
(Only 1-phase devices)
Analog inputs
Page 28
28
100% GEOTHERMAL HEAT
MAINTENANCE
This screen allows checking analog input statuses.
Analog Input (B)
1 Hot gas sensor 1 6 Circuit 1 outgoing temperature sensor
2 Not in use 7 Circuit 2 outgoing temperature sensor
3 Boiler top part temperature sensor 8 Circuit 3 outgoing temperature / Me-
asurement of domestic hot water sensor
4 Boiler foot part temperature sensor 9 Not in use
5 Outside temperatur sensor 10 Brine circuit heat
Analog outputs
This screen allows checking analog output statuses.
Analog Output (Y)
1 Heating circuit 1 regulation motor
2 Heating circuit 2 regulation motor
3 Analog immersion heater control 0-10V
4 Heating circuit 3 regulation motor/ Adjusment of domestic hot water
5 Speed regulation of brine pump
6 Superheat valve regulation
5.4.3. Running information
This screen shows compressor’s current state.
Etusivulle palataan näytön vasemmassa alakulmassa olevasta painikkeesta. Edelliselle sivulle palataan näytön oikeassa alakulmassa olevasta nuolipai-
nikkeesta. Oikean yläkulman i-painikkeesta avautuu ohjesivu. Toimintahäiriössä yläpalkkiin ilmestyy hälytyspainike.
5.4.4. Heat distribution circuit quantity
There may be from 1 to 3 heat distribution circuits, of which circuits 2 and 3 are optional. If three heat distribution circuits are in use, the domestic water temperature limit function cannot be used at the same time
5.4.5. Domestic hot water temperature limit
This screen allows activation of the domestic hot water temperature limit and changing of the domestic hot water temperature sensor and the related position valve connection location. The default setting is that the temperature sensor is connected to analog input B8 and position valve to analog output Y4 .
5.4.6. Positioning valve control
This screen allows determining the settings of position valves associated with heat distribution circuits and domestic hot water temperature limit. Each adjustable circuit has two setting screens.
Page 29
29
100% GEOTHERMAL HEAT
Etusivulle palataan näytön vasemmassa alakulmassa olevasta painikkeesta. Edelliselle sivulle palataan näytön oikeassa alakulmassa olevasta nuolipai-
nikkeesta. Oikean yläkulman i-painikkeesta avautuu ohjesivu. Toimintahäiriössä yläpalkkiin ilmestyy hälytyspainike.
If the temperature at storage tank bottom part is lower than that of the heat distribution circuit, the storage tank temperature is automatically increased so as to meet the heat distribution circuit temperature with additional diver­gence value. Adjustment range 0...10 °C, factory setting 2 °C.
The following settings are possible for all circuits:
Setting Description Example
Reverse control (ON/OFF)
Reversing of position valve adjustment direction
In the OFF position, if voltage is 0 V, the regulator is in its extreme right position. In the ON position, if voltage is 0 V, the regulator is in its extreme left position.
Adjustment range (10...600°C)
The divergence from target temperature in which case the posi­tion valve is adjusted from one extreme position to another. Factory setting: 300 °C.*
If the adjustment range is 140 °C and the target temperature differs from the current temperature by 14 °C, the valve is adjusted to 10% of the maximum. If the temperature changes too quickly, the adjust­ment range is increased. If the temperature changes too slowly, the adjustment range is decreased.
Integration time (5...300 s)
Temperature diver­gence correction interval(s). Factory setting: 50 s.**
If integration time is 10 s, the valve position is changed once in every 10 s, if required.
Derivative time (0...10 s)
Temperature diver­gence reaction time. Factory setting: 0.
The longer the derivative time, the more the regulator position changes upon each adjustment. Consider that increase in derivative time may result in increased regulator uctuation.
Voltage (0...10 V)
Position valve control voltage min and max values. Factory set­ting: 0.0-10.0 VAC.
This setting depends on the regula­tor used.
Temperature di­vergence (0...10 °C)
Allowed divergence from target tempera­ture. Factory setting:
0 °C.
At value 5 °C, the regulator position is changed only after the difference between the actual temperature and target temperature exceeds 5 °C.
Frequency of measurements (0...30 s)
How often is the current temperature checked. Factory setting: 0.
At value 15 s, the current tem­perature is checked once in every 15 s. At value 0 the checking is continuous.
* Domestic water limit 30 °C ** Domestic water limit 40 s.
5.4.7. Part-power / Full power
The maintenance menu allows switching between full power (default setting) and part-power, in which case the equipment allows activation of the electric heating element or some other source of additional heat simultaneously with the compressor.
The heating time before heating element activation can be set under Additional heat settings in the Other set values screen.
5.4.8. Immersion control
Electrical immersions can be controlled with both digital and analogic signal. Selection is made in this screen. Analogic controller adjusment is in the screen Other setting points / External heating control / Settings / Analogic adjusment setting.
Page 30
30
100% GEOTHERMAL HEAT
MAINTENANCE
5.4.9. Temperature gauges
This screen allows choosing the temperature gauges used. By default, the outdoor temperature gauge is present. Indoor temperature gauge is optional.
5.4.10. External alarm
On this page, if in use, external alarm settings are dened. Status is eit­her info or serious. Is the status is info external alarms doesn´t affect to the heat pump operation. Is the status is serious compressors are not starting. External alarm can be connected to digital inputs 17 or 18.
5.4.11. Soft starter alarms
The soft starter alarms can be activated at this page.
5.4.12. Super heat valve control
This menu is for adjusting superheat trim valve settings. Value in the menu indicates the setting point when compressor is running. Valve position bet­ween the compressor runs indicates valve settings point when compressor is not running. Frequency between the ushes is settled with rinse interval. Rinse is implemented on the rst running period of the day when time indicated in the rinse interval is full. Valve type (NP/NC) is dened with the diversed controlling. Manual controlling settles the valve to the percentage indicated in the valve setting point. The factory setting for super heat valve control can be found from the Technical specifations table.
Page 31
31
100% GEOTHERMAL HEAT
5.4.13. Boiler maximum limits
Maximum boiler limits are set on this page.
5.4.14. Cooling
Controlling methods available: Roomtemp, External and Manual. Selection of the brine speed while cooling is operating..
Three way valve control settings in a free cooling.
Digital output selection in exible cooling.
Manual mode for cooling is intended for testing the function. Manual settings can be controlled from the functions menu. From there it’s pos­sible to adjust the cooling systems mode, temperature limits and humi­dity values manually.
5.4.15. Return factory settings
Returning the factory settings and browsing the alarm history in this view.
Page 32
32
WARRANTY CONDITIONS
100% GEOTHERMAL HEAT
6. WARRANTY CONDITIONS
The manufacturer grants its products a two (2) year warranty from the commissioning date specied in the product’s warranty certicate. Dur­ing the warranty period, the manufacturer is responsible for that the product complies with its agreed characteristics and is free of manufac­turing or design defects. The manufacturer’s responsibility for the faults of its products involves only repair of a faulty product or replacement thereof with a faultless products, within a reasonable time and at the manufacturer’s discretion. The manufacturer shall take care of product repairs through its own maintenance service or authorized maintenance centre. Faulty product components must be returned to the manufacturer.
The warranty does not cover any faults discovered in the products that have been caused through negligence of the purchaser or other user of the product, failure to comply with the product’s instructions for use, maintenance or care, extreme voltage uctuations (over ±10 % of the nominal voltage), lightning, re or other respective event. Transport dam­ages are not covered by the warranty. Also, the warranty does not cover situations caused by product installation to the place of use in contradic­tion with instructions for installation or use or otherwise incorrectly, or by product repair, modication or installation by some other party than the manufacturer or a maintenance company authorised by the manufacturer.
The warranty does not cover the adjustments or ground circuit and heat distribution circuit de-aeration procedures specied in the instructions for use. Furthermore, the warranty does not cover any faults caused by use of unauthorised and corrosive uids in the ground circuit piping. The manufacturer only grants the aforementioned warranty and this warranty is the only warranty granted by the manufacturer to its products. The aforementioned warranty does not concern any additional equipment or accessories installed afterwards and subject to their own warranty.
An additional warranty condition associated with Lämpöässä geothermal heat pump is compressor preheating prior to starting thereof for the rst time (see 4.4. Commissioning).
Page 33
33
TECHNICAL SPECIFICATIONS
100% GEOTHERMAL HEAT
7. TECHNICAL SPECIFICATIONS
LÄMPÖÄSSÄ Esi 6 Esi 9 Esi 11
Esi 11
1x230V
Esi 14
Esi 14
1x230V
Esi 17 Emi 22(22P) Emi 28 (28P) Emi 43 (43P) ELi 60 (60P) ELi 90 (90P)
Width mm 595 595 595 595 595 595 595 920 920 920 1200 1200 Depth mm 680 680 680 680 680 680 680 680 680 680 680 680 Height mm 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450 1450 Weight kg 174 178 192 192 202 202 210 395 (387) 395 (387) 412 (420)
515 (505) 605 (595) Heat pump type Brine-to-water Compressor type Scroll Refrigerant R407C R407C R407C R407C R407C R407C R407C R407C R407C R407C R410A R410A Refrigerant volume g 1400 1900 2000 2000 2500 2500 2600 4900 (4700) 5000 (4800) 5700 (5900) 8700 (8500) 10000(9800) Compressor oil POE POE POE POE POE POE POE POE POE POE POE POE Storage tank volume l - - - - - - - - - - - ­Maximum pressure of heat tank bar - - - - - - - - - - - ­Heating regulator ÄssäControl Evaporator material Stainless Steel Brine volume in evaporator l 2,6 2,6 3,2 3,2 4,2 4,2 4,7 7,5 7,5 8,4 10,0 15,0 Condenser material Stainless Steel Water volume in condenser l 1,8 1,8 2,7 2,7 3,6 3,6 4 7,5 7,5 8,4 7,0 10,0 Factory setting of condenser pump Constant curve 2 Constant curve 3 Constant curve 3 Constant curve 3 Factory setting of superheat circuit % 35 35 40 40 40 40 40 55 (-) 55 (-) 55 (-) 75 (-) 85 (-) Sound power level(1 dB 37 37 40 41 41 42 41 45 46 49 - 65 OPERATION LIMITS: Temperature limits (brine/water) °C -10/60, 15/30 -10/60, 20/30 Pressure limit (refrigerant) bar 1,5/29 4/45 PERFORMANCE DATA: Heating power at temperature 35°C
(2
kW 8,44 10,44 12,38 12,14 15,64 14,98 17,75 22,42 29,52 46,19 60,69 91,03
Heating power at temperature 55°C
(2
kW 7,75 9,82 11,45 11,2 14,47 13,65 16,71 20,71 26,75 42,83 58,13 86,24
Cooling power at temperature 35°C
(2
kW 6,91 8,49 10,09 10,24 12,75 12,91 14,37 17,57 23,19 33,15 46,67 67,03
Cooling power at temperature 55°C
(2
kW 5,62 6,88 8,16 8,19 10,28 10,32 11,69 14,25 18,24 27,64 37,22 53,96
Input power at temperature 35°C
(2
kW 1,70 2,15 2,49 2,53 3,20 3,28 3,67 4,99 6,47 10,25 13,06 20,18 Input power at temperature 55°C(2 kW 2,34 3,10 3,44 3,60 4,33 4,62 5,13 6,55 8,62 13,32 18,83 28,26 COP at temperature 35°C(2 4,96 4,84 4,97 4,79 4,88 4,56 4,84 4,49 4,56 4,50 4,64 4,51 COP at temperature 55°C(2 3,30 3,17 3,33 3,11 3,33 2,95 3,25 3,16 3,10 3,22
3,08 3,05
SCOP35°C/Energyefciencyclass35°C
(3
5,24 / A++* 5,13 / A++* 5,29 / A++* 5,10 / A++* 5,31 / A++* 4,97 / A++* 5,22 / A++* 4,98 / A++* 5,09 / A++* 5,06 / A++* 4,95 / A++* -
SCOP55°C/Energyefciencyclass55°C
(3
3,88 / A++* 3,83 / A++* 3,99 / A++* 3,80 / A++* 4,02 / A++* 3,73 / A++* 3,96 / A++* 3,83 / A++* 3,66 / A++* 3,88 / A++* 3,82 / A++* -
Energyefciencyclassat35°C(space
heating / domestic hot water), package
(4
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
A
+++
Energyefciencyclassat55°C(space
heating / domestic hot water), package
(4
A
+++
A
+++
A
+++
A
+++
A
+++
A
++
A
+++
A
+++
A
++
A
+++
A
+++
A
++
ELECTRICS:
Power supply 400V 3N~ 50Hz
230V 1N~
50Hz
400V 3N~
50Hz
230V 1N~
50Hz
400V 3N~
50Hz
400V 3N~ 50Hz 400V 3N~ 50Hz
Starting current A 17 23 32 48 35 32 43 50 60 100 85 125 Running current (35°C / 55°C)(2 A 3,28 / 4,18 4,33 / 5,52 5,04 / 6,29 12,96/17,82 6,84 / 8,17 22,47/29,97 7,45 / 9,24 11,98/13,53 13,70/16,54 19,35/23,74 24,11/32,07 38,60/49,33 Fuse size (bivalent model) A 3 x 10 (16) 3 x 16 (20) 3 x 16 (20) 32 3 x 16 (20) 40 3 x 16 (20) 3 x 25 3 x 25*** 3 x 50 3x63 3x100 Immersion heater as a backup heating kW - - - - - - - - - - - ­Supply cable size (bivalent model)(5 mm2 5x2,5 (5x6) 3 x 6 5x2,5 (5x6) 3 x 10 5x2,5 (5x6) 5 x 10 5 x 10 5 x 16 5 x 25 5 x 50 Soft starter Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Current control Accessory No Accessory No Accessory Accessory Accessory Compressor motor circuit breaker setting A 6 7 9 22 10 - 12 17 21 32 50 79
Page 34
34
TECHNICAL SPECIFICATIONS
100% GEOTHERMAL HEAT
HEAT COLLECTION CIRCUIT(S): Esi 6 Esi 9 Esi 11
Esi 11
1x230V
Esi 14
Esi 14
1x230V
Esi 17 Emi 22(22P) Emi 28 (28P) Emi 43 (43P) ELi 60 (60P) ELi 90 (90P)
Energy class of brine pump A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) Input power of brine pump W 5-89 5-89 10-170 10-170 10-170 10-170 10-170 160-1330 160-1330 160-1330 30-2100 Factory setting of brine pump % 90 90 90 90 90 90 90 90 90 90
90 100
Ground loop maximum length, 1 ground loop
(6
Borehole, PEH, PN6
m 500 350 450 500 - - - - - - - -
Horizontal pipe, PEM, PN10
m 450 300 - 380 - - - - - - - -
Ground loop maximum length, 2 ground loops
(6
Borehole, PEH, PN6
m - 900 1200 1600 900 1000 600 1050 - - - -
Horizontal pipe, PEM, PN10
m - 750 1050 1250 650 800 500 900 - -
- -
Ground loop maximum length, 3 ground loop
(6
Borehole, PEH, PN6
m - - - - - - - - 700 -
500 -
Horizontal pipe, PEM, PN10
m - - - - - - - - 550 - 400 -
Ground loop maximum length, 4 ground loop
(6
Borehole, PEH, PN6
m - - - - - - - - - 750 900 -
Horizontal pipe, PEM, PN10
m - - - - - - - - - 600 700 -
Nominalow
∆T=3K(ISO
14511)
l/s 0,64 0,79 0,94 0,91 1,18 1,11 1,34 1,65 2,19 3,41 - 700
Maximum external pressure drop
kPa 53 48 81 82 65 71 54 203 89*** 127 - 550
Nominalow
∆T=4K
l/s 0,48 0,59 0,70 0,68 0,89 0,83 1,00 1,24 1,64 2,56
- 900
Maximum external pressure drop
kPa 66 65 96 100 84 91 77 208 100*** 152 - 750
HEAT DISTRIBUTION CIRCUIT: Energy class of HC pump A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter) A (inverter)
Accessory
Input power of HC pump W 5-53 5-53 5-53 5-53 5-53 5-53 5-53
Nominalow
∆T=5KFloor
heating
l/s 0,40 0,50 0,59 0,58 0,74 0,71 0,70**
Maximum external pressure drop
kPa 51 42 29 30 15 18 19**
Nominalow
∆T=10KRa-
diator heating
l/s 0,18 0,23 0,27 0,27 0,34 0,33 0,40
Maximum external pressure drop
kPa 71 69 66 66 57 60 51
*MeetstheenergyefciencyclassA+++requirements.MeetsthedomestichotwaterenergyefciencyclassA+requirements. **Calculatedaccordingtonominalowat∆T=7K. ***Maximumexternalpressuredropispossibletoraise191kPa∆T3,(204∆T4)whenusing35Afuses.Contacttoyourlocaldealer.
1) Tested according to ISO 3744/2010 at standard point B0/W55.
2) Tested according to ISO 14511/2013.
3) Tested according to EU 811/2013 at colder climate conditions.
4) Package means the combination of heat pump and heating regulator (EU 811/2013).
5) If conditions are requiring long cable work it is recommended to use 5x6 mm2 cable.
6)Calculatedlengthaccordingtonominalowat∆T=4K.Actualpressuredropisdeterminedcasebycase.
8. ENERGY LABEL
9. HVAC SCHEMES
10. ELECTRICITY SCHEMES
Page 35
A
++
A
++
55 °C 35 °C
60 dB
00 dB
58
58
58
kW
61
61
61
kW
2015 811/2013
ELi 60
A
++
A
+
A B C D E F G
Page 36
+
+
A
++
+
+
A
++
A
+++
A
A
B
C D E
F
+
A
+++
A
++
A
+
A
B
C
D
E
F
G
A
+++
2015 811/2013
X
ELi 60
Page 37
100% GEOTHERMAL HEAT
www.lampoassa.fi
Product description
Name or trademark Lämpöässä Model ELi 60 Seasonal space heating energy efciency class A
++
Rated output under average climate conditions 58 kW Seasonal space heating energy efciency under average climate conditions 153 % Annual electricity consumption for space heating 31414 kWh/a Sound power level indoors 49 dB
Rated heat output, included the rated heat output of any supplementary heater under colder and warmer climate coditions
Colder 58 kW Warmer 58 kW
Seasonal space heating energy efciency under colder and warmer climate conditions Colder 157 %
Warmer 154 %
Annual energy consumption under colder and warmer climate conditions Colder 36542 kWh/a
Warmer 20178 kWh/a
Package information
Controller class III Controller contribution to efciency 1,5 %
Seasonal space heating energy efcieny class of package A+++
Seasonal space heating energy efcieny of package in average climate conditions 154 % Seasonal space heating energy efcieny of package in colder climate conditions 158 % Seasonal space heating energy efcieny of package in warmer climate conditions 155 %
Function Heating Average
Warmer (if designated) Colder (if designated)
Capacity control Fixed
Design load Heating Average Pdesignh 154 kW
Warmer Pdesignh 158 kW Colder Pdesignh 155 kW
Seasonal efciency Heating Average SCOP/A 155 %
Warmer SCOP/W 152 % Colder SCOP/C 160 %
Page 38
100% GEOTHERMAL HEAT
www.lampoassa.fi
Declared capacity for heating at indoor conditions 20°C and outdoor temperature Tj
Heating Average Tj = -7 °C
58,0
kW
3,23
COPd
Tj = 2 °C
58,8
kW
3,78
COPd
Tj = 7 °C
59,3
kW
4,17
COPd
Tj = 12 °C
59,9
kW
4,58
COPd
Tj = bivalent temperature
58,1
kW
3,08
COPd
Tj = operation limit
58,1
kW
3,08
COPd
Warmer Tj = 2 °C
58,1
kW
3,08
COPd
Tj = 7 °C
58,3
kW
3,53
COPd
Tj = 12 °C
59,5
kW
4,33
COPd
Tj = bivalent temperature
58,1
kW
3,08
COPd
Tj = operation limit
58,1
kW
3,08
COPd
Colder Tj = -7 °C
58,6
kW
3,66
COPd
Tj = 2 °C
59,1
kW
4,10
COPd
Tj = 7 °C
59,7
kW
4,47
COPd
Tj = 12 °C
60,1
kW
4,73
COPd
Tj = bivalent temperature
58,1
kW
3,08
COPd
Tj = operation limit
58,1
kW
3,08
COPd
Degradiation coefcient when Tj = -7°C Cdh 1,00
Bivalent temperatures Heating Average. Tbivalent -10 °C
Warmer Tbivalent -22 °C Colder Tbivalent 2 °C
Operation limit temperatures
Heating Average. TOL -10 °C
Warmer TOL -22 °C Colder TOL 2 °C
Seasonal electricity consumption
Heating Average. QHE/A 31414 kWh/a
Warmer QHE/W 36542 kWh/a Colder QHE/C 20178 kWh/a
Modes other than ”active mode” Off mode P
OFF
0,017 kWh
Standby mode P
SB
0,017 kWh
Thermostat off mode P
TO
0,017 kWh
Cranckcaseheater mode P
CK
0,017 kWh
Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy
Address Unikontie 2, 62100 LAPUA, FINLAND
Page 39
A
++
A
++
55 °C 35 °C
60 dB
00 dB
58
58
58
kW
61
61
61
kW
2015 811/2013
ELi 60P
A
++
A
+
A B C D E F G
Page 40
+
+
A
++
+
+
A
++
A
+++
A
A
B
C D E
F
+
A
+++
A
++
A
+
A
B
C
D
E
F
G
A
+++
2015 811/2013
X
ELi 60P
Page 41
100% GEOTHERMAL HEAT
www.lampoassa.fi
Product description
Name or trademark Lämpöässä Model ELi 60P Seasonal space heating energy efciency class A
++
Rated output under average climate conditions 58 kW Seasonal space heating energy efciency under average climate conditions 153 % Annual electricity consumption for space heating 31414 kWh/a Sound power level indoors 49 dB
Rated heat output, included the rated heat output of any supplementary heater under colder and warmer climate coditions
Colder 58 kW Warmer 58 kW
Seasonal space heating energy efciency under colder and warmer climate conditions Colder 157 %
Warmer 154 %
Annual energy consumption under colder and warmer climate conditions Colder 36542 kWh/a
Warmer 20178 kWh/a
Package information
Controller class III Controller contribution to efciency 1,5 %
Seasonal space heating energy efcieny class of package A+++
Seasonal space heating energy efcieny of package in average climate conditions 154 % Seasonal space heating energy efcieny of package in colder climate conditions 158 % Seasonal space heating energy efcieny of package in warmer climate conditions 155 %
Function Heating Average
Warmer (if designated) Colder (if designated)
Capacity control Fixed
Design load Heating Average Pdesignh 154 kW
Warmer Pdesignh 158 kW Colder Pdesignh 155 kW
Seasonal efciency Heating Average SCOP/A 155 %
Warmer SCOP/W 152 % Colder SCOP/C 160 %
Page 42
100% GEOTHERMAL HEAT
www.lampoassa.fi
Declared capacity for heating at indoor conditions 20°C and outdoor temperature Tj
Heating Average Tj = -7 °C
58,0
kW
3,23
COPd
Tj = 2 °C
58,8
kW
3,78
COPd
Tj = 7 °C
59,3
kW
4,17
COPd
Tj = 12 °C
59,9
kW
4,58
COPd
Tj = bivalent temperature
58,1
kW
3,08
COPd
Tj = operation limit
58,1
kW
3,08
COPd
Warmer Tj = 2 °C
58,1
kW
3,08
COPd
Tj = 7 °C
58,3
kW
3,53
COPd
Tj = 12 °C
59,5
kW
4,33
COPd
Tj = bivalent temperature
58,1
kW
3,08
COPd
Tj = operation limit
58,1
kW
3,08
COPd
Colder Tj = -7 °C
58,6
kW
3,66
COPd
Tj = 2 °C
59,1
kW
4,10
COPd
Tj = 7 °C
59,7
kW
4,47
COPd
Tj = 12 °C
60,1
kW
4,73
COPd
Tj = bivalent temperature
58,1
kW
3,08
COPd
Tj = operation limit
58,1
kW
3,08
COPd
Degradiation coefcient when Tj = -7°C Cdh 1,00
Bivalent temperatures Heating Average. Tbivalent -10 °C
Warmer Tbivalent -22 °C Colder Tbivalent 2 °C
Operation limit temperatures
Heating Average. TOL -10 °C
Warmer TOL -22 °C Colder TOL 2 °C
Seasonal electricity consumption
Heating Average. QHE/A 31414 kWh/a
Warmer QHE/W 36542 kWh/a Colder QHE/C 20178 kWh/a
Modes other than ”active mode” Off mode P
OFF
0,017 kWh
Standby mode P
SB
0,017 kWh
Thermostat off mode P
TO
0,017 kWh
Cranckcaseheater mode P
CK
0,017 kWh
Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy
Address Unikontie 2, 62100 LAPUA, FINLAND
Page 43
Page 44
Page 45
Page 46
Page 47
Page 48
Page 49
Page 50
Page 51
Page 52
Page 53
Page 54
Page 55
Page 56
Page 57
Page 58
Page 59
Page 60
Page 61
Page 62
Lämpöässä is a trademark of Suomen Lämpöpumpputekniikka Oy. We reserve the right to make changes.
Suomen Lämpöpumpputekniikka Oy
Unikontie 2
62100 Lapua
FINLAND
www.lampoassa.com
R
Loading...