LAMBORGHINI thin 24 MCS W TOP U/IT Installation And Maintenance Manual

Page 1
CALDAIA MURALE A GAS PER ESTERNO - ALTO RENDIMENTO - MODULANTE
WALL-HUNG GAS BOILER FOR OUTDOOR INSTALLATION - HIGH EFFICIENCY - MODULATING UNIT
CALDERA MURAL A GAS PARA EXTERIOR - ALTO RENDIMIENTO - MODULANTE
CALDEIRA DE PAREDE A GÁS PARA AMBIENTES EXTERNOS - ALTO RENDIMENTO - MODULÁVEL
MANUALE DI
INSTALLAZIONE E
MANUTENZIONE
INSTALLATION
AND MAINTENANCE
MANUAL
MANUAL PARA
LA INSTALACIÓN Y
EL MANTENIMIENTO
MANUAL DE INSTALAÇÃO E MANUTENÇÃO
PREGASI CONSEGNARE L'INSERTO "MANUALE D'USO" AL SIG. UTENTE
PLEASE MAKE SURE THAT THE "USE MANUAL" IS HANDED OVER TO THE USER
TENGAN LA AMABILIDAD DE ENTREGARLE AL USUARIO EL "MANUAL DE USO"
FAVOR ENTREGAR O "MANUAL DE USO" AO SR. UTENTE
0444 351044
AZIENDA CERTIFICATA ISO 9001
-VI
24 MCS W TOP
U/IT
Page 2
37
INDEX PAGE
GENERAL INSTRUCTIONS _______________________________________________39 DESCRIPTION _________________________________________________________40 MAIN COMPONENTS __________________________________________________41 DIMENSIONS _________________________________________________________42 TECHNICAL FEATURES __________________________________________________42 NOZZLE CALIBRATION__________________________________________________43 ELECTRICAL CONNECTIONS - WIRING DIAGRAMS _________________________44 INSTALLATION AND START-UP ___________________________________________47 SETTING THE TIME/DAY OF THE WEEK ___________________________________48 MODES ______________________________________________________________48 “AUTOMATIC” TEMPERATURE CONTROL MODE ____________________________49 “MANUAL” TEMPERATURE CONTROL MODE_______________________________50 SETTING THE TEMPERATURE _____________________________________________51 VIEWING MAIN BOILER PARAMETERS ____________________________________52 RE-ESTABLISHING FACTORY SETTINGS AND CONTROL RESET ________________53 ERROR MESSAGES _____________________________________________________53 INSTALLER SETTINGS ___________________________________________________54 HYDRAULIC CONNECTION _____________________________________________56 HYDRAULIC CIRCUIT____________________________________________________57 INSTALLATION _________________________________________________________ 58 STARTING UP __________________________________________________________58 FLUE EXHAUST TYPES___________________________________________________59 FLUE EXHAUST CONNECTION ___________________________________________ 60 FLUE EXHAUST INSTALLATION ___________________________________________62 ADJUSTMENTS ________________________________________________________63 SWITCHING OFF ______________________________________________________64 MAINTENANCE _______________________________________________________64 OPERATION WITH DIFFERENT TYPES OF GAS ______________________________65 ANTI-FREEZE KIT (ON REQUEST) _________________________________________ 66 FAULT-FINDING CHART _________________________________________________67
Congratulations....
......on an excellent choice.
We thank you for the preference accorded to our products. LAMBORGHINI CALORECLIMA has been actively present in Italy and throughout the world since 1959 with a widespread network of agents and concessionary agents to constantly guarantee the presence of our product on the market. Alongside this is the support of a technical service, “LAMBORGHINI SERVICE”, which is entrusted with the qualified servicing of the product.
For the installation and positioning of the boiler:
CAREFULLY OBSERVE THE LOCAL REGULATIONS IN FORCE
Page 3
Page 4
39
GENERAL INSTRUCTIONS
This booklet constitutes an integral and essential part of the product. Read carefully the instructions contained in this booklet as they provide important directions regarding the safety of installation, use and maintenance. Preserve this booklet with care for any further consultation. The installation of the boiler must be carried out in compliance with current regulations, according to the instructions of the manufacturer and by qualified personnel. An incorrect installation can cause injury or damage to persons, animals and objects, for which the manufacturer cannot be held responsible.
After removing the packaging materials, check the content integrity. In case of doubt, do not use the unit and contact the supplier. The packaging material (wooden crates, nails, clips, plastic bags, foam, etc.) must not be left within reach of children as they are potential sources of danger.
This boiler is designed to heat water to a temperature below boiling (atmospheric pressure). It must be connected to a heating system compatible with its performances and output.
This appliance should be destined only for the use for which it has been expressly envisaged. Any other use is to be considered improper and therefore dangerous. The manufacturer cannot be considered responsible for any damages caused from improper, erroneous or unreasonable use.
ALL INSTALLATION, MAINTENANCE AND GAS CONVERSION OPERATIONS MUST BE CARRIED OUT BY AUTHORISED SKILLED TECHNICIANS.
TO ENSURE THAT BOILER IS INSTALLED CORRECTLY AND THAT IT FUNCTIONS PROPERLY, WE RECOMMEND THAT ONLY LAMBORGHINI ACCESSORIES AND SPARE PARTS BE USED.
ON NOTICING THE SMELL OF GAS DO NOT TOUCH ANY ELECTRIC SWITCH. OPEN DOORS AND WINDOWS, SHUT OFF THE GAS COCKS.
WARNING: FIT A SAFETY DEVICE ON THE FLUE EXHAUST DUCT SO AS TO ELIMINATE ANY SOURCE OF DANGER TO CHILDREN OR ADULTS AND PREVENT CONTACT WITH FLAMMABLE MATERIALS.
Page 5
Page 6
41
MAIN COMPONENTS
LEGEND
1 Ignition electrodes 2 Manual air purge valve 3 Fumes fan 4 Total safety thermostat 5 Fumes pressure switch 6 Heating detector 7 3-way valve 8 Hydrometer 9 Filling cock 10
Reset push-button with lock-out warning light
11 Hot water pressure switch 12 Lack of water pressure switch 13 Manual air purge valve 14 Electric box
15 Instantaneous water-heater 16 Hot water circuit drain cock 17 Hot water detector 18 Automatic air purge valve 19 Circulating pump 20 Heating safety valve 21 Heating circuit drain cock 22 Gas cock 23 Gas valve 24 Electronic control unit 25 Expansion tank
Page 7
Page 8
43
The boilers leave the factory calibrated and predisposed to operate with NATURAL GAS and LIQUID GAS. These calibrations are effected without the connection of the compensating joint (Pos. A).
For the calibrations to put into effect, see the table related below:
BURNER PRESSURE CURVES - OUTPUT
GAS - NOZZLE CALIBRATION
Pressure on nozzles mbars Delivery
Burner
nozzles
min. max. m3/h Ø mm.
Gas type
NATURAL GAS
(G20-20mbars)
LIQUID GAS B
(G30-28/30mbars)
LIQUID GAS P
(G31-37mbars)
2
5
6,2
11
25
32
3,06
0,89
1,17
1,25
0,77
0,77
L.C.V.
kcal/h
8.550
29.330
22.360
A Compensating joint B Connecting pipe
To effect the gas valve calibration, proceed as follows:
a)
take the pipe
i B
off the joint
A;
b)
effect calibration;
c)
connect the pipe B again to the joint A.
Page 9
Page 10
45
PRINCIPLE DIAGRAM
BM Modulating coil CA Ignition control unit Honeywell CiR Circulating pump EC Control electrode ES Spark electrode L Line MAX R
Max. heating setting
N Neutral PF Fumes pressure switch Pma Lack of water pressure switch PR Reset push-button P.risc.
Heating potentiometer
PS Hot water pressure switch P.san.
Hot water potentiometer
RT RL3 relay contact
RS R4 relay contact RP RL2 relay contact RF Anti-interference resistance SB Lock-out warning light SR Heating detector SS Hot water/water-heater detector SW1 Function selector TIMER
Boiler timer adjustment
TR1 Transformer TST Total safety thermostat V 3-way valve VG Gas valve VN Fan
LEGEND
NOTE: Slow ignition (RLA) is of the mechanical type positioned on the gas valve as illustrated in the figure on page 65.
Page 11
Page 12
47
INSTALLATION AND START-UP
Remove the control unit base-block by levering the two lower hooks (fig. 1).
Fix the control unit to the wall via the holes in the base-block. This should be mounted 1.5 m above the floor in an area well away from entry/exit doors, windows or other factors that might influence room temperature readings (fig. 2). After making sure that electrical power at the boiler is OFF proceed with the electrical connections using bi­polar wiring: do not route the wiring parallel to the main power supply wires/leads. If it is not possible to avoid taking the same wiring route use a shielded lead, the braid of which must be connected to an earth. Connect the lead extremities to the ”+IN+” terminal block (fig. 3). It is highly important that you observe the indicated polarities (boiler + to control +, boiler – to control -) Lead length must not exceed 50 m.
fig. 1 fig. 2
fig. 3
BOILER
CONTROL
UNIT SWITCH
OUTDOOR
SENSOR
+ BOILER
- BOILER
Page 13
Page 14
49
“HOT WATER/HEATING” MODE ( AND SYMBOLS DISPLAYED)
This mode provides both hot water and heating, operated automatically according to requirements.
“HEATING” FUNCTION ( SYMBOL DISPLAYED)
This mode enables the boiler for activation of the heating circuit in “Automatic” or “Manual”. When this mode is selected you can adjust heating water temperature and set the on/off times to be used in automatic mode. In this mode, any request for the production of hot water will be ignored.
“AUTOMATIC” TEMPERATURE CONTROL MODE
The control unit has a daily/weekly timer that automatically adjusts room temperature to “comfort” or “low temperature” values over a 24 hour period, with independent settings for each of the seven days.
To enable automatic operation press the key and the symbol will be displayed. Hourly programming of temperature values is only permitted with the Heating or Hot water/Heating functions enabled.
HOURLY PROGRAMMING OF TEMPERATURE VALUES
Press key V to select the desired day on the indicators. The display will then show the programme graph for the selected day by displaying the “indicator lights” next to the “comfort” level.
To modify these settings press P within 5 seconds. The time “00:00” will now appear on the display and the indicator light corresponding to that time will begin to flash. Press the + and – keys to increase or decrease the time in 30-minute steps.
The and symbols show the present value of the indicator light ( comfort temperature
level and low temperature level)
Select the desired value by acting on the (comfort temperature level) and (low tempera­ture level) keys. The indicator light will take on the desired value and programming will advance by one step: the next indicator light to be programmed will then flash. Once programming is over press P to memorise settings or V to cancel the modifications. The timer can memorise up to 48 daily temperature value changes.
Page 15
Page 16
51
SETTING THE TEMPERATURE
The control unit allows the user to set 5 basic temperatures in order to provide maximum comfort and maximum system efficiency.
HOT WATER TEMPERATURE
This temperature may be set with either the Hot water or Hot water/Heating function enabled.
To set press the key and the presently set temperature will appear on the display.
Now hold the
key down and press the – or + keys to modify the temperature setting as desired.
In addition to the displayed value the
symbol graphically illustrates the temperature setting.
Release the key to memorise the new setting.
HEATING WATER TEMPERATURE
This temperature may be set with either the Hot water/Heating or Heating function enabled.
To set press the key and the presently set temperature will appear on the display.
Now hold the key down and press the – or + keys to modify the temperature setting as desired.
In addition to the displayed value the symbol graphically illustrates the temperature setting.
Release the key to memorise the new setting. Should the boiler be equipped with an outdoor sensor, the values being displayed and set are outdoor temperature and heating water temperature.
STANDARD ROOM TEMPERATURE
Sets the standard Manual temperature in either the Heating or Hot water/Heating modes. Press the – or + keys to set the temperature as desired: the display shows the presently set temperature. Five (5) seconds after the end of the setting procedure the data is automatically memorised and the display reverts back to the clock.
COMFORT ROOM TEMPERATURE
This temperature may be set with either the Heating or Hot water/Heating function enabled.
To set press the key: the presently set temperature will appear on the display.
Now hold the key down and press the – or + keys to modify the temperature setting as desired.
Release the key to memorise the new setting.
LOW ROOM TEMPERATURE
This temperature may be set with either the Hot water/Heating or Heating function enabled.
Page 17
Page 18
53
RE-ESTABLISHING FACTORY SETTINGS AND CONTROL RESET
You may wish to re-establish the settings made at the factory: to do so press the key for 10 seconds and the message “Fab” will appear on the display. Going through this procedure resets the following parameters:
- standard temperature 20°C
- comfort temperature: 20°C
- low temperature: 17°C
- standard timer programme
Pressing key R cancels all user-set data.
In this case it will be necessary to reset all the parameters starting from section 1.
ERROR MESSAGES
In the event of a boiler malfunction the control unit governs the warning signals and is used to reset normal operation.
Warnings take the form of a code letter and a number (E XX) followed by the symbol. This symbol is displayed constantly where the anomaly can be reset and flashes when it cannot. To reset a resettable anomaly and restore normal boiler operation press key A.
MESSAGE DISPLAYS
Code E02 THERMOSTAT LIMIT (IF ANY) Code E04 NO WATER Code E05 HEATING SENSOR Code E06 DOMESTIC HOT WATER SENSOR Code E14 IGNITION FAULT
Page 19
Page 20
55
CORRECTING ROOM TEMPERATURE MEASUREMENT
This allows the user to correct the room temperature detected by the control unit and adapt it to different user needs. The entire correction procedure must be done with the control unit powered and connected to the boiler. Room temperature correction: Press key R and keep it pressed:
Press the key. Release key R and wait until the display shows the confirmation message “Son” The next two stages must be done within 5 seconds otherwise the procedure will be aborted.
Release the key. Press the + key to introduce a positive correction (an increase of one unit means an increase of 0.1°C). Press the - key to introduce a negative correction (a decrease of one unit means a decrease of 0.1°C). Wait 5 seconds after the last modification to exit this function and recommence normal operation.
TEMPERATURE CONTROL: SELCTING THE FUNCTION MODE.
These procedures allow the user to select one of the three possible temperature control modes. The entire procedure must be done with the control unit powered and connected to the boiler. Choosing a temperature control function mode: Press key R and keep it pressed:
Press the key. Release key R and wait for the display to show the present temperature regulator mode (tdi, ton or trc). The next two stages must be done within 5 seconds otherwise the procedure will be aborted.
Release the key.
Press the key to disable the temperature regulator, press to select ON - OFF regulator mode
or press to select modulating regulator mode. The display will then show the tdi, ton or trc confirmation message. Wait 5 seconds after the last modification to exit this function and recommence normal operation.
Page 21
Page 22
57
HYDRAULIC CIRCUIT
LEGEND
A GAS B HOT WATER OUTLET C COLD WATER INLET D SYSTEM SUPPLY E RETURN 1 Hot water circuit drain cock 2 Hot water detector 3 Gas valve 4 Instantaneous water-heater 5 Air purge manual valve 6 Hot water pressure switch
7 3-way valve 8 Lack of water pressure switch 9 Burner 10 Fumes exchanger 11 Fumes pressure switch 12 Fumes fan 13 Total safety thermostat 14 Air purge manual valve 15 Expansion tank 16 Heating detector 17 Air purge automatic valve
18 Circulating pump 19 Heating circuit drain cock 20 Heating safety valve 21 Hydrometer 22 Filling cock 23 By-pass
Page 23
Page 24
59
The boiler must be installed and function outdoors. For installation use only original LAMBORGHINI parts.
FLUE EXHAUST TYPES
DOUBLE PIPE OUTLET KIT
To install the double pipe kit insert the funnel 1 (supplied with the boiler) in the fan. Insert the diaphragm 3 between the adhesive seal 2 and the 5 mm spacer 4. Fix the double pipe flue exhaust 5 with the screws and insert the supplied silicon hood 6. The latter must rest on the upper part of the boiler to prevent water infiltrating.
Warning: The boiler can only be fitted with
the high double pipe flue exhaust kit.
CONCENTRIC FLUE EXHAUST KIT
To install the concentric kit insert the funnel 1 (supplied with the boiler) in the fan. Insert the diaphragm 3 between the adhesive seal 2 and the 5 mm spacer 4. Fix the bend 5 with the screws and insert the supplied silicon hood 6. The latter must rest on the upper part of the boiler to prevent water infiltrating.
FAN-FORCED DRAUGHT FLUE EXHAUST KIT
To install the forced draught kit insert the funnel 1 (supplied with the boiler) in the fan. Insert the diaphragm 3 and the adhesive seal 2. Fix the flanged section 4 with the screws and insert the silicon hood
5. The latter must rest on the upper part of the boiler to prevent water infiltrating.
Page 25
Page 26
61
FUMES EVACUATION/AIR INTAKE
1 Concentric flue pipe, from the terrace 2 Fan-forced draught (B22), from a flue pipe 3 Double pipe from separate flues 4 Concentric, connected to concentric flues 5 Fan-forced draught (B22), from the roof
For positioning and for distances of draught terminals from windows, doors, etc. see regulations in force.
Page 27
Page 28
63
The boiler allows to adapt the heating thermal power (without involving the adjustment of the capacity available for the production of hot water) to the thermal need of the rooms to be heated. When leaving the factory all boilers are set to 70% of their maximum output. To adapt the boiler to the thermal power needed by the plant it is necessary to carry out the following operations:
Insert a manometer in the pressure tube (G)
Electrically feed the gas valve with the boiler on in the WINTER position
Adjust the heating potentiometer (1) located on the modulation card until the gas pressure required by the
heating system capacity is reached (see pressure curves).
Should it be necessary to adjust the minimum and maximum regulation of the gas valve (preset at the factory) for the hot water supply, following operations should be carried out:
remove the power supply contacts from the coil (E).
power the gas valve with the boiler on in the SUMMER position and bleed off domestic hot water at the
maximum flow rate (13 litres/min).
turn the adjustment screw (D) all the way down without using any tools.
loosen the locknut (B)
use a wrench to turn the coil screw (A) until maximum gas pressure (values are given on page 43) is
reached.
tighten the locknut (B).
undo the adjustment screw (D) until minimum gas pressure (values are given on page 43) is reached.
reconnect the coil (E).
This task sets the boiler so that it suits the needs of the user.
NOTE: To carry out this adjustment it is necessary to use a water-column pressure gauge, connecting it to the pressure outlet (G).
ADJUSTMENTS
LEGEND
A
Max. capacity adjusting screw
B Adjustment fixing
counter-bolt
C Spring D Min. capacity adjusting
screw
E Coil F Release spring G Pressure outlet H Control unit I Gas diaphragm
(if any)
L Compensation
outlet
Modulation card
Page 29
Page 30
65
OPERATION WITH DIFFERENT TYPES OF GAS
CONVERSION FROM NATURAL GAS TO LIQUID GAS
Proceed with burner jets replacement. Insert the diaphragm (I) included in the kit. Also replace the spring (C) under the rod of the coil (E), checking that it is assembled the right way round. Switch the bridge on the modulation board from NATURAL GAS to the B-P position. Then adjust as indicated in the paragraph “ADJUSTMENTS”, page 63. For jets diameter and operating gas pressure see the table here-under.
Jets pressure mbars Delivery
Burner
jets
min. max. m3/h Ø mm.
Gas type
NATURAL GAS
(G20-20mbars)
LIQUID GAS B
(G30-28/30mbars)
LIQUID GAS P
(G31-37mbars)
2
5
6,2
11
25
32
3,06
0,89
1,17
1,25
0,77
0,77
L.C.V.
kcal/h
8.550
29.330
22.360
Gas diaphragm
(M)
Ø
-
5,4
5,4
LEGEND
A Max. capacity adjusting screw B Adjustment fixing counter-bolt C Spring D Min. capacity adjusting screw E Coil F Release spring G Pressure outlet H Control unit I Gas diaphragm (if any) L Compensation outlet N Slow ignition (RLA)
N
Gas valve
Gas diaphragm
Gasket
Gasket
Page 31
Page 32
67
FAULT-FINDING CHART
1 NO IGNITION
2 CRACKLING
IGNITION
3 SMELL OF GAS
4 SMELL OF
UNBURNT GAS INCOMBUSTI E AND BAD BURNER COMBUSTION
5
CONDENSATION IN THE BOILER
6 COLD
RADIATORS IN WINTER
7 POOR HOT
WATER SUPPLY
FAULT CAUSE
RIMEDY
A. Gas cock closed B. “Off” button locked C. No flame detection D. No ignition spark E. Air inside pipes F. Safety thermostat intervention G. Water not circulating H. Boiler water temperature higher
than figure set on the regulation thermostat
A. Open gas cock B. Reset by pressing C. Nautral and phase inverted D. Call technical service E. Repeat ignition F. Press reset button G. Adjust boiler pressure and check
circulating pump
H. Adjust thermostat setting on desired
temperature.
A. Irregular flame B. Insufficient or wrongly adjusted gas
delivery
A. Call technical service B. Call technical service
A. Leak in pipes circuit (inside and
outside boiler)
A. Check for possible leaks in the external
and external pipes. Call technical service
A. Flue section or height with joint not
suitable for the boiler
B. Excessive gas consumption -
combustion state is imperfect
C. Flames tend to move away D. Flames have yellow tips
A. Replace unsuitable components. B.
Adjust gas delivery on the modulating device.
C. Check/adjust gas valve pressure
stabilizer
D. Check that air volutes and Venturi
cones of the burner are clean. If items A-B-C-D have been checked with negative result call technical service
A. Flue section or height not suitable
(excessive size)
B. Boiler operating at low temperature
A. Replace unsuitable components. B. Adjust boiler thermostat at a higher
temperature and check if air intake pipe/flue exhaust connection is correct.
A. Summer-winter switch in summer
WINTER position
B. Room thermostat adjusted too low or
faulty
C. System or radiators closed D. Circulating pump blocked E. 3-way valve faulty
A. Place it in winter position B. Adjust thermostat at a higher tempera-
ture or replace it.
C. Check if system gate valves and
radiator cocks are opened. If item C has been checked with negative result call technical service
D. Unblock with a screwdriver and check
electrical supply
E. Check electricity sypply
A. Priority thermostat temperature set too
low
B. 3-way valve faulty
A. Adjust priority thermostat at a higher
temperature or replace it
B. Check for correct power supply and
correct positioning of valve body
Page 33
Page 34
0444 351044
AZIENDA CERTIFICATA ISO 9001
-VI
PT 42
CALDEIRA DE PAREDE A GÁS ALTO RENDIMIENTO - MODULANTE
MANUAL DO UTENTE
Àtenção do Sr. INSTALADOR:
Entregue este manual de uso ao UTENTE
ES 28
CALDERA MURAL A GAS ALTO RENDIMIENTO - MODULANTE
MANUAL PARA EL USUARIO
A la atención del sr. INSTALADOR:
Entregar el presente manual para el uso al USUARIO
GB 16
WALL-HUNG GAS BOILER FOR HIGH EFFICIENCY - MODULATING
USER MANUAL
For the attention of the INSTALLATION TECHNICIAN:
make sure that this manual is handed over to the USER
IT 2
CALDAIA MURALE A GAS ALTO RENDIMENTO - MODULANTE
MANUALE PER L‘UTENTE
Alla cortese attenzione del sig. INSTALLATORE:
Consegnare il presente manuale d’uso all’UTENTE
24 MCS W TOP
U/IT
Page 35
Page 36
17
GENERAL INSTRUCTIONS
This booklet constitutes an integral and essential part of the product and should be preserved for any further consultation. Read carefully the instructions contained in this booklet as they provide important directions regarding the operation of the appliance, allowing a great saving in its use and maintenance.
If the appliance is sold or transferred to other people or if you move house and leave your apartment, ensure that the manual remains with the appliance so that it can be used by the new owner.
This appliance should be destined only for the use for which it has been expressly envisaged. Any other use is to be considered improper and therefore dangerous. The manufacturer cannot be considered responsible for any damages caused from improper, erroneous or unreasonable use.
Do not touch the parts of the boiler which during the operation become overheated. These parts can be dangerous for children or inexperienced persons.
Do not obstruct the inlet or dissipation screens.
Do not make the boiler wet with splashes of water or other liquids.
Do not rest any object upon the boiler.
Use of the boiler is prohibited for children or the inexperienced.
Do not carry out any cleaning of the boiler with inflammable substances.
Do not deposit containers of inflammable substances in the location where the boiler is situated.
In the presence of the risk of freezing suitable provisions must be taken which are not however the concern
of the boiler manufacturer
As the boiler has hot spots it is forbidden to leave any object which might explode when exposed to heat.
ALL INSTALLATION, MAINTENANCE AND GAS CONVERSION OPERATIONS MUST BE CARRIED OUT BY AUTHORISED SKILLED TECHNICIANS.
To ensure that boiler is installed correctly and that it functions properly, we recommend that only Lamborghini accessories and spare parts be used.
On noticing the smell of gas do not touch any electric switch. Open doors and windows, shut off the gas cocks.
WARNING: The boiler must be electrically fed even when it is not in use.
Page 37
Page 38
19
CHECKS AND MAINTENANCE
Before starting up the boiler ask qualified personnel “LAMBORGHINI SERVICE to check:
a) that the data on the information plate corresponds to that required by the gas, electrical and water
supply networks;
b) that the pipes which branch off from the boiler are lined with suitable thermally-insulated sheathing; c) the proper functioning of the flue pipe; d) that the comburent air flow and the fumes evacuation take place properly in accordance with the
regulations in force;
e) that correct aeration and maintenance are possible in case of installation in the furniture.
Ensure that the installer has connected the boiler safety discharge to a waste. In the case of the contrary the intervention of the safety valves could flood the premises and the manufacturer would not be held responsible for this.
Ensure that the piping of the installation is not used as an earth outlet for other installations; beyond not being ideal for such a use it could in short bring serious damage to the other appliances connected to it.
Ask qualified personnel “LAMBORGHINI SERVICE to check:
a) the internal and external tightness of the gas system; b) that the gas delivery is that required by the boiler output; c) that the type of gas is suitable for the boiler; d) that the pressure of gas supply is within the values stated on the boiler plate; e) that the gas installation is the correct size and equipped with all the safety and checking devices
prescribed by the current regulations.
Ask periodically to check the proper functioning and the good state of the flue exhaust.
Ensure that the electrical system has been confirmed by qualified personnel to be adequate for the power
required by the appliance itself.
The electricity supply cable must not be replaced by the user, but by qualified personnel only.
The electrical safety of the appliance is attained only if the same has been connected to an effective system
earthed in accordance with the current regulations. The verification of this fundamental prerequisite should be made by qualified persons as the manufacturer will not be responsible for damage caused by the lack of adequate earthing of the installation.
Page 39
Page 40
21
AUTOMATIC TEMPERATURE CONTROL MODE
The control unit has a daily/weekly timer that automatically adjusts room temperature to “comfort” or “low temperature values over a 24 hour period, with independent settings for each of the seven days.
To enable automatic operation press the key and the symbol will be displayed. Hourly programming of temperature values is only permitted with the Heating or Hot water/Heating functions enabled.
HOURLY PROGRAMMING OF TEMPERATURE VALUES
Press key V to select the desired day on the indicators. The display will then show the programme graph for the selected day by displaying the indicator lights next to the “comfort” level. To modify these settings press P within 5 seconds. The time “00:00” will now appear on the display and the indicator light corresponding to that time will begin to flash. Press the + and – keys to increase or decrease the time in 30-minute steps.
The and symbols show the present value of the indicator light ( comfort temperature
level and low temperature level)
Select the desired value by acting on the (comfort temperature level) and (low tempera­ture level) keys. The indicator light will take on the desired value and programming will advance by one step: the next indicator light to be programmed will then flash. Once programming is over press P to memorise settings or V to cancel the modifications. The timer can memorise up to 48 daily temperature value changes.
COPYING HOURLY PROGRAMMING
To speed up programming, you can “paste” the settings for a specific day onto another day. Press V to select the day from which you wish to copy the settings. Press the Copy key within 5 seconds to copy and then press the + and – keys to select the page onto which
you intend to paste them (the destination day is indicated by a flashing indicator). Press P to paste and memorise the settings or V to cancel.
TEMPORARY TEMPERATURE VARIATION
It is possible to vary set room temperature during automatic temperature control mode by acting on the + and – keys. Variations will be shown on the display.
When this function is used the symbol indicating the present level goes out and the indicator light corresponding to the relevant time slot starts flashing. The new temperature will remain operative until the next value change, after which the programme will revert to normal settings.
Page 41
Page 42
23
Release the key to memorise the new setting. Should the boiler be equipped with an outdoor sensor, the values being displayed and set are outdoor temperature and heating water temperature.
STANDARD ROOM TEMPERATURE
Sets the standard Manual temperature in either the Heating or Hot water/Heating modes. Press the – or + keys to set the temperature as desired: the display shows the presently set temperature. Five (5) seconds after the end of the setting procedure the data is automatically memorised and the display reverts back to the clock.
COMFORT ROOM TEMPERATURE
This temperature may be set with either the Heating or Hot water/Heating function enabled.
To set press the key: the presently set temperature will appear on the display.
Now hold the key down and press the – or + keys to modify the temperature setting as desired.
Release the key to memorise the new setting.
LOW ROOM TEMPERATURE
This temperature may be set with either the Hot water/Heating or Heating function enabled.
To set press the key: the presently set temperature will appear on the display.
Now hold the key down and press the – or + keys to modify the temperature setting as desired.
Release the key to memorise the new setting.
VIEWING MAIN BOILER PARAMETERS
Press the key repeatedly to view the main boiler parameters (illustrated below) in sequence. Displayed parameters:
- effective heating water temperature (flashing symbol)
- effective hot water temperature (flashing symbol)
- room temperature setting according to present value (flashing symbol)
- outdoor temperature (flashing symbol). If there is no outdoor sensor the display shows “-:-“.
- system water pressure (flashing symbol) If there is no water pressure indicator the display shows “-:-“.
Page 43
Page 44
25
INSTALLER SETTINGS
The tasks in this section must only be carried out by qualified personnel. Carrying out these procedures wrongly may damage the control unit and boiler or cause them to malfunction.
CONNECTING UP TO THE OUTDOOR TEMPERATURE SENSOR.
The control unit can also be fitted with a sensor that monitors outdoor temperature. The outdoor temperature reading utilised by the control unit may be supplied in one of two different ways:
- when the outdoor temperature sensor is connected to the boiler the temperature reading is sent from
the boiler to the control unit.
- when the outdoor temperature sensor is connected directly to the control unit the reading is acquired
and processed by the control unit directly. If both are present the local sensor is ignored and the outdoor sensor connected to the boiler base is utilised. This situation is highlighted by the appearance of error message E67. To connect the outdoor sensor to the control unit use the S.EXT connection on the terminal block.
With the outdoor sensor connected, pressing the key shows the outdoor temperature and heating water temperature.
ENABLING REMOTE OPERATION
The control unit has an input (TEL + and -) which allows connection of an optional control unit for distance operation. Operating mode:
- TEL input open
The control unit operates as described in the handbook.
- TEL input closed The control unit switches to remote mode, that is: heating and hot water functions enabled, automatic temperature regulation according to timer programme with on-display information while upper display shows the TEL message in place of room temperature. This mode persists until the user disables it by acting on the remote mode switch (TEL input open). Standard operating mode is then restored.
CLOCK SPEED CORRECTION
Allows you to improve clock precision by increasing speed (should it run slow) or decreasing speed (should it run fast). The entire correction procedure must be done with the control unit powered and connected to the boiler. Clock correction: Press key R and keep it pressed. Press the H/Day key Release the R key and wait for the display to show the Hour confirmation message. The next two stages must be done within 5 seconds otherwise the procedure will be aborted (a change of one unit alters clock speed by 30 seconds a year). Release the H/day key. Press the + key to increase clock speed (an increase of one unit speeds up the clock by 30 seconds a year). Press the – key to reduce clock speed (a decrease of one unit slows down the clock by 30 seconds a year). Wait 5 seconds after the last modification to exit this function and recommence normal operation.
Page 45
Page 46
27
FAULT-FINDING CHART
1 NO IGNITION
2 CRACKLING
IGNITION
3 SMELL OF
GAS
4 SMELL OF
UNBURNT GAS AND BAD BURNER COMBUSTION
5
CONDENSATION IN THE BOILER
6 COLD
RADIATORS IN WINTER
7 POOR HOT
WATER SUPPLY
FAULT CAUSE REMEDY
A. Gas cock closed B. Off button locked C. No flame detection D. No ignition spark E. Air inside pipes F. Safety thermostat intervention G. Water not circulating H. Boiler water temperature higher
than figure set on the regulation hermostat
A. Open gas cock B. Reset by pressing C. Neutral and phase inverted D. Call technical service E. Repeat ignition F. Press reset button G. Adjust boiler pressure and check
circulating pump
H. Adjust thermostat setting on desired
temperature.
A. Irregular flame B. Insufficient or wrongly adjusted gas
delivery
A. Call technical service B. Call technical service
A. Leak in pipes circuit (inside and
outside boiler)
A. Check for possible leaks in the external
and external pipes. Call technical service
A. Flue section or height with joint not
suitable for the boiler
B. Excessive gas consumption -
combustion state is imperfect
C. Flames tend to move away D. Flames have yellow tips
A. Replace unsuitable components. B.
Adjust gas delivery on the modulating device.
C. Check/adjust gas valve pressure
stabilizer
D. Check that air volutes and Venturi
cones of the burner are clean. If items A-B-C-D have been checked with negative result call technical service
A. Flue section or height not suitable
(excessive size)
B. Boiler operating at low temperature
A. Replace unsuitable components. B. Adjust boiler thermostat at a higher
temperature and check if air intake pipe/flue exhaust connection is correct.
A. Summer-winter switch in summer
position
B. Room thermostat adjusted too low or
faulty
C. System or radiators closed D. Circulating pump blocked E. 3-way valve faulty
A. Place it in winter position B. Adjust thermostat at a higher tempera-
ture or replace it.
C. Check if system gate valves and
radiator cocks are opened.
If item C has been checked with negative
result call technical service
D. Unblock with a screwdriver and check
electrical supply
E. Check electricity sypply
A. Priority thermostat temperature set too
low
B. 3-way valve faulty
A. Adjust priority thermostat at a higher
temperature or replace it
B. Check for correct power supply and
correct positioning of valve body
Page 47