single loads, local sensing (default) P
single loads, remote sensing P
multiple loads, radial distribution method Pg. 23
le loads connection with distribution terminals Pg. 24
outputs Pg. 24
3.10 LOCAL AND REMOTE SENSING P
3.10.1 Sensin
3.10.2 Local sensin
3.10.3 Remote sensin
wiring P
P
P
3.10.4 J2 sense connector technical information P
3.11 REPACKAGING FOR SHIPMENT P
CHAPTER 4 FRONT AND REAR PANEL CONTROLS AND CONNECTORS
4.1 INTRODUCTION P
4.2 FRONT PANELCONTROLS AND INDICATORS P
4.3 REAR PANELCONNECTIONS AND CONTROLS P
4.4 REAR PANEL SW1 SETUP SWITCH P
4.4.1 SW1
4.4.2 Resettin
ositions functions Pg. 30
the switch Pg. 31
4.5 REAR PANEL J1 PROGRAMMING AND MONITORING CONNECTOR P
4.5.1 Makin
J1 connections Pg. 32
. 18
. 18
. 18
. 18
. 19
. 20
. 23
. 23
. 25
. 25
. 25
. 26
. 26
. 26
P
. 27
. 27
. 27
. 29
. 30
. 32
CHAPTER 5 LOCAL OPERATION
5.1 INTRODUCTION P
5.2 STANDARD OPERATION P
5.2.1 Constant Volta
5.2.2 Constant Current O
e Mode Pg. 34
eration Pg. 35
5.2.3 Automatic Crossover P
5.3 OVER VOLTAGE PROTECTION
5.3.1 Settin
5.3.2 Activated OVP
..….5.3.3 Resettin
the OVP level Pg. 35
rotection indications Pg. 35
the OVP circuit Pg. 35
OVP) P
5.4 UNDER VOLTAGE LIMIT P
5.4.1 Settin
the UVL level Pg. 36
5.5 FOLDBACK PROTECTION P
5.5.1 Settin
5.5.2 Resettin
the Foldback protection Pg. 36
activated Foldback protection Pg. 36
5.6 OUTPUT ON/OFF CONTROL P
5.7 OUTPUT SHUT-OFF
CONTROL VIA REAR PANEL J1 CONNECTOR Pg. 36
5.8 ENABLE/DISABLE CONTROL VIA P
5.9 CV/CC SIGNAL P
5.10 PS OK SIGNAL P
5.11 SAFE START AND AUTO-RESTART MODE P
5.11.1 Automatic start mode P
5.11.2 Safe start mode P
5.12 OVER TEMPERATURE PROTECTION
OTP) P
5.13 LAST SETTING MEMORY P
5.14 SERIES OPERATION P
5.14.1 Series connection for increased out
5.14.2 Series connection for
ositive and negative output voltage Pg. 40
ut voltage Pg. 39
P
. 34
. 34
. 34
. 35
. 35
. 36
. 36
. 36
. 37
. 37
. 38
. 38
. 38
. 38
. 38
. 38
. 38
83-507-5002 Rev. A
g
p
p
g
g
p
p
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
p
p
g
(
g
p
g
g
g
g
g
g
g
p
g
g
g
g
p
g
g
g
p
g
g
g
g
g
g
p
g
g
g
g
p
p
p
5.15 PARALLEL OPERATION P
5.15.1 Basic
5.15.2 Advanced
arallel operation Pg. 41
arallel operation Pg. 42
5.16 DAISY-CHAIN SHUT-OFF CONNECTION P
5.17 FRONT PANEL LOCKING P
5.17.1 Unlocked front
5.17.2 Locked front
anel Pg. 45
anel Pg. 45
CHAPTER 6 REMOTE ANALOG PROGRAMMING
6.1 INTRODUCTION P
6.2 LOCAL/REMOTE ANALOG CONTROL P
6.3 LOCAL/REMOTE ANALOG INDICATION P
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT P
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT P
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT P
CHAPTER 7 RS232 & RS485 REMOTE CONTROL
7.1 INTRODUCTION P
7.2 CONFIGURATION P
7.2.1 Default settin
7.2.2 Address settin
P
P
7.2.3 RS232 or RS485 selection P
7.2.4 Baud rate settin
7.2.5 Settin
the unit into Remote or Local mode Pg. 50
7.2.6 RS232/458
7.2.7 Front
anel in Remote mode Pg. 51
P
ort at Local mode Pg. 51
7.3 REAR PANEL RS232/485 CONNECTOR P
7.4 MD MODE OPTION
7.4.1 MD Mode Descri
Factory Installed) P
tion Pg. 52
7.4.2 MD Mode enable - Serial communication mode P
7.4.3 MD Mode SRQ P
7.4.4 Communication Collisions P
7.4.5 MD Mode SRQ Retransmission P
7.5 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS P
7.5.1 Sin
7.5.2 Multi
le power supply P
ower supply connection to RS232 or RS485 BUS Pg. 54
7.6 COMMUNICATION INTERFACE PROTOCOL P
7.6.1 Data format P
7.6.2 Addressin
7.6.3 End of messa
7.6.4 Command re
Pg. 54
e Pg. 54
eat Pg. 54
7.6.5 Checksum P
7.6.6 Acknowled
7.6.7 Error messa
7.6.8 Backs
e Pg. 54
e Pg. 55
ace Pg. 55
7.7 ERROR MESSAGES P
7.8 COMMAND SET DESCRIPTION P
7.8.1 General
7.8.2 Command set cate
uides Pg. 55
ories Pg. 55
7.8.3 Initialization control commands P
7.8.4 ID control commands P
7.8.5 Out
ut control commands Pg. 56
7.9 GLOBAL OUTPUT COMMANDS P
7.9.1 General P
7.10 SINGLE BYTE COMMANDS P
7.10.1 General P
7.10.2 Global commands without res
7.10.3 Global commands with res
7.10.4 Addressed commands with res
onse Pg. 59
onse Pg. 60
onse Pg. 60
. 41
. 44
. 44
P
. 46
. 46
. 46
. 43
. 47
. 48
. 49
P
. 50
. 50
. 50
. 50
. 50
. 50
. 50
. 51
. 52
. 52
. 52
. 52
. 52
. 53
. 53
. 54
. 54
. 54
. 55
. 55
. 56
. 56
. 58
. 58
. 59
. 59
83-507-5002 Rev. A
p
g
g
p
g
q
g
g
g
g
p
p
g
g
g up
g up
g
g
g
g
g
g
g
g
g
TABLE OF CONTENTS
7.10.5 Addressed commands without res
7.10.6 Status Control Commands P
7.11 STATUS, ERROR AND SRQ REGISTERS P
7.11.1 General Descri
7.11.2 Conditional re
7.11.3 Service Re
7.12 SERIAL COMMUNICATION TEST SET-UP P
CHAPTER 8 ISOLATED ANALOG PROGAMMING OPTION
8.1 INTRODUCTION P
8.2 SPECIFICATIONS P
8.2.1 0-5V/0-10V o
8.2.2 4-20mA o
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR P
8.4 SETUP AND OPERATING INSTRUCTIONS P
8.4.1 Settin
8.4.2 Settin
CHAPTER 9 MAINTENANCE
9.1 INTRODUCTION P
9.2 UNITS UNDER WARRANTY P
9.3 PERIODIC MAINTENANCE P
9.4 ADJUSTMENT AND CALIBRATION P
9.5 PARTS REPLACEMENT AND REPAIRS P
9.6 TROUBLESHOOTING P
9.7 FUSE RATING P
uest Enabled and Event Registers Pg. 65
tion Pg. 69
the power supply for 0-5V/0-10V Isolated Programming and Monitoring Pg. 71
the power supply for 4-20mA Isolated Programming and Monitoring P
onse Pg. 61
tion Pg. 63
isters Pg. 64
tion Pg. 69
. 63
. 63
. 68
P
. 69
. 69
. 69
. 70
. 71
. 71
P
. 72
. 72
. 72
. 72
. 72
. 72
. 72
. 73
83-507-5002 Rev. A
WARRANTY
This Lambda Americas Inc. product is warranted against defects in materials and workmanship for a
period of five years from date of shipment. During the warranty period, Lambda Americas Inc. will, at it’s
option, either repair or replaces products, which prove to be defective.
LIMITATION OF WARRANTY
The warranty shall not apply to defects resulting from improper or inadequate usage or maintenance by
the buyer, buyer supplied products or interfacing. The warranty shall not apply to defects resulting from
unauthorized modifications, or from operation exceeding the environmental specifications of the product, or if the QA seal has been removed or altered by anyone other than Lambda Americas authorized
personnel. Lambda Americas Inc. does not warrant the buyer’s circuitry or malfunctions of Lambda
Americas Inc. products resulting from the buyer’s circuitry. Furthermore, Lambda Americas Inc. does
not warrant any damage occurring as a result of the buyer’s circuitry or the buyer’s - supplied products.
No other warranty is expressed or implied.
WARRANTY SERVICE
This product must be returned to an authorized Lambda Americas Inc. service facility for repairs or
other warranty service. For products returned to Lambda Americas Inc. for warranty service, the buyer
shall prepay shipping charges to Lambda Americas Inc. and Lambda Americas Inc. shall pay the shipping charges to return the product to the buyer. Refer to Section 3.11 for repackaging for shipment.
DISCLAIMER
The information contained in this document is subject to change without notice. Lambda Americas Inc.
shall not be liable for errors contained in this document or for incidental or consequential damages in
connection with the furnishing, performance or use of this material. No part of this document may be
photocopied, reproduced or translated into another language without the prior written consent of
Lambda Americas Inc.
TRADEMARK INFORMATION
Genesys
Microsoft
TM
power supply is a trademark of Lambda Americas Inc.
TM
and WindowsTM are trademarks of Microsoft Corporation.
THE FCC WANTS YOU TO KNOW
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference, in which case
the user will be required to correct the interference at his own expense.
FCC WARNING
Modifications not expressly approved by manufacturer could void the user authority to operate the
equipment under FCC Rules.
1
83-000-016 Rev. D
SAFETY INSTRUCTIONS
CAUTION
The following safety precautions must be observed during all phases of operation, service and repair of
this equipment. Failure to comply with the safety precautions or warnings in this document violates
safety standards of design, manufacture and intended use of this equipment and may impair the built-in
protections within.
Lambda Americas Inc. shall not be liable for user’s failure to comply with these requirements.
INSTALLATION CATEGORY
The GenesysTM power supply series has been evaluated to INSTALLATION CATEGORY II. Installation
category (over voltage category) II: local level, appliances, portable equipment etc. With smaller transient over voltage than Installation Category (over voltage category) III.
GROUNDING
This product is a Safety Class 1 instrument. To minimize shock hazard, the instrument chassis must be
connected to an electrical ground. The instrument must be connected to the AC power supply mains
through a three conductor power cable, with the ground wire firmly connected to an electrical ground
(safety ground) at the power outlet.
For instruments designed to be hard-wired to the supply mains, the protective earth terminal must be
connected to the safety electrical ground before another connection is made. Any interruption of the
protective ground conductor, or disconnection of the protective earth terminal will cause a potential
shock hazard that might cause personal injury.
There is a potential shock hazard at the RS232/RS485 and the IEEE ports when using power supplies
with rated or combined voltage greater than 400V and the Positive Output of the Power Supply is
grounded. Do Not connect the Positive Output to ground when using the RS232/RS485 or IEEE.
OUTPUT TERMINALS GROUNDING
WARNING
FUSES
Fuses must be changed by authorized Lambda Americas Inc. service personnel only. For continued
protection against risk of fire, replace only with the same type and rating of fuse. Refer to Chapter 9 for
fuse ratings.
INPUT RATINGS
Do not use AC supply, which exceeds the input voltage and frequency rating of this instrument. The
input voltage and frequency rating of the Genesys
safety reasons, the mains supply voltage fluctuations should not exceed +/-10% of nominal voltage.
TM
power supply series is: 100-240Vi, 50/60Hz. For
LIVE CIRCUITS
Operating personnel must not remove the instrument cover. No internal adjustment or component replacement is allowed by non-Lambda Americas qualified personnel. Never replace components with
power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external voltage source before touching components.
PARTS SUBSTITUTIONS & MODIFICATIONS
Parts substitutions and modifications are allowed by authorized Lambda Americas service personnel
only. For repairs or modifications, the instrument must be returned to an authorized Lambda Americas
service facility.
2
83-000-018 Rev. D
SAFETY INSTRUCTIONS
ENVIRONMENTAL CONDITIONS
The GenesysTM power supply series safety approval applies to the following operating conditions:
*Indoor use *Ambient temperature: 0°C to 50°C
*Maximum relative humidity: 90% (no condensation) *Altitude: up to 3000m
*Pollution degree 2
CAUTION Risk of Electrical Shock
Instruction manual symbol. The instrument will be marked with this symbol when it is
necessary for the user to refer to the instruction manual.
Indicates hazardous voltage.
Indicates ground terminal.
Protective Ground Conductor Terminal
Off (Supply)
On (Supply)
The WARNING sign denotes a hazard. An attention to a procedure is called. Not
following procedure correctly could result in personal injury.
A WARNING sign should not be skipped and all indicated conditions must be
fully understood and met.
The CAUTION sign denotes a hazard. An attention to a procedure is called. Not following procedure correctly could result in damage to the equipment. Do not proceed beyond a CAUTION sign until all indicated conditions are fully understood and met.
FCC COMPLIANCE NOTICE:
Note: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates electro-magnetic field,
and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense.
3
83-000-018 Rev. D
SICHERHEITS-INSTALLATIONS ANWEISUNGEN
Vorsicht
Vor Anschluss an das Netz ist die Aufstellanleitung wie nachstehend beschrieben zu beachten. Die
nachstehenden Sicherheitsanweisugen mussen während aller Phasen des Betriebes, des Services und
der Reparatur dieser Ausrustung beachtet werden. Alle notwendigen Bedingungen die sicherstellen,
dass die Einrichtung zu keiner Gefahr im Sinne dieser Norm führen kann, sind in diesem Handbuch
beschrieben.
Lambda Americas Inc. ist nich verantwortlich fur Fehler, die bei der Inbetriebnahme des Gerates auf
Grundlage dieser Sicherheitsanweisungen durch den Betreiber entstehen können.
Betriebsbedingungen
Die Genesys
TM
Stromversorgungs-Reihe ist zur installation gemass Uberspannungs-Kategorie 2
entwickelt worden.
Installatios Kategorie (Uberspannungs-Kategories) 2 bedeutet: Kleinindustrie, Geräte, bewegliche
Ausrustung etc.. mit Uberspannungen kleiner als Installation Kategorie 3.
Erdungskonzept
Dieses Produkt ist ein Gerat mit Schutzklasse1. Damit gefahrliche Energieinhalte und Spannungen
vermieden werden, ist das Geratechassis an eine Schutzerde anzuschliessen. Das Gerat muss an die
AC-Wechselspannungsversorgung mit 3 Leitern (L, N, PE) angeschlossen werden. Der PEAnschluss ist an einen festen Erder anzuschliessen. Bei Festverdrahtung des Gerates ist
sicherzustellen, dass der PE Anschluss als erstes durchgefuhrt wird.
Jede mogliche Unterbrechung des PE-Leiters oder Trennung der PE Masses kann einen moglichen
elektrischen Schlag hervorrufen, der Personenschaden zur Folge hatte.
Vorsicht
Erdung des DC-Ausgangs
Es besteht Energiegefahr am RS232/RS485 und IEEE Anschluss, falls die Ausgangsspannung des
Gerates grosser ist als 400V und der positive Ausgangsanschluss des Netzteiles geerdet wird. Dies gilt
insbesondere auch bei Reihenschaltungen von unterschiedlichen Netzteilen. Wird die RS232/485 oder
IEEE Schnittstelle verwendet, ist darauf zu achten, dass der Plus-Ausgangsanschluss nicht geerdet
wird.
Absicherung
Sicherungen durfen nur durch autorisierte Lambda Americas Inc. Service Personen ausgetauscht
werden. Um Brandgefahr vorzubeugen, sind nur Sicherungen zu verwenden mit gleicher Bauart und
Auslosecharakteristik. Siehe hierzu Wartungsanweisungen in Kapitel 6 bezuglich Sicherungen.
Anschluss an Versorgungsstromkreis
Der Betrieb des Gerates ist nur fur den dafur spezifizierten Wechselspannungsbereich und der
angegebenen Frequenz erlaubt.
Der Nominaleingangsspannungsbereich der Genesys
einen sicheren Betrieb des Gerates ist eine Abweichung von max. +/-10% der Nominalspannung
erlaubt.
Spannungsfuhrende Teile
Die Gerateabdeckung darf nur im stromlosen Zustand geoffnet werden. Interne Modifikationen, sowie
Bauteileaustausch ist nur durch Lambda Americas Inc. qualifiziertes Personal erlaubt. Vor Austausch
von Bauteilen ist das Netzkabel bzw. Die Versorgungsspannung zu trennen.
Energieversorgungsanschlusse sind immer zu trennen um Personenverletzungen durch gefahrliche
Energieinhalte und Spannungen auszuschliessen. Die Stromkreise sind zu entladen, extreme
Spannunsquellen sind zu entfernen bevor Bauteile bzw. Komponenten getauscht werden.
TM
Serie liegt bei 100-240VAC mit 50/60Hz. Fur
4
83-000-018 Rev. D
Anderungen and Bauteileersatz
Ersatzteilaustausch – und Anderungen durfen nur von autorisiertem Lambda Americas Inc.
SERVICE-PERSONEN durchgefuhrt werden. Fur Reparaturen oder Anderungen ist das
Gerat zur Lambda Americas Inc. Service-Niederlassung zu retournieren.
SICHERHEITS-HINWEISE
Umweltbedingungen
Die Genesys
TM
Stromversorgungs-Serie ist gemassden Sicherheitsabnahmen fur folgende
Betriebsbedingungen zugelassen.
*Stationare Einrichtungen in Gebauden.
*Umgebungstemperaturebereich: 0-50°C.
*Maximale Relative Luftfeuchtigkeit: 90% (nicht kondensierend).
*Betriebshohe: bis zu 3000m.
*Verschmutzungsgrad 2.
Sicherheits-und Warnsymbole
VORSICHT Spannungsfuhrende Teile-Gefahr durch elektrischen Schlag bzw.
Energieinhalte
Handbuch-Symbol. Das Gerat bzw. Gerateteile werden mit diesem Symbol gekennzeichnet,
wenn es fur den Benutzer notwendig ist, sich auf die Anweisungen im Handbuch zu
beziehen.
Zeigt „spannungsfuhrende Teile“ mit gefahrlicher Spannung an.
Zeigt Masse-Anschluss an, keine Schutzerde. (z.B. Masseanschlussan einenVerbraucher).
Schutzleiter-Anschlussklemme.
Symbol fur Schalter oder Drucknopfe - Zeigt die "Ein" - Stellung hier an.
Symbol fur Schalter oder Drucknopfe - Zeigt die "Aus" - Stellung hier an.
Dieses Warnaufschrift weist auf eine Gefahr hin, die eine Uberprufunganweisung nach sich
ziecht. Nichteinhaltung kann zu Personenschaden fuhren. Dieser Warnhinweis darf nicht
ubersprungen werden und die beschriebene Vorgehensweise musstrikt verstanden werden
und dementsprechend umgesetzt werden.
Diese „Vorsichtswarnung“ weist auf eine Gefahr hin, die einer Vorkehrung bedarf.
Nichteinhaltung kann zur Zerstorung der Anlage oder des Gerates fuhren. Bitte
berucksichtigen Sie alle Anweisungen, die dort beschreiben sind, bevor Sie mit Benutzung
der Anlage bzw. des Gerates fortfahren.
5
83-000-018 Rev. D
CHAPTER 1 GENERAL INFORMATION
1.1 USER MANUAL CONTENT
This User’s Manual contains the operating instructions, installation instructions and specifications
of the Genesys
supplies, including the built-in RS232/RS485 serial communication. For information related to operation with the optional IEEE programming, refer to User’s Manual for Power Supply IEEE Programming Interface. (Lambda Americas P/N 83-030-200).
1.2 INTRODUCTION
TM
GENH 750W power supply series. The instructions refer to the standard power
1.2.1 General Description
TM
Genesys
The Genesys
power supplies are wide output range, high performance switching power supplies.
TM
series is power factor corrected and operates from worldwide AC voltage range
continuously. Output Voltage and Current are continuously displayed and LED indicators show
the complete operating status of the power supply. The Front panel controls allow the user to set
the output parameters, the protections levels (Over-Voltage protection, Under-Voltage limit and
Foldback) and preview the settings. The rear panel includes the necessary connectors to control
and monitor the power supply operation by remote analog signals or by the built-in serial communication (RS232/RS485). GPIB programming and Isolated-Analog programming/monitoring are
optional.
Constant Voltage / Constant Current with automatic crossover.
∗
Active power factor correction.
∗
Universal Input Voltage (85i265Vac), continuous operation.
∗
Embedded Microprocessor Controller.
∗
Built-in RS-232/RS-485 Interface.
∗
Voltage & Current high resolution adjustment by digital encoders.
∗
High accuracy programming/readback.
∗
Software Calibration (no internal trimmers / potentiometers).
∗
Last Setting Memory.
∗
Independent Remote ON/OFF (opto-isolated) and remote Enable/Disable.
∗
6
83-507-5002 Rev. A
Parallel operation (Master/Slave) with Active current sharing.
∗
Remote sensing to compensate for voltage drop of power leads.
∗
External Analog Programming and Monitoring standard (0-5V or 0-10V, user selectable).
∗
Cooling fan speed control for low noise and extended fan life.
∗
Zero stacking-no ventilation holes at the top and bottom surface of the power supply.
∗
Optional GPIB interface (SCPI compatible).
∗
Optional Isolated Analog programming/monitoring (0-5V or 0-10V, user selectable and 4-
∗
20mA).
1.2.4 Multiple output power system
The Genesys
TM
power supplies series can be configured into a programmable power system of
up to 31 units using the built-in RS232/RS485 communication port and the RS485 linking cable
provided with each power supply.
In a GPIB system, each power supply can be controlled using the optional GPIB controller (factory installed).
1.2.5 Control via the serial communication port
The following parameters can be programmed / monitored via the serial communication port:
1. Output Voltage setting.
2. Output Current setting.
3. Output Voltage measurement.
4. Output On/Off control.
5. Output Current measurement.
6. Foldback protection setting
7. Over-voltage protection setting and readback.
8. Under-Voltage limit setting and readback.
9. Power-supply start up mode (Auto-restart or Safe-start mode).
1.2.6 Analog voltage programming and monitoring
Analog inputs and outputs are provided at the rear panel for analog control of the power supply.
The Output Voltage and the Current can be programmed by analog voltage or by resistor, and
can be monitored by analog voltage. The power supply output can be remotely set to On or Off
and analog signals monitor the proper operation of the power supply and the mode of operation
(CV/CC).
1.2.7 Parallel operation
Genesys
TM
power supplies of the same Output Voltage and Current rating can be paralleled in a
master-slave configuration with automatic current sharing to increase power available.
1.2.8 Output connections
Output connections are made to rear panel bus-bars for models up to 60V and to a 4-terminal
wire clamp connector for models above 60V rated output voltage. Either the positive or negative
terminal may be grounded or the output may be floated. Models up to 60VDC Rated Output shall
not float outputs more than +/- 60VDC above/below chassis ground. Models >60VDC Rated Output shall not float outputs more than +/-600VDC above/below chassis ground. Contact factory for
assistance with higher float voltage applications.
Local or remote sense may be used. In remote sense, the voltage drop on the load wires should
be minimized. Refer to the specifications for the maximum voltage drop value.
7
83-507-5002 Rev. A
1.2.9 Cooling and mechanical construction
The Genesys
free airflow into the power supply via the front panel and out of the power supply via the rear
panel. The Genesys
TM
series is cooled by internal fans. At the installation, care must be taken to allow
TM
power supplies have a compact and lightweight package, which allows
easy installation and space saving in the application equipment.
CAUTION
Observe all torque guidelines within this manual. Applying more torque may
damage unit or accessories. Such damage is not covered under manufacturers
warranty.
1.3 ACCESSORIES
1.3.1 General
Accessories are delivered with the power supply or separately upon ordering. The list below
shows the possible accessories and ordering numbers.
1.3.2 Serial Link Cable
Serial link cable, for linking power supplies by RS485 communication is provided with the power
supply.
AC cables are not provided with the power supply. If an AC cable is required, it should be ordered
according to following:
TM
For 750W Genesys
power supplies:
Part No. Market Description
NC301
(GEN/U)
NC302
(GEN/E)
NC303
(GEN/O)
NC305
(GEN/J)
NC306
(GEN/GB
)
USA 13A 125V, unshielded, 2m typical length, with IEC320 connector on one end
and NEMA-5-15P connector on the other end.
Europe 10A 250V, unshielded, 2m typical length, with IEC320 connector on one end
and INT’L 7 standard VII, dual earthing.
General 10A 250V, unshielded, 2m typical length, with IEC320 connector on one end
and unterminated stripped wires on the other end. Use the cable only with
plug approved by the national safety standards of the country of usage.
Japan 13A 125V,unshielded, 2m typical length, with IEC320 connector on one end
and Japan type plug on the other end.
UK 10A 250V unshielded, 2m typical length, with IEC320 connector on one end
and UK type plug on the other end.
1.3.5 Serial Port Cables Refer to Section 7.5
8
83-507-5002 Rev. A
CHAPTER 2 SPECIFICATIONS
9
83-507-5002 Rev. A
10
83-507-5002 Rev. A
NOTES:
*1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
*2: Minimum current is guaranteed to maximum 0.4% of the rated output current.
*3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be
described as 100-240Vac (50/60Hz).
*4: At 100/200V input voltage and maximum output power.
*5: From 85i132Vac or 170i265Vac, constant load.
*6: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote
Sense.
*7: For load voltage change, equal to the unit voltage rating, constant input voltage.
*8: For 6V models the ripple is measured at 2i6V output voltage and full output current. For other
models, the ripple is measured at 10i100% output voltage and full output current.
*9: With rated, resistive load.
*10. For 6i300V models: Measured with JEITA RC-9131A (1:1) probe
For 600V model: Measured with (10:1) probe.
2.12 SUPPLEMENTAL CHARACTERISTICS
The supplemental characteristics give typical but non-warranted performance characteristics. The
supplemental characteristics are useful in assessing applications for the power supply. Several
kinds of supplemental characteristics are listed below.
1. Evaluation Data: Typical performance of the power supply.
2. Reliability Data: Reliability Performance of the power supply.
3. IEC1000 Data: Performance of the power supply under IEC1000 test conditions.
4. EMI Data: Typical EMI (conducted and radiated) performance of the power supply.
The supplemental characteristics data is held in each Lambda sales and service facility. For further details please contact the lambda office nearest you.
11
83-507-5002 Rev. A
2.13 GENESYSTM GENH 750W POWER SUPPLIES OUTLINE DRAWINGS
12
83-507-5002 Rev. A
CHAPTER 3 INSTALLATION
3.1 GENERAL
This Chapter contains instructions for initial inspection, preparation for use and repackaging for
shipment. Connection to PC, setting the communication port and linking Genesys
plies are described in Chapter 7.
TM
power sup-
NOTE
Genesys
TM
power supplies generate magnetic fields, which
might affect the operation of other instruments. If your
equipment is susceptible to magnetic fields, do not position it
adjacent to the power supply.
3.2 PREPARATION FOR USE
In order to be operational the power supply must be connected to an appropriate AC source. The
AC source voltage should be within the power supply specification. Do not apply power before
reading Section 3.6 and 3.7.
Table 3-1 below, describes the basic setup procedure. Follow the instructions in Table 3-1 in the
sequence given to prepare the power supply for use.
Step no. Item Description Reference
1 Inspection Initial physical inspection of the power supply Section 3.3
2 Installation Installing the power supply,
Ensuring adequate ventilation.
3 AC source
AC source requirements
Connecting the power supply to the AC source
6 Default setting The power supply setting at shipment. Section 7.2.1
Table 3-1: Basic setup procedure
3.3 INITIAL INSPECTIONS
Prior to shipment this power supply was inspected and found free of mechanical or electrical defects. Upon unpacking of the power supply, inspect for any damage, which may have occurred in
transit.
The inspection should confirm that there is no exterior damage to the power supply such as broken knobs or connectors and that the front panel and meters face are not scratched or cracked.
Keep all packing material until the inspection has been completed. If damage is detected, file a
claim with carrier immediately and notify the Lambda sales or authorized service facility nearest
you.
13
83-507-5002 Rev. A
3.4 RACK MOUNTING
To install a GENH750W one unit or two units side-by-side in a standard 19” Rack in 1U (1.75”)
height, use option kit P/N: GENH/RM
The Rack Mount kit allows the units to be zero stacked for maximum system flexibility and power
density without increasing the 1U height of the units.
3.4.1 Single unit installation
To install a GENH750W power supply in a standard 19” Rack in 1U (1.75”) height, using a GENH
Rack Mount kit P/N: GENH/RM.
3.4.2 Dual unit installation
To install two GENH750W power supplies side-by-side in a standard 19” Rack in 1U (1.75”)
height, using a GENH Rack Mount kit P/N: GENH/RM.
14
83-507-5002 Rev. A
3.4.3 GENH/RM Rack Mounting outline drawings:
3.5 LOCATION, MOUNTING AND COOLING
This power supply is fan cooled. The air intake is at the front panel and the exhaust is at the rear
panel. Upon installation allow cooling air to each the front panel ventilation inlets. Allow minimum
10cm (4-inch) of unrestricted air space at the front and the rear of the unit.
The power supply should be used in an area that the ambient temperature does not exceed
+50°C.
3.6 AC SOURCE REQUIREMENTS
The GenesysTM series can be operated from a nominal 100V to 240V, single phase, 47i63 Hz.
The input voltage range and current required for each model is specified in Chapter 2. Ensure
that under heavy load, the AC voltage supplied to the power supply does not fall below the specifications described in Chapter 2.
3.7 AC INPUT POWER CONNECTION
CAUTION
Connection of this power supply to an AC power source
should be made by an electrician or other qualified personnel
WARNING
There is a potential shock hazard if the power supply chassis
(with cover in place) is not connected to an electrical safety
ground via the safety ground in the AC input connector.
15
83-507-5002 Rev. A
r
p
WARNING
Some components inside the power supply area are at AC voltage
even when the On/Off switch is in the “Off” position. To avoid electric
shock hazard, disconnect the line cord and load and wait two minutes
before removing cover.
3.7.1 AC Input Connector
An IEC connector is provided on the rear panel for connecting the unit to the AC power source
with an AC cord. The IEC connector also provides the safety ground connection while the AC
cord is plugged into an appropriate AC receptacle.
3.7.2 AC Input Cord
Refer to Section 1.3.4 for details of the AC input cords recommended for the GENH750W models.
WARNING
The AC input cord is the disconnect device of the powe
supply. The plug must be readily identifiable and accessible
to the user. The AC in
ut cord must be no longer than 3m.
3.8 TURN-ON CHECKOUT PROCEDURE
3.8.1 General
The following procedure ensures that the power supply is operational and may be used as a basic incoming inspection check. Refer to Fig.4-1 and Fig.4-2 for the location of the controls indicated in the procedure.
3.8.2 Prior to Operation
1. Ensure that the power supply is configured to the default setting:
– AC On/Off switch at Off position.
– Dip switch: All positions at Down (“Off”) position.
– Sense connector: Configured to Local Sense as shown in Fig.3-4:
– For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default)
position (Refer to Fig.4-2, Item 9 for location), if checkout is to be done in IEEE mode.
1 Remote (+) sense
2 Local (+) sense
3 Not connected
4 Local (-) sense
5 Remote (-) sense
Fig.3-4: Sense connector default connection
2. Connect the unit to an AC source as described in Section 3.7.
3. Connect a DVM with appropriate cables for the rated voltage to the output terminals.
16
83-507-5002 Rev. A
4. Turn the front panel AC power switch to On.
3.8.3 Constant Voltage Check
1. Turn on the output by pressing the OUT pushbutton so the OUT LED illuminates.
2. Observe the power supply VOLT display and rotate the Voltage encoder. Ensure that the
Output Voltage varies while the VOLT encoder is rotated. The minimum control range is from
zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel VOLT display to verify the accuracy of the
VOLT display. Ensure that the front panel VOLT LED is On.
3. Turn Off the front panel AC power switch.
3.8.4 Constant Current Check
1. Ensure that the front panel AC power switch is at the Off position and the DVM connected to
the output terminals shows zero voltage.
2. Connect a DC shunt across the output terminals. Ensure that the shunt and the wire current
ratings are higher than the power supply rating. Connect a DVM to the shunt.
3. Turn the front panel AC power switch to the On position,
4. Turn On the output by pressing OUT pushbutton so the OUT LED illuminates.
5. Observe the power supply CURRENT display and rotate the CURRENT encoder. Ensure that
the Output Current varies while the CURRENT encoder is rotated. The minimum control
range is from zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel CURRENT display to verify the accuracy of
the CURRENT display. Ensure that the front panel CURRENT LED is On.
6. Turn Off the front panel AC power switch.
7. Remove the shunt from the power supply output terminals.
3.8.5 OVP Check
Refer to Section 5.3 for explanation of the OVP function prior to performing the procedure below.
1. Turn the front panel AC power switch to the On position and turn on the output by pressing
OUT pushbutton.
2. Using the VOLT encoder, adjust the Output Voltage to approx. 10% of the unit voltage rating.
3. Momentarily press the OVP/UVL button so that the CURRENT display shows “OUP”. The
VOLTAGE display will show the last setting of the OVP level.
4. Rotate the VOLT encoder CCW to adjust the OVP setting to 50% of the unit voltage rating.
5. Wait a few seconds until the VOLT display returns to show the Output Voltage.
6. Adjust the Output Voltage toward its maximum and check that the Output Voltage cannot be
increased more than the OVP setting.
7. Adjust OVP limit to the maximum by repeating Step 3 and rotating the VOLT encoder CW.
3.8.6 UVL Check
Refer to Section 5.4 for explanation of the UVL function prior to performing the procedure below.
1. Press the OVP/UVL button TWICE so that the CURRENT display shows “UUL”. The
VOLTAGE display will show the last setting of the UVL level.
2. Rotate the VOLT encoder to adjust the UVL level to approx. 10% of the unit voltage rating.
3. Wait a few seconds until the VOLT display returns to show the output voltage.
4. Adjust the output voltage toward its minimum and check that the output voltage cannot be decreased below the UVL setting.
5. Adjust the UVL limit to the minimum by repeating step 1 and rotating the VOLT encoder CCW.
3.8.7 Foldback Check
17
83-507-5002 Rev. A
WARNING
Shorting the output may expose the user to hazardous
voltages. Observe proper safety procedures.
Refer to Section 5.5 for explanation of the FOLD function prior to performing the procedure below.
1. Ensure that the Output Voltage is set to approx. 10% of the unit rating.
2. Adjust the CURRENT encoder to set the Output Current setting to approx. 10% of the unit
rating.
3. Momentarily press the FOLD button. Ensure that the FOLD LED illuminates. The Output Voltage remains unchanged.
4. Short the output terminals momentarily (approx. 0.5 sec.). Ensure that the Output Voltage
falls to zero, the VOLT display shows “Fb” and the ALARM LED blinks.
5. Press the FOLD button again to cancel the protection. The Output Voltage remains zero.
6. Press the OUT button. Ensure that the Output Voltage returns to its last setting.
7. Turn the output off by pressing the OUT button. Ensure that the VOLT display shows “OFF”.
3.8.8 Address Setting
1. Press and hold the REM/LOC button for approx. 3 sec. The VOLT display will show the communication port address.
2. Using the VOLT adjust encoder, check that the address can be set within the range of 0 to 30.
3.8.9 Baud Rate Setting (RS-232 and RS-485 only)
1. Press and hold the REM/LOC button for approx. 3 sec. The CURRENT display will show the
communication port Baud Rate.
2. Using The CURRENT adjust encoder, check that the Baud Rate can be set to 1200, 2400,
4800, 9600 and 19200.
3.9 CONNECTING THE LOAD
Turn Off the AC input power before making or changing any rear
panel connection. Ensure that all connections are securely tightened before applying power. There is a potential shock hazard
when using a power supply with a rated output greater than 40V.
3.9.1 Load Wiring
The following considerations should be made to select wiring for connecting the load to the power
supply:
Current carrying capacity of the wire (refer to Section 3.9.2)
∗
Insulation rating of the wire should be at least equivalent to the maximum output voltage of
∗
the power supply.
Maximum wire length and voltage drop (refer to Section 3.9.2)
∗
Noise and impedance effects of the load wiring (refer to Section 3.9.4).
∗
3.9.2 Current Carrying Capacity
Two factors must be considered when selecting the wire size:
1. Wires should be at least heavy enough not to overheat while carrying the power supply
load current at the rated load, or the current that would flow in the event the load wires
were shorted, whichever is greater.
2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the
rated current. Although units will compensate for up to 5V in each load wire, it is recom-
WARNING
18
83-507-5002 Rev. A
Loading...
+ 56 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.