single loads, local sensing (default) P
single loads, remote sensing P
multiple loads, radial distribution method Pg. 23
le loads connection with distribution terminals Pg. 24
outputs Pg. 24
3.10 LOCAL AND REMOTE SENSING P
3.10.1 Sensin
3.10.2 Local sensin
3.10.3 Remote sensin
wiring P
P
P
3.10.4 J2 sense connector technical information P
3.11 REPACKAGING FOR SHIPMENT P
CHAPTER 4 FRONT AND REAR PANEL CONTROLS AND CONNECTORS
4.1 INTRODUCTION P
4.2 FRONT PANELCONTROLS AND INDICATORS P
4.3 REAR PANELCONNECTIONS AND CONTROLS P
4.4 REAR PANEL SW1 SETUP SWITCH P
4.4.1 SW1
4.4.2 Resettin
ositions functions Pg. 30
the switch Pg. 31
4.5 REAR PANEL J1 PROGRAMMING AND MONITORING CONNECTOR P
4.5.1 Makin
J1 connections Pg. 32
. 18
. 18
. 18
. 18
. 19
. 20
. 23
. 23
. 25
. 25
. 25
. 26
. 26
. 26
P
. 27
. 27
. 27
. 29
. 30
. 32
CHAPTER 5 LOCAL OPERATION
5.1 INTRODUCTION P
5.2 STANDARD OPERATION P
5.2.1 Constant Volta
5.2.2 Constant Current O
e Mode Pg. 34
eration Pg. 35
5.2.3 Automatic Crossover P
5.3 OVER VOLTAGE PROTECTION
5.3.1 Settin
5.3.2 Activated OVP
..….5.3.3 Resettin
the OVP level Pg. 35
rotection indications Pg. 35
the OVP circuit Pg. 35
OVP) P
5.4 UNDER VOLTAGE LIMIT P
5.4.1 Settin
the UVL level Pg. 36
5.5 FOLDBACK PROTECTION P
5.5.1 Settin
5.5.2 Resettin
the Foldback protection Pg. 36
activated Foldback protection Pg. 36
5.6 OUTPUT ON/OFF CONTROL P
5.7 OUTPUT SHUT-OFF
CONTROL VIA REAR PANEL J1 CONNECTOR Pg. 36
5.8 ENABLE/DISABLE CONTROL VIA P
5.9 CV/CC SIGNAL P
5.10 PS OK SIGNAL P
5.11 SAFE START AND AUTO-RESTART MODE P
5.11.1 Automatic start mode P
5.11.2 Safe start mode P
5.12 OVER TEMPERATURE PROTECTION
OTP) P
5.13 LAST SETTING MEMORY P
5.14 SERIES OPERATION P
5.14.1 Series connection for increased out
5.14.2 Series connection for
ositive and negative output voltage Pg. 40
ut voltage Pg. 39
P
. 34
. 34
. 34
. 35
. 35
. 36
. 36
. 36
. 37
. 37
. 38
. 38
. 38
. 38
. 38
. 38
. 38
83-507-5002 Rev. A
g
p
p
g
g
p
p
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
g
p
p
g
(
g
p
g
g
g
g
g
g
g
p
g
g
g
g
p
g
g
g
p
g
g
g
g
g
g
p
g
g
g
g
p
p
p
5.15 PARALLEL OPERATION P
5.15.1 Basic
5.15.2 Advanced
arallel operation Pg. 41
arallel operation Pg. 42
5.16 DAISY-CHAIN SHUT-OFF CONNECTION P
5.17 FRONT PANEL LOCKING P
5.17.1 Unlocked front
5.17.2 Locked front
anel Pg. 45
anel Pg. 45
CHAPTER 6 REMOTE ANALOG PROGRAMMING
6.1 INTRODUCTION P
6.2 LOCAL/REMOTE ANALOG CONTROL P
6.3 LOCAL/REMOTE ANALOG INDICATION P
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT P
6.5 RESISTIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT P
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT P
CHAPTER 7 RS232 & RS485 REMOTE CONTROL
7.1 INTRODUCTION P
7.2 CONFIGURATION P
7.2.1 Default settin
7.2.2 Address settin
P
P
7.2.3 RS232 or RS485 selection P
7.2.4 Baud rate settin
7.2.5 Settin
the unit into Remote or Local mode Pg. 50
7.2.6 RS232/458
7.2.7 Front
anel in Remote mode Pg. 51
P
ort at Local mode Pg. 51
7.3 REAR PANEL RS232/485 CONNECTOR P
7.4 MD MODE OPTION
7.4.1 MD Mode Descri
Factory Installed) P
tion Pg. 52
7.4.2 MD Mode enable - Serial communication mode P
7.4.3 MD Mode SRQ P
7.4.4 Communication Collisions P
7.4.5 MD Mode SRQ Retransmission P
7.5 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS P
7.5.1 Sin
7.5.2 Multi
le power supply P
ower supply connection to RS232 or RS485 BUS Pg. 54
7.6 COMMUNICATION INTERFACE PROTOCOL P
7.6.1 Data format P
7.6.2 Addressin
7.6.3 End of messa
7.6.4 Command re
Pg. 54
e Pg. 54
eat Pg. 54
7.6.5 Checksum P
7.6.6 Acknowled
7.6.7 Error messa
7.6.8 Backs
e Pg. 54
e Pg. 55
ace Pg. 55
7.7 ERROR MESSAGES P
7.8 COMMAND SET DESCRIPTION P
7.8.1 General
7.8.2 Command set cate
uides Pg. 55
ories Pg. 55
7.8.3 Initialization control commands P
7.8.4 ID control commands P
7.8.5 Out
ut control commands Pg. 56
7.9 GLOBAL OUTPUT COMMANDS P
7.9.1 General P
7.10 SINGLE BYTE COMMANDS P
7.10.1 General P
7.10.2 Global commands without res
7.10.3 Global commands with res
7.10.4 Addressed commands with res
onse Pg. 59
onse Pg. 60
onse Pg. 60
. 41
. 44
. 44
P
. 46
. 46
. 46
. 43
. 47
. 48
. 49
P
. 50
. 50
. 50
. 50
. 50
. 50
. 50
. 51
. 52
. 52
. 52
. 52
. 52
. 53
. 53
. 54
. 54
. 54
. 55
. 55
. 56
. 56
. 58
. 58
. 59
. 59
83-507-5002 Rev. A
p
g
g
p
g
q
g
g
g
g
p
p
g
g
g up
g up
g
g
g
g
g
g
g
g
g
TABLE OF CONTENTS
7.10.5 Addressed commands without res
7.10.6 Status Control Commands P
7.11 STATUS, ERROR AND SRQ REGISTERS P
7.11.1 General Descri
7.11.2 Conditional re
7.11.3 Service Re
7.12 SERIAL COMMUNICATION TEST SET-UP P
CHAPTER 8 ISOLATED ANALOG PROGAMMING OPTION
8.1 INTRODUCTION P
8.2 SPECIFICATIONS P
8.2.1 0-5V/0-10V o
8.2.2 4-20mA o
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR P
8.4 SETUP AND OPERATING INSTRUCTIONS P
8.4.1 Settin
8.4.2 Settin
CHAPTER 9 MAINTENANCE
9.1 INTRODUCTION P
9.2 UNITS UNDER WARRANTY P
9.3 PERIODIC MAINTENANCE P
9.4 ADJUSTMENT AND CALIBRATION P
9.5 PARTS REPLACEMENT AND REPAIRS P
9.6 TROUBLESHOOTING P
9.7 FUSE RATING P
uest Enabled and Event Registers Pg. 65
tion Pg. 69
the power supply for 0-5V/0-10V Isolated Programming and Monitoring Pg. 71
the power supply for 4-20mA Isolated Programming and Monitoring P
onse Pg. 61
tion Pg. 63
isters Pg. 64
tion Pg. 69
. 63
. 63
. 68
P
. 69
. 69
. 69
. 70
. 71
. 71
P
. 72
. 72
. 72
. 72
. 72
. 72
. 72
. 73
83-507-5002 Rev. A
WARRANTY
This Lambda Americas Inc. product is warranted against defects in materials and workmanship for a
period of five years from date of shipment. During the warranty period, Lambda Americas Inc. will, at it’s
option, either repair or replaces products, which prove to be defective.
LIMITATION OF WARRANTY
The warranty shall not apply to defects resulting from improper or inadequate usage or maintenance by
the buyer, buyer supplied products or interfacing. The warranty shall not apply to defects resulting from
unauthorized modifications, or from operation exceeding the environmental specifications of the product, or if the QA seal has been removed or altered by anyone other than Lambda Americas authorized
personnel. Lambda Americas Inc. does not warrant the buyer’s circuitry or malfunctions of Lambda
Americas Inc. products resulting from the buyer’s circuitry. Furthermore, Lambda Americas Inc. does
not warrant any damage occurring as a result of the buyer’s circuitry or the buyer’s - supplied products.
No other warranty is expressed or implied.
WARRANTY SERVICE
This product must be returned to an authorized Lambda Americas Inc. service facility for repairs or
other warranty service. For products returned to Lambda Americas Inc. for warranty service, the buyer
shall prepay shipping charges to Lambda Americas Inc. and Lambda Americas Inc. shall pay the shipping charges to return the product to the buyer. Refer to Section 3.11 for repackaging for shipment.
DISCLAIMER
The information contained in this document is subject to change without notice. Lambda Americas Inc.
shall not be liable for errors contained in this document or for incidental or consequential damages in
connection with the furnishing, performance or use of this material. No part of this document may be
photocopied, reproduced or translated into another language without the prior written consent of
Lambda Americas Inc.
TRADEMARK INFORMATION
Genesys
Microsoft
TM
power supply is a trademark of Lambda Americas Inc.
TM
and WindowsTM are trademarks of Microsoft Corporation.
THE FCC WANTS YOU TO KNOW
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference, in which case
the user will be required to correct the interference at his own expense.
FCC WARNING
Modifications not expressly approved by manufacturer could void the user authority to operate the
equipment under FCC Rules.
1
83-000-016 Rev. D
SAFETY INSTRUCTIONS
CAUTION
The following safety precautions must be observed during all phases of operation, service and repair of
this equipment. Failure to comply with the safety precautions or warnings in this document violates
safety standards of design, manufacture and intended use of this equipment and may impair the built-in
protections within.
Lambda Americas Inc. shall not be liable for user’s failure to comply with these requirements.
INSTALLATION CATEGORY
The GenesysTM power supply series has been evaluated to INSTALLATION CATEGORY II. Installation
category (over voltage category) II: local level, appliances, portable equipment etc. With smaller transient over voltage than Installation Category (over voltage category) III.
GROUNDING
This product is a Safety Class 1 instrument. To minimize shock hazard, the instrument chassis must be
connected to an electrical ground. The instrument must be connected to the AC power supply mains
through a three conductor power cable, with the ground wire firmly connected to an electrical ground
(safety ground) at the power outlet.
For instruments designed to be hard-wired to the supply mains, the protective earth terminal must be
connected to the safety electrical ground before another connection is made. Any interruption of the
protective ground conductor, or disconnection of the protective earth terminal will cause a potential
shock hazard that might cause personal injury.
There is a potential shock hazard at the RS232/RS485 and the IEEE ports when using power supplies
with rated or combined voltage greater than 400V and the Positive Output of the Power Supply is
grounded. Do Not connect the Positive Output to ground when using the RS232/RS485 or IEEE.
OUTPUT TERMINALS GROUNDING
WARNING
FUSES
Fuses must be changed by authorized Lambda Americas Inc. service personnel only. For continued
protection against risk of fire, replace only with the same type and rating of fuse. Refer to Chapter 9 for
fuse ratings.
INPUT RATINGS
Do not use AC supply, which exceeds the input voltage and frequency rating of this instrument. The
input voltage and frequency rating of the Genesys
safety reasons, the mains supply voltage fluctuations should not exceed +/-10% of nominal voltage.
TM
power supply series is: 100-240Vi, 50/60Hz. For
LIVE CIRCUITS
Operating personnel must not remove the instrument cover. No internal adjustment or component replacement is allowed by non-Lambda Americas qualified personnel. Never replace components with
power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external voltage source before touching components.
PARTS SUBSTITUTIONS & MODIFICATIONS
Parts substitutions and modifications are allowed by authorized Lambda Americas service personnel
only. For repairs or modifications, the instrument must be returned to an authorized Lambda Americas
service facility.
2
83-000-018 Rev. D
SAFETY INSTRUCTIONS
ENVIRONMENTAL CONDITIONS
The GenesysTM power supply series safety approval applies to the following operating conditions:
*Indoor use *Ambient temperature: 0°C to 50°C
*Maximum relative humidity: 90% (no condensation) *Altitude: up to 3000m
*Pollution degree 2
CAUTION Risk of Electrical Shock
Instruction manual symbol. The instrument will be marked with this symbol when it is
necessary for the user to refer to the instruction manual.
Indicates hazardous voltage.
Indicates ground terminal.
Protective Ground Conductor Terminal
Off (Supply)
On (Supply)
The WARNING sign denotes a hazard. An attention to a procedure is called. Not
following procedure correctly could result in personal injury.
A WARNING sign should not be skipped and all indicated conditions must be
fully understood and met.
The CAUTION sign denotes a hazard. An attention to a procedure is called. Not following procedure correctly could result in damage to the equipment. Do not proceed beyond a CAUTION sign until all indicated conditions are fully understood and met.
FCC COMPLIANCE NOTICE:
Note: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates electro-magnetic field,
and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference
in which case the user will be required to correct the interference at his own expense.
3
83-000-018 Rev. D
SICHERHEITS-INSTALLATIONS ANWEISUNGEN
Vorsicht
Vor Anschluss an das Netz ist die Aufstellanleitung wie nachstehend beschrieben zu beachten. Die
nachstehenden Sicherheitsanweisugen mussen während aller Phasen des Betriebes, des Services und
der Reparatur dieser Ausrustung beachtet werden. Alle notwendigen Bedingungen die sicherstellen,
dass die Einrichtung zu keiner Gefahr im Sinne dieser Norm führen kann, sind in diesem Handbuch
beschrieben.
Lambda Americas Inc. ist nich verantwortlich fur Fehler, die bei der Inbetriebnahme des Gerates auf
Grundlage dieser Sicherheitsanweisungen durch den Betreiber entstehen können.
Betriebsbedingungen
Die Genesys
TM
Stromversorgungs-Reihe ist zur installation gemass Uberspannungs-Kategorie 2
entwickelt worden.
Installatios Kategorie (Uberspannungs-Kategories) 2 bedeutet: Kleinindustrie, Geräte, bewegliche
Ausrustung etc.. mit Uberspannungen kleiner als Installation Kategorie 3.
Erdungskonzept
Dieses Produkt ist ein Gerat mit Schutzklasse1. Damit gefahrliche Energieinhalte und Spannungen
vermieden werden, ist das Geratechassis an eine Schutzerde anzuschliessen. Das Gerat muss an die
AC-Wechselspannungsversorgung mit 3 Leitern (L, N, PE) angeschlossen werden. Der PEAnschluss ist an einen festen Erder anzuschliessen. Bei Festverdrahtung des Gerates ist
sicherzustellen, dass der PE Anschluss als erstes durchgefuhrt wird.
Jede mogliche Unterbrechung des PE-Leiters oder Trennung der PE Masses kann einen moglichen
elektrischen Schlag hervorrufen, der Personenschaden zur Folge hatte.
Vorsicht
Erdung des DC-Ausgangs
Es besteht Energiegefahr am RS232/RS485 und IEEE Anschluss, falls die Ausgangsspannung des
Gerates grosser ist als 400V und der positive Ausgangsanschluss des Netzteiles geerdet wird. Dies gilt
insbesondere auch bei Reihenschaltungen von unterschiedlichen Netzteilen. Wird die RS232/485 oder
IEEE Schnittstelle verwendet, ist darauf zu achten, dass der Plus-Ausgangsanschluss nicht geerdet
wird.
Absicherung
Sicherungen durfen nur durch autorisierte Lambda Americas Inc. Service Personen ausgetauscht
werden. Um Brandgefahr vorzubeugen, sind nur Sicherungen zu verwenden mit gleicher Bauart und
Auslosecharakteristik. Siehe hierzu Wartungsanweisungen in Kapitel 6 bezuglich Sicherungen.
Anschluss an Versorgungsstromkreis
Der Betrieb des Gerates ist nur fur den dafur spezifizierten Wechselspannungsbereich und der
angegebenen Frequenz erlaubt.
Der Nominaleingangsspannungsbereich der Genesys
einen sicheren Betrieb des Gerates ist eine Abweichung von max. +/-10% der Nominalspannung
erlaubt.
Spannungsfuhrende Teile
Die Gerateabdeckung darf nur im stromlosen Zustand geoffnet werden. Interne Modifikationen, sowie
Bauteileaustausch ist nur durch Lambda Americas Inc. qualifiziertes Personal erlaubt. Vor Austausch
von Bauteilen ist das Netzkabel bzw. Die Versorgungsspannung zu trennen.
Energieversorgungsanschlusse sind immer zu trennen um Personenverletzungen durch gefahrliche
Energieinhalte und Spannungen auszuschliessen. Die Stromkreise sind zu entladen, extreme
Spannunsquellen sind zu entfernen bevor Bauteile bzw. Komponenten getauscht werden.
TM
Serie liegt bei 100-240VAC mit 50/60Hz. Fur
4
83-000-018 Rev. D
Anderungen and Bauteileersatz
Ersatzteilaustausch – und Anderungen durfen nur von autorisiertem Lambda Americas Inc.
SERVICE-PERSONEN durchgefuhrt werden. Fur Reparaturen oder Anderungen ist das
Gerat zur Lambda Americas Inc. Service-Niederlassung zu retournieren.
SICHERHEITS-HINWEISE
Umweltbedingungen
Die Genesys
TM
Stromversorgungs-Serie ist gemassden Sicherheitsabnahmen fur folgende
Betriebsbedingungen zugelassen.
*Stationare Einrichtungen in Gebauden.
*Umgebungstemperaturebereich: 0-50°C.
*Maximale Relative Luftfeuchtigkeit: 90% (nicht kondensierend).
*Betriebshohe: bis zu 3000m.
*Verschmutzungsgrad 2.
Sicherheits-und Warnsymbole
VORSICHT Spannungsfuhrende Teile-Gefahr durch elektrischen Schlag bzw.
Energieinhalte
Handbuch-Symbol. Das Gerat bzw. Gerateteile werden mit diesem Symbol gekennzeichnet,
wenn es fur den Benutzer notwendig ist, sich auf die Anweisungen im Handbuch zu
beziehen.
Zeigt „spannungsfuhrende Teile“ mit gefahrlicher Spannung an.
Zeigt Masse-Anschluss an, keine Schutzerde. (z.B. Masseanschlussan einenVerbraucher).
Schutzleiter-Anschlussklemme.
Symbol fur Schalter oder Drucknopfe - Zeigt die "Ein" - Stellung hier an.
Symbol fur Schalter oder Drucknopfe - Zeigt die "Aus" - Stellung hier an.
Dieses Warnaufschrift weist auf eine Gefahr hin, die eine Uberprufunganweisung nach sich
ziecht. Nichteinhaltung kann zu Personenschaden fuhren. Dieser Warnhinweis darf nicht
ubersprungen werden und die beschriebene Vorgehensweise musstrikt verstanden werden
und dementsprechend umgesetzt werden.
Diese „Vorsichtswarnung“ weist auf eine Gefahr hin, die einer Vorkehrung bedarf.
Nichteinhaltung kann zur Zerstorung der Anlage oder des Gerates fuhren. Bitte
berucksichtigen Sie alle Anweisungen, die dort beschreiben sind, bevor Sie mit Benutzung
der Anlage bzw. des Gerates fortfahren.
5
83-000-018 Rev. D
CHAPTER 1 GENERAL INFORMATION
1.1 USER MANUAL CONTENT
This User’s Manual contains the operating instructions, installation instructions and specifications
of the Genesys
supplies, including the built-in RS232/RS485 serial communication. For information related to operation with the optional IEEE programming, refer to User’s Manual for Power Supply IEEE Programming Interface. (Lambda Americas P/N 83-030-200).
1.2 INTRODUCTION
TM
GENH 750W power supply series. The instructions refer to the standard power
1.2.1 General Description
TM
Genesys
The Genesys
power supplies are wide output range, high performance switching power supplies.
TM
series is power factor corrected and operates from worldwide AC voltage range
continuously. Output Voltage and Current are continuously displayed and LED indicators show
the complete operating status of the power supply. The Front panel controls allow the user to set
the output parameters, the protections levels (Over-Voltage protection, Under-Voltage limit and
Foldback) and preview the settings. The rear panel includes the necessary connectors to control
and monitor the power supply operation by remote analog signals or by the built-in serial communication (RS232/RS485). GPIB programming and Isolated-Analog programming/monitoring are
optional.
Constant Voltage / Constant Current with automatic crossover.
∗
Active power factor correction.
∗
Universal Input Voltage (85i265Vac), continuous operation.
∗
Embedded Microprocessor Controller.
∗
Built-in RS-232/RS-485 Interface.
∗
Voltage & Current high resolution adjustment by digital encoders.
∗
High accuracy programming/readback.
∗
Software Calibration (no internal trimmers / potentiometers).
∗
Last Setting Memory.
∗
Independent Remote ON/OFF (opto-isolated) and remote Enable/Disable.
∗
6
83-507-5002 Rev. A
Parallel operation (Master/Slave) with Active current sharing.
∗
Remote sensing to compensate for voltage drop of power leads.
∗
External Analog Programming and Monitoring standard (0-5V or 0-10V, user selectable).
∗
Cooling fan speed control for low noise and extended fan life.
∗
Zero stacking-no ventilation holes at the top and bottom surface of the power supply.
∗
Optional GPIB interface (SCPI compatible).
∗
Optional Isolated Analog programming/monitoring (0-5V or 0-10V, user selectable and 4-
∗
20mA).
1.2.4 Multiple output power system
The Genesys
TM
power supplies series can be configured into a programmable power system of
up to 31 units using the built-in RS232/RS485 communication port and the RS485 linking cable
provided with each power supply.
In a GPIB system, each power supply can be controlled using the optional GPIB controller (factory installed).
1.2.5 Control via the serial communication port
The following parameters can be programmed / monitored via the serial communication port:
1. Output Voltage setting.
2. Output Current setting.
3. Output Voltage measurement.
4. Output On/Off control.
5. Output Current measurement.
6. Foldback protection setting
7. Over-voltage protection setting and readback.
8. Under-Voltage limit setting and readback.
9. Power-supply start up mode (Auto-restart or Safe-start mode).
1.2.6 Analog voltage programming and monitoring
Analog inputs and outputs are provided at the rear panel for analog control of the power supply.
The Output Voltage and the Current can be programmed by analog voltage or by resistor, and
can be monitored by analog voltage. The power supply output can be remotely set to On or Off
and analog signals monitor the proper operation of the power supply and the mode of operation
(CV/CC).
1.2.7 Parallel operation
Genesys
TM
power supplies of the same Output Voltage and Current rating can be paralleled in a
master-slave configuration with automatic current sharing to increase power available.
1.2.8 Output connections
Output connections are made to rear panel bus-bars for models up to 60V and to a 4-terminal
wire clamp connector for models above 60V rated output voltage. Either the positive or negative
terminal may be grounded or the output may be floated. Models up to 60VDC Rated Output shall
not float outputs more than +/- 60VDC above/below chassis ground. Models >60VDC Rated Output shall not float outputs more than +/-600VDC above/below chassis ground. Contact factory for
assistance with higher float voltage applications.
Local or remote sense may be used. In remote sense, the voltage drop on the load wires should
be minimized. Refer to the specifications for the maximum voltage drop value.
7
83-507-5002 Rev. A
1.2.9 Cooling and mechanical construction
The Genesys
free airflow into the power supply via the front panel and out of the power supply via the rear
panel. The Genesys
TM
series is cooled by internal fans. At the installation, care must be taken to allow
TM
power supplies have a compact and lightweight package, which allows
easy installation and space saving in the application equipment.
CAUTION
Observe all torque guidelines within this manual. Applying more torque may
damage unit or accessories. Such damage is not covered under manufacturers
warranty.
1.3 ACCESSORIES
1.3.1 General
Accessories are delivered with the power supply or separately upon ordering. The list below
shows the possible accessories and ordering numbers.
1.3.2 Serial Link Cable
Serial link cable, for linking power supplies by RS485 communication is provided with the power
supply.
AC cables are not provided with the power supply. If an AC cable is required, it should be ordered
according to following:
TM
For 750W Genesys
power supplies:
Part No. Market Description
NC301
(GEN/U)
NC302
(GEN/E)
NC303
(GEN/O)
NC305
(GEN/J)
NC306
(GEN/GB
)
USA 13A 125V, unshielded, 2m typical length, with IEC320 connector on one end
and NEMA-5-15P connector on the other end.
Europe 10A 250V, unshielded, 2m typical length, with IEC320 connector on one end
and INT’L 7 standard VII, dual earthing.
General 10A 250V, unshielded, 2m typical length, with IEC320 connector on one end
and unterminated stripped wires on the other end. Use the cable only with
plug approved by the national safety standards of the country of usage.
Japan 13A 125V,unshielded, 2m typical length, with IEC320 connector on one end
and Japan type plug on the other end.
UK 10A 250V unshielded, 2m typical length, with IEC320 connector on one end
and UK type plug on the other end.
1.3.5 Serial Port Cables Refer to Section 7.5
8
83-507-5002 Rev. A
CHAPTER 2 SPECIFICATIONS
9
83-507-5002 Rev. A
10
83-507-5002 Rev. A
NOTES:
*1: Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
*2: Minimum current is guaranteed to maximum 0.4% of the rated output current.
*3: For cases where conformance to various safety standards (UL, IEC etc.) is required, to be
described as 100-240Vac (50/60Hz).
*4: At 100/200V input voltage and maximum output power.
*5: From 85i132Vac or 170i265Vac, constant load.
*6: From No-load to Full-load, constant input voltage. Measured at the sensing point in Remote
Sense.
*7: For load voltage change, equal to the unit voltage rating, constant input voltage.
*8: For 6V models the ripple is measured at 2i6V output voltage and full output current. For other
models, the ripple is measured at 10i100% output voltage and full output current.
*9: With rated, resistive load.
*10. For 6i300V models: Measured with JEITA RC-9131A (1:1) probe
For 600V model: Measured with (10:1) probe.
2.12 SUPPLEMENTAL CHARACTERISTICS
The supplemental characteristics give typical but non-warranted performance characteristics. The
supplemental characteristics are useful in assessing applications for the power supply. Several
kinds of supplemental characteristics are listed below.
1. Evaluation Data: Typical performance of the power supply.
2. Reliability Data: Reliability Performance of the power supply.
3. IEC1000 Data: Performance of the power supply under IEC1000 test conditions.
4. EMI Data: Typical EMI (conducted and radiated) performance of the power supply.
The supplemental characteristics data is held in each Lambda sales and service facility. For further details please contact the lambda office nearest you.
11
83-507-5002 Rev. A
2.13 GENESYSTM GENH 750W POWER SUPPLIES OUTLINE DRAWINGS
12
83-507-5002 Rev. A
CHAPTER 3 INSTALLATION
3.1 GENERAL
This Chapter contains instructions for initial inspection, preparation for use and repackaging for
shipment. Connection to PC, setting the communication port and linking Genesys
plies are described in Chapter 7.
TM
power sup-
NOTE
Genesys
TM
power supplies generate magnetic fields, which
might affect the operation of other instruments. If your
equipment is susceptible to magnetic fields, do not position it
adjacent to the power supply.
3.2 PREPARATION FOR USE
In order to be operational the power supply must be connected to an appropriate AC source. The
AC source voltage should be within the power supply specification. Do not apply power before
reading Section 3.6 and 3.7.
Table 3-1 below, describes the basic setup procedure. Follow the instructions in Table 3-1 in the
sequence given to prepare the power supply for use.
Step no. Item Description Reference
1 Inspection Initial physical inspection of the power supply Section 3.3
2 Installation Installing the power supply,
Ensuring adequate ventilation.
3 AC source
AC source requirements
Connecting the power supply to the AC source
6 Default setting The power supply setting at shipment. Section 7.2.1
Table 3-1: Basic setup procedure
3.3 INITIAL INSPECTIONS
Prior to shipment this power supply was inspected and found free of mechanical or electrical defects. Upon unpacking of the power supply, inspect for any damage, which may have occurred in
transit.
The inspection should confirm that there is no exterior damage to the power supply such as broken knobs or connectors and that the front panel and meters face are not scratched or cracked.
Keep all packing material until the inspection has been completed. If damage is detected, file a
claim with carrier immediately and notify the Lambda sales or authorized service facility nearest
you.
13
83-507-5002 Rev. A
3.4 RACK MOUNTING
To install a GENH750W one unit or two units side-by-side in a standard 19” Rack in 1U (1.75”)
height, use option kit P/N: GENH/RM
The Rack Mount kit allows the units to be zero stacked for maximum system flexibility and power
density without increasing the 1U height of the units.
3.4.1 Single unit installation
To install a GENH750W power supply in a standard 19” Rack in 1U (1.75”) height, using a GENH
Rack Mount kit P/N: GENH/RM.
3.4.2 Dual unit installation
To install two GENH750W power supplies side-by-side in a standard 19” Rack in 1U (1.75”)
height, using a GENH Rack Mount kit P/N: GENH/RM.
14
83-507-5002 Rev. A
3.4.3 GENH/RM Rack Mounting outline drawings:
3.5 LOCATION, MOUNTING AND COOLING
This power supply is fan cooled. The air intake is at the front panel and the exhaust is at the rear
panel. Upon installation allow cooling air to each the front panel ventilation inlets. Allow minimum
10cm (4-inch) of unrestricted air space at the front and the rear of the unit.
The power supply should be used in an area that the ambient temperature does not exceed
+50°C.
3.6 AC SOURCE REQUIREMENTS
The GenesysTM series can be operated from a nominal 100V to 240V, single phase, 47i63 Hz.
The input voltage range and current required for each model is specified in Chapter 2. Ensure
that under heavy load, the AC voltage supplied to the power supply does not fall below the specifications described in Chapter 2.
3.7 AC INPUT POWER CONNECTION
CAUTION
Connection of this power supply to an AC power source
should be made by an electrician or other qualified personnel
WARNING
There is a potential shock hazard if the power supply chassis
(with cover in place) is not connected to an electrical safety
ground via the safety ground in the AC input connector.
15
83-507-5002 Rev. A
r
p
WARNING
Some components inside the power supply area are at AC voltage
even when the On/Off switch is in the “Off” position. To avoid electric
shock hazard, disconnect the line cord and load and wait two minutes
before removing cover.
3.7.1 AC Input Connector
An IEC connector is provided on the rear panel for connecting the unit to the AC power source
with an AC cord. The IEC connector also provides the safety ground connection while the AC
cord is plugged into an appropriate AC receptacle.
3.7.2 AC Input Cord
Refer to Section 1.3.4 for details of the AC input cords recommended for the GENH750W models.
WARNING
The AC input cord is the disconnect device of the powe
supply. The plug must be readily identifiable and accessible
to the user. The AC in
ut cord must be no longer than 3m.
3.8 TURN-ON CHECKOUT PROCEDURE
3.8.1 General
The following procedure ensures that the power supply is operational and may be used as a basic incoming inspection check. Refer to Fig.4-1 and Fig.4-2 for the location of the controls indicated in the procedure.
3.8.2 Prior to Operation
1. Ensure that the power supply is configured to the default setting:
– AC On/Off switch at Off position.
– Dip switch: All positions at Down (“Off”) position.
– Sense connector: Configured to Local Sense as shown in Fig.3-4:
– For units equipped with IEEE option, ensure that the IEEE_En switch is in Up (default)
position (Refer to Fig.4-2, Item 9 for location), if checkout is to be done in IEEE mode.
1 Remote (+) sense
2 Local (+) sense
3 Not connected
4 Local (-) sense
5 Remote (-) sense
Fig.3-4: Sense connector default connection
2. Connect the unit to an AC source as described in Section 3.7.
3. Connect a DVM with appropriate cables for the rated voltage to the output terminals.
16
83-507-5002 Rev. A
4. Turn the front panel AC power switch to On.
3.8.3 Constant Voltage Check
1. Turn on the output by pressing the OUT pushbutton so the OUT LED illuminates.
2. Observe the power supply VOLT display and rotate the Voltage encoder. Ensure that the
Output Voltage varies while the VOLT encoder is rotated. The minimum control range is from
zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel VOLT display to verify the accuracy of the
VOLT display. Ensure that the front panel VOLT LED is On.
3. Turn Off the front panel AC power switch.
3.8.4 Constant Current Check
1. Ensure that the front panel AC power switch is at the Off position and the DVM connected to
the output terminals shows zero voltage.
2. Connect a DC shunt across the output terminals. Ensure that the shunt and the wire current
ratings are higher than the power supply rating. Connect a DVM to the shunt.
3. Turn the front panel AC power switch to the On position,
4. Turn On the output by pressing OUT pushbutton so the OUT LED illuminates.
5. Observe the power supply CURRENT display and rotate the CURRENT encoder. Ensure that
the Output Current varies while the CURRENT encoder is rotated. The minimum control
range is from zero to the maximum rated output for the power supply model.
Compare the DVM reading with the front panel CURRENT display to verify the accuracy of
the CURRENT display. Ensure that the front panel CURRENT LED is On.
6. Turn Off the front panel AC power switch.
7. Remove the shunt from the power supply output terminals.
3.8.5 OVP Check
Refer to Section 5.3 for explanation of the OVP function prior to performing the procedure below.
1. Turn the front panel AC power switch to the On position and turn on the output by pressing
OUT pushbutton.
2. Using the VOLT encoder, adjust the Output Voltage to approx. 10% of the unit voltage rating.
3. Momentarily press the OVP/UVL button so that the CURRENT display shows “OUP”. The
VOLTAGE display will show the last setting of the OVP level.
4. Rotate the VOLT encoder CCW to adjust the OVP setting to 50% of the unit voltage rating.
5. Wait a few seconds until the VOLT display returns to show the Output Voltage.
6. Adjust the Output Voltage toward its maximum and check that the Output Voltage cannot be
increased more than the OVP setting.
7. Adjust OVP limit to the maximum by repeating Step 3 and rotating the VOLT encoder CW.
3.8.6 UVL Check
Refer to Section 5.4 for explanation of the UVL function prior to performing the procedure below.
1. Press the OVP/UVL button TWICE so that the CURRENT display shows “UUL”. The
VOLTAGE display will show the last setting of the UVL level.
2. Rotate the VOLT encoder to adjust the UVL level to approx. 10% of the unit voltage rating.
3. Wait a few seconds until the VOLT display returns to show the output voltage.
4. Adjust the output voltage toward its minimum and check that the output voltage cannot be decreased below the UVL setting.
5. Adjust the UVL limit to the minimum by repeating step 1 and rotating the VOLT encoder CCW.
3.8.7 Foldback Check
17
83-507-5002 Rev. A
WARNING
Shorting the output may expose the user to hazardous
voltages. Observe proper safety procedures.
Refer to Section 5.5 for explanation of the FOLD function prior to performing the procedure below.
1. Ensure that the Output Voltage is set to approx. 10% of the unit rating.
2. Adjust the CURRENT encoder to set the Output Current setting to approx. 10% of the unit
rating.
3. Momentarily press the FOLD button. Ensure that the FOLD LED illuminates. The Output Voltage remains unchanged.
4. Short the output terminals momentarily (approx. 0.5 sec.). Ensure that the Output Voltage
falls to zero, the VOLT display shows “Fb” and the ALARM LED blinks.
5. Press the FOLD button again to cancel the protection. The Output Voltage remains zero.
6. Press the OUT button. Ensure that the Output Voltage returns to its last setting.
7. Turn the output off by pressing the OUT button. Ensure that the VOLT display shows “OFF”.
3.8.8 Address Setting
1. Press and hold the REM/LOC button for approx. 3 sec. The VOLT display will show the communication port address.
2. Using the VOLT adjust encoder, check that the address can be set within the range of 0 to 30.
3.8.9 Baud Rate Setting (RS-232 and RS-485 only)
1. Press and hold the REM/LOC button for approx. 3 sec. The CURRENT display will show the
communication port Baud Rate.
2. Using The CURRENT adjust encoder, check that the Baud Rate can be set to 1200, 2400,
4800, 9600 and 19200.
3.9 CONNECTING THE LOAD
Turn Off the AC input power before making or changing any rear
panel connection. Ensure that all connections are securely tightened before applying power. There is a potential shock hazard
when using a power supply with a rated output greater than 40V.
3.9.1 Load Wiring
The following considerations should be made to select wiring for connecting the load to the power
supply:
Current carrying capacity of the wire (refer to Section 3.9.2)
∗
Insulation rating of the wire should be at least equivalent to the maximum output voltage of
∗
the power supply.
Maximum wire length and voltage drop (refer to Section 3.9.2)
∗
Noise and impedance effects of the load wiring (refer to Section 3.9.4).
∗
3.9.2 Current Carrying Capacity
Two factors must be considered when selecting the wire size:
1. Wires should be at least heavy enough not to overheat while carrying the power supply
load current at the rated load, or the current that would flow in the event the load wires
were shorted, whichever is greater.
2. Wire size should be selected to enable voltage drop per lead to be less than 1.0V at the
rated current. Although units will compensate for up to 5V in each load wire, it is recom-
WARNING
18
83-507-5002 Rev. A
g. (
mended to minimize the voltage drop (1V typical maximum) to prevent excessive output
power consumption from the power supply and poor dynamic response to load changes.
Please refer to Tables 3-2 and 3-3 for minimum wire length (to limit voltage drop) in
American and European dimensions respectively.
Table 3-3: Maximum wire length for 1 V drop on lead (in meters)
For currents not shown in Table 3-2 and 3-3, use the formula:
Maximum length=1000/(current x resistivity)
Where current is expressed in Amperes and resistivity in ohms/km or ohms/1000ft.
3.9.3 Wire termination
The wires should be properly terminated with terminals securely attached. DO NOT use unterminated wires for load connection at the power supply.
CAUTION
When local sensing, a short from +LS or +S to -V or -S or -LS,
will cause damage to the power supply. Reversing the sense
wires might cause damage to the power supply in local and
remote sensin
Do not connect -S to +V or +S to -V).
19
83-507-5002 Rev. A
3.9.4 Noise and Impedance Effects
To minimize the noise pickup or radiation, the load wires and remote sense wires should be
twisted pairs to the shortest possible length. Shielding of sense leads may be necessary in high
noise environments. Where shielding is used, connect the shield to the chassis via a rear panel
Ground screw. Even if noise is not a concern, the load and remote sense wires should be
twisted-pairs to reduce coupling, which might impact the stability of power supply. The sense
leads should be separated from the power leads.
Twisting the load wires reduces the parasitic inductance of the cable, which could produce high
frequency voltage spikes at the load and the output of the power supply, because of current
variation in the load itself.
The impedance introduced between the power supply output and the load could make the ripple
and noise at the load worse than the noise at the power supply rear panel output. Additional filtering with bypass capacitors at the load terminals may be required to bypass the high frequency
load current.
3.9.5 Inductive loads
Inductive loads can produce voltage spikes that may be harmful to the power supply. A diode
should be connected across the output. The diode voltage and current rating should be greater
than the power supply maximum output voltage and current rating. Connect the cathode to the
positive output and the anode to the negative output of the power supply.
Where positive load transients such as back EMF from a motor may occur, connect a surge suppressor across the output to protect the power supply. The breakdown voltage rating of the suppressor must be approximately 10% higher than the maximum output voltage of the power supply.
3.9.6 Making the load connections
WARNING
Hazardous voltages may exist at the outputs and the load connections
when using a power supply with a rated output greater than 40V. To
protect personnel against accidental contact with hazardous voltages,
ensure that the load and its connections have no accessible live parts.
Ensure that the load wiring insulation rating is greater than or equal to
the maximum output voltage of the power supply.
CAUTION
Ensure that the load wiring mounting hardware does not short the output
terminals. Heavy connecting cables must have some form of strain relief
to prevent loosening the connections or bending the bus-bars.
6V to 60V Models
Refer to Fig.3-5 for connection of the load wires to the power supply bus-bars and to Fig.3-6 for
mounting the bus-bars shield to the chassis.
20
83-507-5002 Rev. A
Fig. 3-6: bus-bars shield mounting
80V to 600V Models
Hazardous voltages exist at the outputs and the load connections. To
protect personnel against accidental contact with hazardous voltages,
ensure that the load and its connections have no accessible live parts.
Ensure that the load wiring insulation rating is greater than or equal to
the maximum output voltage of the power supply.
WARNING
21
83-507-5002 Rev. A
The 80V to 600V models have a four terminal wire clamp output connector. The two left terminals
are the positive outputs and the two right terminals are the negative outputs. The connector requirements are as follows:
1. Wires: AWG18 to AWG10.
2. Tightening torque: 6.5-7.0 Lb-inch.
Follow the instructions below for connection of the load wires to the power supply:
1. Strip approx. 10mm (0.39 inches) at the end of each of the wires.
2. Loosen the connector terminal screws.
3. Insert the stripped wires into the terminal and tighten the terminal screw securely (see
Fig.3-7)
4. Loosen the two chassis screws marked “A” halfway as shown in Fig.3-8.
5. Assemble the protective shield to the chassis and tighten the two screws to fix the shield
to the chassis (see Fig.3-8). Screws tightening torque: 4.8-5.3 Lb-inch.
6. Tighten the wires to one of the shield sides using ty-wrap or equivalent. Refer to Fig.3-9.
Ensure that the wire length inside the shield is long enough to provide proper strain relief.
22
83-507-5002 Rev. A
3.9.7 Connecting single loads, local sensing (default).
Fig.3-10 shows recommended load and sensing connections for a single load. The local sense
lines shown are default connections at the rear panel J2 sense connector. Local sensing is suitable for applications where load regulation is less critical.
Fig.3-11 shows recommended remote sensing connection for single loads. Remote sensing is
used when, in Constant Voltage mode, the load regulation is important at the load terminals. Use
twisted or shielded wires to minimize noise pick-up. If shielded wires are used, the shield should
be connected to the ground at one point, either at the power supply chassis or the load ground.
The optimal point for the shield ground should be determined by experimentation.
Fig.3-11: Remote sensing, single load
Load lines. Twisted pair
shortest length possible.
+V
+
Load
Power
-V
Supply
-
Rem.sense
-
Local sense
+
Local sense
+
Rem.sense
Sense lines. Twisted
pair or shielded.
3.9.9 Connecting multiple loads, radial distribution method
Fig.3-12 shows multiple loads connected to one supply. Each load should be connected to the
power supply’s output terminals using separate airs of wires. It is recommended that each pair of
wires will be as short as possible and twisted or shielded to minimize noise pick-up and radiation.
The sense wires should be connected to the power supply output terminals or to the load with the
most critical load regulation requirement.
23
83-507-5002 Rev. A
Power
Supply
Rem.sense
-
Local sense
-
Local sense
+
Rem.sense
+
+V
-V
Fig.3-12: Multiple loads connection, radial distribution, local sense
3.9.10 Multiple load connection with distribution terminals
If remotely located output distribution terminals are used, the power supply output terminals
should be connected to the distribution terminals by pair of twisted and/or shielded wires. Each
load should be separately connected to the remote distribution terminals (see Fig.3-13).
If remote sensing is required, the sensing wires should be connected to the distribution terminals
or at the most critical load.
Power
Supply
-
Rem.sense
-
Local sense
+
Local sense
+
Rem.sense
+V
-V
Distribution terminal
+V
-V
+
Load#1
+
Load#2
+
Load#3
Fig.3-13: Multiple loads connection with distribution terminal
3.9.11 Grounding outputs
Either the positive or negative output terminals can be grounded. To avoid noise probems caused
by common-mode current flowing from the load to ground, it is recommended to ground the
output terminal as close as possible to the power supply chassis ground.
Always use two wires to connect the load to the power supply regardless of how the system is
grounded.
WARNING
Models up to 60VDC Rated Output shall not float outputs more
than +/-60VDC above/below chassis ground. Models > 60VDC
Rated Output shall not float outputs more than +/-600VDC
above/below chassis ground.
24
83-507-5002 Rev. A
p
p
(NC)
There is a potential shock hazard at the RS232/RS485 and the IEEE ports when
using power supplies with rated or combined voltage greater than 400V with the
Positive Output of the power supplies grounded. Do not connect the Positive output to ground when using the RS232/RS485 or IEEE under the above conditions.
OUTPUT TERMINAL GROUNDING
WARNING
3.10 LOCAL AND REMOTE SENSING
The rear panel J2 sense connector is used to configure the power supply for local or remote
sensing of the Output Voltage. Refer to Fig.3-14 for sense connector location.
3.10.1 Sense wiring
WARNING
There is a potential shock hazard at the sense connector when using a power
supply with a rated Output Voltage greater than 40V. Local sense and remote
sense wires should have a minimum insulation rating equivalent or greater than
the maximum Output Voltage of the power supply. Ensure that the connections at
the load end are shielded to prevent accidental contact with hazardous voltages.
3.10.2 Local sensing
The power supply is shipped with the rear panel J2 sense connector wired for local sensing of the
Output Voltage. See Table 3-4 for J2 terminals assignment. With local sensing, the Output Voltage regulation is made at the output terminals. This method does not compensate for voltage
drop on the load wires, therefore it is recommended only for low load current applications or
where the load regulation is less critical.
Fig.3-14: Sense connector location
Terminal Function
J2-1 Remote
J2-2 Local
J2-3 Not connected
ositive sense (+S)
ositive sense. Connected internally to the positive output terminal (+LS).
J2-4 Local negative sense. Connected internally to the negative output terminal (-LS).
J2-5 Remote negative sense (-S).
Table 3-4: J2 terminals
25
83-507-5002 Rev. A
3.10.3 Remote sensing
WARNING
There is a potential shock hazard at the sense point when using a power supply
with a rated Output Voltage greater than 40V. Ensure that the connections at the
load end are shielded to prevent accidental contact with hazardous voltages.
CAUTION
When using shielded sense wires, ground the shield
in one place only. The location can be the power supply chassis or one of the output terminals.
Use remote sense where the load regulation at the load end is critical. In remote sense, the
power supply will compensate for voltage drop on the load wires. Refer to the power supply
specifications for the maximum voltage drop on load wires. The voltage drop is subtracted from
the total voltage available at the output. Follow the instructions below to configure the power supply for remote sensing:
1. Ensure that the AC On/Off is in the Off position.
2. Remove the local sense jumpers from J2.
3. Connect the negative sense lead to terminal J2-5 (S) and the positive sense lead to terminal
J2-1(+S) of the J2 mating connector. Ensure that the J2 mating connector is plugged securely
into the rear panel sense connector, J2.
4. Turn On the power supply.
Notes:
1. If the power supply is operating in remote sense and either the positive or negative load wire
is not connected, an internal protection circuit will activate and shut down the power supply.
To resume operation, turn the AC On/Off to the Off position, connect the open load wire, and
turn On the power supply.
2. If the power supply is operated without the remote sense lines or local sense jumpers, it will
continue to work, but the output voltage regulation will be degraded. Also, the OVP circuit
may activate and shut down the power supply.
To ensure safe transportation of the instrument, contact the Lambda sales or service facility near
you for Return Authorization and shipping information. Please attach a tag to the power supply
describing the problem and specifying the owner, model number and serial number of the power
supply. Refer to Warranty Information for further instructions.
26
83-507-5002 Rev. A
CHAPTER 4 FRONT AND REAR PANEL CONTROLS AND CONNECTORS
4.1 INTRODUCTION
The GenesysTM Power Supply series has a full set of controls, indicators and connectors that allow the user to easily setup and operate the unit. Before starting to operate the unit, please read
the following Sections for explanation of the functions of the controls and connectors terminals.
-Section 4.2: Front Panel Controls and Indicators.
-Section 4.3: Rear Panel Connections and Controls.
4.2 FRONT PANEL CONTROLS AND INDICATORS
See Fig.4-1 to review the controls, indicators and meters located on the power supply front panel.
6
POWER
19
1
VOLTAGE
18
2
DC VOLTS
ALARM FINE
17
3
14
OVP
UVLFOL D
13
PREV/
16
15
4
DC AMPS
REM/LOC
11
OUT
7
9
12
10
5
CURRENT
8
Fig.4-1: Front panel controls and indicators
Table 4-1: Front Panel controls and indicators
Number Control/Indicator Description Section
1 VOLTAGE
control
High resolution rotary encoder for adjusting the Output Voltage. Also adjusts the OVP/UVL levels and
selects the Address
5.2.1
5.3.1
5.4.1
7.2.2
2 VOLTAGE in-
dicator
Green LED, lights for constant-Voltage mode operation.
3 VOLTAGE dis-
play
4 digit, 7-segment LED display. Normally displays
the Output Voltage. When the PREV button is
pressed, the display indicates the programmed setting of the Output Voltage. When the OVP/UVL button is pressed, the Voltage display indicates the
OVP/UVL setting.
27
83-507-5002 Rev. A
Table 4-1: Front Panel Controls and Indicators
Number Control/Indicator Description
4 CURRENT display
4 digit, 7 segment LED display. Normally displays the Output
Current. When the PREV button is pressed, the display indicates the programmed setting of Output Current.
5 CURRENT indicator Green LED, lights for Constant-Current mode operation
6 CURRENT control
High resolution rotary encoder for adjusting the Output Current.
Auxiliary Function:
1) Selects the Baud-Rate of communication port
2) Set desired mode of the Master Power Supply in
Advanced parallel operation.
7 OUT button
Main function: Output ON/OFF control. Press OUT to set the
output On or Off. Press to reset and turn On the output after
OVP or FOLD alarm events have occurred. Auxiliary function:
Selects between “Safe-Start” and “Auto-Restart” modes. Press
and hold OUT button to toggle between “Safe-Start” and “AutoRestart”. The VOLT display will cycle between “SAF” and “AUT”.
Releasing the OUT button while one of the modes is displayed,
selects that mode.
8 OUT indicator Green LED, lights when the DC output is enabled.
Main function: Go to local. Press REM/LOC to put the unit into
Local mode (REM/LOC button is disabled at Local Lockout
mode).
Auxiliary function: Address and Baud Rate setting. Press and
9
REM/LOC button
hold REM/LOC for 3 sec. to set the Address with the VOLTAGE
encoder and the Baud Rate with the CURRENT encoder.
10 REM/LOC indicator Green LED, lights when the unit is in Remote mode.
11
FOLD button
Foldback protection control.
-Press FOLD to set Foldback protection to On.
-To release Foldback alarm even, press OUT to enable the output and re-arm the protection.
-Press FOLD again to cancel the Foldback protection.
12 FOLD indicator Green LED, lights when Foldback protection is On.
13 OVP/UVL button
Over Voltage Protection and Under Voltage limit setting.
-Press once to set OVP using VOLTAGE encoder (the current
display shows “OUP”)
-Press again to set the UVL using VOLTAGE encoder (the current display shows “UUL”).
14 PREV button
Main function: Press PREV to display the Output Voltage and
Current setting. For 5 sec. the display will show the setting and
then it will return to show the actual Output Voltage and Current.
Auxiliary function: Front Panel Lock. Press and hold PREV
button to toggle between “Locked front panel” and “Unlocked
front panel”. The display will cycle between “LFP” and “UFP”.
Releasing the PREV button while one of the modes is displayed
selects that mode.
Table 4-1: Front Panel Controls and Indicators (continued)
28
83-507-5002 Rev. A
Section
5.2.2
7.2.4
5.15.2
5.6
5.11
7.2.5
7.2.2
7.2.4
5.5
5.3
5.4
5.17
Number Control/Indicator Description
15 PREV indicator
16 FINE button
Green LED, lights when PREV button is pressed
Voltage and Current Fine/Coarse adjustment control. Op-
erates as a toggle switch. In Fine mode, the VOLTAGE
and CURRENT encoders operate with high resolution and
in Coarse mode with lower resolution (approx. 6 turns).
Auxiliary function: Set units as Master or Slave in Ad-
Section
5.15.2
vanced parallel operation.
17 FINE indicator
18 ALARM indicator
Green LED, lights when the unit is in Fine mode.
Red LED, blinks in case of fault detection. OVP, OTP
Foldback, Enable and AC fail detection will cause the
ALARM LED to blink.
19 AC Power switch AC On/Off control.
4.3 REAR PANEL CONNECTIONS AND CONTROLS
See Fig.4-2 to review the connections and controls located on the power supply rear panel. Refer
to Table 4-2 for explanations about the rear panel connections and controls.
Fig.4-2: Rear panel connections and controls
Table 4-2: Rear panel connections and controls
Number Item Description
1
AC input
connector
2 DC output
Wire clamp connector for 1500W units.
IEC connector for 750W units.
Bus-bars for 6V to 60V models.
Wire clamp connector for 80V to 600V models.
3 Remote-In
connector
RJ-45 type connector, used for connecting power supplies to
RS232 or RS485 port of computer for remote control purposes.
When using several power supplies in a power system, the first
unit Remote-In is connected to the computer and the remaining
units are daisy-chained, Remote-In to Remote-Out.
Table 4-2: Rear panel Connections and Controls (continued)
29
83-507-5002 Rev. A
Section
3.7.1
3.7.2
3.9.6
7.3
7.5
Number Item Description
4
Remote Out
connector
5 J1 Analog
Remote
connector
RJ-45 type connector, used for daisy-chaining power supplies to
form a serial communication bus.
Connector for remote analog interface. Includes Output Voltage and
Current programming and monitoring signals, Shut-off control (electrical signal), Enable/Disable control (dry-contact), Power Supply
OK (PS_OK) signal and operation mode (CV/CC) signal.
6 SW1 Setup
switch
Nine position DIP-switch for selecting remote programming and
monitoring modes for Output Voltage, Output Current and other
control functions.
7
J2 Remote
sense
Connector for making remote sensing connections to the load for
regulation of the load voltage and compensation of load wire drop.
connector
8 Blank
Sub-plate
Blank sub-plate for standard units. Isolated Remote Analog programming connector for units equipped with Isolated Analog control
option. IEEE connector for units equipped with IEEE programming
option (shown).
9 IEEE switch
Two position DIP-switch for selecting IEEE mode or RS232/RS485
mode when IEEE option is installed.
10
Ground
screw
M4x0.7, 8mm long DBL-SEMS screw for chassis ground
connection.
4.4 REAR PANEL SW1 SETUP SWITCH
The SW1 Setup switch (see Fig.4-3) is a 9-position DIP-switch that allows the user to choose the
following:
Internal or remote programming for Output Voltage and Output Current.
−
Remote voltage or resistive programming of Output Voltage and Output Current limit.
−
Select range of remote voltage and resistive programming.
−
Select range of output Voltage and Output Current monitoring.
−
Select the Remote Shut-Off control logic.
−
Select between RS232 and RS485 communication interface.
−
Enable or disable the rear panel Enable/Disable control (dry contact).
−
Section
7.3
7.5
4.5
4.4
3.10
3.8.2
Fig. 4.2
Fig. 4.2
Fig. 4.2
4.4.1 SW1 position function
Refer to Table 4-3 for description of SW1 position functions. The factory default setting is
Down for all positions.
Table 4-3: SW1 Positions Functions
9
8
7
6
5
4
3
2
1
Fig.4-3: SW1 setup DIP-switch
30
83-507-5002 Rev. A
Position Function
SW1-1
SW1-2
Output Voltage
remote analog programming
Output Current
remote analog programming
Terminals 12, 22 and 23 of J1 are connected internally to the
Programming Range Select
SW1-3
SW1-4
negative sense (-S) potential of the power supply. Do not
(Remote voltage/resistive)
attempt to bias any of these terminals relative to the negative sense. Use the Isolated Programming interface option to
Output Voltage and
Current Monitoring Range
allow control from a programming source at a different potential relative to the power supply negative.
Off: Low (0-0.6V) or Short
On: High (2-15V) or Open
Output Voltage
programmed by Front
Panel
Output Current
programmed by Front
Panel
Rear panel
Enable/Disable control is
not Active
programmed by remote
programmed by remote
Off: Low (2-15V) or Open
On: High (0-0.6V) or Short
programmed by external
Enable/Disable control
UP
Output Voltage
analog voltage
Output Current
analog voltage
Output Voltage
programmed by
external resistor
Output Current
resistor
Rear panel
is Active
4.4.2 Resetting the SW1 switch
Before making any changes to the SW1 switch setting, disable the power supply output by
pressing the front panel OUT button. Ensure that the Output Voltage falls to zero and the
OUT LED is Off. Then use any small flat-bladed screwdriver to change the SW1 switch setting.
4.5 REAR PANEL J1 PROGRAMMING AND MONITORNG CONNECTOR
The J1 Programming and Monitoring connector is a DB25 subminiature connector located on the
power supply rear panel. Refer to Table 4-4 for description of the connector functions. The power
supply default configuration is Local operation, which does not require connections to J1. For remote operation using J1 signals, use the plug provided with power supply (or equivalent type). It
is essential to use a plastic body plug to conform to Safety Agency requirements. If a shield is
required for the J1 wires, connect the shield to a power supply chassis ground screw.
Before making any connection, turn the AC on/Off switch to the Off position and wait until the
front panel display has turned Off.
31
83-507-5002 Rev. A
CV/CC
LOC/REM SIGNAL
Fig.4-4: J1 connector terminals and functions
Same ground
as P/S negative
VMON
COM
12
13
PENA_OUT
IMON
IPGM_RTN
VPGM_RTN
sense (-S)
IPGM
VPGM
LOC/
REM
8
9
1011
22232425
7
2021
19
as RS 232/R S485
56
1718
Isolated from
PS outputs,
same ground
IF_COM
IF_COM
ENA_IN
4
2
3
1
141516
SO
PS_OK
To prevent ground loops and to maintain power supply isolation when programming from J1, use an ungrounded programming source.
CAUTION
There is a potential shock hazard at the output when using a
power supply with rated output greater than 40V. Use wires
with minimum insulation rating equivalent to the maximum
output voltage of the power supply.
WARNING
32
83-507-5002 Rev. A
Table 4-4: J1 connector terminals and functions
J1
contact
J1-1 ENA_IN Enable/Disable the power supply output by dry-contact
Signal
name Function Reference
Sec. 5.8
(short/open) with ENA_OUT.
J1-2
J1-3
IF_COM Isolated Interface Common. Return for the SO control,
PS_OK signal and for the optional IEEE interface.
Sec.5.7,
5.10
J1-4i7 N/C No Connection
J1-8 LOCAL/
REMOTE
J1-9 VPGM Input for remote analog voltage/resistance programming
J1-10 IPGM Input for remote analog voltage/resistance programming
Input for selecting between Local or Remote analog pro-
gramming of Output Voltage and Output Current.
of the Output Voltage.
of the Output Current.
Sec. 6.2
Sec.
6.1i6.4
Sec.
6.1i6.4
J1-11 VMON Output for monitoring the power supply Output Voltage. Sec. 6.6
J1-12 COM
J1-13 CV/CC Output for Constant-Voltage/Constant-Current mode
Control Common. Return for VMON, IMON, CV/CC, LOC/REM.
Connected internally to the negative sense potential (-S).
Sec. 5.9
indication.
J1-14 ENA_OUT Enable/Disable the power supply output by dry-contact
Sec. 5.8
(short/open) with ENA_IN.
J1-15 SO Input for Shut-Off control of the power supply output. Sec. 5.7
J1-16 PS_OK Output for indication of the power supply status. Sec. 5.10
J1-17i20 N/C No Connection.
J1-21 LOC/REM
SIGNAL
Output for indicating if the unit is in Local or Remote ana-
log programming mode.
Sec. 6.3
J1-22 VPGM_RTN Return for VPGM input. Connected internally to the “-S”. Sec. 6.1,
6.4, 6.5
J1-23 IPGM_RTN Return for IPGM input. Connected internally to the “-S”. Sec. 6.1,
6.4, 6.5
J1-24 IMON Output for monitoring the power supply Output Current. Sec. 6.6
J1-25 P Output for current balance in parallel operation.
33
83-507-5002 Rev. A
CHAPTER 5 LOCAL OPERATION
5.1 INTRODUCTION
This Chapter describes the operating modes that are not involved in programming and monitoring
the power supply via its serial communication port (RS232/RS485) or by remote analog signals.
Ensure that the REM/LOC LED on the front panel is Off, indicating Local mode. If the REM/LOC
LED is On, press the front panel REM/LOC button to change the operating mode to Local.
-For information regarding Remote Analog Programming, refer to Chapter 6.
-For information regarding usage of the Serial Communication Port, refer to Chapter 7.
5.2 STANDARD OPERATION
The power supply has two basic operating modes: Constant Voltage Mode and Constant Current
Mode. The mode in which the power supply operates at any given time depends on the Output
Voltage setting, Output Current setting and the load resistance.
5.2.1 Constant Voltage Mode
1. In constant voltage mode, the power supply regulates the Output Voltage at the selected
value, while the load current varies as required by the load.
2. While the power supply operates in constant voltage mode, the VOLTAGE LED on the front
panel illuminates.
3. Adjustment of the Output Voltage can be made when the power supply output is enabled
(Output On) or disabled (Output Off). When the output is enabled, simply rotate the
VOLTAGE encoder knob to program the output voltage. When the output is disabled, press
the PREV button and then rotate the VOLTAGE encoder knob. The VOLTAGE meter will
show the programmed Output Voltage for 5 seconds after the adjustment has been completed. Then the VOLTAGE meter will display “OFF”.
4. Adjustment resolution can be set to coarse or fine resolution. Press FINE button to select between the lower and higher resolution. The FINE LED turns On when the resolution is set to
FINE.
If after completing the adjustment, the display shows a different value
than the setting, the power supply may be at current limit. Check the
load condition and the power supply Output Current setting.
NOTE
The maximum and minimum setting values of the output voltage are
limited by the Over Voltage protection and Under Voltage limit setting.
Refer to Sections 5.3 and 5.4 for more details.
5.2.2 Constant Current Mode
1. In constant current mode, the power supply regulates the Output Current at the selected
value, while the voltage varies with the load requirement.
2. While the power supply is operating in constant current mode, the CURRENT LED on the
front panel illuminates.
3. Adjustment of the Output Current setting can be made when the power supply output is enabled (Output On) or disabled (Output Off).
-Disabled output (Off): Press PREV button and then rotate the Current encoder knob. The
CURRENT meter will show the programmed Output Current limit for 5 seconds after the adjustment has been completed. Then the VOLTAGE meter will display “OFF”.
NOTE
34
83-507-5002 Rev. A
-Enabled output, power supply in Constant Voltage mode: Press the PREV button and
then rotate the CURRENT encoder knob. The CURRENT meter will show the programmed Output Current for 5 seconds after the adjustment has been completed, and
then will return to show the actual load current.
-Enabled output, power supply in Constant Current mode: Rotate the CURRENT encoder
knob to adjust the Output Current.
4. Adjustment resolution can be set to Coarse or Fine adjustment. Press the FINE button to select between the Coarse and Fine resolution. The FINE LED turns On when the resolution is
set to FINE.
5.2.3 Automatic Crossover
If the power supply operates in Constant Voltage mode, while the load current is increased to
greater than the current limit setting, the power supply will automatically switch to Constant Current mode. If the load is decreased to less than the current limit setting, the power supply will
automatically switch back to Constant Voltage mode.
5.3 OVER VOLTAGE PROTECTION (OVP)
The OVP circuit protects the load in the event of a remote or local programming error or a power
supply failure. The protection circuit monitors the voltage at the power supply sense points and
thus provides the protection level at the load. Upon detection of an Over Voltage condition, the
power supply output will shut down.
5.3.1 Setting the OVP level
The OVP can be set when the power supply output is Enabled (On) or Disabled (Off). To set the
OVP level, press the OVP/UVL button, so that the CURRENT meter shows “OUP”. The
VOLTAGE meter shows the OVP setting level. Rotate the VOLTAGE encoder knob to adjust the
OVP level. The display will show “OUP” and the setting value for 5 seconds after the adjustment
has been completed, and then will return to its previous state.
The minimum setting level is approximately 105% of
the set Output Voltage, or the value in Table 7-6,
whichever is higher. The maximum setting level is
shown in Table 5-1.
To preview the OVP setting, press the OVP/UVL
pushbutton so that the CURRENT display will show
“OUP”. At this time, the VOLTAGE display will show
Model Max.
OVP
6V
8V
12.5V
20V
30V
40V
7.5V
10.0V
15.0V
24.0V
36.0V
44.0V
the OVP setting. After 5 seconds, the display will return to its previous state. Table 5-1: Maximum OVP setting levels
5.3.2 Activated OVP protection indications
When the OVP is activated the power supply output shuts down. The VOLTAGE display shows
“OUP” and the ALARM LED blinks.
Model Max.
OVP
60V
80V
100V
150V
300V
600V
66.0V
88.0V
110.0V
165.0V
330.0V
660.0V
5.3.3 Resetting the OVP circuit
To reset the OVP circuit after it activates:
1. Reduce the power supply Output Voltage setting below the OVP set level.
2. Ensure that the load and the sense wiring are connected properly.
3. There are four methods to reset the OVP circuit.
3.1 Press the OUT button.
3.2 Turn the power supply Off using the AC On/Off switch, wait until the front panel display
turns Off, then turn the power supply On using the AC On/Off switch.
3.3 Turn the power supply output Off and then On using the SO control (refer to Section 5.7).
In this method the power supply should be set to Auto-Restart mode.
3.4 Send an OUT 1command via the RS232/RS485 communication port.
35
83-507-5002 Rev. A
5.4 UNDER VOLTAGE LIMIT (UVL)
The UVL prevents adjustment of the Output Voltage below a certain limit. The combination of
UVL and OVP functions, allow the user to create a protection window for sensitive load circuitry.
5.4.1 Setting the UVL level
Setting the UVL can be made when the power supply output is Enabled (On) or Disabled (Off). To
set the UVL level, press the OVP/UVL button TWICE, so that the CURRENT meter shows “UUL”.
The VOLTAGE meter shows the UVL setting level. Rotate the VOLTAGE encoder knob to adjust
the UVL level. The display will show ‘UUL” and the setting value for 5 seconds after the adjustment has been completed and then will return to its previous state.
UVL setting values are limited at the maximum level to approximately 95% of the Output Voltage
setting. Attempting to adjust the UVL above this limit will result in no response to the adjustment
attempt. The minimum UVL setting is zero.
5.5 FOLDBACK PROTECTION
Foldback protection will shut down the power supply output if the load current exceeds the current limit setting level. This protection is useful when the load circuitry is sensitive to an overcurrent condition.
5.5.1 Setting the Foldback protection
To arm the Foldback protection, the FOLD button should be pressed so that the FOLD LED illuminates. In this condition, transition from Constant Voltage to Constant Current mode will activate
the Foldback protection. Activation of the Foldback protection disables the power supply output,
causes the ALARM LED to blink and displays “Fb” on the VOLTAGE meter.
5.5.2 Resetting activated Foldback protection
There are four methods to reset an activated Foldback protection.
1. Press the OUT button. The power supply output is enabled and the Output Voltage and Current will return to their last setting. In this method, the Foldback protection remains armed,
therefore if the load current is higher than the current limit setting, the Foldback protection will
be activated again.
2. Press the FOLD button to cancel the Foldback protection. The power supply output will be
disabled and the VOLTAGE display will show “OFF”. Press the OUT button to enable the
power supply output.
3. Turn the power supply output Off and then On using the SO control (refer to Section 5.7). In
this method the Foldback protection remains armed, therefore if the load current is higher
than the output current setting, the Foldback protection will be activated.
4. Turn the power supply Off using the AC On/Off switch, wait until the front panel display turns
Off, then turn the unit back ON again. The power supply output is enabled and the Output
Voltage and Current will return to their last setting. In this method, the Foldback protection
remains armed, therefore if the load current is higher than the output current setting, the
Foldback protection will be activated again.
5.6 OUTPUT ON/OFF CONTROL
The Output On/Off Enables or Disables the power supply output. Use this function to make adjustments to either the power supply or the load without shutting off the AC power. The Output
On/Off can be activated from the front panel using the OUT button or from the rear panel J1 connector. The OUT button can be pressed at any time to Enable or Disable the power supply output. When the output is disabled, the Output Voltage and Current fall to zero and the VOLTAGE
display shows “OFF”.
5.7 OUTPUT SHUT-OFF (SO) CONTROL VIA REAR PANEL J1 CONNECTOR
Contacts 2, 3 and 15 of J1 (Fig.4-2, Item 5) serve as Output Shut-Off (SO) terminals. The SO
terminals accept a 2.5V to 15V signal or Open-Short contact to disable or enable the power supply output. The SO function will be activated only when a transition from On to Off is detected after applying AC power to the unit. (Thus, in Auto-Restart mode, the output will be Enabled after
applying AC power; even if SO is at an Off level). After an On to Off transition it is detected, the
SO will Enable or Disable the power supply output according to the signal level or the short/open
36
83-507-5002 Rev. A
p
applied to J1. This function is useful for connecting power supplies in a “Daisy-chain” (refer to
Section 5.16). The SO control can also be used to reset the OVP and Fold Protection (refer to
Section 5.3 and 5.5 for details).
When the unit is shut-off by a J1 signal, the VOLTAGE display will show “SO” to indicate the unit
state. J1 contact 15 is the SO signal input and contacts 2 and 3, IF_COM, are the signal return
(connected internally). Contacts 2, 3 and 15 are optically isolated from the power supply output.
The SO control logic can be selected by the rear panel SW1 Setup switch. Refer to Table 5-2 for
SW1 setting and SO Control Logic.
SW1-5 setting SO signal level
J1-2(3), 15
Down (default) 2-15V or Open
0-0.6V or Short
Up 2-15V or Open
0-0.6V or Short
Table 5-2: SO logic selection
Power supply
output
On
Off
Off
On
Display
Voltage/Current
“SO”
“SO”
Voltage/Current
5.8 ENABLE/DISABLE CONTROL VIA REAR PANEL J1 CONNECTOR
Contacts 1 and 14 of J1 (Fig.4-2, item 5) serve as Output Enable/Disable terminals by switch or
relay. This function is Enabled or Disabled by the SW1 Setup switch position 9. Refer to Table 53 for Enable/Disable function and SW1 setting.
SW1-9 setting Enable/Disable Inputs Power supply output Display ALARM LED
Down (Default) Open or Short On Voltage/Current Off
Open Off “ENA” Blinking
CAUTION
To prevent possible damage to the unit, do not connect any of the
Enable/Disable in
Safe Start mode-If the Enable/Disable fault condition clears when units in safe start mode recovery is by pressing OUT button or by sending an ‘OUT 1’ serial command. Auto RestartmodeThe output will return back ON automatically when the Enable/Disable fault conditions clears.
uts to the positive or negative output potential.
NOTE
Short On Voltage/Current Off
Table 5-3: Enable/Disable function and SW1 setting
5.9 CV/CC SIGNAL
CV/CC signal indicates the operating mode of the power supply, Constant Voltage or Constant
Current. The CV/CC signal is an open collector output with a 30V parallel zener, at J1-13, referenced to the COM potential at J1-12 (connected internally to the negative sense potential). When
the power supply operates in Constant Voltage mode, CV/CC output is open. When the power
supply operates in Constant Current mode, the CV/CC signal output is low (0-0.6), with maximum
10mA sink current.
Do not connect the CV/CC signal to a voltage source higher than 30VDC. Always
connect the CV/CC signal to voltage source with a series resistor to limit the sink
current to less than 10mA.
CAUTION
5.10
37
83-507-5002 Rev. A
PS_OK SIGNAL
The PS_OK signal indicates the fault condition of the power supply. PS_OK is a TTL signal output at J1-16, referenced to IF_COM at J1-2, 3 (Isolated Interface Common). When a fault condition occurs, the PS_OK level is low, with a maximum sink current of 1mA; when no fault condition
occurs, the PS_OK level is high with a maximum source current of 2mA. The following faults will
set the PS_OK to a Fault state:
*OTP *Enable/Disable open (Power supply is disabled)
*OVP *SO (Rear panel Shut-Off, Power Supply is shut off)
*Foldback *IEEE failure (With optional IEEE interface)
*AC fail *Output Off
5.11 SAFE-START AND AUTO-RESTART MODES
When turning On the power supply AC On/Off, it can start to its last setting of Output Voltage and
Current with the output Enabled (Auto-restart mode) or start with the output Disabled (Safe-start
mode). Press and hold the OUT button to select between Safe-start and Auto-restart modes. The
VOLTAGE display will continuously cycle between “SAF” and “AU7” every 3 seconds. Releasing
the OUT pushbutton while one of the modes is displayed, selects that mode. The default setting
at shipment is Safe-start mode.
5.11.1 Auto-restart mode
In this mode, the power supply restores its last operation setting. Upon start-up, the output is enabled or disabled according to its last setting.
5.11.2 Safe-start mode
In this mode, the power supply restores its last operation setting and sets the Output to an Off
state. At start-up, the output is Disabled and the Output Voltage and Current are zero. To Enable
the output and restore the last Output Voltage and Current values, momentarily press the OUT
button.
5.12 OVER TEMPERATURE PROTECTON (OTP)
The OTP circuit shuts down the power supply before the internal components can exceed their
safe internal operating temperature. When an OTP shutdown occurs, the display shows “O7P”
and the ALARM LED blinks.
Resetting the OTP circuit can be automatic (non-latched) or manual (latched) depending on the
Safe-start or Auto-restart mode.
1. Safe-start mode: In Safe-start mode, the power supply stays Off after the over temperature
condition has been removed. The display continues to show “O7P” and the ALARM LED continues to blink. To reset the OTP circuit, press the OUT button (or send an OUT ON command
via the serial port).
2. Auto-restart mode: In Auto-restart mode, the power supply recovers to its last setting automatically when the over temperature condition is removed.
5.13 LAST SETTING MEMORY
The power supply is equipped with Last Setting Memory, which stores several power supply parameters at each AC turn-off sequence.
STORED PARAMETERS:
1. OUT On or Off
2. Output Voltage setting (PV setting)
3. Output Current setting (PC setting)
4. OVP level
5. UVL level
6. FOLD setting
7. Start-up mode (Safe-start or Auto-restart)
8. Remote/Local: If the last setting was Local Lockout, (latched mode), the supply will return to
Remote mode (non-latched).
38
83-507-5002 Rev. A
9. Address setting
10. Baud rate
11. Locked/Unlocked Front Panel (LFP/UFP)
(Items 8, 9, 10 are related to Remote Digital Control operation and are explained in Chapter 7)
12. Master/Slave setting.
5.14 SERIES OPERATION
Power supplies of the SAME MODEL can be connected in series to obtain increased output voltage. Split connection of the power supplies gives positive and negative output voltage.
5.14.1 Series connection for increased output voltage
In this mode, two units are connected so that their outputs are summed. Set the Current of each
CAUTION
Do not connected power supplies from different
manufacturers in series or in parallel.
power supply to the maximum that the load can handle without damage. It is recommended that
diodes be connected in parallel with each unit output to prevent reverse voltage during start up
sequence or in case one unit shuts down. Each diode should be rated to at least the power supply rated Output Voltage and Output Current. Refer to Fig.5-1 and 5-2 for series operation with
local and remote sensing.
When power supplies are connected in series, and
the load or one of the output terminals is grounded,
no point may be at a greater potential of +/-60VDC
from ground for models up to 60VDC Rated Output
and +/-600VDC from ground for models >60VDC
Rated Output. When using RS232/RS485 or IEEE,
refer to the OUTPUT TERMINALS GROUNDING
warning in Section 3.9.11.
+S
Fig.5-1: Series connection, local sensing
+LS
POWER
SUPPLY
+LS
POWER
SUPPLY
-LS
-LS
+S
-S
-S
+
(*)
-
+
LOAD
-
+
(*)
-
(*) Diodes are
user supplied.
WARNING
POWER
SUPPLY
+LS
POWER
SUPPLY
+LS
-LS
-LS
+S
+S
-S
-S
+
(*)
-
+
LOAD
-
+
(*)
-
Fig.5-2: Series connection, remote sensing
Remote programming in series operation for increased output voltage:
39
83-507-5002 Rev. A
1. Programming by external voltage: The analog programming circuits of this power sup-
ply are referenced to the negative output potential.
Therefore, the circuits used to control each series
connected unit must be separated and floated from
each other.
2.Using the SO function and PS_OK signal: The Shut-Off and PS_OK circuits are referenced to
the isolated interface common, IF_COM (J1-2,3).
The IF_COM terminals of different units can be
connected to obtain a single control circuit for the
power supplies connected in series.
3. Programming by external resistor: Programming by external resistor is possible. Refer
to Section 6-5 for details.
4. Programming via the Serial The communication port is referenced to the
IF_COM
Communication port (RS232/RS485): which is isolated from the power supply output po-
tential. Therefore power supplies connected in series
can be daisy-chained using the Remote-In and Remote-Out connectors. Refer to Chapter 7 for details.
5.14.2 Series connection for positive and negative output voltage
In this mode, two units are configured as a positive and negative output. Set the Output Current
limit of each power supply to the maximum that the load can handle without damage. It is recommended that diodes be connected in parallel with each unit output to prevent reverse voltage during start-up or in case one of the units shuts down. Each diode should be rated to at least the
power supply rated output voltage and output current. Refer to Fig.5-3 for this operating mode.
POWER
SUPPLY
POWER
SUPPLY
Fig.5-3: Series connection for positive/negative output voltages
+LS
+LS
-LS
-S
+S
-S-LS
+S
+
(*)
-
+
-
+
(*)
(*) Diodes are user supplied.
-
Remote programming in series operation for positive and negative output voltage
40
83-507-5002 Rev. A
1. Programming by external voltage: The analog programming circuits of this power
supply are referenced to the negative output potential. Therefore, the circuits used to control
each series connected unit must be separated
and floated from each other.
2. Using the SO function and PS_OK signal: The Shut-Off and PS_OK circuits are referenced
to the isolated interface common, IF_COM (J12,3). The IF_COM terminals of the units can be
connected to obtain a single control circuit for the
power supplies connected in series.
3. Programming by external resistor: Programming by external resistor is possible. Refer to section 6.5 for details.
4. Programming via the Serial
Communication port (RS232/RS485):
The communication port is referenced to the
IF_COM which is isolated from the power supply
output potential. Therefore power supplies connected in series can be chained using the Remote-In and Remote-Out connectors. Refer to
chapter 7 for details.
5.15 PARALLEL OPERATION
Up to four units of the same VOLTAGE and CURRENT rating can be connected in parallel to
provide up to four times the Output Current capability. One of the units operates as a Master and
the remaining units are Slaves. The Slave units are analog programmed by the Master unit. In
remote digital operation, only the Master unit can be programmed by the computer, while the
Slave units may be connected to the computer for voltage, current and status readback only. Follow the following procedure to configure multiple supplies for parallel operation. Refer to Sec.
5.15.1 and to Sec. 5.15.2 for detailed explanation.
5.15.1 Basic parallel operation
In this method, setting the units as Master and Slaves is made by the rear panel J1 connections
and the setup switch SW1. Each unit displays its own output current and voltage. To program the
load current, the Master unit should be programmed to the total load current divided by the number
of units in the system. Refer to the following procedure to configure multiple supplies for simple
parallel operation.
1. Setting up the Master unit
Set the Master unit Output Voltage to the desired voltage. Program the Output Current to the desired load current divided by the number of parallel units. During operation, the Master unit operates in CV mode, regulating the load voltage at the programmed Output Voltage. Connect the
sensing circuit to local or remote sensing as shown in Fig.5-4 or fig.5-5.
2. Setting up the Slave units
-1. The Output Voltage of the Slave units should be programmed 2-5% higher than the Output
Voltage of the Master unit to prevent interference with the Master unit’s control. The Output
Current setting of each unit should be programmed to the desired load current divided by the
number of parallel units.
-2. Set the rear panel setup switch SW1 position 2 to the up position.
-3. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
-4. Connect J1 terminal 10(IPGM) of the slave unit to J1 terminal 25(P) of the master unit.
During operation, the Slave units operate as a controlled current source following the Master
Output Current. It is recommended that the power system be designed so that each unit supplies
41
83-507-5002 Rev. A
up to 95% of its current rating because of the imbalance which may be caused by cabling and
connection voltage drop.
3. Setting Over Voltage protection
The Master unit OVP setting should be programmed to the desired OVP level. The OVP setting of the slave units should be programmed to a higher value than the Master OVP. When
the Master unit shuts down, it programs the Slave unit to zero Output Voltage. If a Slave unit
shuts down (when its OVP is set lower than the Master Output Voltage), only that Slave unit
would shut down, and the remaining Slave units would supply all the load current.
4. Setting Foldback protection
Foldback protection, is desired, may only be used with the Master unit. When the Master unit
shuts down, it programs the Slave units to zero Output Voltage.
5. Connection to the load
In parallel operation, power supplies can be connected in local or remote sensing. Refer to
Fig. 5-4 and 5-5 for typical connections of parallel power supplies. The figures show connection of two units, however the same connection method applies for up to 4 units.
5.15.2 Advanced parallel operation
In this method, multiple supplies can be configured to parallel operation as a single power supply.
The total load current and output voltage are displayed by the Master unit and can be readback
from the Master unit. The Slave units display only their operating status (On, Off or Fault condition).
Refer to the following procedure to configure multiple supplies for Advanced parallel operation.
1. Basic configuration.
SW1 position 2 - Down in the Master Supply and up in all Slave Supplies.
•
Connect a short between J1-8 and J1-12 in all Slave Supplies.
•
Connect J1-25 of the Master Supply to J1-10 of all Slave Supplies.
•
Connect J1-16 of the Master Supply to J1-15 of the ‘First’ Slave Supply.
•
Connect J1-16 of the ‘First’ Slave Supply to J1-15 of the ‘Second’ Slave Supply (if
•
any)
Connect J1-16 of the ‘Second’ Slave Supply to J1-15 of the ‘Third’ Slave Supply (if
•
any)
Connect J1-16 of the ‘Last’ Slave Supply to J1-15 of the Master Supply
•
Connect J1-12 common to all supplies
•
Select Local or Remote sense - Ref. Figures 5-4 and 5-5
•
2. Setting the units as Master or Slave
a) Depress and hold the FINE button for 3 seconds. The Master/Slave configuration will be displayed on the Current Display. Rotate the CURRENT encoder to obtain the desired mode. Refer
to Table 5-4 for the CURRENT display and modes of operation.
CURRENT Display Operating Mode
H1 Single supply (default)
H2 Master supply with 1 Slave supply
H3 Master supply with 2 Slave supplies
H4 Master supply with 3 Slave supplies
S Slave supply
Table 5-4: Setting mode of operation
b) When the desired configuration is obtained, depress and release the FINE button or wait
approx. 5 seconds.
3. Master and Slave units default operation
42
83-507-5002 Rev. A
a) When a unit is programmed to Slave mode it enters the Remote mode with
Local Lockout. In this mode, the front panel controls are disabled to prevent
accidental setting change (refer to Sec. 7.2.7 for details).
J1-25
J1-10
P
IPGM
-LS-S
+S-S
+LS
+S
b) The Slave units parameters will
automatically set the following:
*Output voltage to
To J 1-1 0
SLAVE#2
POWER SUPPLY
MASTER
POWER SUPPLY
approximate. 102% of rated
output voltage.
*Programmed Current to zero.
*UVL to zero volts
J1-8 J1-12
SLAVE#1
POWER SUPPLY
*OVP to its maximum value
Twi sted
pair
As short as possible
V
+
-
V
V
+
-
V
+S
-S
Twi sted
pair
+S
LOAD
-S
*AST On
*OUT On
*Foldback protection Off
Fig.5-5: Parallel operation with Remote sensing
c) The Master and Slave modes are stored in the power supply EEPROM when the AC power is
turned off. The system will return to the Master/Slave mode upon re-application of AC power.
4. CURRENT display accuracy
In the advanced parallel mode, the Master unit calculates the total current by multiplying the Master
output current by the number of Slave units. In this method, the CURRENT display accuracy is 2%
+/- 1 count. In cases that higher accuracy is required, it is recommended to use the basic parallel operation mode.
5. To release units from Slave mode
Slave units can be released using the following procedure:
a) Depress FINE button for 3 seconds. The Master/Slave configuration will be displayed on the
CURRENT display.
b) Select H1 mode using the CURRENT encoder.
c) Depress FINE button again or wait 5 seconds.
d) Turn the AC power Off to store the new setting.
e) After exiting from Slave operation the unit’s parameters will be set to:
*Programmed Voltage to zero
*Programmed Current to zero
*UVL to zero volts
*OVP to its maximum value
*AST OFF
*OUT OFF
*Foldback protection OFF
*Locked Front Panel
To J 1-1 0
SLAVE#2
POWER SUPPLY
-LS
-S
MASTER
POWER SUPPLY
J1-25
P
IPGM
J1-8 J1-12
SLAVE#1
POWER SUPPLY
J1-10
-LS
-S
+LS +S
+LS
+S
+
V
-
V
+
V
-
V
As short as possible
Twi sted
pair
LOAD
Fig.5-4: Parallel connection with local sensing
43
83-507-5002 Rev. A
CAUTION Make sure that the connection between –V terminals is reliable to avoid disconnection
during operation. Disconnection may cause damage to the power supply.
NOTE
With local sensing it is important to minimize the wire length and resistance. Also the positive and
negative wire resistance should be close as possible to each other to achieve current balance between power supplies
5.16 DAISY-CHAIN CONNECTION
It is possible to configure a multiple power supply system to shut down all the units when a fault
condition occurs in one of the units. When the fault is removed, the system recovers according to
its setting to Safe-start or Auto-restart mode.
Setup switch SW1, position 5 should be set to its DOWN position to enable the Daisy-chain operation. Other SW1 positions can be set according to the application requirements.
If a fault occurs in one of the units, its PS_OK signal will be set to a low level and the display will
indicate the fault. The other units will shut off and their display will indicate “SO”. When the fault
condition is removed, the units will recover to their last setting according to their Safe-start or
Auto-restart setting.
Fig.5-6 shows connection of three units, however the same connection method applies to systems with a larger number of units.
POWER SUPPLY
#
IF_COM
1
PS_OK
J1-2,3 J1-16
J1-15
SO
POWER SUPPLY
#
2
J1-16
J1-2,3J1-15
IF_COM
PS_OK
SO
POWER SUPPLY
#3
J1-16
J1-2,3
IF_COM
PS_OK
J1-15
SO
5.17 FRONT PANEL LOCKING
The front panel controls can be locked to protect from accidental power supply parameter
change. Press and hold the PREV button to toggle between “Locked front panel’ and “Unlocked
front panel”. The display will cycle between “LFP” and “UFP”. Releasing the PREV button while
one of the modes is displayed, selects that mode.
Fig.5-6: Daisy-chain connection
44
83-507-5002 Rev. A
5.17.1 Unlocked front panel
In this mode, the front panel controls are Enabled to program and monitor the power supply parameters.
5.17.2 Locked front panel
In this mode the following front panel controls are Disabled:
-VOLTAGE and CURRENT encoders.
-FOLD button.
-OUT button
The power supply will not respond to attempts to use these controls. The VOLT display will show
“LFP” to indicate that the front panel is locked.
OVP/ UVL button is active to preview the OVP and UVL setting.
Use the PREV button to preview the Output Voltage and Current setting or to unlock the front
panel.
45
83-507-5002 Rev. A
CHAPTER 6 REMOTE ANALOG PROGRAMMING
6.1 INTRODUCTION
The rear panel connector J1 allows the user to program the power supply Output Voltage and
Current with an analog device. J1 also provides monitoring signals for Output Voltage and Output Current. The programming range and monitoring signals range can be selected between 05V or 0-10V using the setup switch SW1. When the power supply is in Remote Analog programming mode, the serial communication port is active and can be used to query the power supply
settings.
COM (J1-12), VPGM_RTN (J1-22) AND IPGM_RTN (J1-23) terminals of J1
connect internally to the -Sense potential (-S). Do not connect these terminals
to any potential other than -Sense (-S), as it may damage the power supply.
6.2 LOCAL/REMOTE ANALOG INDICATION
Contact 8 of J1 (Fig.4-2, Item 5) accepts TTL signal or Open-Short contact (referenced to J1-12)
to select between Local or Remote Analog programming of the Output Voltage and Current.
In Local mode, the Output Voltage and Output Current can be programmed via the front panel
VOLTAGE and CURRENT encoders or via the RS232/RS485 port. In Remote Analog mode, the
Output Voltage and current can be programmed by analog voltage or by programming resistors
via J1 contacts 9 and 10 (refer to Sections 6.4 and 6.5). Refer to Table 6-1 for Local/Remote
Analog control (J1-8) function and Setup switch SW1-1, 2 setting.
SW1-1, 2 setting J1-8 function
Down (default) No effect Local
Up
CAUTION
Output Voltage/
Current setting
“0” or Short Remote
“1” or Open Local
Table 6-1: Local/Remote Analog control function
6.3 LOCAL/REMOTE ANALOG INDICATION
Contact 21 of J1 (Fig. 4-2, Item 5) is an open collector output that indicates if the power supply is
in Local mode or in Remote Analog mode. To use this output, connect a pull-up resistor to a voltage source of 30Vdc maximum. Choose the pull-up resistor so that the sink current will be less
than 5mA when the output is in a low state. Refer to table 6-2 for J1-21 function.
J1-8 SW1-1 SW1-2 J1-21 signal Mode
TTL “0” or short
Down Down Open Local (FP)
Down Up 0i0.6V Remote Analog
Up Down 0i0.6V Remote Analog
Up Up 0i0.6V Remote Analog
TTL “1” or open Down or Up Down or Up Open Local (FP)
Table 6-2: Local/Remote Analog indication
6.4 REMOTE VOLTAGE PROGRAMMING OF OUTPUT VOLTAGE AND OUTPUT
CURRENT LIMIT
46
83-507-5002 Rev. A
To maintain the power supply isolation and to prevent ground loops, use an
isolated programming source when operating the power supply via remote
analog programming at the J1 connector.
CAUTION
Perform
the
following procedure to set the power supply to Remote Voltage programming:
1. Turn the power supply AC On/Off switch to Off.
2. Set setup switch SW1, positions 1 and 2 to their UP position.
3. Set SW1, position 3 to select the programming voltage range according to Table 6-3.
4. Ensure that SW1, positions 7 and 8 are at their DOWN (default) position.
5. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming source to the mating plug of J1 as shown in Fig.6-1. Observe correct polarity for the voltage source.
7. Set the programming sources to the desired levels and turn the power supply ON. Adjust the programming sources to change the power supply output.
NOTES:
1. SW1, positions, 4, 5, 6 and 9 are not required for remote programming. Their settings
can be determined according the application.
2. The control circuits allow the user to set the Output Voltage and Output Current up to
5% over the model-rated maximum value. The power supply will operate within the extended range, however it is not recommended to operate the power supply over its
voltage and current rating, and performance is not guaranteed.
SW1-3 setting Output Voltage programming
VPGM (J1-9)
Output Current programming
IPGM (J1-10)
UP 0-10V 0-10V
DOWN 0-5V 0-5V
Table 6-3: SW1-3 setting and programming range
J1 connector, rear panel view
Fig.6-1: Remote voltage programming connection
OUTPUT CURRENT
PROGRAMMING
+
1012
13
25
2322
83-507-5002 Rev. A
9
47
OUTPUT VOLTAGE
PROGRAMMING
+
8
1
14
6.5 RESISITIVE PROGRAMMING OF OUTPUT VOLTAGE AND CURRENT LIMIT
For resistive programming, internal current sources, for Output Voltage and/or Output Current
control, supply 1mA current through external programming resistors connected between J1-9 &
22 and J1-10 & 23. The voltage across the programming resistors is used as a programming
voltage for the power supply. Resistance of 0i5Kohm or 0i10Kohm can be selected to program
the Output Voltage and Output Current from zero to full scale.
A variable resistor can control the output over its entire range, or a combination of variable resistor and series/parallel resistors can control the output over restricted portion of its range.
Perform the following procedure to set the power supply to Resistive programming:
1. Turn the AC On/Off switch to Off.
2. Set setup switch SW1, positions 1 and 2 to their UP position.
3. Set SW1, position 3 to select the programming resistor range according to Table 6-4.
4. Set SW1, positions 7 and 8 to their UP position, to enable resistive programming mode.
5. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
6. Connect the programming resistors to the mating plug of J1 as shown in Fig.6-2.
7. Set the programming resistors to the desired resistance and turn the power supply ON. Adjust
the resistors to change the power supply output.
NOTES:
1. SW1, positions 4, 5, 6 and 9 are not required for remote programming. Their settings can be
determined according to the application requirements.
2. The control circuits allow the user to set the Output Voltage and Output Current up to 5% over
the model-rated maximum value. The power supply will operate within the extended range,
however it is not recommended to operate the power supply over its voltage and current rating and performance is not guaranteed.
3. To maintain the temperature stability specification of the power supply, the resistors used for
programming should be stable and low noise resistors, with temperature coefficient of less
than 50ppm.
4. When resistive programming is used, front panel and computer control (via serial communication port) of Output Voltage and Current are disabled.
SW1-3 setting Output Voltage programming
VPGM (J1-9)
UP 0-10Kohm 0-10Kohm
DOWN 0-5Kohm 0-5Kohm
Table 6-4: SW1-3 setting and programming range
J1 connector, rear panel view
OUTPUT VOLTAGE
PROGRAMMING
8
PROGRAMMING
RESISTOR
OPTIONAL SETS
LOWER LIMIT
OUTPUT CURRENT
PROGRAMMING
13
25
12
109
2322
Output Current programming
IPGM (J1-10)
PROGRAMMING
RESISTOR
1
14
OPTIONAL SETS
LOWER LIMIT
OPTIONAL SETS
UPPER LIMIT
6.6 REMOTE MONITORING OF OUTPUT VOLTAGE AND CURRENT
OPTIONAL SETS
UPPER LIMIT
Fig.6-2: Remote resistive programming
48
83-507-5002 Rev. A
The J1 connector, located on the rear panel provides analog signals for monitoring the Output
Voltage and Output Current. Selection of the voltage range between 0-5V or 0-10V is made by
setup switch SW1-4. The monitoring signals represent 0 to 100% of the power supply Output
Voltage and Output Current. The monitor outputs have 500 ohm series output resistance. Ensure
that the sensing circuit has an input resistance of greater than 500 Kohm or accuracy will be reduced.
Refer to Table 6-5 for the required J1 connection, SW1-4 setting and monitoring voltage range.
Signal
Signal function
name
VMON Vout monitor J1-11
IMON Iout monitor J1-24
VMON Vout monitor J1-11
IMON Iout monitor J1-24
J1 connection
Signal (+) Return (-)
J1-12 0-5V Down
J1-12 0-10V Up
Range SW1-4
Table 6-5 Monitoring signals setting
Notes:
1. Radiated emissions, RCC requirements: FCC requirements for radiated emissions; use a
shielded
cable for the analog control signals. If using unshielded cable, attach an EMI ferrite suppressor to
the cable, as close as possible to the power supply.
2. Front panel encoders operation: In Remote analog mode, the output voltage and cur-
rent can’t be set by the VOLTAGE and CURRENT
encoders.
3. Front panel PREV button: Use the PREV button to display the Output Voltage
and Current setting, as defined by the encoders or
digital communication.
4. Communication: In Remote analog mode, all power supply parame-
ters can be programmed and readback via the communication port, except the Output Voltage and Current setting.
49
83-507-5002 Rev. A
CHAPTER 7 RS232 & RS485 REMOTE CONTROL
7.1 INTRODUCTION
This Chapter describes the operation of the Genesys
communication port. Details of the initial set-up, operation via RS232 or RS485, the command set
and the communication protocol are described in this Chapter.
TM
3300W power supplies via the serial
7.2 CONFIGURATION
7.2.1 Default setting
The power supply is shipped with the following settings:
The power supply address can be set to any address between 0 and 30. Follow the instructions
described below to set the unit address.
1. If the unit is in Remote mode (front panel REM/LOC LED illuminated), press the REM/LOC
button to put the unit into Local mode.
2. Press and hold for the REM/LOC button for approximately 3 sec. The VOLTAGE display will
indicate the unit address.
3. Using the VOLTAGE adjust encoder, select the unit address.
To preview the power supply address at any time, press and hold the REM/LOC button for
approx. 3 sec. The VOLTAGE display will indicate the power supply address.
7.2.3 RS232 or RS485 selection
To select between RS232 or RS485 set the rear panel setup switch SW1-6 position to:
-DOWN for RS232
-UP for RS485
7.2.4 Baud Rate setting
Five optional Baud rates are possible: 1200, 2400, 4800, 9600 and 19200. To select the desired
rate, the following steps should be taken:
1. If the unit is in Remote mode (front panel REM/LOC LED illuminates), press REM/LOC button
to put the unit into Local mode.
2. Press and hold the REM/LOC button for approximately 3 sec. The CURRENT display will
show the unit Baud Rate.
3. Using the CURRENT adjust encoder, select the desired Baud Rate.
7.2.5 Setting the unit into Remote or Local mode
1. The unit will be put into Remote mode only via serial communication command. Commands
that will put the unit into Remote mode are:
RST PV n
OUT n PC n
RMT n
(for n values see Tables 7-5 and 7-7)
50
83-507-5002 Rev. A
2. There are two Remote modes:
1. Remote: In this mode, return to local can be made by the front panel REM/LOC or via
serial port command RMT 0. Set the unit into Remote mode via serial port
RMT 1 command.
2. Local Lockout: In this mode the unit can be returned to Remote mode via the serial port
RMT 1 command or by turning off the AC power until the display turns off,
and then turn it to on again. In local Lockout mode, the front panel
REM/LOC button is not active. Set the unit into Local Lockout mode via serial port RMT 2 command.
7.2.6 RS232/RS485 port in Local mode
When the power supply is in Local mode, it can receive queries or commands. If a query is received, the power supply will reply and remain in Local mode. If a command that affects the output is received, the power supply will perform the command and change to Remote mode.
Serial commands may be sent to set the status registers and read them while the unit is in Local
mode. If the Enable registers are set (refer to Section 7.11) the power supply will transmit SRQ’s
while in Local.
7.2.7 Front panel in Remote mode
Front panel control in Remote mode is Disabled except for:
1. PREV: use to preview the Voltage and Current setting.
2. OVP/UVL: use to preview the OVP/UVL setting.
3. LOC/REM: use to set the unit into Local mode.
In Local Lockout mode, only the PREV and OVP/UVL pushbuttons are active.
7.3 REAR PANEL RS232/RS485 CONNECTOR
The RS232/RS485 interface is accessible through the rear panel RS232/RS485 IN and RS485
OUT connectors. The connectors are 8 contact RJ-45. The IN and OUT connectors are used to
connect power supplies in a RS232 or RS485 chain to a controller. Refer to Fig. 7-1 for IN/OUT
connectors.
SG
NC
+
TXD
RXD
NC
-
TXD
NC
+
-
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
OUT
IN
Fig.7-1: Rear panel J3 IN/OUT connectors pinout
NOTE
Tx and Rx are used for RS232 communication. Txd +/- and Rxd +/- are used for RS485
communication. Refer to RS-232 and RS-485 cabling and connection details.
TXDRXD
RXD
RX
TX
-
RXD
-
+
TXD
+
NC
SG
Shield
(connector enclosure)
51
83-507-5002 Rev. A
7.4 MD MODE OPTION (Factory Installed)
7.4.1 MD Mode Description
The GEN supply is capable of operating in a multi drop environment - more than 1 supply
conducting serial communications on a single serial bus. A maximum of 31 GEN supplies
can operate in this single bus. Upon power up the Gen will enter the point-to-point mode
in which it is assumed that only 1 supply will operate on a serial bus. MD Mode must be
enabled - Ref. Section 7.10.2.2. The user must set all Slave supplies to a unique address.
No two supplies may have the same address.
7.4.2 MD Mode enable – Serial communication mode
Refer to section 7.10.2.2. MD Mode is entered into via a Single byte command. In MD
Mode the Master supply shall operate in one of the two serial modes, RS232 or RS485,
depending upon the rear panel DIP switch setting and the Slave supplies shall operate in
the RS485 serial mode.
7.4.3 MD Mode SRQ
In MD Mode the SRQ generated by the supply is replaced by a single byte SRQ sent two
times in sequence. The SRQ byte, in binary, will contain the address of the supply in the
least significant 5 bits with bits 5 and 6 set to logic zero and bit 7 set to logic 1. Ref. Table
7-4.
7.4.4 Communication Collisions
In MD Mode it is possible to have one supply issue an SRQ while another supply is
transmitting data/response to a command. When this happens, the HOST PC will receive
garbled data and assume that the data/response was corrupted and thus re-send the
command - the SRQ will probably be lost. The method of recovery will be SRQ retransmission, Ref. Section 7.4.5, or polling all attached supplies to see who issued the SRQ available by reading the SEVE? Register.
7.4.5 MD Mode SRQ Retransmission
The supply can be commanded to retransmit the SRQ at regular intervals until it is answered to by the HOST PC (Ref. Section 7.10.2.4). The retransmission interval is 10 ms
plus the supply address multiplied by 20 ms.
52
83-507-5002 Rev. A
7.5 CONNECTING POWER SUPPLIES TO RS232 OR RS485 BUS
7.5.1 Single power supply
1. Select the desired interface RS232 or RS485 using rear panel setup switch SW1-6 (Section 4-
4).
-RS232: DOWN position
-RS485: UP position
2. Connect rear panel IN connector to the controller RS232 or RS485 port using a suitable
shielded cable. Refer to Figures 7-2, 7-3 and 7-4 for available RS232 and RS485 cables.
13
1
Sockets
DB-25 CONNECTOR
PIN NO.
1
2
3
7
SHIELD
TX
RX
SG
8 PIN CONNECTORREMARKS
PIN NO.NAME
8
7
1
NAME
SHIELD
RX
TX
SG
TWISTED
PAIR
8
1
Fig.7-2: RS232 cable with DB25 connector (P/N: GEN/232-25)
L=2m typ.
L=2m typ.
5
1
Sockets
DB-9 CONNECTOR
PIN NO.
HOUSING
2
3
5
SHIELD
RX
TX
SG
8 PIN CONNECTOR
PIN NO.NAME
HOUSING
7
8
1
NAME
SHIELD
TX
RX
SG
REMARKS
TWISTED
PAIR
8
1
Fig.7-3: RS232 cable with DB9 connector (P/N: GEN/232-9)
5
1
Sockets
Fig.7-4: RS485 cable with DB9 connector (P/N: GEN/485-9)
L=2m typ.
DB-9 CONNECTOR
PIN NO.
HOUSINGHOUSING
9
8
1
5
4
SHIELD
-
TXD
+
TXD
SG
-
RXD
+
RXD
8 PIN CONNECTOR
PIN NO.NAMENAME
6
3
1
5
4
SHIELD
RXD
RXD
SG
TXD
TXD
REMARKS
-
+
-
+
TWISTED
PAIR
TWISTED
PAIR
53
83-507-5002 Rev. A
8
1
7.5.2 Multi power supply connection to RS232 or RS485 bus
Up to 31 units can be connected (daisy chained) to the RS232 or RS485 bus. The first unit connects to the controller via RS232 or RS485 and the other units are connected via the RS485 bus.
1. First unit connection: Refer to Section 7.5.1 for connecting the first unit to the controller.
2. Other units connection: The other units on the bus are connected via their RS485 interface.
Refer to Figure 7-5 for typical connection.
- Set rear panel setup switch SW1-6 to its UP position.
- Using the Linking cable supplied with each unit (refer to Fig. 7-6), connect each unit OUT
connector to the next unit IN connector.
RS232/RS485
RS485RS485
RS485
INOUT
POWER SUPPLY
#1
IN
POWER SUPPLY
OUT
#2
INOUT
POWER SUPPLY
#3
IN
POWER SUPPLY
OUT
#31
Fig7-5: Multiple power supply RS232/485 connection
1
8
Fig.7-6:
L=0.5m typ.
PIN NO.
HOUSINGHOUSING
SHIELD
SG
1
6
3
5
4
TXD
TXD
RXD
RXD
-
+
-
+
PIN NO.NAME
NAME
SHIELD
SG
1
6
3
5
4
RXD
RXD
TXD
TXD
-
+
-
+
Serial link cable with RJ-45 shielded connectors (P/N: GEN/RJ-45)
8
1
NOTE
The address (ADR n) command must return an “OK” response before
any other commands are accepted.
7.6 COMMUNICATION INTERFACE PROTOCOL
7.6.1 Data format
Serial data format is 8 bit, one start bit and one stop bit. No party bit.
7.6.2 Addressing
The Address is sent separately from the command. It is recommended to add 100msec delay between query or sent command to next unit addressing. Refer to Section 7.8.3 for details.
7.6.3 End of Message
The end of message is the Carriage Return character (ASCII 13). The power supply ignores the
Line Feed (ASCII 10) character.
7.6.4 Command Repeat
The backslash character “\” will cause the last command to be repeated.
7.6.5 Checksum
The user may add a checksum (optional) to the end of the command. The checksum is “$” followed by two hex characters. If a command or a query has a checksum, the response will also
have one. There is no CR between the command string and the “$” sign.
Example: STT?3A
54
83-507-5002 Rev. A
STAT?$7B
7.6.6 Acknowledge
The power supply acknowledges received commands by returning an “OK” message. If an error
is detected the power supply will return an error message. The rules of checksum also apply to
the acknowledge.
7.6.7 Error message
If an error is detected in command or query, the power supply will respond with an error message. Refer to Section 7.7 for details.
7.6.8 Backspace
The backspace character (ASCII 8) clears the last character sent to the power supply.
7.7 ERROR MESSAGES
The power supply will return error messages for illegal commands and illegal programming parameters. Refer to Table 7-1 for programming error messages and Table 7-2 for command error
messages.
Table 7-1: Programming error messages
Error
Code
Description
E01 Returned when program voltage (PV) is programmed above acceptable range.
Example: PV above ‘105% of supply rating’ or PV above 95% of OVP setting’.
E02 Returned when programming output voltage below UVL setting.
E04 Returned when OVP is programmed below acceptable range.
Example: OVP less than “5% of supply voltage rating’ plus ‘voltage setting’.
E06 Returned when UVL is programmed above the programmed output voltage.
E07 Returned when programming the Output to ON during a fault shut down.
Table 7-2: Commands error messages
Error
Code
C01
Description
Illegal command or query
C02 Missing parameter
C03
Illegal parameter
C04 Checksum error
C05 Setting out of range
7.8 COMMAND SET DESCRIPTION
7.8.1 General guide
1. Any command or argument may be in capital letters or small letters.
2. In commands with an argument, a space must be between the command and the argument.
3. For any command that sets a numeric value, the value may be up to 12 characters
long.
4. Carriage Return: If the CR character (ASCII 13) is received by itself, the power supply
will respond with “OK” and CR.
7.8.2 Command set categories
1. Initialization control
2. ID control
55
83-507-5002 Rev. A
3. Output control
4. Status control
7.8.3 Initialization Control Commands
# Command Description
1 ADR n
ADR is followed by address, which can be 0 to 30 and is used to access the
power supply.
2 CLS
3 RST
Clear status. Sets FEVE and SEVE registers to zero (refer to Section 7-11).
Reset command. Brings the power supply to a safe and known state:
Output voltage: zero, Remote: non-lockout remote,
Output current: zero, Auto-start: Off,
Output: Off, OVP: maximum,
FOLD: Off, UVL: zero
The conditional registers (FLT and STAT) are updated, the other registers
are not changed.
4 RMT
5 RMT?
Sets the power supply to local or remote mode:
1. RMT 0 or RMT LOC, sets the power supply into Local mode.
2. RMT 1 or RMT REM, sets the unit into remote mode.
3.
RMT 2 or RMT LLO, sets the unit into Local Lockout mode (latched remote
mode).
Returns to the Remote mode setting:
1. “LOC” - The unit is in Local mode.
2. “REM” - The unit is in Remote mode.
3. “LLO” - The unit is in Local Lockout (latched remote) mode.
6 MDAV?
Returns MD MODE OPTION Status. 1 indicates installed and 0 indicates not
installed.
7 \
Repeat last command. If \<CR> is received, the power supply will repeat the
last command.
7.8.4 ID Control Commands
# Command Description
1 IDN?
2 REV?
3 SN?
4 DATE?
Returns the power supply model identification as an ASCII string:
GENX-Y
Returns the software version as an ASCII string.
Returns the unit serial number. Up to 12 characters.
Returns date of last test. Date format: yyyy/mm/dd
7.8.5 Output Control Commands
# Command Description
Sets the output voltage value in Volts. The range of voltage value is de1 PV n
scribed in Table 7-5. The maximum number of characters is 12. See the fol-
lowing examples for PV n format: PV 12, PV 012, PV 12.0, PV 012.00, etc…
Reads the output voltage setting. Returns the string “n” where “n” is the exact
2 PV?
string sent in the PV n command. When in Local mode, returns the
PREVIEW (front panel) settings in a 5 digit string.
3 MV?
PC n
4
(See
Reads the actual output voltage. Returns a 5 digits string.
grammed Current, Over Voltage Set Point and Under Voltage Set Point.
Example: 5.9999,6.0000,010.02,010.00,7.500,0.000
8
FILTER
nn
Set the low pass filter frequency of the A to D Converter for Voltage and Cur-
rent Measurement where nn = 18, 23 or 46.
9 FILTER? Returns the A to D Converter filter frequency: 18,23 or 46 Hz.
Turns the output to ON or OFF. Recover from Safe-Start, OVP or FLD fault.
10 OUT n
11 OUT?
12 FLD n
OUT 1 (or OUT ON)-Turn On.
OUT 0 (or OUT OFF)-Turn Off
Returns the output On/Off status string.
ON - output On. OFF - output Off.
Sets the Foldback protection to ON or OFF.
FLD 1 (or FOLD ON) - Arms the Foldback protection
FLD 0 (or FOLD OFF) - Cancels the Foldback protection.
When the Foldback protection has been activated, OUT 1 command will re-
lease the protection and re-arm it, while FLD 0 will cancel the protection.
13 FLD?
Returns the Foldback protection status string:
“ON” - Foldback is armed. “OFF” - Foldback is cancelled.
Add (nn x 0.1) seconds to the Fold Back Delay. This delay is in addition to
14 FBD nn
the standard delay. The range of nn is 0 to 255. The value is stored in eprom
at AC power down and recovered at AC power up.
15 FBD ?
16 FBDRST
Supply returns the value of the added Fold Back Delay.
Reset the added Fold Back Delay to zero.
Sets the OVP level. The OVP setting range is given in Table 7-7. The num-
ber of characters after OVP is up to 12. The minimum setting level is ap-
17 OVP n
proximately 105% of the Output Voltage setting, or the value in Table 7-7,
whichever is higher. The maximum OVP setting level is shown in Table 5-1.
Attempting to program the OVP below this level will result in an execution
error response (“E04”). The OVP setting stays unchanged.
Returns the setting “n” where “n” is the exact string in the user’s “OVP n”.
18 OVP?
When in Local mode, returns the last setting from the front panel in a 4 digit
string.
19 OVM
20 UVL n
Sets OVP level to the maximum level. Refer to Table 7-7.
Sets Under Voltage Limit. Value of “n” may be equal to PV setting, but re-
turns “E06” if higher. Refer to Table 7-8 for UVL programming range.
Returns the setting “n” where “n” is the exact string in the user’s “UVL n”.
21 UVL?
When in Local mode, returns the last setting from the front panel in a 4 digit
string.
Sets the Auto-restart mode to ON or OFF.
22 AST n
AST 1 (or AST ON): Auto restart On.
AST 0 (or AST OFF): Auto restart Off.
57
83-507-5002 Rev. A
23 AST? Returns the string auto-restart mode status.
Saves present settings. The settings are the same as power-down last set-
24 SAV
ting. These settings are erased when the supply power is switched Off and
the new “last settings” are saved.
25 RCL
Recalls last settings. Settings are from the last power-down or from the last
“SAV” command.
Returns the power supply operation mode. When the power supply is On
26 MODE?
(OUT 1) it will return “CV” or “CC”. When the power supply is OFF (OUT 0 or
fault shutdown) it will return “OFF”.
27 MS?
Returns the Master/Slave setting. Master: n= 1, 2, 3, or 4 Slave: n=0
NOTES:
1. In Advanced parallel mode (refer to Sec. 5.15.2), “n” is the total system current.
2. In Advanced parallel mode, “MC?” returns the Master unit current multiplied by the number of
slave units +1.
7.9 GLOBAL OUTPUT COMMANDS
7.9.1 GENERAL
All supplies, even if not the currently addressed supply, receiving a global command will
execute the command. No response to the PC issuing the command will be returned to
the PC. The PC issuing the command will be responsible to delay and any other communications until the command is execute. 200 Ms minimum is the suggested delay.
If the command contains an error, out of range values for example, no error report will be
sent to the issuing PC.
Table 7-3
GRST Reset. Brings the power supply to a safe and known state:
Output voltage: 0V, output current: 0A, OUT: Off, Remote: RMT 1,
AST: Off OVP: Max, UVL: 0.
The conditional register (FLT and STAT) are updated. Other registers are
not
changed.
Non-Latching faults (FB, OVP, SO) are cleared, OUT fault stays
GPV n Sets the output voltage value in volts. The range of voltage values is shown in
Table 7-5. ‘n’ may be up to 12 char plus dec. pt
GPC n Program the output current value in amperes. The range of current values is
shown in Table 7-6. ‘n’ may be up to 12 char plus dec. pt
GOUT
Turns the output to ON or OFF:
“OUT 1/ON” = turn on
“OUT 0/OFF” = turnoff, clears CV and CC bits in the Status Condition (STAT).
OUT ON will respond with “E07’ if the output cannot be turned on because of a
latching fault (OTP< AC, ENA, SO) shutdown.
GSAV
Save present settings. Same settings as power-down last settings listed in Error!
Reference source not found. Except the address and Baud rate are not saved
Saves to the RAM. These settings are erased when the supply power is
switched off and the new ‘last settings’ are saved.
GRCL Recall last settings. Settings are from last power-down or from last ‘SAV’ or
‘GSAV’ command. Address and Baud rate are not recalled so communication is
not interrupted.
58
83-507-5002 Rev. A
7.10 SINGLE BYTE COMMANDS
7.10.1 General
Single byte commands are commands in which all the necessary data for the supply to act
upon is contained in a single byte. Single byte commands will be executed immediately by
the supply. If the command requires data to be sent to the HOST PC or IEEE Board (see
sections 7.10.4 and 7.10.3.1) that response will be transmitted immediately with no delay
due to any software overhead. With the exception of the Disconnect from communications
command, section 7.10.3.1, commands must be sent by the HOST PC or IEEE Board 2
times in sequence for verification. Alll have the most significant bit, D7, set to a logic 1. A
CR, carriage return, character is not included in a single byte command. The RST command will not change any setting made by a single byte command.
All Single Byte commands will be executed in 1 ms or less. This does not include any response sent to the HOST/IEEE Board, which is dependent upon the response length and
the serial transmission speed (Baud rate).
Disable is the default condition upon power up. The Hex value of the command is
0xA0. Send it two times in sequence. All supplies, both the currently addressed supply
and all non-addressed supplies, will disable MD Mode as a result of this command.
7.10.2.2 Enable MD Mode (MD MODE OPTION REQUIRED)
Send to enable Multi Drop Mode. The Hex value of the command is 0xA1. Sent it two
times in sequence. When this command is sent, the supply will set SRQ retransmission to the disable state; if you wish it to be enabled you must send the enable command. All supplies, both the currently addressed supply and all non-addressed supplies, will enable MD Mode as a result of this command.
Disable is the default condition upon power up. The Hex value of the command is
0xA2. Sent it two times in sequence. If the supply sends an SRQ it will only sent it 1
time. All supplies, both the currently addressed supply and all non-addressed supplies, will disable SRQ retransmission as a result of this command. All status registers
will retain their data when this command is sent.
Enable retransmission of SRQs. This is only available when the Multi Drop Mode is
enabled in the supply. The Hex value of the command is 0xA3. Send it two times in
sequence. If the supply sends an SRQ it will be repeated on a timely basis, 10 ms plus
20 ms times the supply address, until answered. All supplies, both the currently addressed supply and all non-addressed supplies, will enable SRQ retransmission as a
result of this command.
7.10.2.5 Enable FLT Bit in the SENA Register
The Hex value of the command is 0xA4. Send it two times in sequence.
59
83-507-5002 Rev. A
7.10.3 Global commands with response
7.10.3.1 Disconnect from communications
Command the supply to end all data transmissions to the HOST PC/IEEE Board and
cease its role as the active addressed supply. The HOST PC/IEEE Board will be required to re-send the ‘ADR nn’ command to reestablish communications with the supply. After receiving the first command the supply will respond with an OK<CR>. The
Hex value of the command is 0xBF. All supplies, both the currently addressed supply
and all non-addressed supplies, will respond to this command; but only the currently
addressed supply (if any) will respond with the ‘OK’.
7.10.4 Addressed commands with response
7.10.4.1 Read registers
Send (0x80 + Address) (1 byte binary - send 2 times sequentially). The supply will return the contents of the Status Condition Register, the Status Enable Register, the
Status Event Register (SEVE?), the Fault Condition Register, the Fault Enable Register and the Fault Event Register IFEVE/). All registers will be represented in two Hex
bytes. Following the register data, a single dollar sign, $, will be added to signal the
end of data and the start of a checksum. The checksum will be the sum of all register
data and will be represented in two Hex bytes. The transmission will end with the CR
character. If repetitive sending of SRQs was active and the supply was sending them,
the supply will stop sending repetitive SRQs but leave the function active. The contents of the registers will not be destroyed. Note that the supply does snot have to be
the active addressed supply.
Note that this command will not execute if another command is being processed.
7.10.4.2 Print Power On Time
Print the total time the supply has operated under AC power. Send 2 bytes in sequence, A6 Hex and the address of the supply in binary. A 32 bit integer will be returned in 8 Hex bytes. The data will be the number of minutes that power has been
‘ON’ in the supply in binary. A ‘$’ sign and 2 byte Hex checksum will be appended to
the data. There is no method provided to reset this number.
Retransmit last message.
Send (0xC0 + Address) (1 byte binary - send 2 times sequentially). The supply will re-
turn the last message sent. Note that the supply does not have to be the active addressed supply.
This command will not execute if another command is being processed.
Note that Single byte commands do not load data into the supply’s data output buffer.
Thus this command will not cause the supply to retransmit data obtained from any
previous Single Byte Command.
7.10.4.3 Retransmit Last Message
Send (0xC0 + Address) (1 byte binary - send 2 times sequentially). The supply will return the last message sent. Note that the supply does not have to be the active addressed supply.
This command will not execute if another command is being processed.
Note that Single byte commands do not load data into the supply’s data output buffer.
Thus this command will not cause the supply to retransmit data obtained from any
previous Single Byte Command.
83-507-5002 Rev. A
60
y
7.10.4.4 Test if MD Mode is Installed
Send AA Hex followed by the address of the supply in binary. If not installed, the supply will return a ‘1’. If installed, the supply will return a ‘0’.
7.10.5 Addressed commands without response
7.10.5.1 Acknowledge SRQ
Send (0xE0 + Address) (1 byte binary - send 2 times sequentially). The supply will
stop re-sending SRQ. If Enable SRQ retransmission is active, it will remain active.
7.10.5.2 Re-enable SRQ with out reading/clearing the SEVE Register
Send A5 Hex followed by the address of the supply in binary and new SRQ’s generated by new events in the Fault Event will be enabled without reading and clearing the
Status Event Register. All events previously recorded in the Fault Event Register must
have been serviced by the user’s software prior to this command to take affect.
Name Bit Positions Response Description
Global
Commands
Disable MD Mode 1010 0000 None Set supplies out of MD Mode (de-
fault)
Enable MD Mode 1010 0001 None Set supplies into MD Mode
Disable SRQ
retransmission
Enable SRQ
retransmission
1010 0010 None
1010 0011 None
Disable retransmission of SRQs by
supplies (default)
Enable retransmission of SRQs by
supplies
Enable FLT Bit 1010 0100 None Enable the FLT bit in the SENA
Register
Disconnect serial
communications
1011 1111 OK
All supplies will halt transmission
and enter the non-addressed
state.
Addressed
Commands
Read Registers 100x xxxx Register data Non destructive read of all regis-
ter. x xxxx is the address of the
supply in binary.
Re-enable SRQ
Print Power On
Time
Byte 1
1010 0101
Byte 2
xxxx xxxx
Byte 1
1010 0110
Byte 2
xxxx xxxx
None
Power On
time in min-
utes
Re-enable SRQ without reading or
clearing the SEVE Register. xxxx
xxxx is the address of the supply in
binary. Works only in MD Mode.
Read the time the supply is active
under AC Power. xxxx xxxx is the
address of the supply in binary.
Returns a 32 Bit integer as 8 Hex
bytes. A ‘$’ sign is appended to
the data followed by a 2 byte
check-sum. A total of 11 b
tes are
61
83-507-5002 Rev. A
Retransmit last
110x xxxx
message
Acknowledge
111x xxxx
SRQ
Test if MD Mode
is Installed
Byte 1
1010 1010
Byte 2
xxxx xxxx
Supply Initiated
Communications
SRQ 100x xxxx
Table 7-4. SINGLE BYTE COMMUNICATIONS
Last message
None
0 or 1
N/A
returned.
Retransmit last response from a
command. x xxxx is the address of
the supply in binary.
Acknowledge SRQ. If retransmission of SRQ is enabled, it will remain enabled for the next SRQ. X
xxxx is the address of the supply in
binary.
Returns a 0 if not installed or a 1 if
installed. A ‘$’ sign followed by a 2
bytes checksum and Carriage Return is appended to the data. xxxx
xxxx is the address of the supply in
binary.
SRQ from supply when in MD
Mode. X xxxx is the address of the
supply in binary.
GEN750W models
Table 7-5: Current programming range
Model Minimum
(A)
-
-
-
-
-
-
-
-
-
-
-
-
Maximum
(A)
NOTE:
The power supply can accept values higher 5% than the table values, however it is not
recommended to program the power supply over the rated values.
Table 7-6: OVP programming range Table 7-7: UVL programming range
Example response: MV(45.201),PV(45), MC(4.3257), PC(10), SR(30), FR(00)
2 FLT? Reads Fault Conditional Register. Returns 2-digit hex.
3 FENA Set Fault Enable Register using 2-digit hex.
4 FENA? Reads Fault Enable Register. Returns 2-digit hex.
5 FEVE? Reads Fault Event Register. Returns 2-digit hex. Clears bits of Fault Event Register.
6 STAT? Reads Status Conditional Register. Returns 2-digit hex.
7 SENA Sets Status Enable Register using 2-digit hex.
8 SENA? Reads Status Enable Register. Returns 2-digit hex.
9 SEVE? Reads Status Event register. Returns 2-digit hex. Clears bits of Status Event register.
7.11 STATUS, ERROR AND SRQ REGISTERS
7.11.1 General Description
This Section describes the various status error and SRQ registers structure. The registers can be
read or set via the RS232/RS485 commands. When using the IEEE option, refer to the User’s
Manual for Genesys
TM
Power Supply IEEE Programming Interface.
Refer to Fig. 7-7 for the Status and Error Registers Diagram.
63
83-507-5002 Rev. A
Constant Voltage
Constant Current
No Fault
Fault
Auto Start
Fold Enabled
Spare
Local Mode
Spare
AC Fail
Over Temperature
Foldback (tripped)
Over Volt Prot
Shut Off (rear panel)
Output Off (front panel)
Enable Open
Command Error (”Cnn”)
Execution Error (”Enn”)
Query Response (”message”)
Command Response (”OK”)
Status Registers
LSB
MSB
Condition
0
CV
1
CC
2
NFLT
3
FLT
4
AST
5
FDE
6
0
7
LCL
“STAT?”
Enable
0
0
0
“SENA xx”
“SENA?”
Event
CV
CC
NFLT
FLT
0
0
0
LCL
“SEVE?”
Fault Registers
LSB
MSB
Condition
0
0
1
AC
2
OTP
3
FLD
4
OVP
5
SO
6
OFF
7
ENA
“FLT?”
Enable
“FENA xx”
“FENA?”
Event
“FEVE?”
Fig.7-7: Status and Error Registers Diagram
0
AC
OTP
FLD
OVP
SO
OFF
ENA
Response
messages
SRQ
Messages
One response for every command
or query received.
Serial
TXD
“Inn” and CR
One SRQ when SEVE goes
from all zeroes to any bit set.
Setting more SEVE bits does
not cause more SRQs.
Positive Logic:
0 = No Event
1 = Event Occured
7.11.2 Conditional Registers
The fault Condition Register and the Status Condition Register are read only registers that the
user may read to see the condition of the Power supply. Refer to Table 7-8 for description of the
Fault Condition Register bits and Table 7-9 for the Status Condition register bits.
64
83-507-5002 Rev. A
7.11.2 Conditional Registers (continued)
Table 7-8: Fault Condition Register
BIT Fault name Fault symbol Bit Set condition Bit Reset condition
0 (LSB) Spare bit SPARE Fixed to zero Fixed to zero
1 AC Fail AC AC fail has occurred. The AC input returns to normal.
2 Over
temperature
3 Foldback FOLD Foldback shutdown
4 Over volt-
age
5 Shut Off SO Rear panel J1 “Shut
OTP OTP shutdown has
occurred.
has occurred
OVP OVP shutdown has
occurred.
Off” condition has oc-
The power supply cools down.
The supply output is turned On by
front panel button or OUT 1 command.
The supply output is turned ON by
front panel button or OUT 1 command.
Rear panel J1 “Shut Off” condition has
been removed.
curred.
6 Output Off OFF Front panel OUT but-
ton pressed to Off.
7(MSB) Enable ENA Rear panel J1 Enable
terminal (J1-1&J1-14)
The supply output is turned On by
front panel button or OUT 1 command.
Rear panel J1 Enable terminals
closed.
opened.
Table 7-9: Status Condition Register
BIT Fault name Fault symbol Bit Set condition Bit Reset condition
0 (LSB) Constant
Voltage
1 Constant
Current
2 No Fault NFLT
3 Fault active FLT One or more faults
4 Auto-
Restart Enabled
5 Fold
Enabled
6 Spare bit SPARE Fixed to zero. Fixed to zero.
7(MSB) Local Mode LCL Supply in Local mode. Supply in Remote mode or Local-
CV Output is On and the
supply in CV.
CC Output is ON and the
supply in CC.
The power supply is
operating normally or
fault reporting is not
enabled.
See “OUT n” command in Section
7.7.5.
are enabled and occur.
AST Supply is in Auto-
Restart mode (from
Front Panel or serial
command).
FDE Fold protection is
enabled (from Front
Panel or serial
command).
Output is ON and the supply is not in
CV.
Output is ON and the supply is not in
CC.
One or more faults are active and fault
reporting is enabled (using “FENAxx”).
Fault Event Register cleared (FEVE?).
Supply is in Safe-Start mode (from
Front Panel or serial command).
Fold protection disabled (from Front
Panel or serial command).
Lockout mode.
7.11.3 Service Request: Enable and Event Registers
The conditional Registers are continuously monitored. When a change is detected in a register bit
which is enabled, the power supply will generate an SRQ message.
65
83-507-5002 Rev. A
The SRQ message is: “Inn” terminated by CR, where the nn is the power supply address. The
SRQ will be generated either in Local or Remote mode.
Refer to Tables 7-10 to 7-13 for details of the Enable and Event registers.
1. Fault Enable Register
The Fault Enable Register is set to the enable faults SRQs.
Table 7-10: Fault Enable Register
BIT
Enable
bit name
0 (LSB) Spare bit SPARE
1 AC Fail AC
2 Over Temperature OTP
3 Foldback FOLD
Fault symbol Bit Set condition Bit reset condition
User command:
“FENA nn” where
nn is hexadecimal
User command: “FENA nn”
where nn is hexadecimal (if
nn=”00”, no fault SRQs will
be generated).
4 Over Voltage OVP
5 Shut Off SO
6 Output Off OFF
7(MSB) Enable ENA
2. Fault Event Register
The Fault Event will set a bit if a condition occurs and it is Enabled. The register is cleared when
FEVE?, CLS or RST commands are received.
Table 7-11: Fault Event Register
BIT
Enable
bit name
0 (LSB) Spare bit SPARE
1 AC Fail AC
2 Over Temperature OTP
3 Foldback FOLD
4 Over Voltage OVP
5 Shut Off SO
6 Output Off OFF
Fault symbol Bit Set condition Bit reset condition
Fault condition
occurs and it is
enabled.
The fault can set a
bit, but when the
fault clears the bit
remains set.
Entire Event Register is
cleared when user sends
“FEVE?” command to read
the register.
“CLS” and power-up also
clear the Fault Event Register. (The Fault Event
Register is not cleared by
RST)
7(MSB) Enable ENA
66
83-507-5002 Rev. A
3. Status Enable Register
The Status Enable Register is set by the user to Enable SRQs for changes in power supply
status.
Table 7-12: Status Enable Register
BIT Status name
0 (LSB)
1
2
3
4
5
6
7 (MSB)
Constant Voltage
Constant Current
No Fault
Fault active
Auto-Restart en-
Fold enabled
Spare
Local Mode
Status sym-
bol
CV
CC
NFLT
FLT
Bit Set condition Bit reset condition
User command:
“SENA nn” is
received, where
nn is hexadecimal bits.
User command: “SENA
nn” is received, where nn
is hexadecimal bits.
If “nn”=00, no SRQ is sent
when there is a change in
Status Condition Register.
AST Always zero Always zero
FDE Always zero Always zero
Spare Always zero Always zero
LCL
“SENA nn”
command
“SENA nn”
command
4. Status Event Register
The Status Event Register will set a bit if a change in the power supply status occurs and it is enabled. The register is cleared when the “SEVE?” or “CLS” commands are received. A change in
this register will generate SRQ.
Table 7-13: Status Event Register
BIT Status name
0 (LSB)
1
2
3
4
5
6
7 (MSB)
Constant Voltage
Constant Current
No Fault
Fault active
Auto-Restart en-
Fold enabled
Spare
Local Mode
Status sym-
bol
Bit Set condition Bit reset condition
Changes in status
CV
occur and it is
Enabled.
CC
The change can
set a bit, but when
NFLT
FLT
0 Always zero
the change clears
the bit remains
set.
Entire Event Register is
cleared when user sends
“SEVE?” command to
read the register.
“CLS” and power-up also
0 Always zero
0 Always zero
clear the Status Event
Register.
Unit is set to Lo-
LCL
cal by pressing
front panel
REM/LOC button.
67
83-507-5002 Rev. A
7.12 SERIAL COMMUNICATION TEST SET-UP
Use the following instructions as basic set-up to test the serial communication operation.
1.Equipment: PC with Windows Hyper Terminal, software installed, Genesys
Power supply, RS232 cable.
2. PC set-up: 2.1 Open Hyper Terminal……………………. New Connection.
2.2 Enter a name
2.3 Connect to………………………………… Direct to Com 1 or Com 2
2.4 Configure port properties:
Bits per second……9600
Data bits……………8
Parity……………….None
Stop bits……………1
Flow control……….None
2.5 Open Properties in the program File………………….Properties
2.6 Setting: ASCII Set Up
Select Echo characters locally, select send line ends with line feed.
On some PC systems, pressing the number keypad “Enter” will distort displayed messages. Use the alphabetic “Enter” instead.
3. Power supply set-up:
TM
3.1 Connect the power supply to the PC using the RS232 cable.
3.2 Set via the front panel: Baud Rate: 9600, Address: 06 (default).
3.3 Set via the rear panel: RS232/RS485 to RS232 (refer to Section 4-4).
4. Communication Test:
4.1 Model identification:
PC:write: ADR 06
Power supply response: “OK”
4.2 Command test:
PC write: OUT1
Power supply response: “OK”
PC write: PVn
Power supply response: “OK”
PC write: PCn (for values of n see Tables 7-4, 7-5 and 7-6)
Power supply response: “OK”
The power supply should turn on and the display will indicate the actual Output
Voltage and the actual Output Current.
68
83-507-5002 Rev. A
CHAPTER 8 ISOLATED ANALOG PROGRAMMING OPTION
8.1 INTRODUCTION
Isolated Analog Programming is an internal Option Card for analog programming of the Gene-
TM
sys
power supply series. The option is factory installed and cannot be obtained with a GPIB
(IEEE-488) Interface. Output Voltage and Output Current can be programmed and readback
through optically isolated signals which are isolated from all other ground references in the power
supply.
There are two types of Isolated Analog programming cards:
1. 0-5V/0-10V option (PN: IS510): Using 0-5V or 0-10V signals for programming and readback.
2. 4-20mA option (PN: IS420): Using current signals for programming and readback.
8.2 SPECIFICATIONS
8.2.1 0-5V/0-10V OPTION (PN: IS510)
Programming
Inputs
Monitoring
Outputs
Output Voltage programming accuracy % +/-1
Output Current programming accuracy % +/-1
Output Voltage programming temperature coefficient PPM/°C +/-100
Output Current programming temperature coefficient PPM/°C +/-100
Input impedance Ohm 1M
Absolute maximum voltage Vdc 0-15
Max. voltage between program inputs and supply outputs Vdc 600
Output Voltage monitoring accuracy % +/-1.5
Output Current monitoring accuracy % +/-1.5
Output Impedance (see Note) Ohm 100
Max. voltage between monitoring outputs and supply out-Vdc 600
NOTE:
Use 100Kohm minimum input impedance for the monitoring circuits to minimize the readback error.
8.2.2 4-20mA option (PN: IS420)
Programming
Inputs
Output Voltage programming accuracy % +/-1
Output Current programming accuracy % +/-1
Output Voltage programming temperature coefficient PPM/°C +/-200
Output Current programming temperature coefficient PPM/°C +/-200
Input impedance Ohm 50
Absolute maximum input current Vdc 0-30
Max. voltage between program inputs and supply outputs Vdc 600
Monitoring
Outputs
Output Voltage monitoring accuracy % +/-1.5
Output Current monitoring accuracy % +/-1.5
Maximum load impedance Ohm 500
Max. voltage between monitoring outputs and supply out-Vdc 600
69
83-507-5002 Rev. A
8.3 ISOLATED PROGRAMMING & MONITORING CONNECTOR
Refer to Table 8-1 for detailed description of the rear panel Isolated Programming & Monitoring
connector. To provide the lowest noise performance, it is recommended to use shielded-twisted
pair wiring.
Refer to Fig.8-1 for description of the Isolated Analog Programming & Monitoring connector.
Isolated programming plug P/N: MC1.5/8-ST-3.81, Phoenix.
Table 8-1: Detailed description of Isolated programming & Monitoring connector
Range 0-5/0-
Terminal Signal name Function
10V
IS510 option
1 SHLD
2 +VPROG_ISO
3 +IPROG_ISO
4 GND
5 GND
6 +VMON_ISO
7 +IMON_ISO
8 SHLD
Shield, connected internally to
chassis of the power supply.
Output Voltage programming
input
Output Current programming
input
Ground for programming signals.
Ground for programming signals.
Output voltage monitoring output
Output current monitoring output
Shield, connected internally to
chassis of the supply.
Chassis ground
0-5V/0-10V 4-20mA
0-5V/0-10V 4-20mA
Ground Ground
Ground Ground
0-5V/0-10V 4-20mA
0-5V/0-10V 4-20mA
Chassis ground
CAUTION
When the Isolated Analog Option is installed, do not apply any signals to the
non-isolated VPGM and IPGM (J1-9 and J1-10) pins. All other J1 features may
be used normally. Refer to Section 4.5 for a description of J1 features.
Range 4-
20mA IS420
option
70
83-507-5002 Rev. A
8.4 SETUP AND OPERATING INSTRUCTIONS
To prevent damage to the unit, do not program the output voltage and
current to higher than the power supply rating.
8.4.1 Setting
up the power supply for 0-5V/0-10V Isolated Programming and Monitoring
Perform the following procedure to configure the power supply:
1. Turn the power supply AC power switch to Off.
2. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
3. Set the Setup switch SW1, positions 1 and 2 to the UP position.
4. Set SW1, position 3 to select the Programming Voltage Range: Down=0-5V, Up=0-10V.
5. Set SW1, position 4 to select the Monitoring Range: Down=0-5V, Up=0-10V.
6. Ensure that SW1, positions 7 and 8 are in the Down position.
7. Connect the programming sources to the mating plug of the Isolated Programming connector. Observe for correct polarity of the voltage source.
J1-8 and J1-12 must be shorted together with a wire jumper.
8. Set the programming sources to the desired levels and turn the power supply ON.
CAUTION
NOTE
8.4.2 Setting up the power supply for 4-20mA Isolated Programming and Monitoring
Perform the following procedure to configure the power supply:
1. Turn the power supply AC power switch to Off.
2. Connect a wire jumper between J1-8 and J1-12 (refer to Table 4-4).
3. Set the Setup switch SW1, positions 1 and 2 to the Up position.
4. Set SW1, position 3 to the Up position.
5. Set SW1, position 4 to the Up position.
6. Ensure that SW1 positions 1 and 2 to their Up position.
7. Connect the programming source to the mating plug of the Isolated Programming connector.
Observe for correct polarity of the voltage source.
J1-8 and J1-12 must be shorted together with a wire jumper.
NOTE
8. Set the programming sources to the desired levels and turn the power supply ON.
SW1 position 3 and 4 must be in the Up position for operation
with 4-20mA Isolated Programming and Monitoring.
NOTE
71
83-507-5002 Rev. A
CHAPTER 9 MAINTENANCE
9.1 INTRODUCTION
This Chapter provides information about maintenance, calibration and troubleshooting.
9.2 UNITS UNDER WARRANTY
Units requiring repair during the warranty period should be returned to a Lambda authorized service facility. Refer to the addresses listing on the back cover of this User’s Manual. Unauthorized
repairs performed by other than the authorized service facilities may void the warranty.
9.3 PERIODIC MAINTENANCE
No routine maintenance of the power supply is required except for periodic cleaning. To clean,
disconnect the unit from the AC supply and allow 30sec. For discharging internal voltages. The
front panel and the metal surfaces should be cleaned using a mild solution of detergent and
water. The solution should be applied onto a soft cloth, and not directly to the surface of the unit.
Do not use aromatic hydocarbons or chlorinated solvents for cleaning. Use low pressure
compressed air to blow dust from the unit.
9.4 ADJUSTMENTS AND CALIBRATION
No internal adjustment or calibration is required. There is NO REASON to open the power supply
cover.
9.5 PARTS REPLACEMENT AND REPAIRS
As repairs are made only by the manufacturer or by authorized service facilities, no parts replacement information is provided in the manual. In case of failure, unusual or erratic operation of
the unit, contact a Lambda sales or service facility nearest you. Please refer to the Lambda sales
offices addresses listing on the back cover of this User’s Manual.
9.6 TROUBLESHOOTING
If the power supply appears to be operating improperly, use the Troubleshooting Guide (Table 9-
1) to determine whether the power supply, load or external control circuit are the cause.
Configure the power supply for basic front panel operation and perform the tests of Section 3.8 to
determine if the problem is with the supply.
Table 9-1 provides the basic checks that can be performed to diagnose problems, with refer-
ences to Sections of this User’s Manual for further information.
Table 9-1: Troubleshooting guide
SYMPTOM CHECK ACTION REF
No output. All displays and
indicators are blank.
Output is present
momentarily but shuts Off
quickly. The display
indicates “AC”.
Output is present
momentarily but shuts off
quickly.The display indicates
“OUP”.
Is the AC power cord
defective?
Is the AC input voltage
within range?
Does the AC source
voltage sag when load is
applied?
Is the power supply
configured to Remote
sense?
Check continuity, replace
if necessary.
Check AC input voltage.
Connect to appropriate
voltage source.
Check AC input voltage.
Connect to appropriate
voltage source.
Check if the positive or
negative load wire is
loose.
3.7
3.6
3.7
3.6
3.9.6
3.9.8
72
83-507-5002 Rev. A
SYMPTOM CHECK ACTION REF
Output Voltage will not
adjust. Front panel CC LED
Is the unit in constant
current mode?
Check Output Current
setting and load current.
5.2.1
5.2.2
is On.
Output Voltage will not
adjust Front panel CV Led is
On.
Check if output voltage is
adjusted above OVP
setting or below UVL
Set OVP or UVL so they will
not limit the output.
5.3
5.4
setting.
Output Current will not
adjust. Front panel CV LED
Is the unit in constant
voltage mode?
Check Output Current and
voltage setting
5.2
is on.
Large ripple present in
output.
No output. Display indicates
“OUP”
Is the power supply in
remote sense?
Is the voltage drop on the
load wire high?
Overvoltage Protection
circuit is tripped.
Check load and sense wires
connection for noise and
impedance effects. Minimize
the drop on the load wires.
Turn off the AC power
switch. Check load
3.9.4
3.9.8
5.3
connections. If Analog
Programming is used, check
if the OVP is set lower than
the output.
No output. Front panel
ALARM LED is blinking.
exhaust are blocked. Check
if the unit is installed
adjacent to heat generating
equipment.
Display indicates “Fb” Check Foldback setting and
5.5
load current.
Poor Load regulation.
Front panel CV LED is on.
Are sensing wires
connected properly?
Connect the sense wires
according to User’s Manual
3.9.8
instructions.
The front panel controls are
non-functional.
Is the power supply in
Local-Lockout mode?
Turn Off the AC power and
wait until the display turns
7.2.5
off. Turn on the AC power
and press front panel
REM/LOC button.
9.7 FUSE RATING
There are no user replaceable fuses in the power supply. Internal fuses are sized for fault protection and if a fuse was opened, it would indicate that service is required. Fuse replacement should
be made by qualified technical personnel. Refer to Table 9-2 for a listing of the fuses.
73
83-507-5002 Rev. A
Table 9-2: Internal fuses
Fuse designation 750W model
F301
F302, F304
F31, F32
20A 250VAC, FAST
2A 400VDC, NORMAL
NOT USED
74
83-507-5002 Rev. A
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.