INSTRUCTION MANUALPOWER SUPPLYMODEL ____71____ SPEC._______LAMBDA ELECTRONICS CORP.COLLEGE POINT 56, N. Y.
INSTRUCTION MANUALFORREGULATED POWER SUPPLYMODEL 71
MANUFACTURED BYLAMBDA ELECTRONICS CORP.CORONA 68, NEW YORK
ISSUE A MODEL NO. 711-55-123 SERIAL NO. 1525
INSTRUCTION MANUALFORREGULATED POWER SUPPLYMODEL 71
1. GENERAL DESCRIPTION
1. GENERAL DESCRIPTION.The Model 71 power supply described in this manual is
designed for general purpose use in industry, laboratory,radio station and school to supply power to electronic andother equipment. The DC output voltages are electronicallyregulated, are practically independent of normal line voltagefluctuations and substantially free from hum and noise. Thehigh-voltage DC output is constant (within the specifiedlimits) from zero to maximum load and features a continuously-variable voltage·control with an auxiliary vernier-controlfor precise voltage adjustment. The DC bias-voltage outputis also continuously adjustable and is closely regulated forline voltage variations. The following output voltages aresupplied:
for line voltage variation.Output #3: 6.5 VAC, 5A, unregulated.Output #4: 6.5 VAC, 5A, unregulated.The easy-to-read 3-1/2" panel meters permit monitoring
of output voltage and current. Magnetic circuit-breakersprovide convenient AC and DC overload protection. A time-delay relay circuit protects the tubes during the initialwarm-up period. Sturdy, insulated binding-posts areprovided for front panel connections. A 5651 voltagereference tube insures long time stability for operation.Quality components, conservatlvély rated, guarantee long,dependable trouble~free service.
1.
2. ELECTRICAL SPECIFICATIONS:Input; 105-125 VAC, 50-60 CPS, 475 W (max)DC Output No. 1; (regulated for line and load)Voltage: 0-500 VDC (continuously variable)Current; 0-200 MA (over entire voltage range)Regulation (line); 0.15% or 0.3 volt (whichever is
greater)Regulation (load); 0.15% or 0.3 volt (whichever is
greater)Internal Impedence: Less than 4 ohmsRipple and Noise: Less than 5 millivolts rmsPolarity: Either positive or negative terminal
may be grounded.DC Output No. 2; (regulated for line only)Voltage ranges: Internal Resistance:a) 0-50 VDC (no load) 5,500 ohmsb) 0-200 VDC (no load) 25,000 ohmsCurrent range:Any value of external load impedance may be used
including a continuously applied low impedance or short-clrcult. Insignificant interactlon on Output No. 1. ShortCircuit Current: 9 MA (max.)
Regulation (line): Better than 0.1%.Ripple and Noise; Less than 5 millivolts rms.Polarity: Positive terminal connected
internally to negative terminal ofDC Output No. 1.
AC Outputs (unregulated):Two outputs, isolated and ungrounded. Each is 6.5 VAC
at 5A (at 115 VAC input). Allows for drop in connectingleads. May be connected in series for 13.0 VAC(nominal) at 5A, or in parallel for 6.5 VAC (nom1nal)at 10A.
2.
Ambient Temperature And Duty Cycle:Continuous duty at full load up to 40°C (104°F) ambient.Overload Protection:External overload protection AC and DC systems
utilize magneticcircuit breakers. Trip-Free. Instant manualreset. Front panel.
Internal Failure Protection Fuses, access throughrear of cabinet.
Input And Output Connections:Input 8 foot heavy duty rubber
covered line cord withintegral molded plug,rear of cabinet.
Output Current 3-1/2" rectangularmllliammeter calibrated0-200 MA.
Voltage Reference Tube:A stable 5651 reference tube is used to obtain superior
long—t1me voltage stability.Time·Delay Relay Circuit:A 30-sec time delay circuit is provided to allow tube
heaters to come to proper operating temperature beforehigh voltage can be applied.
3.
TUBE COMPLEMENT:Tube Type Quantity Function
5R4·GY 1 Rectifier6X4 1 Rectifier6w6-GT 6 Control Tubes6N030 1 Time Delay Relay12AX7 3 Voltage Amplifier5651 1 Voltage Reference0A2 1 Voltage Stabilizer
3. MECHANICAL SPECIFICATIONS:Size and Weight and FinishSize 13" H x 8-3/4" W x 14-1/2" DWeight 49 lbs.Finish Two-tone gray
4.
II. OPERATING INSTRUCTIONS.MODEL 71
1. OPERATING CONTROLS.a) The "AC" circuit-breaker is in series with the AC
line and controls power to the supply. When the toggle ofthe "AC" breaker is in the "ON" position, the adjacent pilot-light indicator marked "AC" is illuminated, the heaters ofall the tubes in the supply are energized, and a thirty-secondprotective thermal time·delay relay is set into operation.
b) The "DC" circuit·breaker contacts are in serieswith the plate power relay and controls the application ofplate voltage to the rectifiers of the high—voltage DC andbias supplies. The “DC“ circuit breaker is interlocked withthe thermal time-delay relay so that the delay cycle iscompleted after the tube heaters reach operating temperature.After the delay cycle is completed the “DC" breaker, whenthrown to the ‘DC—ON" position, will apply "DC" power, andthe adjacent pilot—light indicator will be illuminated. The"DC" breaker may then be used in normal switch fashion toturn DC power on and off without delay.
c) The "VOLTMETER" toggle~switch connects the"OUTPUT VOLTAGE" meter to either the "HV" output or the"BIAS" output circuits so that either voltage can be monitoredas desired. The voltmeter circuit is designed so thatswitching from bias to high·voltage reading will disturbneither output voltage.
d) The "HV" control consists of a variable transformerand a precision wirewound potentiometer ganged together,and permits the high voltage DC output to be set at anyvalue from 0 to 500 VDC. The calibration of this controlindicates the value of the DC output—voltage and permitspresetting of the "HV" control before the "DC" breaker isturned on. It also provides an indication of the high—voltageDC output when the "OUTPUT VOLTAGE" meter is used to monitorthe bias output voltage.
e) The "/\HV" control is a wirewound potentiometerpermitting vernier control of the high voltage DC outputfor precise voltage adjustment. It has a range of plus orminus 5 volts and a calibration accuracy of 5%.
f) The "BIAS RANGE" toggle switch provides two rangesof bias output voltage, 0-50 or 0-200 volts DC.
5.
g) The "BIAS" control is a wirewound potentiometerwhich permits the bias output voltage to be set to anyvalue from zero to the maximum output voltage of eitherbias voltage range.
h) The "OUTPUT VOLTAGE" meter is a 3-1/2 inch panelinstrument which indicates either the "HV" output or "BIAS"voltage output depending upon the position of the "VOLTMETER"toggle switch. In the "HV" position it reads 0-500 VDC fullscale (black numerals). In the "BIAS" position it readseither 0-200 VDC or 0-50 VDC (red numerals) depending uponthe position of the "BIAS RANGE" switch.
i) The "OUTPUT CURRENT" meter is a 3-1/2 inch panelinstrument in series with the "HV" output and indicates theexternal load current of the high—voltage DC output only.
2. OUTPUT TERMINALS.a) FRONT PANEL TERMINALS:The output terminals are sturdy insulated "captive—
head" binding-posts which can be used in a number of waysand are sufficiently sturdy to take a substantial amount ofhandling and abuse. They will accept "wrap·around" wireconnections, "alligator clips", banana plugs, spade lugs,and wire as large as #12 AWG for permanent feed—throughclamping. The 'HV" "BIAS" and each of the "6.5 vAc" outputterminal—pairs are spaced on 3/4 inch centers so that theywill accept standard double banana plugs.
b) "HV" OUTPUT CONNECTIONS:The regulated high-voltage DC output is available
at the front panel terminals marked "HV".The positive connection is brought out through
the red binding post marked "+". The negative connectionis brought out through the black binding post marked "—".
In most applications, it is usual for the negativeterminaleto be at ground potential. In some cases, it maybe desired to place the positive terminal at ground potential.Still other applications may require that neither positive nornegative terminal be at ground potential. In such caseswhere either the positive or negative terminal is to be atground potential, the appropriate terminal on the panelshould be connected by means of a Jumper wire to the binding epost, marked "INT GND".
6.
For minimum output ripple, it is recommendedthat either the positive or negative high voltage DCoutput terminal be grounded.
c) "BIAS° OUTPUT CONNECTIONS:The regulated DC bias-output voltage is available
at the front panel terminals marked "BIAS". The positive"BIAS" connection is internally tied to the negative "HV"connection and is brought out through the black bindingpost marked "BIAS+" and "HV-". The negative "BIAS" connectionis brought out through the black binding post marked "BIAS-".
d) AC OUTPUT CONNECTIONS:The AC output connections marked "6.5 VAC 5A"
provide two independent sources of unregulated voltage forvacuum-tube heater—circuits. Both output sources areavailable at the front-panel binding-posts. The AC outputterminals may be connected in series to provide 13.0 VACat 5 amperes, or in parallel to provide 6.5 VAC at 10 amperes.The schematic diagram on the panel below the AC output bindingposts shows the proper connections of the terminals forcorrect "phasing' of these voltages.
_SAFETY NOTICE_DANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT.
OBSERVE THE USUAL SAFETY PRECAUTIONS WHEN OPERATING ORSERVICING THE EQUIPMENT TO AVOID SEVERE SHOCK OR INJURY.
3. PLACING MODEL 71 INTO OPERATION.a) Both the "AC" and "DC" circuit·breakers snouid be
in the "OFF" position. The "HV" control and the "BIAS"control should be in their extreme counter—clockwise positions,the "/\HV" control in the center or "O" position.
b) Plug the power cord into a source of 115 volts AC50/60 cycles.
c) Connect the desired AC and DC loads to the outputterminals of the supply. Note the schematic diagram on thefront panel showing proper phasing of the 6.5 VAC outputsfor series or parallel operation.
d) Throw the "AC" circuit breaker to the "ON" position.The AC pilot indicator marked "AC" will be illuminated, and
6.5 volts AC will be present at the front panel bind1ng·posts.The thermal time-delay circuit will start itS 30·second delay-cycle.
7.
e) After approximately 30 seconds, throw the "DC"circuit-breaker to the "ON" position. The pilot-lightindicator marked "DC" will be illuminated, and the internalplate-power·relay will close. If the "DC" circuit breakeris thrown to the "ON" position before the 30 second timedelay has elapsed, the pilot indicator will not light norwill the plate-power-relay close until the time-delay cycleis complete.
f) After the pilot "DC" indicator 1e illuminated throwthe "VOLTMETER" selector switch to the "HV" position. Turnthe "HV" control clockwise to the desired DC output voltageas indicated on the "OUTPUT VOLTAGE" voltmeter. The "/\HV"vernier control may be utilized for precise voltage adjustment.If an external load is connected to the "HV" output terminals,the output current will be indicated on the "OUTPUT CURRENT"meter.
g) If use of the "BIAS" output voltage is desired,throw the "DC" breaker off, connect the bias-load to the"BIAS" terminals, set the "BIAS RANGE" switch to the biasvoltage range desired, the "VOLTMETER" selector switchto "BIAS" and the "BIAS" control to zero. Throw the "DC"breaker on. Turn the "BIAS" control clockwise to the requiredvoltage as indicated on the proper red scale of the "0UTPUTVOLTAGE" meter. The "OUTPUT VOLTAGE" meter may be used tomonitor the bias voltage, the calibration on the "HV" controlthen serving as an indication of the "HV" output voltage.
h) If it is desired to turn off the DC output only,use the "DC" circuit breaker, leaving the "AC" breaker inthe "ON" position. In this manner, the supply will be ina standby condition ready for instant use.
CAUTION: Turning the supply on and off rapidlyby means of the "AC" breaker (with the DC breaker in the"ON" position) may seriously damage or impair the life ofthe high voltage rectifier tube. If less than one minuteelapses between the time the "AC” breaker is turned off andturned on again (the time required for the protectivethermal time-delay relay to re—cycle) the "DC" breaker shouldbe kept in the ”OFF" position for at least 20 seconds afterthe "AC" breaker is turned on to permit the rectifier heatersto return to proper operating temperature.
4. OVERLOAD PROTECTION.a) AC OUTPUT CIRCUITS:An overload or short circuit of the 6.5 VAC 5A
output circuits will trip the "AC" circuit breaker shuttingoff the entire supply. Removing the overeload and turning
8.
the "AC" breaker on again will restore operation. If thesupply is off for more than one minute the thermal delay-relay may re-cycle before DC voltage will be present atthe output terminals. (see CAUTION note in paragraph 3above).
b) HIGH VOLTAGE DC OUTPUT CIRCUITS:An overload or short circuit of the "HV" output
will trip the "DC“ circu1t—breaker releasing the plate-power·relay and disconnecting the plate-voltage from therectifier tubes of both the high-voltage DC and bias supplies.Removing the overload or short-circuit and throwing the "DC"breaker to the "ON" position will restore operationimmediately.
c) DC BIAS OUTPUT CIRCUIT:The bias output circuit is so designed that it
may be short·circuited for indefinitely long periods oftime without damage to any component or effect on the highvoltage DC output.
5. INTERNAL POWER SUPPLY FAILURE PROTECTION:a) In general, external overload of the output voltage
circuits will result in tripping of the circuit breakers.Internal failure of the power supply components may resultin tripping of the breakers or blowing of the internalprotective fuses mounted as the rear of the unit. Failureof F1, the I/2 ampere 3AG "Slo-Blo" fuse, indicates failureof a component of the bias reference supply. Failure of thisfuse will probably require servicing of the power supply.Refer to Section III for maintenance data before servicingof equipment or replacement of the fuse.
NOTE: Failure of this fuse will result in removalof voltage from all DC output terminals.
b) F2, a 10-ampere 3AG "Slo-Blo" input line fuselocated adjacent to F1 provides protection against failureof the powerstat TA-1, Lambda Part No. TA-549, and inputwiring. This fuse will also protect the power supply inevent that the unit is accidentally plugged into a 220 VACcircuit or into a DC.circuit. This fuse will not fail inthe case of overloads of the DC or AC output circuits.Thls protection is provided by the circuit breakers.
9.
6. NOISE AND RIPPLE OUTPUT:The noise and ripple output of the high-voltage
DC supply should be less then 5 millivolts rms and theDC bias supply less than 5 millivolts rms at all voltagesand load conditions within the specifications. Measurementof thls level of voltage may be made with an AC VTVMcapable of reading 5-8 millivo1ts rms. Meesurements ofthese low values of voltege should be made using a shieldedcable connecting the power supply output to the AC VTVM.
It is recommended that either the positive ornegative terminal of the "HV" output be connected by a Jumperwire to the "INT-GND" terminal for minimum ripple output.
7 . INTERNAL IMPEDANCE.a) "HV" OUTPUT:The internal impedance of the hlgh voltage DC
supply is approximately 4 ohms for DC. A 2 mfd oll-filledpaper capacitor is ln shunt with the DC output circuitfor two purposes: 1) to maintain this low value of outputlmpedence at audio, and at low and medium radio frequencies,
2) to provide a reservoir to supply transient currents ofshort duratlon having peak values greater than 200 MA.
An additional external capacitor shunted acrossthe "HV" output will provide even lower AC output impedanceand allow even higher peak transient currents to be drawn.For low impedance to high frequency RF·currents, the commonpractice is to use a mica capacitor shunt close to the RF unit.
b) DC BIAS OUTPUT:The internal resistance of the DC bias supply
O-200 VDC range is approximately 25,000 ohms. For lowimpedance to AC, an external capacitor should be shuntedacross the "BIAS OUTPUT" terminals. For low impedance tohigh-frequency RF currents, the common practice is to usea mica capacitor shunt close to the RF unit. The internalresistance of the bias supply 0-50 VDC range is 5,500 ohms.
10.
III. MAINTENANCESAFETY NOTICEDANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT.
OBSERVE THE USUAL SAFETY PRECAUTIONS WHEN OPERATING ORSERVICING THE EQUIPMENT TO AVOID SHOCK OR INJURY.
1. GENERAL.Under normal conditions no special maintenance
of the Model 71 regulated power supply is required exceptfor occasional tube replacement. In the event of failure,or inability of the regulated DC output circuits to functionproperly a list of typical symptoms and their probable causesis given in paragraph "6" of this section.
2. REMOVAL OF POWER SUPPLY UNIT FROM CABINET.If tube replacement or servicing of the unit is
necessitated, the power susply unit must be removed fromits cabinet. This is accomplished by removing the fourlarge diameter nickel-plated screws on the rear face ofthe cabinet and sliding the unit out.
NOTE: It is not necessary to loosen any screwsother than the four mentioned above for removal of thesupply from the cabinet. At no time should removal ofthe painted screws in the rear of the cabinet be attempted.
3. SERVICING OF POWER SUPPLY WHEN REMOVED FROM CABINET.a) Upon removal of the cabinet, all tubes are made
accessible, and tube replacement is simply accomplished.6W6-GT tubes and the 6N030 tube are secured to theirsockets by means of spring~type retainer clamps. Theseretaining clamps must be depressed into and held in aflattened position before removing these tubes. whenreplacing the miniature type tubes, they should be insertedinto a pin straightener before putting them into the socketsto avoid bending pins. Bent pins create strain on the glassbases with the resulting possibility of breakage or crackingin time. When tubes are replaced, adjustment of calibratingpotentiometers should be checked.
11.
b) 6N030 TIME-DELAY·RELAY:The 6N030 1s most readily checked under actual
operatlng conditions. If the power supply is turned onfrom a cold start, and the "DC" circuit·breaker left inthe "ON" position, the internal plate-power-relay willc1ose with an audible click, and the "DC ON" pilot lightlndlcator will be llluminated within 30 to 45 seconds.
At high AC line-voltages, the relay may close1n as early as 20 seconds, at low line-voltages as lateas 1 minute. If the plate·power-relay closes much earlierthan 20 seconds or later than 1 minute from a cold start,the 6N030 should be replaced.
c) 0A2 VOLTAGE REGULATOR TUBE:Upon placing the Model 71 power supply into an
operating condition at any setting of output voltage the0A2 should exhibit an lnternal pale purple glow. If tubefalls to glow or appears to flicker, the tube should bereplaced. If the new tube does not operate properly, thecircuit voltages should be checked against the circuitdiagram.
d) 5651 VOLTAGE REFERENCE TUBE:No special check of the 5651 tube is required.
The tube operates normally with a bright orange glow on thesurface of its dlsc-shaped cathode. If the tube fails toglow or appears to flicker, it should be replaced. Ifthen the fault is not remsved, a voltage check should bemade of the tube and its associated circuits. The voltageacross the 5651 should range between 82 and 92 VDC andshould not fluctuate.
4. ADJUSTMENT OF CALIBRATING POTENTIOMETERS R35 & R36:If any of the tubes other than the rectifiers,
(5R4-GY and 6x4), the series control tubes, (6w6·GT), andthe time·delay relay, (6N030), are replaced, the calibratingand alignment potentiometers, R35 and R36, may requirereadjustment. This readjustment should be made accordingto the following procedure:
a) With AC and DC circuit breakers in the "OFF"position, zero-set the "Output Voltage" and "Output Current"meters accurately.
b) Turn the "HV" control to its extreme clockwiseposition. The pointer on the control knob should line upwith the 500 volt callbratlon line or very close to it.
12.
If a major discrepancy exists, loosening of the two setscrews in the knob will permit readjustment of its position.
c) Set the "/\HV" control to its center or "0"position.
d) Set the "Voltmeter" switch to the "HV" position.e) With no external AC or DC load on the power supply,
turn both "AC" and "DC" circuit breakers on and allow thesupply to warm up for at least 10 mlnutes.
f) With the "HV" control set to 500, adjust R36 sothat the "Output Voltage" voltmeter reads 500 volts (blackscale).
g) Turn the "HV" control to the zero mark. AdjustR35 so that the "Output Voltage" voltmeter reads zero.
h) Repeat steps "f" and "g" until the "HV" controlreads zero in its extreme counter clockwise position and500 volts ln its extreme clockwise position.
5. OPERATIONAL CHECK.a) REGULATION WITH LOAD:After tubes have been replaced or the equipment
serviced, a simple check of the proper operation of the0-500 VDC output circuit supply may be made by alternatelyconnecting and disconnecting a 200 MA load to the supplywith the 'Output Voltage" meter in the "HV" position.Except for a transient kick of the meter needle when theload is connected to the supply, the change in outputvoltage should be barely perceptable (less than 1/10 of1 division on the meter scale) for proper operation. AnAC VTVM capable of reading 5 millivolts rms may be employedto check the noise and ripple level output of the supplywhen making this check. Shielded leads should be employedto connect the AC VTVM to the power supply output terminals.
Note that the "DC" "BIAS OUTPUT" circuit is notregulated for load variations. (See Electrical Specifications)
b) REGULATION WITH LINE:A Variac or Powerstat connected between the ACpower line and the input to the Model 71 may be employedto check the regulation of the DC output circuits. Withthe "Output Voltage" voltmeter ln the circuit being monitoredand the line voltage varied from 105 to 125 VAC, the changein output voltage should be barely perceptible (less thanl/10 of 1 meter division) for proper operation.
13.
6. TYPICAL POWER SUPPLY FAILURE CONDITIONS AND THEIRPORTABLE CAUSES.
SAFETY NOTICEDANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT.
OBSERVE THE USUAL SAFETY PRECAUTIONS WHEN OPERATING ORSERVICING THE EQUIPMENT TO AVOID SEVERE SHOCK OR INJURY.
Refer to the Schematic Diagram for properoperating voltages in the equipment.
It is recommended that the input plug be removedfrom the 115 VAC source when removing or replacing tubes.
OPERATING CONDITION REMEDY OR SOLUTIONa) AC circuit breaker Check AC output for overload
trips repeatedly or short circuit. Removeoverload condition.
b) DC circuit breaker 1) Check "HV" output loadtrips repeatedly circuit for overload or shortcircuit. Remove overloadcondition.
2), If this does not eliminatetripping of DC breaker, thencheck for faulty 5R4-GY tube.This tube should be tested ina tube checker. If foundfaulty, it should be replaced.
3) If tube is found to begood or if replacement by a newtube does not eliminate breakertripping, check capacitors,C1 and C2A for breakdown orshort circuit. If these arefound to be cause of breakertripping, replacement of thesecapacitors is required.c) Presence of high DC 1) Shorted 6W6-GT tubes, V2positive voltage at through V6. Shorting of tubeterminals compared to elements within tube envelopethat indicated on "HV" will result in loss of control.dial, along with high A visual inspection of theripple and poor individual tubes may lead toregulation. (no external identification of faulty tube.load is applied to "HV" If this is not the case, eachoutput.) tube individually should beremoved while the outputvoltage is monitored on the"Output Voltage" meter.
14.
If upon removal of any tubeV2-V6, this condition iseliminated, replace thisfaulty tube with a new tube.
2) Filament burnout of 12AX7.V8. lf tubes V2-V6 ere allfound to be good, the 12AX7,V8 may have a burned outfilament. This is slmplychecked for by replacing thel2AX7 with a new tube.
3) Loss of bias supply voltagewill result in rise of outputvoltage. If bias supply outputvoltage approaches zero volts,and 5651, V14 is extinguishedand voltage across C5A is zero,the bias supply system fuse,F1, 1/2 A has failed. Inserta 1 Ampere AC ammeter in placeof the fuse and turn on thesupply. lf current exceeds
0.4 Amperes check 6X4, V10 forshort or gassy condition, andC5A, CSB for shorted capacitors.If any of these components arefound to be faulty, replacethese components.
4) Absence of voltage acrossfilter capacitors C5A, C5B.check V10, 6X4 tube for openor burned out filament. Thisis most simply accomplished byreplacing tube with a new tube.
5) Presence of bias supplyinput filter voltage andabsence of supply outputvoltages a) 6W6—GT, V1filament is burned out, replacetube.b) Filament burnout of 12AX7,V12. This is easily checkedfor by replacement with e newtube.
15.
d) Presence of positive 1) Filament burnout of l2AX7,low level "HV" voltage as V11. This is easily checkedcompared with that by replacement with a newindicated on the "HV" dial, tube.poor regulation and highripple. (no external load 2) Check voltage acrossapplied to "HV" output.) capacitor, C2A for voltageconditions specified onschematic diagram. If farbelow indicated voltage, checkfilter capacitor for opencircuit.
3) An abnormal increase ofreference supply voltageresults in reduced powersupply "HV" output voltage.High bias supply voltage withassociated high referencesupply ripple voltage. This maybe the result of internal gridto cathode or screen grid short of6W6-GT, V1. Replace with a new6W6-GT tube.
4) Burnout of V8, 12AX7 willcause the bias voltage to rise.It will have a similar effecton the "HV" supply of greatermagnitude in the "HV" supply.Therefore the net result offilament burnout of this tubeis a rise of "HV" voltage.
e) Apparent satisfactory 6W6-GT tubes, V2 through V6,operation at 200 MA load exhibit poor cut-offwith rise of ripple voltage characteristic. To checkat zero external load. cut—off characteristic,operate at zero load and low"HV" output voltage. Monitorthe "HV" output with a VTVMor high impedance AC voltmeter.Remove one tube at a timeuntil faulty tube is identified.Faulty tube is identified byreturn to normal of "HV"output ripple voltage. Careshould be exercised inhandling 6W6-GT tubes toprevent burning of hands dueto touching hot glass envelope.In removing 6W6-GT tube,depress retaining clampmaintaining this position ofthe clamp while tube isremoved.
16.
f) Apparent satisfactory 1) Faulty 6W6-GT tubes, V2operation at low current through v6, will causevalues with supply failure remaining 6W6-GT tubes toat 200 MA external and carry excess load. Tubes105 line. should be visually inspectedfor filament burnout. Ifburnout is not apparent, thentubes should be checked ona tube checker.
2) Faulty 5R4-GY, V9,rectifier tube. A similarcondition applies to the 5R4-GYrectifier. If tube drop isexcessive under load, thenoperation at 200 MA and at105 VAC line will be impaired.The tube should be checked ina tube checker, and if faulty,it should be replaced.
g) Apparent instability Faulty bias and main amplifierln Power Supply Voltage, input tubes cause this voltagedrift of order 1 volt wandering. The tubes involvedmagnitude or greater. are 12AX7 tubes, V11 and V12.One tube should be firstreplaced and the output voltagemonitored. If this conditionis not removed, replace thesecond l2AX7 tube.A schematic diagram of thepower supply will be found inthe rear of this manual. Thediagram contains typicaloperating voltages for aspecific set of operatingconditions.The pilot light indicatorlamps are NE51 neon lamps.They are accessible from thefront panel by merelyunscrewlng the pilot·1ight dome.
_SAFETY NOTICE_DANGEROUS VOLTAGES EXIST INTHIS EQUIPMENT. OBSERVE THEUSUAL SAFETY PRECAUTIONS WHENOPERATING OR SERVICING THEEQUIPMENT TO AVOID SEVERESHOCK OR INJURY.
17.
7. MAINTENANCE OF THE POWERSTAT ("HV" CONTROL).a) DETERMINING DEFECTIVE OPERATION:When the brush contact of the "Powerstat"
indicates excessive wear (less than 1/32" of the carbonbrush extends from the brush holder) or arcing occurs whenthe "Powerstat" is rotated with a load on the supplyresulting in high noise output from the equipment or hashin RF equipment in the laboratory, the brush contact shouldbe examined. A properly adjusted "Powerstat" should notarc or spark under load when the rotor shaft is turned.If arcing is present, the "Powerstat" should be examinedand serviced.
b) SERVICING THE "POWERSTAT".The "Powerstat" can be easily reached by removal
of the cabinet from the power supply. If closer examinationor adjustment of the powerstat is required, greateraccessibility is realized by removal of the front panel.This is accomplished.by unscrewing the six large phillipshead screws on the front panel. After removing the sixscrews, draw the panel forward then tilt it being carefulto clear the powerstat from the frame in doing so. Thepowerstat brush is now free and clear. If wear isindicated, replacement of the brush is effected byloosening the two set screws in the brush holder andremoving the holder. Care must be exercised in replac1ngthe holder to insure the new holder very nearly assumesits former position.
1. DIRTY OR PITTED COMMUTATOR SEGMENTS.Dirty or pitted commutator segments may
be cleaned with carbon-tetrachloride.and/or sandedlightly with fine crocus-cloth. Excessively pittedcommutator segments are a result of failure to replacea worn brush or severe overload of the "Powerstat".Replacement of the entire "Powerstat" assembly maybe necessary. (See paragraph 8a) Refer to LambdaPart No. TA-549 when ordering.
8. SERVICE NOTES.a) REMOVAL OF THE "HV" POWERSTAT AND PRECISION
POTENTIOMETER ASSEMBLY.
1. Remove the connections to the powerstatand the precision potentiometer. Identifyleads to facilitate replacement of entireassembly.
2. Remove the "HV" control knob.
18.
3. Separate the assembly from panel byunscrewing of the four phillips headscrews holding the unit to the frontpanel.
4. Powerstat and precision potentiometerassembly may now be separated frompanel.
b) REPLACEMENT OF POWERSTAT OR PRECISIONPOTENTIOMETER.
1. Remove powerstat potentiometer assemblyfrom the equipment as per (a) above.
2. Loosen the set screws holding the flexiblecoupling between the two units.
3. Loosen the nut securing the powerstatto the bracket and remove the powerstat.
4. Replace the powerstat if required, insuringthat at the extremes of rotation of thepotentiometer shaft, the powerstat brushtakes symmetrical positions with regardto the mounting screw in the rear of thepowerstat.
(NOTE: At no time should the stop collar screwsof the potentiometer be loosened and the collarmoved with regard to the potentiometer shaft.These set screws are set hard and should remainuntouched.)
5. If the potentiometer is to be replaced,after removal of the powerstat, loosenthe three pan head phillips head screwssecuring the potentiometer to the bracket.Replace the potentiometer with the newunit. Refer to Lambda Part No. RW—559Vwhen ordering. Before tightening thescrews securing the potentiometer to thebracket estimate the center to centerdistance between the shaft of thepotentiometer and the stop screw inthe spacer plate. This is best donewith a pair of calipers. This distanceshould approximate 29/64. The powerstatshould now be remounted, and the Millencoupling joined to the powerstat andpotentiometer shafts. Rotation of thepotentlometer should now be tried andthe Millen coupling should be adjustedso that at the extreme clockwise andcounter-clockwise positions of the shaft,the brush holder of the powerstat shouldtake symmetrical positions with regard tothe mounting screw in the rear of the powerstat.
19.
6. Check the assembly for smoothrotation and reassemble intoequipment.
b) REPLACEMENT OF THE "VOLTMETER" AND "BIAS RANGE"SWITCHES.
The replacement of either of these switchescan be facilitated by removing the panel as outlinedabove.
_SAFETY NOTICE_DANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT. OBSERVE
THE USUAL SAFETY PRECAUTIONS WHEN OPERATING OR SERVICINGTHE EQUIPMENT TO AVOID SEVERE SHOCK OR INJURY.
********************************************************* ** ** _W A R R A N T Y_ ** ** We warrant each Instrument manufactured by us, and sold ** by us or our authorized agents, to be free from defects ** in material and workmanship; our obligation under this ** warranty being limited to repairing or replacing any ** instrument or part thereof (except tubes and fuses) ** which shall, within one year after delivery to the ** original purchaser, be returned to us with transpor- ** tation charges prepaid, prove after our examination ** to be thus defective. ** ** we reserve the right to discontinue instruments without ** notice, and to make modifications in design at any time ** without incurring any obligation to make such modifi- ** cations to instruments previously sold. *********************************************************
L A M B D A E L E C T R O N I C S C O R P .103-02 Northern BoulevardCorona, New York
NOTES
1. Tolerance of wirewound resistors is +/-5%, unless noted. SCHEMATIC DIAGRAM
2. Voltage rating of capacitors is 600 VDC, unless noted.
3. Tolerance of capacitors is +/-10%, unless noted. REGULATED POWER SUPPLY
4. Arrows indicate clockwise rotation of potentiometer shafts.
5. V Indicates connection to chassis. MODEL 71
6. * Indicates factory adjustments. See instruction manual.
7. (/) Indicates screwdriver slot. /L\
8. (2) Encircled numbers designate terminal board markings.CONDITIONS OF VOLTAGE MEASUREMENT LAMBDA ELECTRONICS CORP.
b. "HV" control set to 500VDC, no load. "/\HV" control set to zero. CORONA NEW YORK"BIAS" control set to zero.c. Indicated voltages (italicized numbers) are average values.d. Measurements made using 20,000 ohm per volt meter between "HV"negative terminal and indicated points except as otherwise noted.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.