Lambda 71 schematic

INSTRUCTION MANUAL POWER SUPPLY MODEL ____71____ SPEC._______ LAMBDA ELECTRONICS CORP. COLLEGE POINT 56, N. Y.
INSTRUCTION MANUAL FOR REGULATED POWER SUPPLY MODEL 71
MANUFACTURED BY LAMBDA ELECTRONICS CORP. CORONA 68, NEW YORK
ISSUE A MODEL NO. 71 1-55-123 SERIAL NO. 1525
INSTRUCTION MANUAL FOR REGULATED POWER SUPPLY MODEL 71
1. GENERAL DESCRIPTION
1. GENERAL DESCRIPTION. The Model 71 power supply described in this manual is
designed for general purpose use in industry, laboratory, radio station and school to supply power to electronic and other equipment. The DC output voltages are electronically regulated, are practically independent of normal line voltage fluctuations and substantially free from hum and noise. The high-voltage DC output is constant (within the specified limits) from zero to maximum load and features a continuously- variable voltage·control with an auxiliary vernier-control for precise voltage adjustment. The DC bias-voltage output is also continuously adjustable and is closely regulated for line voltage variations. The following output voltages are supplied:
Output #1: 0-500 VDC, 0-200 MA, regulated. Output #2: 0-200 VDC, 0-50 VDC, bias output. Regulated
for line voltage variation. Output #3: 6.5 VAC, 5A, unregulated. Output #4: 6.5 VAC, 5A, unregulated. The easy-to-read 3-1/2" panel meters permit monitoring
of output voltage and current. Magnetic circuit-breakers provide convenient AC and DC overload protection. A time- delay relay circuit protects the tubes during the initial warm-up period. Sturdy, insulated binding-posts are provided for front panel connections. A 5651 voltage reference tube insures long time stability for operation. Quality components, conservatlvély rated, guarantee long, dependable trouble~free service.
1.
2. ELECTRICAL SPECIFICATIONS: Input; 105-125 VAC, 50-60 CPS, 475 W (max) DC Output No. 1; (regulated for line and load) Voltage: 0-500 VDC (continuously variable) Current; 0-200 MA (over entire voltage range) Regulation (line); 0.15% or 0.3 volt (whichever is
greater) Regulation (load); 0.15% or 0.3 volt (whichever is
greater) Internal Impedence: Less than 4 ohms Ripple and Noise: Less than 5 millivolts rms Polarity: Either positive or negative terminal
may be grounded. DC Output No. 2; (regulated for line only) Voltage ranges: Internal Resistance: a) 0-50 VDC (no load) 5,500 ohms b) 0-200 VDC (no load) 25,000 ohms Current range: Any value of external load impedance may be used
including a continuously applied low impedance or short- clrcult. Insignificant interactlon on Output No. 1. Short Circuit Current: 9 MA (max.)
Regulation (line): Better than 0.1%. Ripple and Noise; Less than 5 millivolts rms. Polarity: Positive terminal connected
internally to negative terminal of DC Output No. 1.
AC Outputs (unregulated): Two outputs, isolated and ungrounded. Each is 6.5 VAC
at 5A (at 115 VAC input). Allows for drop in connecting leads. May be connected in series for 13.0 VAC (nominal) at 5A, or in parallel for 6.5 VAC (nom1nal) at 10A.
2.
Ambient Temperature And Duty Cycle: Continuous duty at full load up to 40°C (104°F) ambient. Overload Protection: External overload protection AC and DC systems
utilize magnetic circuit breakers. Trip- Free. Instant manual reset. Front panel.
Internal Failure Protection Fuses, access through rear of cabinet.
Input And Output Connections: Input 8 foot heavy duty rubber
covered line cord with integral molded plug, rear of cabinet.
Output Sturdy insulated "5-way" binding posts, front panel.
Meters: Output Voltage Multi—range 3-1/2"
rectangular voltmeter calibrated 0-50 VDC, 0-200 VDC, 0-500 VDC.
Output Current 3-1/2" rectangular mllliammeter calibrated 0-200 MA.
Voltage Reference Tube: A stable 5651 reference tube is used to obtain superior
long—t1me voltage stability. Time·Delay Relay Circuit: A 30-sec time delay circuit is provided to allow tube
heaters to come to proper operating temperature before high voltage can be applied.
3.
TUBE COMPLEMENT: Tube Type Quantity Function
5R4·GY 1 Rectifier 6X4 1 Rectifier 6w6-GT 6 Control Tubes 6N030 1 Time Delay Relay 12AX7 3 Voltage Amplifier 5651 1 Voltage Reference 0A2 1 Voltage Stabilizer
3. MECHANICAL SPECIFICATIONS: Size and Weight and Finish Size 13" H x 8-3/4" W x 14-1/2" D Weight 49 lbs. Finish Two-tone gray
4.
II. OPERATING INSTRUCTIONS. MODEL 71
1. OPERATING CONTROLS. a) The "AC" circuit-breaker is in series with the AC
line and controls power to the supply. When the toggle of the "AC" breaker is in the "ON" position, the adjacent pilot- light indicator marked "AC" is illuminated, the heaters of all the tubes in the supply are energized, and a thirty-second protective thermal time·delay relay is set into operation.
b) The "DC" circuit·breaker contacts are in series with the plate power relay and controls the application of plate voltage to the rectifiers of the high—voltage DC and bias supplies. The “DC“ circuit breaker is interlocked with the thermal time-delay relay so that the delay cycle is completed after the tube heaters reach operating temperature. After the delay cycle is completed the “DC" breaker, when thrown to the ‘DC—ON" position, will apply "DC" power, and the adjacent pilot—light indicator will be illuminated. The "DC" breaker may then be used in normal switch fashion to turn DC power on and off without delay.
c) The "VOLTMETER" toggle~switch connects the "OUTPUT VOLTAGE" meter to either the "HV" output or the "BIAS" output circuits so that either voltage can be monitored as desired. The voltmeter circuit is designed so that switching from bias to high·voltage reading will disturb neither output voltage.
d) The "HV" control consists of a variable transformer and a precision wirewound potentiometer ganged together, and permits the high voltage DC output to be set at any value from 0 to 500 VDC. The calibration of this control indicates the value of the DC output—voltage and permits presetting of the "HV" control before the "DC" breaker is turned on. It also provides an indication of the high—voltage DC output when the "OUTPUT VOLTAGE" meter is used to monitor the bias output voltage.
e) The "/\HV" control is a wirewound potentiometer permitting vernier control of the high voltage DC output for precise voltage adjustment. It has a range of plus or minus 5 volts and a calibration accuracy of 5%.
f) The "BIAS RANGE" toggle switch provides two ranges of bias output voltage, 0-50 or 0-200 volts DC.
5.
g) The "BIAS" control is a wirewound potentiometer which permits the bias output voltage to be set to any value from zero to the maximum output voltage of either bias voltage range.
h) The "OUTPUT VOLTAGE" meter is a 3-1/2 inch panel instrument which indicates either the "HV" output or "BIAS" voltage output depending upon the position of the "VOLTMETER" toggle switch. In the "HV" position it reads 0-500 VDC full scale (black numerals). In the "BIAS" position it reads either 0-200 VDC or 0-50 VDC (red numerals) depending upon the position of the "BIAS RANGE" switch.
i) The "OUTPUT CURRENT" meter is a 3-1/2 inch panel instrument in series with the "HV" output and indicates the external load current of the high—voltage DC output only.
2. OUTPUT TERMINALS. a) FRONT PANEL TERMINALS: The output terminals are sturdy insulated "captive—
head" binding-posts which can be used in a number of ways and are sufficiently sturdy to take a substantial amount of handling and abuse. They will accept "wrap·around" wire connections, "alligator clips", banana plugs, spade lugs, and wire as large as #12 AWG for permanent feed—through clamping. The 'HV" "BIAS" and each of the "6.5 vAc" output terminal—pairs are spaced on 3/4 inch centers so that they will accept standard double banana plugs.
b) "HV" OUTPUT CONNECTIONS: The regulated high-voltage DC output is available
at the front panel terminals marked "HV". The positive connection is brought out through
the red binding post marked "+". The negative connection is brought out through the black binding post marked "—".
In most applications, it is usual for the negative terminaleto be at ground potential. In some cases, it may be desired to place the positive terminal at ground potential. Still other applications may require that neither positive nor negative terminal be at ground potential. In such cases where either the positive or negative terminal is to be at ground potential, the appropriate terminal on the panel should be connected by means of a Jumper wire to the binding e post, marked "INT GND".
6.
For minimum output ripple, it is recommended that either the positive or negative high voltage DC output terminal be grounded.
c) "BIAS° OUTPUT CONNECTIONS: The regulated DC bias-output voltage is available
at the front panel terminals marked "BIAS". The positive "BIAS" connection is internally tied to the negative "HV" connection and is brought out through the black binding post marked "BIAS+" and "HV-". The negative "BIAS" connection is brought out through the black binding post marked "BIAS-".
d) AC OUTPUT CONNECTIONS: The AC output connections marked "6.5 VAC 5A"
provide two independent sources of unregulated voltage for vacuum-tube heater—circuits. Both output sources are available at the front-panel binding-posts. The AC output terminals may be connected in series to provide 13.0 VAC at 5 amperes, or in parallel to provide 6.5 VAC at 10 amperes. The schematic diagram on the panel below the AC output binding posts shows the proper connections of the terminals for correct "phasing' of these voltages.
_SAFETY NOTICE_ DANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT.
OBSERVE THE USUAL SAFETY PRECAUTIONS WHEN OPERATING OR SERVICING THE EQUIPMENT TO AVOID SEVERE SHOCK OR INJURY.
3. PLACING MODEL 71 INTO OPERATION. a) Both the "AC" and "DC" circuit·breakers snouid be
in the "OFF" position. The "HV" control and the "BIAS" control should be in their extreme counter—clockwise positions, the "/\HV" control in the center or "O" position.
b) Plug the power cord into a source of 115 volts AC 50/60 cycles.
c) Connect the desired AC and DC loads to the output terminals of the supply. Note the schematic diagram on the front panel showing proper phasing of the 6.5 VAC outputs for series or parallel operation.
d) Throw the "AC" circuit breaker to the "ON" position. The AC pilot indicator marked "AC" will be illuminated, and
6.5 volts AC will be present at the front panel bind1ng·posts. The thermal time-delay circuit will start itS 30·second delay- cycle.
7.
e) After approximately 30 seconds, throw the "DC" circuit-breaker to the "ON" position. The pilot-light indicator marked "DC" will be illuminated, and the internal plate-power·relay will close. If the "DC" circuit breaker is thrown to the "ON" position before the 30 second time delay has elapsed, the pilot indicator will not light nor will the plate-power-relay close until the time-delay cycle is complete.
f) After the pilot "DC" indicator 1e illuminated throw the "VOLTMETER" selector switch to the "HV" position. Turn the "HV" control clockwise to the desired DC output voltage as indicated on the "OUTPUT VOLTAGE" voltmeter. The "/\HV" vernier control may be utilized for precise voltage adjustment. If an external load is connected to the "HV" output terminals, the output current will be indicated on the "OUTPUT CURRENT" meter.
g) If use of the "BIAS" output voltage is desired, throw the "DC" breaker off, connect the bias-load to the "BIAS" terminals, set the "BIAS RANGE" switch to the bias voltage range desired, the "VOLTMETER" selector switch to "BIAS" and the "BIAS" control to zero. Throw the "DC" breaker on. Turn the "BIAS" control clockwise to the required voltage as indicated on the proper red scale of the "0UTPUT VOLTAGE" meter. The "OUTPUT VOLTAGE" meter may be used to monitor the bias voltage, the calibration on the "HV" control then serving as an indication of the "HV" output voltage.
h) If it is desired to turn off the DC output only, use the "DC" circuit breaker, leaving the "AC" breaker in the "ON" position. In this manner, the supply will be in a standby condition ready for instant use.
CAUTION: Turning the supply on and off rapidly by means of the "AC" breaker (with the DC breaker in the "ON" position) may seriously damage or impair the life of the high voltage rectifier tube. If less than one minute elapses between the time the "AC” breaker is turned off and turned on again (the time required for the protective thermal time-delay relay to re—cycle) the "DC" breaker should be kept in the ”OFF" position for at least 20 seconds after the "AC" breaker is turned on to permit the rectifier heaters to return to proper operating temperature.
4. OVERLOAD PROTECTION. a) AC OUTPUT CIRCUITS: An overload or short circuit of the 6.5 VAC 5A
output circuits will trip the "AC" circuit breaker shutting off the entire supply. Removing the overeload and turning
8.
the "AC" breaker on again will restore operation. If the supply is off for more than one minute the thermal delay- relay may re-cycle before DC voltage will be present at the output terminals. (see CAUTION note in paragraph 3 above).
b) HIGH VOLTAGE DC OUTPUT CIRCUITS: An overload or short circuit of the "HV" output
will trip the "DC“ circu1t—breaker releasing the plate- power·relay and disconnecting the plate-voltage from the rectifier tubes of both the high-voltage DC and bias supplies. Removing the overload or short-circuit and throwing the "DC" breaker to the "ON" position will restore operation immediately.
c) DC BIAS OUTPUT CIRCUIT: The bias output circuit is so designed that it
may be short·circuited for indefinitely long periods of time without damage to any component or effect on the high voltage DC output.
5. INTERNAL POWER SUPPLY FAILURE PROTECTION: a) In general, external overload of the output voltage
circuits will result in tripping of the circuit breakers. Internal failure of the power supply components may result in tripping of the breakers or blowing of the internal protective fuses mounted as the rear of the unit. Failure of F1, the I/2 ampere 3AG "Slo-Blo" fuse, indicates failure of a component of the bias reference supply. Failure of this fuse will probably require servicing of the power supply. Refer to Section III for maintenance data before servicing of equipment or replacement of the fuse.
NOTE: Failure of this fuse will result in removal of voltage from all DC output terminals.
b) F2, a 10-ampere 3AG "Slo-Blo" input line fuse located adjacent to F1 provides protection against failure of the powerstat TA-1, Lambda Part No. TA-549, and input wiring. This fuse will also protect the power supply in event that the unit is accidentally plugged into a 220 VAC circuit or into a DC.circuit. This fuse will not fail in the case of overloads of the DC or AC output circuits. Thls protection is provided by the circuit breakers.
9.
6. NOISE AND RIPPLE OUTPUT: The noise and ripple output of the high-voltage
DC supply should be less then 5 millivolts rms and the DC bias supply less than 5 millivolts rms at all voltages and load conditions within the specifications. Measurement of thls level of voltage may be made with an AC VTVM capable of reading 5-8 millivo1ts rms. Meesurements of these low values of voltege should be made using a shielded cable connecting the power supply output to the AC VTVM.
It is recommended that either the positive or negative terminal of the "HV" output be connected by a Jumper wire to the "INT-GND" terminal for minimum ripple output.
7 . INTERNAL IMPEDANCE. a) "HV" OUTPUT: The internal impedance of the hlgh voltage DC
supply is approximately 4 ohms for DC. A 2 mfd oll-filled paper capacitor is ln shunt with the DC output circuit for two purposes: 1) to maintain this low value of output lmpedence at audio, and at low and medium radio frequencies,
2) to provide a reservoir to supply transient currents of short duratlon having peak values greater than 200 MA.
An additional external capacitor shunted across the "HV" output will provide even lower AC output impedance and allow even higher peak transient currents to be drawn. For low impedance to high frequency RF·currents, the common practice is to use a mica capacitor shunt close to the RF unit.
b) DC BIAS OUTPUT: The internal resistance of the DC bias supply
O-200 VDC range is approximately 25,000 ohms. For low impedance to AC, an external capacitor should be shunted across the "BIAS OUTPUT" terminals. For low impedance to high-frequency RF currents, the common practice is to use a mica capacitor shunt close to the RF unit. The internal resistance of the bias supply 0-50 VDC range is 5,500 ohms.
10.
III. MAINTENANCE SAFETY NOTICE DANGEROUS VOLTAGES EXIST IN THIS EQUIPMENT.
OBSERVE THE USUAL SAFETY PRECAUTIONS WHEN OPERATING OR SERVICING THE EQUIPMENT TO AVOID SHOCK OR INJURY.
1. GENERAL. Under normal conditions no special maintenance
of the Model 71 regulated power supply is required except for occasional tube replacement. In the event of failure, or inability of the regulated DC output circuits to function properly a list of typical symptoms and their probable causes is given in paragraph "6" of this section.
2. REMOVAL OF POWER SUPPLY UNIT FROM CABINET. If tube replacement or servicing of the unit is
necessitated, the power susply unit must be removed from its cabinet. This is accomplished by removing the four large diameter nickel-plated screws on the rear face of the cabinet and sliding the unit out.
NOTE: It is not necessary to loosen any screws other than the four mentioned above for removal of the supply from the cabinet. At no time should removal of the painted screws in the rear of the cabinet be attempted.
3. SERVICING OF POWER SUPPLY WHEN REMOVED FROM CABINET. a) Upon removal of the cabinet, all tubes are made
accessible, and tube replacement is simply accomplished. 6W6-GT tubes and the 6N030 tube are secured to their sockets by means of spring~type retainer clamps. These retaining clamps must be depressed into and held in a flattened position before removing these tubes. when replacing the miniature type tubes, they should be inserted into a pin straightener before putting them into the sockets to avoid bending pins. Bent pins create strain on the glass bases with the resulting possibility of breakage or cracking in time. When tubes are replaced, adjustment of calibrating potentiometers should be checked.
11.
b) 6N030 TIME-DELAY·RELAY: The 6N030 1s most readily checked under actual
operatlng conditions. If the power supply is turned on from a cold start, and the "DC" circuit·breaker left in the "ON" position, the internal plate-power-relay will c1ose with an audible click, and the "DC ON" pilot light lndlcator will be llluminated within 30 to 45 seconds.
At high AC line-voltages, the relay may close 1n as early as 20 seconds, at low line-voltages as late as 1 minute. If the plate·power-relay closes much earlier than 20 seconds or later than 1 minute from a cold start, the 6N030 should be replaced.
c) 0A2 VOLTAGE REGULATOR TUBE: Upon placing the Model 71 power supply into an
operating condition at any setting of output voltage the 0A2 should exhibit an lnternal pale purple glow. If tube falls to glow or appears to flicker, the tube should be replaced. If the new tube does not operate properly, the circuit voltages should be checked against the circuit diagram.
d) 5651 VOLTAGE REFERENCE TUBE: No special check of the 5651 tube is required.
The tube operates normally with a bright orange glow on the surface of its dlsc-shaped cathode. If the tube fails to glow or appears to flicker, it should be replaced. If then the fault is not remsved, a voltage check should be made of the tube and its associated circuits. The voltage across the 5651 should range between 82 and 92 VDC and should not fluctuate.
4. ADJUSTMENT OF CALIBRATING POTENTIOMETERS R35 & R36: If any of the tubes other than the rectifiers,
(5R4-GY and 6x4), the series control tubes, (6w6·GT), and the time·delay relay, (6N030), are replaced, the calibrating and alignment potentiometers, R35 and R36, may require readjustment. This readjustment should be made according to the following procedure:
a) With AC and DC circuit breakers in the "OFF" position, zero-set the "Output Voltage" and "Output Current" meters accurately.
b) Turn the "HV" control to its extreme clockwise position. The pointer on the control knob should line up with the 500 volt callbratlon line or very close to it.
12.
If a major discrepancy exists, loosening of the two set screws in the knob will permit readjustment of its position.
c) Set the "/\HV" control to its center or "0" position.
d) Set the "Voltmeter" switch to the "HV" position. e) With no external AC or DC load on the power supply,
turn both "AC" and "DC" circuit breakers on and allow the supply to warm up for at least 10 mlnutes.
f) With the "HV" control set to 500, adjust R36 so that the "Output Voltage" voltmeter reads 500 volts (black scale).
g) Turn the "HV" control to the zero mark. Adjust R35 so that the "Output Voltage" voltmeter reads zero.
h) Repeat steps "f" and "g" until the "HV" control reads zero in its extreme counter clockwise position and 500 volts ln its extreme clockwise position.
5. OPERATIONAL CHECK. a) REGULATION WITH LOAD: After tubes have been replaced or the equipment
serviced, a simple check of the proper operation of the 0-500 VDC output circuit supply may be made by alternately connecting and disconnecting a 200 MA load to the supply with the 'Output Voltage" meter in the "HV" position. Except for a transient kick of the meter needle when the load is connected to the supply, the change in output voltage should be barely perceptable (less than 1/10 of 1 division on the meter scale) for proper operation. An AC VTVM capable of reading 5 millivolts rms may be employed to check the noise and ripple level output of the supply when making this check. Shielded leads should be employed to connect the AC VTVM to the power supply output terminals.
Note that the "DC" "BIAS OUTPUT" circuit is not regulated for load variations. (See Electrical Specifications)
b) REGULATION WITH LINE: A Variac or Powerstat connected between the AC power line and the input to the Model 71 may be employed to check the regulation of the DC output circuits. With the "Output Voltage" voltmeter ln the circuit being monitored and the line voltage varied from 105 to 125 VAC, the change in output voltage should be barely perceptible (less than l/10 of 1 meter division) for proper operation.
13.
Loading...
+ 33 hidden pages