
SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS with 500 and 550 option.
A36D/TPSD
Modbus TCP
SCADA INTERFACE
OPTION 21Q
INSTRUCTIONS
This manual is valid for A36D/TPSD Chargers equipped with 341S control cards with
P341S0012 or P341S0013 software and 383S Communications Board
106 BRADROCK DRIVE
DES PLAINES, IL. 60018-1967
(847) 299-1188
FAX: (847) 299-3061
ISSUE DATE: ECN 21183-7 11/2017
INSTRUCTION DRAWING NUMBER:
P25-LOPT21Q-A36D-TPSD-1-341S

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 2 of 10
Default Settings
The LaMarche Communications Card is shipped with the following default settings;
Port: RS232
Baud Rate: 9600
Data Bits: 8
Stop Bits: 1
Parity: None
Board Configuration
The communications card may be configured for RS232, RS485 or TCP communications.
SW2 configures the board for either Serial or TCP/IP communications.
SW4 configures the board for either RS232 or RS485 communications.
SW3 configures the BIAS and Termination Resistor(s) when using RS485.
The photo below shows the location of the dipswitches of the communications board.
Setting the Modbus Address, Baud Rate & Parity
To change the Address, Baud Rate and Parity you need to enter the customer calibration mode where
you can choose the following;
Modbus Type: Serial or TCP
Modbus Address: 1 through 247
Modbus Baud Rate (Serial Only): 1200, 2400, 4800, 9600, 19200, 38400
Modbus Parity Type (Serial Only): NONE, ODD, EVEN
Read Only Mode: This mode does not allow any settings to be modified remotely.

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 3 of 10
RS232 & RS485 Serial Applications
To configure the card for Serial applications you need to configure the board’s dipswitches and set the
Address, Baud Rate and Parity as required in the customer calibration mode.
TCP/IP Applications
To configure the card for TCP/IP applications you need to configure the boards dipswitches and confirm
the Address = 1, Baud Rate = 9600 and Parity = NONE in the customer calibration mode.
You will also likely want to change the IP, Subnet and Gateway. To accomplish this please refer to the
next section.
Changing the TCPIP Settings
The RTU to TCP/IP module is set at the factory as follows:
IP Address: 192.168.0.6
Netmask: 255.255.255.0
Gateway: 192.168.0.1
TCP Port Number: 502
To change the TCPIP settings it is necessary to load and install the DeviceInstaller Software provided by
Lantronix Inc. from the following URL:
http://www.lantronix.com/device-networking/utilities-tools/device-installer.html
Once this software is installed you should reconfigure your Network Adaptor to the same subnet (see
default settings above) as the Lantronix device. Connect the device to your laptop/PC using a nullmodem for a direct connection. Use a straight through if connecting through a switch or hub. If the
device is powered when you run the DeviceInstaller it will automatically begin a search and find the
device. If DeviceInstaller is running when the device is connected the Search command on the Toolbar
Menu will locate the device. Once the device is located, the screen should appear as pictured below.

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 4 of 10
To assign the desire IP settings press the Assign IP button on the Toolbar. This will bring up the
following screen:
The Device Identification is located on the device itself as described in the dialog text above. An example
of the Lantronix device is pictured below.
In the example above the Device Identification would be 00-20-4A-C4-DF-E8. Note this is unique to each
device. After entering the ID press Next.

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 5 of 10
This dialog presents a choice between assigning an IP dynamically which would allow the device to
operate on a network with a DHCP server however it is recommended that a specific IP address be
assigned so it can be referenced directly on a SCADA Network.
Selecting “Assign a specific IP address” will bring up the following dialog:
Enter your desired IP settings and press Next.

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 6 of 10
Pressing Assign will start the process of programming the device to the new IP Settings.
A progress bar and Status will appear indicating a successful operation as shown below:
Pressing Finish will complete the IP setting change process. The DeviceInstaller Application can now be
closed.

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 7 of 10
LaMarche Modbus Implementation
Supported Modbus Types
RTU
TCP
Supported Modbus Function Codes
01 – Read Coil Status (0X)
02 – Read Discrete Input Registers (1X)
03 – Read Holding Registers (4X)
04 – Read Input Registers (3X)
05 – Write Single Coil
06 – Write Single Register
10 – Write Multiple Coils
0F – Write Multiple Registers
Float/EQ Mode Indicator (FLOAT=0, EQUALIZE=1)
Temperature Compensation Enable (ENABLED=1).
LCD Backlight Timeout Enable (ENABLED=1)
This has no effect on Chargers equipped with VFD Displays.
Include Low Current Alarm in Summary Alarm (INCLUDED=1)
Include AC Alarm in Summary Alarm (INCLUDED=1)
Include Ground Detection Alarms in Summary Alarm (INCLUDED=1). TPSD ONLY.
For A36D this point will always read 0 and writes to are prohibited.
Include Over Temperature Alarm in Summary (INCLUDED=1)
Latch Summary Alarm (YES=1)
Latch AC Fail Alarm (YES=1)
Latch Low Voltage Alarm (YES=1)
Latch High Voltage Alarm (YES=1)
Latch High Voltage Shutdown Alarm (YES=1)
Latch Positive Ground Alarm (YES=1). TPSD ONLY.
For A36D this point will always read 0 and writes to are prohibited.
Latch Negative Ground Alarm (YES=1). TPSD ONLY.
For A36D this point will always read 0 and writes to are prohibited.
Latch Overload Alarm (YES=1)
Latch End of Discharge Alarm (YES=1)
Reset Alarms (YES=1)
Write a “1” to reset alarms. After alarms are reset software in the controller sets this
point to “0”.
Ground Detection Alarm Enable. (ENABLED=1, DISABLED=0) TPSD ONLY.
For A36D this point will always read 0 and writes to are prohibited.
Test All Alarm Contacts (BEGIN TEST=1, END TEST=0). Note the HVSD alarm contacts
are not tested remotely.
Test Negative Ground Contacts (BEGIN TEST=1, END TEST=0). TPSD ONLY.
Test High Voltage Alarm Contacts (BEGIN TEST=1, END TEST=0).

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 8 of 10
Test Low Voltage Alarm Contacts (BEGIN TEST=1, END TEST=0).
Test Positive Ground Contacts (BEGIN TEST=1, END TEST=0). TPSD ONLY.
Test AC Alarm Contacts (BEGIN TEST=1, END TEST=0).
Test Summary Alarm Contacts (BEGIN TEST=1, END TEST=0).
Test Low Current Alarm Contacts (BEGIN TEST=1, END TEST=0).
Test Open DC Protection Alarm Contacts (BEGIN TEST=1, END TEST=0). A36D ONLY.
AC Alarm Indicator (FAILURE=1)
High Voltage Alarm Indicator (FAILURE=1)
High Voltage Shutdown Alarm Indicator (FAILURE=1)
Low Current Alarm Indicator (FAILURE=1)
Open DC Protection Alarm Indicator (FAILURE=1) A36D ONLY.
For TPSD this point will always read 0.
Positive Ground Alarm Indicator (FAILURE=1). TPSD ONLY.
For A36D this point will always read 0.
Negative Ground Alarm Indicator (FAILURE=1). TPSD ONLY.
For A36D this point will always read 0.
Summary Alarm Indicator (FAILURE=1)
End of Discharge Alarm Indicator (FAILURE=1).
Overload Alarm Indicator (FAILURE=1)
Over Temperature Alarm Enable (ENABLED=1)
Over Temperature Alarm Status (FAILURE=1)
Charger in Settings Menu (Set to 1 when charger is manually put into the settings menu
through the front panel) Remote setting changes are disabled when this is set to 1 until
the local operator exits the Settings Menu.
SCADA Read Only Mode (ENABLED=1). Setting changes are not allowed when the
charger is in the settings menu or when the SCADA Read Only Mode has been selected.
Negative Ground Alarm Relay Contacts (CLOSED=1, OPEN=0). TPSD ONLY.
High Voltage Alarm Relay Contacts (CLOSED=1, OPEN=0).
Low Voltage Alarm Relay Contacts (CLOSED=1, OPEN=0).
Positive Ground Alarm Relay Contacts (CLOSED=1, OPEN=0). TPSD ONLY.
AC Fail Alarm Relay Contacts (CLOSED=1, OPEN=0).
Summary Alarm Relay Contacts (CLOSED=1, OPEN=0).
Low Current Alarm Relay Contacts (CLOSED=1, OPEN=0).
Open DC Protection Alarm Relay Contacts (CLOSED=1, OPEN=0).

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 9 of 10
Description, Units, Valid Settings/Range
Equalize Timer Mode (0,1 2,3,4)
Equalize Timer Setting (0 to 144)
Low Voltage Alarm Threshold, Volts, (0 to MAXAV)
High Voltage Alarm Threshold, Volts, (0 to MAXAV)
High Voltage Shutdown Alarm Threshold, Volts, (0 to MAXAV)
Low DC Current Alarm Threshold, Amps, (0 to MAXAI)
Low DC Current Alarm Recovery Threshold, Amps (Low DC
Current Alarm Threshold to MAXAI)
Low Voltage Alarm Recovery Threshold, Percent (0 to 20)
Low Voltage Alarm Delay, Seconds, (1 to 300)
Equalize Timer Mode 4 (Auto Equalize on LV Alarm Recovery)
Delay, Seconds (1 to 300)
High Voltage Alarm Delay, Seconds, (1 to 300)
High Voltage Alarm Recovery Threshold, Percent (0 to 20)
High Voltage Shutdown Alarm Delay, Seconds, (1 to 300)
Low Current Alarm Delay, Seconds, (1 to 300)
End of Discharge Alarm Threshold, Volts, (0 to MAXAV)
End of Discharge Alarm Recovery Threshold, Percent (0 to 20)
Overload Alarm Threshold, Amps, (0 to MAXAI)
Overload Alarm Recovery Threshold, Percent (0 to 20)
AC Alarm Delay, Seconds, (1 to 300)
Ground Detection Alarm Delay, Seconds, (1-300) TPSD
ONLY. For A36D this point will always read 0 and writes to are
prohibited.
End of Discharge Alarm Delay, Seconds (1-300)
Overload Alarm Delay, Seconds (1-300)
Heartbeat
This register increases once per second and may be used to
determine if communications are still occurring.
Board Number. Will read 205 for 205T card.
Software Version, Version of software on 205T card.
Equalize Cycle Time Hours Remaining, Hours, Minutes
Note: The last two digits are the minutes.
Auto Equalize Timer, Days
Auto Equalize Timer, Hours, Minutes
Note: The last two digits are the minutes.
Low DC Current Alarm Low Limit, Amps. Setting the Low DC
Current Alarm below this will result in disabling the Low DC
Current Alarm Status Indicator.

SCADA INTERFACE INSTRUCTIONS - OPTION 21Q - FOR A36D/TPSD SYSTEMS/341S
Page 10 of 10
Local Temperature Probe Reading, Degrees C
Note: A shorted probe will give a reading of –273 and an open
probe will give a reading of+273
Temperature Probe Status
OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3
Maximum Settable Alarm Voltage, MAXAV, Volts
Maximum Settable Alarm Current, MAXAI, Amps
Over Temperature Probe Reading, Degrees C
Note: A shorted probe will give a reading of –273 and an open
probe will give a reading of+273
Over Temperature Probe Status
OK=0,SHORTED=1,OPEN=2,HARDWARE FAILURE=3
Charger Series. (0=TPSD,1=A36D)
Battery Voltage, Volts
Note: This point should only be monitored when DI 10015=1
NOT AVAILABLE= 30000, FAILED = 30001
Aux Temperature Probe #1, C
Note: NOT AVAILABLE=30000, SHORTED=30001,
OPEN=30002, FAILED=30003
Aux Temperature Probe #2, C
Note: NOT AVAILABLE=30000, SHORTED=30001,
OPEN=30002, FAILED=30003
Low Voltage Alarm Status (0=NO ALARM,1=LOW VOLTAGE
ALARM,2=LOW BATTERY VOLTAGE ALARM)
P60-407S Board Failure Alarm (0=N/A,1=NO ALARM,2ALARM)