CONTROL
OUTPUT CONFIGURATION
Outputs are congured with parameters OC1, OC2, OC3, OC4. Parameter OCx controls the operation of output OUTx: OCx=1…100 indicates the power in
percentage over the total power, of the compressor connected to OUTx. With OCx= -1, output OUTx is associated to a stage, which is active when the relay is
closed. With OCx= -2, output OUTx is associated to a stage, which is active when the relay is open. With OCx=0, output OUTx is not used for control.
Warning: the output associated to the compressor motor must always be wired in the terminals located before the terminals where the outputs controlling the
stages are. Example: in a system with two compressors of different power (the rst with 60% of total power, the second with 40%), each compressor having a
stage, the conguration of outputs is as follows: OC1 = 60, OUT1 is connected to the motor of compressor 1 of power equal to 60% of total power. OC2 = -1,
OUT2 is connected to the stage of compressor 1, the stage is active when the relay is closed. OC3 = 40, OUT3 is connected to the motor of compressor 2 of
power equal to 40% of total power. OC4 = -1, OUT4 is connected to the stage of compressor 2.
CONTROL ALGORITHM
Parameter CM provides the control algorithm.
CM ■ =ROT: rotation of outputs of equal power. This algorithm minimises the number of starts/stops per hour of each load. When the system calls for more power,
the output which has been off for longer will be activated. When demand for power decreases, the output which has been on for longer will be switched off. When
an output remains active for more than LRT minutes, the controller looks for an inactive output fullling the requirements to be activated (less hours of operation,
minimum off time elapsed,…) and the rotation of the two outputs will take place. In this way, an equal sharing of the total operation time among all loads will be
achieved (see Fig. 2). Note:the compressor rotation algorithm assumes that compressors have got an equal power. In this case, parameter OCx is used only to
dene if output OUTx either controls a compressor or a stage. So, if the value is positive, it will have no effect on OCx, regardless of what you program. Example:
in a system consisting of four compressors, each will have a power equal to 25% of the total value, regardless of the value programmed to OCx.
CM ■ =SEN: sequential activation of the enabled outputs. The outputs are switched on/off with xed sequence, from output 1 to output 4 (see Fig. 3).
CM ■ =PO: optimisation of the available power. The controller combines the outputs in such a way as to obtain a ne control, both in case of calls for more
power and less power. Example: OC1=10, OC2=20, OC3=30, OC4=50. If a capacity of 90 is required, outputs OUT1, OUT3, OUT4 (10+30+50) are switched
on. If a capacity of 50 is required, outputs OUT2 and OUT3 (20+30) are switched on (see Fig. 4).
CONFIGURATION PARAMETERS
To get access to the parameter conguration menu, press button ■
is released, the newly programmed value is stored and the following parameter is displayed;
to exit from the setup, press button ■ or wait for 30 seconds.
Note: re-programming some parameters causes a complete re-conguration of the controller operation. So please put the controller on stand-by, if you have
to modify the parameters relating to the output conguration or the selection of the control algorithm.
(In the parameter description, we refer to ‘pressure control’. In case of temperature based control, please replace the word ‘pressure’ with ‘temperature’ and
‘bar’ with ‘°C’).
PAR RANGE DESCRIPTION
INP 1-P, 2-T Input selection for control
1-P: input 1-P is used for pressure control; input 2-T is disabled.
2-T: input 2-T is used for temperature control; input 1-P is disabled.
INP=1-P
MPI 0MA, 4MA Min. current input range.
0MA: input 0…20mA; 4mA: input 4…20mA
RLO -1.0…RHI bar Min. scale range.
RLO takes the minimum value measured by the transmitter (corresponding to 0/4mA).
RHI RLO...45.0bar Max. scale range.
RHI takes the maximum value measured by the transmitter (corresponding to 20mA).
OS1 -12.0..12.0bar Probe offset
REF 404,507,22,134 Refrigerant used. It allows Pressure - Temperature conversion.
404=R404A, 507=R507, 22=R22, 134=R134A
SPL RLO…SPH Minimum limit for SP and 2SP setting
SPH SPL…RHI Maximum limit for SP and 2SP setting
SP SPL...SPH Main setpoint, indicates the pressure to be maintained.
2SP SPL...SPH Alternate Setpoint.
Pressure refence point is 2SP if DI1 (DI2) = 2SP and the corresponding input is active.
DBL -10.0...0.0bar Lower neutral zone.
The state of outputs remains unchanged as long as pressure is within the band SP+DBL
and SP+DBH.
DBH 0.0...10.0bar Higher neutral zone.
LON 0...250s Load start delay.
Pressure must remain higher than SP+DBH for LON seconds before the next load is switched on.
LOF 0...250s Load stop delay.
Pressure must remain lower than SP+DBL for LOF seconds before the next load is switched off.
SON 0...250s Stage start delay.
Pressure must remain higher than SP+DBH for SON seconds before the next stage is switched on.
SOF 0...250s Stage stop delay.
Pressure must remain lower than SP+DBL for SOF seconds before the next stage is switched off.
PB 0...20.0bar Proportional band (PWM output control, see Fig. 5).
Zone above setpoint in which the PWM output is activated proportionally.
Example: pressure < SP, PWM=0%; pressure=SP+PB/2, PWM=50%; pressure>SP+PB, PWM=100%.
IT 0...250s Integral action time (control of PWM output, see Fig. 5).
The greater the IT value, a more stable control takes place.
CM ROT,
SEN,
PO
Selection of control algorithm.
ROT: rotation of equal power outputs. SEN: sequential activation of outputs.
PO: optimisation of available power.
OC1,
OC2,
OC3,
OC4
-2...100 Control of output 1, 2, 3, 4.
1…100: power (percentage of total) of the load connected to output OUTx (x=1, 2, 3, 4);
0: output OUTx not used;
-1: output OUTx connected to a stage, which is activated when the contact is closed.
-2: output OUTx connected to a stage, which is activated when the contact is open.
MLS 0...30min Minimum off time of loads.
Minimum time which must elapse between when the load is switched off and when it’s switched on again.
LRT 0...120min Time of forced rotation of loads (only with CM=ROT).
This parameter, if greater than 0, provides the operation time of a load after which the controller takes into
account the possibility of rotation of two outputs.
DPU 0...120min Start delay.
Delay between the time when the controller is switched on when the outputs are activated, in order for the
compressor crankcases to warm up.
SCD 0...100 % Down Scaling.
It indicates the maximum per cent power usable during an alarm with enabled down scaling action.
ALA RLO...AHA Low value measured alarm threshold.
AHA ALA...RHI High value measured alarm threshold.
AID 0...120min High/Low alarm delay.
D1M
D2M
NON,
SBY,
2SP,
ALR
Function of digital input DI1, DI2.
NON: input disabled;
SBY: when input DI1 (DI2) is active, the controller is put on a stand-by.
2SP: when input DI1 (DI2) is active, the control setpoint is 2SP.
ALR: when input DI1 (DI2) is active, the controller detects a generic alarm which causes the display to show
ALR, to load to be switched off and control to be stopped. When the alarm is over, the controller resumes output
control automatically (automatic reset).
D1C
D2C
OPN,
CLS
Activation of digital input DI1, DI2.
OPN: active input is open;
CLS: active input is closed
DxM NON,HP, LP,
OIL, LL, ALR
Function of digital input DI3, DI4, DI5.
NON: input disabled. HP: high pressure alarm. LP: low pressure alarm. OIL: low compressor oil level. LL: low
refrigerant level alarm. ALR: generic alarm.
DxC OPN, CLS Activation of digital input DI3, DI4, DI5 (see D1C).
DxD 0...120min Activation delay of alarm DI3, DI4, DI5.
The digital input must remain in the activation condition for this time before the alarm is detected.
DxA DSP,
SAR,
SMR
Reaction following alarm DI3, DI4, DI5.
DSP: alarm display.
SAR: in addition to the alarm displayed, a down scaling (SCD) is activated and control is stopped. When the
alarm is over, the controller resumes output control automatically (automatic reset).
SMR: in addition to alarm displayed, all loads are switched off and control is stopped. When the alarm is over,
control is resumed but only after the alarm has been acknowledged by pressing button (manual reset).
MTC 0...600
(x100hours)
Maintenance.
When the operation hours of any load achieve this value, a maintenance warning will ash on display. To eliminate
this warning, after performing maintenance, rest the hour counters as described in paragraph “info menu”.
SB NO/YES Stand-by button enabling.
TLD 1...30min Delay for min / max input loggin.
SND NO/YES Alarm buzzer enabling
ADR 1...255 MS27 address for PC communication.
OPERATION EXAMPLES