Lae AT2-5 User Manual

AT2-5 INSTRUCTIONS FOR USE
Thank you for having chosen a LAE electronic product. Before installing the instrument, please read these instructions carefully to ensure maximum performance and safety.
DESCRIPTION INDICATIONS
Thermostat output
Auxiliary output
Activation of 2nd parameter set
Alarm
Fig.1 — Front panel
Info / Setpoint but ton. Increase / manual activation but ton.
Manual defrost / Decrease button. Exit / Stand-by button.
INSTALLATION
Inser t the controller through a hole measuring 71x29 mm. Make sure that electrical connec tions comply with the paragraph “wiring diagrams”. To reduce the effects of electromagnetic
disturbance, keep the sensor and signal cables well separate from the power wires.
Fix the controller to the panel by means of the suitable clips, by pressingly gently; if fi tted, check that the rubber gasket
adheres to the panel perfec tly, in order to prevent debris and moisture infi ltration to the back of the instrument.
Place the probe T1 inside the room in a point that truly represents the temperature of the stored produc t. Place the probe T2 on the evaporator where there is the maximum formation of fros t.
OPERATION
DISPLAY
During normal operation, the display shows either the temperature measured or one of the following indications :
DEF
Defrost in progress
HI
Room high temperature alarm
REC
Recovery after defrost
LO
Room low temperature alarm
OFF
Controller in stand-by
E1
Probe T1 failure
CL
Condenser clean warning
E2
Probe T2 failure
DO
Door open alarm
INFO MENU
The information available in this menu is :
T1
Instant probe 1 temperature
TLO
Minimum probe 1 temperature recorded
T2
Instant probe 2 temperature
CND
Compressor working weeks
THI
Maximum probe 1 temperature recorded
LOC
Keypad state lock
Access to menu and information displayed.
Press and immediately release but ton . With button
!
or !select the data to be displayed. Press button !to display value. To exit from the menu, press button
X
!
or wait for 10 seconds .
Reset of THI, TLO, CND recordings
With button !or !select the data to be reset. Display the value with but ton . While keeping button
!
pressed, use button
X
!
.
SETPOINT (display and modifi cation of desired temperature value )
Press button !for at least half second, to display the setpoint value. By keeping button !pressed, use button !or !to set the desired value (adjustment is within the minimum SPL and the
maximum SPH limit).
When button !is released, the new value is stored.
STAND-BY
Button , when pressed for 3 seconds, allows the controller to be put on a standby or output control to be resumed (with
SB=YES only).
KEYPAD LOCK
The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controllers is operating in a public place. In the INFO menu, set parameter LOC =YES to inhibit all functions of the buttons. To resume normal operation of keypad, adjust setting so that LOC =NO.
SELECTION OF SECOND PARAMETER GROUP
It’s possible to select control parameters between two dif ferent pre-programmed groups, in order for the fundamental control parameters to be adapted quickly to changing needs. With IISM=MAN, changeover from Group I to Group II takes place manually by pressing button
!
for 2 seconds. The activation of Group II is signalled by the lighting up of the relevant LED on
the controller display. If IISM=NON, switchover to group II is inhibited.
DEFROST Timed defrost. Defrosting star ts automatically when necessary time has elapsed to obtain the defrosting frequency set with DFR (IIDF). For example, with DFR=4 defrosting oc curs once every 6 hours. The internal timer is set to zero when power is
applied to the controller and at each subsequent defrost start. When the controller is put on a standby, the a ccumulated time count is “frozen” (is not incremented ).
Manual defrost. Defrosting may also be induced manually by keeping the button
!
pressed for 2 seconds.
Defrost type. Once defrost has star ted, Compressor and Defrost outputs are controlled according to the parameter s DTY and OAU. The AUX output is associated to defrost function with OAU=DEF exclusively. If FID=Y ES the evaporator fans are active all through defrost.
Defrost termination. Defrost lasts as long as time DTO but, if the evaporator probe has been enabled (T2=YES) and temperature DLI is achieved before this time elapses, defrost will be terminated in advance.
Resuming thermostatic cycle. When defrost is over, if DRN is greater than 0, all outputs will remain of f for DRN minutes,
in order for the ice to melt completely and the resulting water to drain. Moreover, if probe T2 is active (T2=YES), the fans will re-start when the evaporator gets to a temperature lower than FDD; Vice versa, if such condition does not occur after 4 minutes following defros t termination, the fans will be switched on anyway.
Caution: if C-H= HEA all defrost functions are inhibited; if DFR= 0 the timed defrost function is excluded; during defrost, the high temperature alarm is inhibited.
CONFIGURATION PARAMETERS
The setup menu is accessed by pressing button X+!for 5 seconds. With button !or !select the parameter to be modifi ed. Press button !to display the value. By keeping button !pressed, use button !or ! to set the desired value. When button !is released, the newly programmed value is stored and the following parameter is displayed. To exit from the setup, pres s but ton
X
!
or wait for 30 seconds.
PAR
RANGE DESCRIPTION
SCL
1°C; 2°C;
°F
Readout scale. 1°C (only wit h INP=SN4 ): measuring r ange - 50/ -9 .9 … 19 .9/80 °C 2°C : measuring r ange - 50 … 120°C °F : measuring range -5 5 … 240° F
Caut ion: upon changing the SCL value, it is then absolutely necessary t o reconfigure t he parameters relevant to t he absolute and relative temperatures ( SPL, SPH, SP, AL A, AHA, etc .. )
SPL
-50..SPH Minimum limit for SP setting
SPH
SPL .120 ° Maximum limit for SP sett ing
SP
SPL ... SPH Setpoint (value t o be maintained in the room ).
C-H
REF ; HEA Refrigerating (R EF ) or Heating (HE A) cont rol mode
HYS
1...10 ° OFF /ON thermostat differen tial
OFF
ON
SP SP+HY
T[°]
OFF
ON
SPSP-HY
T[°]
Refrigerating control ( C-H= REF ) Heating cont rol ( C-H=HEA)
CRT
0.. .30min Compressor rest time . The output is s witched on again af ter CRT minu tes have elapsed since the previous swi tchover. We recommend to set CRT= 03 with HYS<2.0°.
CT1
0.. .30min Ther mostat output run when probe T1 is faul ty. With CT1= 0 the output w ill always remain OFF.
CT2
0.. .30min Ther mostat output s top when probe T1 is fault y. Wi th CT2=0 and CT1>0 t he outpu t wil l always be ON. Example : CT1=4, CT2= 6 : In case of probe T1 failure, t he compressor will cycle 4 minutes ON and 6 minutes OFF.
CSD
0.. 30min Compr essor st op delay af ter t he door has been opened (ac tive only if DS=YES).
DFR
0.. . 24(1/2 4h ) Defro st f requency expressed in cycles /24 hour s.
DLI
-50...120° Defrost end temperature.
DTO
1...12 0min Max imum defrost duration.
DTY
OFF; ELE; GAS
Defrost ty pe OFF : off cycle defros t (Compressor and Heater OFF) . ELE: electric de frost * (Compressor OF F and Heater ON) . GAS: ho t gas defrost * (Compressor and Heater ON). * The de frost output is acti ve if only OAU =DEF.
DRN
0.. .30min Pause aft er defros t (evaporator drain down t ime).
DDY
0.. .60min Display during defros t. If DDY=0 during def ros t the temperature cont inues to be displayed. If DDY > 0, during defrost the display show s DEF, and at the end of defros t it shows R EC for DDY minut es.
FID
NO/ YES Fans ac tive during def rost.
FDD
-50...120° Evaporator fan re -star t tempera ture af ter defrost.
FTC
NO/ YES Optimised fan cont rol enabling. W ith FTC = NO the fans remain on all the time
ON
OFF
FT3FT3 FT2FT2FT1
CMP ON CMP OFF CMP ON
Fig. 2 Opt imised fan cont rol (FTC=YES)
FT1
0.. .180 sec Fan stop delay af ter compressor s top. See F ig. 2 .
FT2
0.. .30min Timed fan s top. With FT2= 0 the fans remain on all the time.
FT3
0.. .30min Timed fan run. W ith FT3= 0, and FT2 > 0, the fans remain off all the time.
ATM
NON; ABS;
REL
Alar m threshold management . NON : all temperature alar ms are inhibited (the follow ing parameter will be ADO). ABS : the values programmed in ALA and AHA represent the real alarm t hresholds. REL : the values programmed in ALR and AHR are alarm differen tials referred to SP and SP+HY.
OFF
ON
-
T[°]
OFF
ON
-
-
T[°]
Tempera ture alarm with relative thresholds, Temperat ure alarm wi th relative t hresholds, refrigerat ing control (ATM =REL, C-H = REF) . heating control ( ATM= REL, C-H=HEA).
ALA
-50... 12 0° Low tempera ture alarm t hreshold .
AHA
-50... 12 0° High temperature alarm threshold.
ALR
-12.. . 0° Low temperature alarm dif ferential. W ith ALR= 0 the low temperature alar m is excluded.
AHR
0.. . 12° High temperature alarm differen tial. Wi th AHR=0 t he high temperat ure alarm is excluded.
ATD
0.. . 120min Delay bef ore alarm temperature warning.
ADO
0.. . 30min Delay before door open alarm war ning .
ACC
0...52
weeks
Condenser periodic cleaning. When the compressor operation time, expressed in weeks, matches the ACC value programmed, “CL” flashe s in the display. With ACC= 0 the condenser cleaning warning is disabled.
IISM
NON;
MAN;
Swi tchover mode to second parameter set NON : inhibition to use the second paramet er group (the follo wing parameter wil l be SB).
MAN: but ton
M
swi tches the t wo paramet er groups over.
IISL
-50...IISH
Minimum limit f or IISP setting.
IISH
IISL...120°C
Maximum limit for IISP sett ing.
IISP
IISL ... IISH
Setpoin t in mode 2
IIHY
1...10°
OFF /ON dif ferent ial in mode 2.
IIFT
NO/YES
Optimised fan cont rol enabling in mode 2.
IIDF
0...99hours
Defrost timer set to star t a defrost in mode 2.
SB
NO/YES
Stand-by butt on enabling
.
DS
NO/ YES Door switch input enabling (closed when door is closed) .
LSM
NON; MAN;
DOR
Light con trol mode NON : light ou tput not controlled.
MAN : ligh t oupu t controlled through butt on
M
!
(if OAU=LGT).
DOR : light ouput s witched on when door is opened (if OAU=LGT).
OAU
NON;
0-1; DEF; LGT; AL0;
AL1
AUX output operation. NON : ou tpu t disabled ( always off ). 0-1 : the relay cont acts foll ow the on /standby state of con troller. DEF : output programmed f or defrost contr ol. LGT : output enabled for light control. AL 0 : contact s open w hen an alarm condition occurs. AL1 : contacts make when an alarm condit ion occurs.
INP
SN4 ; ST1 Temperat ure sensor selec tion. Wi th I NP = SN4, the probes must be the L AE models SN4 ..; wit h INP = ST1, the probes
must be the L AE models ST 1...
OS1
-12.5..12 .5°C Probe T 1 offse t.
T2
NO/ YES Probe T2 enabling (evaporator) .
OS2
-12.5..12 .5°C Probe T 2 offset.
TLD
1...30 min Delay for minimum temperature ( TLO) and maximum temperature (THI) logging.
SIM
0...100 Display slowdown.
ADR
1...255 AT2-5 address for PC communication.
WIRING DIAGRAM
TECHNICAL DATA
Power supply
AT2-5…E 23 0Vac±10 %, 50 /60 Hz, 3W AT2-5…U 115Vac ±10%, 5 0/60 Hz, 3W AT2-5…D 12Vac /dc±10 %, 3W
Relay outputs
AT2-5.Q… Compressor 12( 5)A 240vac AT2-5.S… Compressor 16 (5) A 240vac Evaporat or fans 7 (2)A 24 0vac Aux iliary loads 7(2 )A 2 40vac
AT2-5.Q… maximum to tal current 12 A AT2-5.S… maximum total curren t 16A
Inputs
NTC 10K 1@ 25°C, L AE part No . SN4... PTC 1000 1@2 5°C, L AE part No. ST1…
Measurement Range
-50…120 °C, -55…24 0°F
-50 / -9.9 … 19.9 / 8 0°C (N TC10K onl y)
Measurement accuracy
<0 .5°C wi thin the measurement range
Operating conditions
-10 … + 50 °C; 15% ... 80% r.H.
CE – UL (Approvals and Reference Norms)
EN6 0730-1; E N607 30-2- 9; EN5 5022 (Class B ); EN50082-1 UL 607 30 -1A
Front protection
IP55
VIA PADOVA, 25 31046 ODERZO /TV /ITALY TEL. +39 - 0422 815320 FAX +39 - 0422 814073 www.lae-electronic.com E-mail: sales@lae-electronic.com
PARTNER VENEZIA • 041 5460713
16(5)A
TTL
T1ComT2
7(2)A 7(2)A
AUX
34512
78 91110
Door
Switch
AT2-5BS4E-AG