Labkotec LOKASET R D18067Be Installation And Operation Instructions Manual

LOKASET R
WIRELESS TANK FULL ALARM
Installation and Operation Instructions
D18067Be
Contents
1. Introduction 3
3. Installation 5
4. Operating Mode 7
5. Service and Repairs 8
6. Alarms 9
7. Technical Speci cations 10
LOKASET R | Installation and Operation Instructions | D18067Be2
1. Lokaset R – Introduction
Lokaset R is designed for use as a high level alarm in liquid tanks. It can be used for instance to indicate that a closed septic tank or pumping station is full. Lokaset R is equipped with visual and acoustic alarm indicators as well as an alarm relay.
The Lokaset R device consists of a central unit (1), transmitter (2) and a probe (3). The central unit is used for controlling and moni­toring device operation. The enclosed transmitter transmits the alarm signal wirelessly from the probe to the central unit. Lokaset R can be installed in new and existing tanks without excavation works.
Similarly to many Labkotec products, also Lokaset R can be con­nected to the versatile and easy-to-use LabkoNet system enab­ling automated tank emptying.
Keep these Operating Instructions near the central unit. To view these Operating Instructions in electronic form, please visit www.labkotec. .
Thank you for choosing reliable Labkotec technology.
1
2
3
3LOKASET R | Installation and Operation Instructions | D18067Be
2. Lokaset R – Operation
1
45
23
Lokaset R is designed for use as a tank full alarm for septic tanks.
The principle of operation is that when the probe comes into contact with liquid, the transmitter transmits a signal to the Lokaset R central unit. The signal is sent every 10 minutes or alternatively every 30 se­conds and the alarm is activated by two consecutive notes from the probe. The relay will de-energize in case of an alarm.
The central unit (1) signals the alarm with a buzzer sound and an alarm indicator light (2). The buzzer is silenced by the alarm reset button (3). The alarm mode can be deactivated by emptying the tank. The probe should be installed in the tank at the height of the liquid alarm level.
The central unit is plugged to the mains (230 V). When the power is connected, the green power light (4) and the radio signal indicator (5) are on. The transmitter is battery-powered. The battery is supplied with the device. In normal use, the maximum battery life is 10 years or around 2 years when the 30-second interval is in use. The central unit signals an alarm when the transmitter is not powered or the battery needs to be replaced.
The Lokaset R probe (SET/LV) is not suitable for measuring explosive or corrosive liquids.
LOKASET R | Installation and Operation Instructions | D18067Be4
3. Lokaset R – Installation
The Lokaset R central unit (Figure 1) is installed in a dry indoor location. A good installation location enables easy reading and control of the device. Do not cover the central unit as this may interfere with signal reception from the transmitter. The Lokaset R central unit is mounted on a wall with screws through the ho­les at the bottom of the device. The lid of the housing must be opened for installation. The device is plugged to the 230 V mains via the power cord.
Operation of the probe and the transmitter should be tested du­ring installation in order to ensure that the radio signal can travel freely. Activate the transmitter test mode (see Service instruc­tions, p. 8). Immerse the measuring head momentarily in water. If the central unit is operational, the blue light (SIGNAL) should turn o every 8 seconds and the alarm should be signalled within 8 seconds.
Installation of the Lokaset R transmitter is illustrated on the adja­cent page. The transmitter is installed on the cover (1) of the tank’s outlet pipe using the provided plate screws (2); 4 pcs, 2.9–3 x 25 mm.
Place the rubber gasket (3) between the transmitter and the co-
Kuva 1.
ver. The cover of the transmitter must be opened for installation. Make a lead-through for the cable (4) or for the entire probe in the cover of the outlet pipe.
Connect the probe cable conductors to the screw terminals (5) on the transmitter circuit board. The polarity of the cable connec­tion has no signi cance to device operation. Tighten the probe cable gland (6). Install a cable tie above the cable gland as a cable clamp. Place the supplied battery CR123A in the battery compart­ment (7) with the positive pole (+) facing upward. Correct installa­tion of the probe cable and battery is illustrated on page 8.
5LOKASET R | Installation and Operation Instructions | D18067Be
With the help of a jumper on the transmitter’s circuit card you can
9
10
6
5
choose how often the signal is sent from the transmitter to the central unit. When the jumper is in place, the signal is sent every 30 seconds and when it is not in place or only connected to one terminal block, the signal is sent every 10 minutes. In case the jumper’s operation mode has been changed, the transmitter and the central unit have to be paired again (see paragraph 5: service and repairs). The jumper’s place is shown in picture on page 8.
8
7
2
4 3
1
11
LOKASET R | Installation and Operation Instructions | D18067Be6
Ensure that the tightening O-ring (8), Ø 69.5 x 3.0 mm NBR70, is seated properly in the groove. Close the protective cover (9) with the supplied stainless steel screws (10); 2 pcs, 3 x 16 mm.
Note! Proper seating of the O-ring and tightness of the cable gland are important in ensuring the tightness of the transmitter enclosure. If the cover cannot be properly secured, ensure that the O-ring is installed correctly.
The Lokaset R transmitter is supplied with a 3 metre cable. The height of the probe may be adjusted using the provided cable tie. Make a loop in the probe cable. Secure the loop with the cable tie (11). This facilitates height adjustment of the probe. Do not leave the probe in the tank during vacuum disposal. Do not secure the probe cable to tank walls.
4. Lokaset R - Operating Mode
The Lokaset R central unit has three indicator lights and one but­ton. The green light (POWER) is the power indicator, the blue light (SIGNAL) the wireless transmission indicator and the red light (ALARM) the alarm indicator. The button is used for resetting the buzzer alarm.
The Lokaset R transmitter transmits a signal to the central unit every 10 minutes or every 30 seconds. The central unit interprets whether the probe is in the air (normal mode), in water or dama­ged (alarm mode). When the unit signals a tank full alarm, the red light is on. If there is a malfunction, the red light  ashes. In case of an alarm or fault, the relay is de-energized (closing poles 1 and 2).
1. GREEN 2. BLUE 3. RED
Normal operation mode
Alarm > Buzzer signal > Tank full
Malfunction > Probe failure
Malfunction > Communication failure
Central unit cannot recognise transmitter
No power
Reset the buz zer > Arrange disposal
Check probe connection
Check transmitter operation
Pair devices > p. 9
Connect the device to the mains
1
2
3
On
Flashes
O
7LOKASET R | Installation and Operation Instructions | D18067Be
5. Lokaset R - Maintenance and Repairs
The best way to maintain proper operation of the Lokaset R device is to ensure that the probe is clean and that the radio communication between the transmitter and the central unit is unobstructed. All barriers, such as leaves, debris, snow, ice or ve­hicles may interfere with the reception of the radio signal. If the battery ceases to discharge power, the central unit will signal an alarm. The easiest way to clean the Lokaset R probe is during tank emptying. The probe may be cleaned using running water.
Operation of the Lokaset R device can be checked in conjunction with maintenance by activating the transmitter test mode. Ac­tivate the test mode by pushing the function button (1) on the transmitter. When the test mode is activated, the blue indicator (SIGNAL) of the central unit  ashes every 8 seconds during test transmission. The device returns to the normal operating mode after running the test mode for 5 minutes.
The Lokaset R central unit does not include serviceable parts. In the event of damage, please contact the supplier. The power cord of the central unit may only be replaced by the device manufac­turer or an authorised service organization.
2
1
LOKASET R | Installation and Operation Instructions | D18067Be8
Pairing the central unit and the transmitter:
The Lokaset R central unit and transmitter form a device pair. Any subsequent spare part deliveries require re-pairing.
Pair the devices by simultaneously pressing the alarm reset but­ton and powering the central unit. All lights on the central unit will  ash, indicating that the devices are being paired.
Press the function button (p. 8) on the Lokaset R transmitter. The green light (POWER) and red light (ALARM) are on and the blue light (SIGNAL)  ashes. Complete the process by pressing the central unit reset button again. The blue light (SIGNAL) remains on and  ashes every 8 seconds to indicate the test mode. The Lokaset R central unit and transmitter are now paired. The device returns to the normal operating mode after 5 minutes.
6. Lokaset R – Alarms
Tan k f ull al arm: Red light (1) is on (continuous buzzer sound)
a) Reset the alarm (2) b) Arrange tank disposal
2
1
9LOKASET R | Installation and Operation Instructions | D18067Be
7. Lokaset R - Technical Speci cations
Central Unit
Typ e/m ode l
Manufacturer
Supply voltage
Operation method
Relay output
Dimensions: hxwxd
Installation and
operation class
Operation
Approvals
LOKASET R | Installation and Operation Instructions | D18067Be10
Lokaset R Receiver
Labkotec Oy, Myllyhaantie 6,
33960 Pirkkala, Finland
230 VAC, 50/60 Hz, 1 VA
Wireless receiver, 433 MHz
De-energised on alarm, potential-free
switching contacts (μ). Max. connection
values: 250 V / 4 A / 100 VA
35 x 130 x 80 mm
Class II, Indoor use only
Green, blue and red indicator light, buzzer
R&TTE approval,
CE Marking
Tra nsmi tte r
Typ e/m ode l
Manufacturer
Supply voltage
Operation method
Operating radius
Dimensions: h x Ø
Installation and
operation class
Protection class
Approvals
Probe
Typ e/m ode l
Operation method
Lokaset R Transmitter
Labkotec Oy, Myllyhaantie 6,
33960 Pirkkala, Finland
3 V battery, CR 123A
Wireless transmitter, 433 MHz
150 m, max. transmission range 650 m
75 x 95 mm
Class III, indoor and outdoor use,
ambient temperature -30 … +60°C
IP 67
R&TTE approval,
CE Marking
SET/LV
Conductivity-operated
11LOKASET R | Installation and Operation Instructions | D18067Be
Labkotec Oy
Myllyhaantie 6 33960 Pirkkala, Finland
Tel. +358 29 006260 (exchange) Fax +358 29 0061260
info@labkotec. www.labkotec.
We reserve the right to changes. © 2009 Labkotec Oy