Type A2, 12-inch Sash Biosafety Cabinet Models
30242 30252 30262
PuriCare Procedure Stations
12-inch Sash Procedure Station Models
31242 31252 31262
Page 2
2
Labconco Training Programs:
In order to assist technicians gain a better understanding of our products,
Labconco Corporation offers Training Seminars at our Kansas City Facility on a
regular basis. For further details about these training programs, contact
Labconco's Product Service Department at 800-821-5525, or (816) 333-8811
from 7:30 a.m. to 5:30 p.m. C.S.T.
Additional Copies:
Additional copies of this document can be downloaded from Labconco’s website
at www.labconco.com. Electronic copies are available to members of the service
community free of charge. Please request electronic copies by contacting our
Product Service Department.
All Rights reserved. No part of this document may be translated or reproduced in
any form without written permission from Labconco Corporation, 8811 Prospect,
Kansas City, Missouri, 64132, U.S.A.
While the advice and information offered in this document are believed to be
true and accurate at the date of going to press, neither the author, nor Labconco
Corporation can accept any legal responsibly for any errors or omissions that
may be made.
P/N 3849912
Rev. F, ECO L560
Product Service 1-800-522-7658
Page 3
3
Table of Contents
Introduction 7
Contacting Labconco 7
Section One – Background Information
QuickStarts 9
What’s the password for the Cabinet? 10
How do I calibrate blower speed, filter life & airflow sensor? 11-12
How do I see the current settings? 13
How do I change the configuration? 14-15
How do I run a diagnostic on the: Sash position switches? 16
Keypad, relays and contact? 17
Inlet Relief Valve? 18
Airflow Sensor? 19
How do I set up automatic operation of the blower & lights? 20
Cabinet Filter Life Gauge Operation and Resetting for Local Conditions 21
QuickCharts
12-Inch Sash Type A2 BSCs 22-24
Identifying Cabinet Models 25
Serial Number Tags 26
Model Numbering System 27
Cabinet Data Plate 28
Final Inspection and Test Report 29
Theory of Operation Background 30
Airflow Patterns and Features 30
ECM Motor 30-31
Electronics 32-33
Section Two – Installation Requirements
Prerequisites 35
Space Requirements 35
Clearance 35
Location Requirements 36
If You Intend to Connect the Cabinet to an Exhaust System 37
Electrical Requirements 38
Service Line Requirements 39
Product Service 1-800-522-7658
Page 4
4
Section Three – Installation 41
Unpacking the Biosafety Cabinet 42
Preparing the Biosafety Cabinet for operation 42
Moving and Lifting the Cabinet 43
Installing the Biosafety Cabinet on an Existing Work Surface 43
Installing the Cabinet on a Labconco Base Stand 44
Telescoping Base Stands 44
Manual or Electric Lift Base Stands 44
SoLo Electric Hydraulic Lift Base Stands 45
Connecting the Biosafety Cabinet to Utility Service Lines 46
Optional Ventus Canopy Exhaust Connection 47
Optional Vacu-Pass Cord and Cable Portal 48
Drain Valve Installation (optional) 49
Section Four – Initial Operation of the Cabinet
System Reset Switch 51
Information Center 52
Alarm Screens 53
Operating the Sliding Sash 54
Starting the Biosafety Cabinet 54
The Cabinet Touchpad 55
Navigating the Cabinet Menu Screens 56
Navigating the MyLogic Menu Screens 57-59
Setting the Clock 57
Configuring the Cabinet 58-59
Navigating the Settings Menu Screens 59-61
Display Options
Units of Measure 59
Startup Tone 60
Security Lock 60
RS-232 Output 60
UV Settings
UV Lamp Hour meter 61
Reset UV Lamp Hour Meter 61
Change UV Lamp Life 61
Timer Operation Interval Timer Operation 62
Stopwatch Timer Operation 62
If An Airflow Alert Activates 62
Resetting the Airflow Alert System 62
Product Service 1-800-522-7658
Page 5
5
Section Five – Certification Procedures for the Cabinet
Accessing the Certifier’s Menu63
Adjusting the Inflow, Downflow and Filter Life Gauges 63-64
Cabinet Filter Life Gauge Operation and Resetting for Local Conditions 65
HEPA Filter Leak Test Information HEPA Filter Leak Test 66
If the Cabinet is contaminated 66
HEPA Filter Leak Test Specifications 66
If the Cabinet is uncontaminated 67-69
Exhaust HEPA Filter Leak Test 70-71
Downflow Velocities 72-73
Inflow Velocity Calculation Primary Inflow Method 74
Secondary Inflow Method 75-77
Work Area Air Cleanliness Test (optional) 78
Fluorescent Light Level (optional) 79
Noise Level (optional) 79
Vibration (optional) 80
UV intensity (optional) 80
Ground Fault Circuit Interrupter 81
Section Six – Cabinet Service Operations
Recommended Tools for Service 83
External Dress Components Front Dress Panel Removal and Installation 83-84
Side Panel Removal 84
Side Panel Installation 84
Corner Post Lower Trim 85
Sash Operation/Adjustment 86
Sash Position Switches Sash Closure Position Switch 87-88
Sash Operating Position Opening Switch 87-88
Sash Cable Retainer 89
HEPA Filter Replacement 89-92
Supply Motor/Blower Replacement 92-94
Exhaust Motor/Blower Replacement 94-95
Work Surface Removal 96
Grille Removal 96
Towel Catch Removal 97
Diffuser Removal 98-99
Preparing the Logic for Gaseous Sterilization 100
Product Service 1-800-522-7658
Page 6
6
Section Seven –Electrical System Service Operations
Fluorescent Lamp Lamp Identification 101
Changing the Fluorescent Lamp 101
Troubleshooting 141-43
Purifier Logic Replacement Parts 145
Dimensions 146
Product Service 1-800-522-7658
Page 7
7
INTRODUCTION
This text is designed for you, the Biohazard Cabinet Certifier. Based on your
suggestions, comments, and ideas, Labconco has compiled this information
for you to use in the certification or servicing of our Purifier Cabinet
Biosafety Cabinets.
When you use this document in your office or in the field, we would
appreciate your input so that we can make further improvements to future
editions.
As always, we at Labconco want to assist you in having a better
understanding of our products and their operation; if you have any questions,
or need additional information, please contact us.
Thanks again for all your support in the past, and in the future.
Labconco
CONTACTING LABCONCO
Labconco’s Address is:
LABCONCO Corporation
8811 Prospect
Kansas City, MO 64132
Our hours of operation are from 07:30 - 17:30 CST, Monday through Friday,
except national holidays
We can be reached at the following numbers:
(800) 821-5525
(816) 333-8811
Our Fax numbers are:
(816) 444-5343
(816) 363-0130
Should you require Technical Assistance, Service Parts, or have general questions
regarding the Purifiers, please direct them to our Product Service Department, so
that your call can be properly routed and answered.
Product Service 1-800-522-7658
Page 8
8
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
Page 9
9
SECTION ONE –
Background Information
Quickstart
While many internal components are the same or similar to our Logic+-platform
products, its operation and certification are different. The
you show you how to answer the questions asked in each case. Keystrokes are shown in
bold blue italics
, while screen selections are shown in
Quickstarts
green italics
that follow will help
.
Product Service 1-800-522-7658
Page 10
10
Quickstart
What’s the password for the Cabinet?
Like the Logic, and Logic+ models, these BSCs use password protection to prevent the
user from entering the
airflow sensor readings. New to the Cabinet is a
Configuration
connection status and whether it has a UV light; there is more on this in the Quickstart
“How do I change the BSC configuration?”
The password for all protected screens is:
1. Light
2. UV Light
3. Timer
4. Timer
5. OK/Mute
; entering this option allows you to configure the Cabinet’s canopy
Calibration
menu to adjust the blower speed, filter gauge or the
Service
menu selection entitled
Product Service 1-800-522-7658
Page 11
11
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics
Configuration
Calibration
Service
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Calibration
OK to proceed, MENU to return
PASSWORD:
Calibration
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Supply Fan Speed
or to change motor speed,
OK to select, MENU to escape
How do I recalibrate the
blower speed
filter life gauge
airflow sensor reading
of the Cabinet?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. You will see a
alter the BSC’s settings.
7. Press
8. When requested for the password press
Timer, Timer
9. If the password is properly entered, the first certification screen
will display the supply blower motor’s PWM setting. Press the ▲
or ▼ button to increase or decrease the blower speed as
needed. When the speed is set properly, press the
button to lock the new blower speed setting, and continue to the
filter life screen.
Menu
OK/Mute
OK/Mute
warning screen
OK/Mute
then
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Calibration
option is highlighted (it
to start the calibration procedure.
alerting you that you are about to
to input the password.
Light, UV light
OK/Mute
.
OK/Mute
,
Product Service 1-800-522-7658
Page 12
12
Quickstart
The Inflow displayed
value is: 102 FPM
Calibration
Inflow Display
or to chang e display value,
UV Light to res et to 105 FPM,
OK to select, ME NU to finish
Calibration
Supply Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
Leave Gauge unchanged
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Exhaust Fan Speed
or to change motor speed,
OK to select, MENU to escape
Calibration
Exhaust Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
10. If this is an initial certification or a recertification after supply
HEPA filter replacement, select
this is an annual recertification, select
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
11. The next certification screen will display the exhaust blower
motor’s PWM setting. Press the ▲ or ▼ button to increase or
decrease the blower speed as needed. When the speed is set
properly, press the
OK/Mute
speed setting, and continue to the filter life screen.
12. If this is an initial certification or a recertification after exhaust
HEPA filter replacement, select
this is an annual recertification, select
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
13. If the unit is has no airflow sensor, after the filter gauge option
is selected and you press
down, and then restart with the new settings. If the Unit has an
airflow sensor, you will then be asked to calibrate the inflow
sensor to match the value you obtained when you measured the
inflow. After the inflow is calibrated, and you press
the Cabinet will power down, and then restart with the new
settings.
Reset Filter Gauge to 100%
Leave Gauge unchanged
OK/Mute
.
button to lock the new blower
Reset Filter Gauge to 100%
Leave Gauge unchanged
OK/Mute
OK/Mute
, the Cabinet will power
.
. If
Set
. If
Set
OK/Mute
.
.
,
Product Service 1-800-522-7658
Page 13
13
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choo se,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics
Calibration
Configuration
Service
Current Settings
Supply System
or to change, OK to return
The ECM setting is: 65
The current RPM is: 0
The average RPM is: 0
The new filter RPM is: 1450
C1, with afs, with UV
10484 -
Current Settings
Exhaust System
or to change, OK to return
The ECM setting is: 65
The current RPM is: 0
The average RPM is: 0
The new filter RPM is: 1450
C1, with afs, with UV
10484 -
How do I see the Current Settings of the Cabinet?
1. Press the
2. Press the ▼ button until the
turn yellow). Press
screen.
3. Press the ▼ button until the
highlighted (it will turn white). Press
configuration.
4. The first screen shows the current settings of the supply blower
system.
5. By pressing the ▲ or ▼ button, you can see the current
settings of the exhaust blower system. If you are recertifying the
unit, you may want to record the data on this screen. The
firmware revision is shown in the bottom right corner as a -, or
as a letter.
Menu
button.
OK/Mute
Services
option is highlighted (it will
to enter the Services menu
Current Settings
OK/Mute
option is
to see the
Product Service 1-800-522-7658
Page 14
14
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choo se,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics
Calibration
Configuration
Service
Configuration
PASSWORD:
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Configuration
OK to proceed, MENU to return
How do I change the Configuration of the Cabinet?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
(it will turn white).
5. Press
6. You will see a
alter the BSC’s settings.
7. Press
8. When requested for the password press
Timer, Timer
Menu
OK/Mute
OK/Mute
warning screen
OK/Mute
then
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Configuration
option is highlighted
to alter the configuration.
alerting you that you are about to
to input the password.
Light, UV light
OK/Mute
.
,
Product Service 1-800-522-7658
Page 15
15
Quickstart
This Logic has:
or to choose,
OK to select, MENU to escape
a UV light
NO UV light
UV Settings
Configuration
Type A Canopy Option
This cabinet has:
or t o choose,
OK to select, M ENU to escape
a canopy
no canopy
How do I change the Configuration of the Cabinet? – continued
1. This screen allows you to configure the cabinet for a canopy or
not.
2. This screen configures the unit for a UV light or not. After your
selection is chosen, and you press OK/Mute, the unit will shut off
and then reset in the new configuration.
3. If the unit is configured to NOT have a UV light, and the user
presses the UV Light button, they will get this message.
Product Service 1-800-522-7658
Page 16
16
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choo se,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration
Configuration
Diagnostics
Service
How do I run a diagnostic on the sash position switches?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
highlighted (it will turn white). Press
7. Lower the sash, and note the status line – it should properly
report the sash as open too high, open or closed when the sash
is in the corresponding position. Press
diagnostic.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Sash sensors
OK/Mute
OK/Mute
.
to exit the
option is
Product Service 1-800-522-7658
Page 17
17
Quickstart
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choo se,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration
Configuration
Diagnostics
Service
How do I run a diagnostic on the keypad, relays and contacts?
How do I run a diagnostic on the (canopy) Inlet Relief Valve?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
is highlighted (it will turn white). Press
7. The display shows the status of the Inlet Relief Valve. During
normal operation, it will be open, and during an exhaust alarm,
it will be closed. NOTE: The inlet relief valve function is
OPPOSITE OF THE MAGNETIC SWITCH FUNCTION! – WHEN
THE INLET VALVE IS OPEN, THE MAGNETIC SWITCH IS
CLOSED.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Inlet Relief Valve
OK/Mute
.
Product Service 1-800-522-7658
option
Page 19
19
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choo se,
OK to select, ME NU to return
Current Settings
Restore Default
Calibration
Configuration
Diagnostics
Service
Quickstart
How do I run a diagnostic on the Airflow Sensor?
1. Press the
2. Press the ▼ button until the
turn yellow).
3. Press
4. Press the ▼ button until the
will turn white).
5. Press
6. Press the ▼ button until the Diagnostic
highlighted (it will turn white). Press
7. The display shows the status of the airflow sensor. Its current
output, alarm setting and zero point in Millivolts, along with the
corrected Inflow velocity currently being displayed.
Menu
OK/Mute
OK/Mute
button.
Services
option is highlighted (it will
to enter the Services menu screen.
Diagnostic
option is highlighted (it
to enter the Diagnostic submenu.
Airflow Sensor
OK/Mute
.
Product Service 1-800-522-7658
option is
Page 20
20
Quickstart
How do I set up automatic operation of the blower and lights?
1. Press the
2. Press the ▼ button until the
turn blue).
3. Press
4. Press the ▼ button until the option
option is highlighted (it will turn white).
5. Press the ▼ button to select either Smart-Start or manual
operation of the cabinet blower. (In Smart-Start, the cabinet
blower will automatically start every time the sash is opened.
6. Press the ▼ button to select either Smart-Start or manual
operation of the fluorescent lights.
7. Press the ▼ button to select either Night-Smart or manual
operation of the cabinet blower. (In Night-Smart, the cabinet
blower will automatically operate at idle every time the sash is
closed.
8. Press the ▼ button to select either Night-Smart or manual
operation of the UV Light.*
9. Press the ▼ button to select the time interval the UV light will
operate for until it automatically shuts off.*
* - These screens will only appear if the unit is configured for a UV light.
Menu
OK/Mute
button.
MyLogic
to enter the MyLogic menu screen.
option is highlighted it will
configure my Logic for use
Product Service 1-800-522-7658
Page 21
21
Cabinet Filter Life Gauge Operation
and Resetting for Local Conditions
The filter life gauge calculates the remaining filter life by measuring and comparing the
current motor speed to the initial speed noted at the factory during assembly, and the
calculated maximum motor speed, using the formula:
100-(100x (current speed-original speed) ) = % filter life left
max. speed-original speed
So
anything
Blocking the grille.
Raising the air temperature.
Lowering the barometric pressure.
will increase the motor’s speed, causing the Filter Life Gauge to decrease. Electronic
dampening of the gauge will limit the change in readings to approximately 1%/minute.
Cabinet Biosafety Cabinets being installed at altitudes or operating at temperatures
significantly different from those at the time of manufacture (900 +/- 500 ft above sea
level, 75o +/- 5o F)
Failure to do so will result in the users noticing a steady drop in Percent (%) Filter Life
remaining as the unit operates. Below are the instructions on how to correct the Filter
Life Gauge for local conditions.
that changes the motor’s current speed, like:
must
have their filter life gauge recalibrated for local conditions.
1. Ensure to correct all measurement equipment for local conditions
(temperature, absolute pressure). Anemometers may not have this
ability and might have to be done manually; whereas, a ShortRidgeTM
instrument has a setting to correct for local conditions.
2. As the elevation or the ambient temperature rises, the motor power
factor will have to be reduced to compensate. For an initial certification,
the motor speed should be reduced until it equals the Cabinet’s“Initial Motor Speed”as reported on the unit’s test sheet, plus approximately
10-15 RPM per each additional 1000 feet of elevation.
3. The Cabinet MUST be recertified using instruments corrected for local
conditions.
4. When the unit is recertified, and operating properly, the certifier MUST
RESET THE FILTER LIFE GAUGE, INDICATING A NEW FILTER HAS BEEN
INSTALLED.
5. Only by performing Step #4 AFTER THE UNIT IS READJUSTED AND
RECERTIFIED FOR ITS LOCAL CONDITION, will the filter life gauge
register 100% (+/- 2%) during operation. As the Filters then load, the
filter life gauge will then begin to drop as appropriate.
Product Service 1-800-522-7658
Page 22
22
QuickChart–12-Inch Sash Type A2 BSCs–Imperial Units
Model
30242
30252
30262
Type
A2
A2
A2
Cabinet Size (in feet)
4 5 6
Sash Opening (inches)
12
12
12
Starting Serial #
1601_
1601_
1601_
Downflow Data
Nominal Avg. Downflow (FPM)
60+/-5
60+/-5
60+/-5
grid # of points (rows x columns)
24 (3x8)
30 (3x10)
36(3x12)
Grid distance from back & sides
6.0
6.0
6.0
Distance between rows
5.44
5.44
5.44
Distance between columns
5.21
5.39
5.50
Inflow/Exhaust Data
Nominal Average Inflow (FPM)
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
4.04
5.05
6.06
Nominal Avg. Exhaust Vol. (CFM)
424
530
636
Avg. Exhaust Vol. Range (CFM)
404-444
505-555
606-666
Secondary Inflow Data
Sash Opening Template
1
4+
5+
6+
Sensor distance (inches)2
3.25
3.25
4
# of Test points
8
10
12
Test point location
* * *
As Measured Nominal Avg. Inflow Vel. (NAIV) (FPM)
408
530
636
Acceptable Avg. Inflow Vel. (AIV) Range (FPM)
388-427
505-556
303-333
Correction Factor (CF)
1.08
1.0
2.0
Corrected AIV (CAIV) = (AIV x CF)
404-444
505-556
606-666
Sash Open Area (Sq. Ft)
4.04
5.05
6.06
Inflow Velocity Range (CAIV / Sash open area)
100-110
100-110
100-110
HEPA Filter Leak Test Data
Air Displacement (CFM)
900
1135
1380
Laskin Nozzles needed
2 2 2
Theoretical aerosol conc. (ug/l)3
30
24
20
Actual aerosol conc. (ug/l)4
15
13
10
Supply HEPA Data
Width x Depth x Height (in.)4
48x18x3.06
48x18x3.06
72x18x3.06
Rated Performance (CFM)
445
555
665
Rated Performance (Pressure in. H2O)
.5+/-.1”
.5+/-.1”
0.38-.5”
Labconco P/N
3838401
3838402
3838403
Exhaust HEPA Data
Width x Depth x Height (in.)
4
26x18x5.88
26x18x5.88
48x18x5.88
Rated Performance (CFM)
354
354
529
Rated Performance (Pressure in. H2O)
<0.3
<0.3
<0.3
Labconco P/N
3838501
3838502
3838503
Supply & Exhaust Motor/Blower Data (1 each)
Motor HP5
1/3
1/3
1/3
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F40T8 SP41
F40T8 SP41
Fluor. Lamp Labconco Part #
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889201
3889202
3889203
Canopy Slot Area (ft2)
.12
.12
.12
Canopy Inflow Range (CFM)
50-100
50-100
50-100
Nominal Canopy Slot Velocity (FPM)
240-260
240-260
240-260
Nominal Canopy Slot Volume (CFM)
50
50
50
Canopy Vacuum (In. H2O)
0.1-0.15
0.1-0.15
0.1-0.15
Nominal Total Exhaust Volume -
Cabinet + Canopy (CFM)6
474
580
686
Traverse Total Exhaust Volume -
Cabinet + Canopy (CFM)7
521
638
755
Product Service 1-800-522-7658
Page 23
23
QuickChart–12-Inch Sash Type A2 BSCs–Metric Units
Model
30242
30252
30262
Type
A2
A2
A2
Cabinet Size (in m)
1.22
1.62
1.83
Sash Opening (mm)
305
305
305
Starting Serial #
1601_
1601_
1601_
Downflow Data
Nominal Avg. Downflow (mps)
0.34
0.34
0.34
grid # of points (rows x columns)
24 (3x8)
24 (3x8)
36(3x12)
Grid distance from back & sides (mm)
152
152
152
Distance between rows (mm)
141
146
141
Distance between columns (mm)
132
132
140
Inflow/Exhaust Data
Nominal Average Inflow (m/s)
.533+/-.03
.533+/-.03
.533+/-.03
Sash Open Area (Sq. m)
0.375
0.469
0.563
Nominal Avg. Exhaust Vol. (m3/s)
0.20
0.25
0.300
Avg. Exhaust Vol. Range (m3/s)
0.190-0.210
0.238-0.262
0.286-0.300
Secondary Inflow Data
Sash Opening Template
1
4+
5+
6+
Sensor distance (mm)2
83
83
102
# of Test points
8
10
12
Test point location
* * *
As Measured Nominal Avg. Inflow Vel. (NAIV) (m/s)
2.07
2.69
3.23
Acceptable Avg. Inflow Vel. Range (m/s)
1.97-2.17
2.57-2.82
1.54-1.69
Correction Factor (CF)
0.0966
0.0929
0.194
Corrected AIV (CAIV) = (Avg. velocity x CF)
0.190-0.210
0.238-0.262
0.51-0.56
Sash Open Area (Sq. m)
0.375
0.469
0.563
Inflow Velocity Range (CAIV / Sash open area)(m/s)
0.51-0.56
0.51-0.56
0.51-0.56
HEPA Filter Leak Test Data
Air Displacement (m3/s)
0.427
0.536
0.654
Laskin Nozzles needed
2 2 2
Theoretical aerosol conc. (ug/l)3
30
24
20
Actual aerosol conc. (ug/l)4
15
13
10
Supply HEPA Data
Theoretical aerosol conc. (ug/l)3
25
25
20
Width x Depth x Height (in.)4
48x18x3.06
48x18x3.06
72x18x3.06
Rated Performance (CFM)
445
555
665
Rated Performance (Pressure in. H2O)
.5+/-.1”
.5+/-.1”
0.38-0.5”
Labconco P/N
3838401
3838401
3838403
Exhaust HEPA Data
Theoretical aerosol conc. (ug/l)3
38
48
26
Width x Depth x Height (in.)
4
26x18x5.88
26x18x5.88
48x18x5.88
Rated Performance (CFM)
283
283
423
Rated Performance (Pressure in. H2O)
<0.3
<0.3
<0.3
Labconco P/N
3838501
3838501
3838503
Supply & Exhaust Motor/Blower Data (1 each)
Motor HP5
1/3
1/3
1/3
Fluorescent Lamp Data
Fluorescent Lamps (2 each)
F32T8 TL741
F40T8 SP41
F40T8 SP41
Fluor. Lamp Labconco Part #
9721900
9721903
9721903
Fluor. Ballast Labconco Part #
3838100
3838100
3838100
Ventus Canopy Data
Labconco Canopy P/N
3889201
3889202
3889203
Canopy Slot Area (m2)
.0111
.0111
.0111
Canopy Inflow Range (m/s)
.025-.047
.025-.047
.025-.047
Nominal Canopy Slot Velocity (m/s)
1.22-1.32
1.22-1.32
1.22-1.32
Nominal Canopy Slot Volume (m3/s)
.025
.025
.025
Canopy Vacuum (Pa)
25-37
25-37
25-37
Nominal Total Exhaust Volume -
Cabinet + Canopy (m3/s)6
0.200
0.250
0.300
Traverse Total Exhaust Volume -
Cabinet + Canopy (m3/s)7
0.220
0.274
0.330
Product Service 1-800-522-7658
Page 24
24
QuickChart – 12-Inch Sash Type A2 BSCs footnotes
Cabinet Model Identification
The primary serial tag is on the lower right edge of the front dress panel.
The secondary serial tag is located on the front of the electronics module on the top right
side of the cabinet.
The first two digits of the serial number are the year of production; the next two are the
month. The next 5 digits are the sequence of production, and the letter following the
serial number is the revision level of the cabinet.
Downflow Test Specifications
All models are classified as uniform downflow.
All tests performed as described in ANSI/NSF Standard 49:2014.
UV Lamp, IV bar and all other accessories must be removed before measuring downflow.
Inflow Test Specifications
All tests performed as described in ANSI/NSF Standard 49:2014.
Secondary Inflow Test Specifications
Must use Labconco holder P/N 3836405 to perform this test properly.
1. Use the appropriate template included in Certifier Kit# 3858403.
2. Measured from the bottom edge of the probe holder to the center of the thermal
anemometer sensor element.
* - Locate the single row of holes at the front of the grille. Mark the 6th hole from the side wall
and subsequent test points every 9 holes until the number of test points marked equals the
width of the cabinet in feet (3-foot cabinet, mark the first 3 points). Repeat for the opposite
side.
HEPA Filter Leak Test Specifications
3. Based on mineral oil.
4. Without gasket Aerosol generator should be placed in the left rear corner of the work area, pointing
toward the rear grille.
For uncontaminated units, the upstream concentration can be sampled from the tube
located under the work surface.
Metric calculation of concentration is:
# of Laskin nozzles @ 138K Pascal x 6.372/Volume of air in m
ug/l
Motor / Blower Specifications
5. Each motor must be programmed by Labconco for the appropriate width cabinet.
The speed control settings will fluctuate depending on local temperature and
pressure.
VENTUS Canopy Data
6. DIM = Direct Inflow Meter
7. These values are approximations, as the calculated traverse volume value may
vary depending on sampling location, exhaust system, and methodology.
UV lamp Specifications
For all models, the UV lamp number is G30T8. The Labconco p/n is 1271300.
For all 115/230 VAC models, the ballast assembly is Labconco p/n 3829901.
For all 100 VAC models, the ballast assembly is Labconco p/n 3830600.
3
/sec. = Conc. In
Product Service 1-800-522-7658
Page 25
25
IDENTIFYING CABINET MODELS
The Cabinet platform Biosafety Cabinet can be identified readily by several
external features, as shown in Figure 1-1:
Model number Stars with 302x2xxxx, or 312x2xxxx
Serial number beginning with 1601xxxxx.
12” sash opening marker.
Figure 1-1
12-Inch Sash
Marker
Product Service 1-800-522-7658
Page 26
26
SERIAL NUMBER TAGS
The model/serial number tag is located on the bottom right edge of the dress
panel. A second tag is located on the front of the electronics module on the top
of the unit. This tag includes the unit’s operating voltage and amperage. The
model and serial numbers of each unit are also recorded on the unit test report
attached beneath the front dress panel. These items are shown graphically in the
figures 1-3 to 1-5 below:
Figure 1-3
Primary Serial Tag
Figure 1-4
Secondary Serial Tag
Figure 1-5
Final Inspection and Test Report Form
Obviously, you can get confirmation of the Biosafety Cabinet's model by
contacting Labconco's Product Service Department, and providing us with the
serial number. From this number, we can tell the date of production and its
model.
Product Service 1-800-522-7658
Page 27
27
CABINET MODEL NUMBERING SYSTEM
Cabinet units’ model numbers define the configuration of the cabinet. The first
five digits define the unit's configuration, while the last four are assigned based
on the unit's options and electrical configuration. Thus, a model number of:
30242xxxx
Labconco Product Group
3=Laminar Flow Products
Indicates the Product Family
0= Logic
1= PuriCare
2-4= Cell Logic
The Cabinet Data Plate contains much of the information required to certify the
unit. Information on the plate includes nominal inflow and downflow velocity
settings, a description of how to establish the downflow grid and the secondary
inflow methodology are also included on the data plate, as shown below. The
plate is located in the upper left corner of the dress panel.
Figure 1-6
Product Service 1-800-522-7658
Page 29
29
Final Inspection and Test Report Form
A copy of the Final Inspection Test Report is attached to the blower plenum
cover, beneath the front dress panel. The report contains initial setup
information on inflow and downflow velocities, and the initial blower torque
setting. A copy of the report is shown in Figure 1-7, below
Figure 1-7
Model/Serial
Numbers
HEPA Filter
Information
Test Results
Downflow Test
Results
Product Service 1-800-522-7658
Page 30
30
Theory of Operation
This section offers a brief overview of the theory of operation of the Cabinet.
Airflow Patterns
Figure 1-8
All cabinets meet the airflow
requirements of ANSI/NSF Standard
49:2014. Approximately 55-60% of the
air in the cabinet is filtered and
recirculated, while 40-45% is filtered
and exhausted. ALL Cabinets feature
intrinsically safe designs, jacketing
contaminated positive pressure areas
with negative pressure zones.
ECM Motor
The modern Class II Biosafety Cabinet was developed in the early 1960’s as a
result of the increased availability of High Efficiency Particulate Air (HEPA) filter
technology. The motor of choice at the time to drive the cabinet’s blower was
the Permanent Split Capacitor (PSC) type. At the time, the PSC motor offered
manufacturers an inexpensive power source whose speed could be electronically
controlled to allow for airflow adjustment as the HEPA filter(s) loaded.
The PSC motor is known as an induction type, for stationary windings (stator)
surround a rotating part (rotor) composed of iron or steel. As current passes
through the stator windings, it induces a magnetic field in the rotor, causing it to
rotate towards the shifting field in the stator. Because a magnetic field must be
induced in the rotor, the PSC motor is asynchronous, with the rotor constantly
lagging behind the fields being created in the stator. As a result of this
asynchronous operation, the PSC motor is inefficient, and generates high
amounts of waste heat. Attempting to control the blower speed by reducing its
voltage only increases the inefficiency of the PSC motor.
Product Service 1-800-522-7658
Page 31
31
DC motors are more efficient than their AC counterparts. In a typical DC motor,
the stator in an AC motor is replaced with permanent magnets. The rotor then
has a series of windings around it. When current is applied to the motor, a
magnetic field is created in some of the windings of the rotor, causing it to rotate
toward the magnetic field created by the permanent magnets. Brushes in contact
with a commutator allow the current, and thus the magnetic field in the rotor to
progressively shift from winding to winding, forcing the rotor to keep rotating.
The greatest drawback of brushed DC motors is the brushes-they wear
themselves and the commutator down, eventually causing motor failure.
With the development of greater microprocessor power in the 1970s and 80s,
the stage was set for an even more efficient type of DC motor – the
Electronically Commutated Motor (ECM).
Figure 1-9
In the ECM, the magnets and windings switch position –
the permanent magnet is on the rotor, and the series of
windings are placed around the rotor. The
microprocessor precisely controls the creation of
magnetic fields in the stator, so that the rotor is always
synchronous with the magnetic fields being created in
the stator. As a result, the ECM will always run more
efficiently and cooler than a comparable PSC motor.
Because of the simple, robust construction of the ECM, it
offers far greater reliability and operational service life
than the PSC motor.
Controlling the motor’s operation with a microprocessor adds numerous
advantages. Motor speed can be efficiently controlled across a speed range that
would damage or destroy a PSC motor. Given enough microprocessor memory
and power, the manufacturer can program in any number of user-selected
programs controlling motor speed, power and even direction of rotation. The
ultimate expression of the power of the ECM was the development of the
constant volume algorithm, by General Electric, and used in the Cabinet BSC. By
testing a prototype model to a variety of airflows and filter pressures, the
motor/blower can be “characterized” for that size cabinet. This characterization
allows for the creation of a model-specific motor-blower curve. By programming
the curve values into the motor during assembly, the motor will deliver the
correct volume of air as the HEPA filters load.
Product Service 1-800-522-7658
Page 32
32
Electronics
The Cabinet utilizes three microprocessors. The first two are part of the ECM
motor, attached to end of the motor housing, as shown in Figure 1-10. This
processor controls motor operation, and communication with the display board.
The second is located on the control board, located on the right side wall, as
shown in Figure 1-11. It controls the display and its interface to the touchpad.
Figure 1-10
The ECM Microprocessor board is encapsulated in
epoxy to prevent moisture and dirt contamination of
the microelectronics.
Figure 1-11
The control board assembly
(located on the right side wall)
The Cabinet has five circuit boards. The two ECM microprocessor and power
supply boards, located in the end of the ECMs, the control board on the right
side wall, shown in Figure 1-11, the power supply board and the Transition
boards, located in the electronics module, as shown in Figure 1-12.
Product Service 1-800-522-7658
Page 33
33
Figure 1-12
UV Relay
Light Relay
Outlet Relay
RS-232 Board
Location
Power Supply
Board
Transition Board
The Cabinet also has an optional contact/RS232 board. This must be installed if
the user wants to signal external building monitors or controllers, or wants the
Cabinet to output operating information to a data logger. The optional board is
located in the electronics module.
Figure 1-13
RS-232 Board
Product Service 1-800-522-7658
Page 34
34
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
Page 35
35
Section Two –
Installation Requirements
This section offers an overview of site requirements and how to prepare the unit
for operation.
Prerequisites
Before you install the Cabinet, you need to prepare the site for installation.
Examine the location where you intend to install it. You must be certain that the
area is level and of solid construction. In addition, a dedicated source of
electrical power must be located near the installation site.
Carefully read this chapter to learn:
Location requirements.
Electrical power requirements.
Exhaust requirements.
Service utility requirements.
Space requirements.
Refer to
and environmental conditions, specifications and requirements.
Section Nine: Miscellaneous
, for complete biosafety cabinet electrical
Space Requirements
The overall dimensions for the 4-foot Cabinet are 64.2 inches (163 cm) high, 32
inches (81 cm) deep, and 54.2 inches (138 cm) wide. The overall dimensions for the
6-foot Cabinet are 64.2 inches (163 cm) high, 32.6 inches (83 cm) deep, and 78.2
inches (199 cm) wide.
Complete dimensions for the cabinets are shown in
Section Nine: Miscellaneous
.
Clearance
A minimum clearance of at least 4 inches (100 mm) is suggested on the top and
6 inches (150mm) on both sides of the cabinet for service.
Product Service 1-800-522-7658
Page 36
36
Location Requirements
Figure 2-1
Note: The cabinet should be located away from traffic patterns, doors, fans,
ventilation registers, fume hoods and any other air-handling devices that could
disrupt its airflow patterns. All windows in the room should remain closed. Figure
2-1 shows the preferred location for the biosafety cabinet.
Preferred location
Air register blocked or redirected
to prevent cabinet disruption
Alternate location
Main Disconnect Device
(Power cord plug in back
of the electronics module).
Do not position the unit so that it is difficult to operate the main
disconnect device.
Ne placez pas l'appareil de sorte qu'il est difficile de faire fonctionner le
dispositif principal de déconnexion.
Product Service 1-800-522-7658
Page 37
37
Exhaust Requirements
If you intend to connect the biosafety cabinet to the optional VentusTM Canopy
Connection Kit, first examine the location to ensure that it accommodates the
cabinet’s exhaust duct. The area directly above the cabinet’s exhaust port should
be clear of structural elements, water and utility lines, or other fixed
obstructions. There should be enough clearance to accommodate a 10-inch
diameter duct. Avoid cabinet locations that require an elbow directly above the
cabinet’s exhaust connection or an excessive number of elbows in the exhaust
system. For further information about the cabinet’s exhaust system
requirements, please refer to
Before deciding on a location, examine it carefully to ensure that it
accommodates the cabinet’s exhaust duct. The area directly above the cabinet’s
exhaust port should be clear of structural elements, water and utility lines, or
other fixed obstructions. There should be enough clearance to allow for the
passage of a 10" stainless steel duct. Avoid cabinet locations that require either
an elbow directly on top of the cabinet’s exhaust connection or an excessive
number of elbows to clear other items. For a further discussion of the cabinet’s
exhaust system requirements, please go to
Section 3: Installation.
Section 3: Installation.
Product Service 1-800-522-7658
Page 38
38
Electrical Requirements
Model #
Requirements
30242xx0x
115 VAC, 60 Hz, 16 Amps
31242xx2x
100 VAC, 50/60 Hz, 16 Amps
30242xx-10, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
31242xx-10, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
30252xx0x
115 VAC, 60 Hz, 16 Amps
31252xx2x
100 VAC, 50/60 Hz, 16 Amps
30252xx-10, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
31252xx-10, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
30262xx0x
115 VAC, 60 Hz, 16 Amps
31262xx2x
100 VAC, 50/60 Hz, 16 Amps
30262xx-10, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
3126xx-10, 30, 40, 50, 60, 70
230 VAC, 50/60 Hz, 8 Amps
Table 2-1
The biosafety cabinet models have the following electrical requirements:
Note: A dedicated outlet with an appropriate circuit breaker should be
located as close as possible to the right rear side of the cabinet, at a
height even with, or higher than, the top of the bench or stand. Consult
your local electrical codes for properly rated circuit breakers. For safe
operation the dedicated outlet must provide the protective earthing
ground connection to the cabinet.
Note: On 100 and 115 VAC models, both electrical outlets are protected by a
ground fault interrupter circuit (GFIC). Labconco does not recommend plugging
the biosafety cabinet into a GFIC outlet.
Electrical outlets in the cabinet are restricted to 5 amps maximum
current.
Prises électriques dans l'armoire sont limitées à 5 courant maximum ampères.
The biosafety cabinet models have the following electrical requirements:
Do not use any detachable power cord that is not adequately rated for
the unit.
Ne pas utliser un fil électrique amovible qui n’est pas du tension
nominale de l’appareil.
Product Service 1-800-522-7658
Page 39
39
Service Line Requirements
All utility service lines should be ¼ inch O.D., brass, copper, or stainless steel,
and equipped with an easily accessible shut-off valve. If the service line pressure
exceeds 40 PSI (276 kPa), it must be equipped with a pressure regulator to
reduce the line pressure.
Note: The use of flammable gases or solvents should be avoided in the
biosafety cabinet. Open flame in the cabinet will disrupt the laminar airflow in the
cabinet and may damage the HEPA filters. Flammable gases or solvents may
reach explosive concentrations in the cabinet or ductwork. If you feel that the
procedure requires the use of an open flame or flammable materials, contact the
institution’s safety office.
The use of air or gases under high pressure should be avoided as they may
seriously disrupt the airflow patterns in the cabinet.
Product Service 1-800-522-7658
Page 40
40
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
Page 41
41
Section Three –
Installation
Now that the installation is properly prepared, you are ready to inspect, install, and
certify the biosafety cabinet. This chapter covers how to:
Unpack and move the biosafety cabinet.
Install the cabinet.
Connect the electrical supply source.
Connect the service lines.
Connect to an exhaust system (optional).
Tools required for installation the biosafety cabinet include two 1/2" wrenches, a flatblade screwdriver, a #2 Phillips screwdriver, and a carpenter’s level.
Note: The biosafety cabinet models weigh between 400–700 lbs. (182-318 kg). The
shipping pallet allows for lifting with a mechanical lift truck or floor jack. If you must lift
the product manually, use at least six (6) persons and follow safe-lifting guidelines.
Product Service 1-800-522-7658
Page 42
42
Unpacking the Biosafety Cabinet
Carefully remove the outer carton and inspect the cabinet for damage that may have
occurred in transit. If the biosafety cabinet is damaged, notify the delivery carrier
immediately and retain the entire shipment intact for inspection by the carrier.
Note: United States Interstate Commerce Commission rules require that claims be filed
with the delivery carrier within fifteen (15) days of delivery.
Do not return goods without the prior authorization of Labconco. Unauthorized returns
will not be accepted.
If the cabinet was damaged in transit, you must file a claim directly with the freight
carrier. Labconco Corporation and its dealers are not responsible for shipping damages.
Do not discard the carton or packing material for the biosafety cabinet until all of the
components have been checked, installed and tested.
The cabinet is secured to the pallet in two places on each side. To access the nuts and
bolts, remove the side panels by removing and keeping the two Phillips screws on both
panels. Swing the front of each panel away from the cabinet, and lift it straight up to
remove the panel from the cabinet.
Note: The side panels must be removed to access the fasteners that secure the
biosafety cabinet to the pallet. DO NOT ATTEMPT TO LIFT THE BIOSAFETY
CABINET BY THE SIDE PANELS; DAMAGE WILL OCCUR.
Preparing the Biosafety Cabinet for
Operation
Installation instructions (Labconco P/N 1056801) are attached to the sash of the
cabinet. If these instructions are missing or unclear, contact Product Service at 800-8215525 or 816-333-8811. The following are located in a box either taped to the top of or
underneath the work surface:
User’s Manual CD
Drain Valve Assembly and fasteners
Power Cord
Product Registration Card
Vacu-Pass
If you did not receive one or more of the components listed for the cabinet, or if any of
the components are damaged, contact Labconco Corporation immediately for further
instructions.
TM
Accessories (optional)
Product Service 1-800-522-7658
Page 43
43
Moving and Lifting the Cabinet
Move the cabinet, attached to its pallet, by using a floor jack, or a furniture dolly underneath the
unit. DO NOT move the cabinet by tilting it onto a hand truck.
When lifting the cabinet DO NOT lift the cabinet in the middle front area of the hull. Lifting here
may bend or distort the bottom of the cabinet, causing damage to the unit.
Installing the Biosafety Cabinet on an
Existing Work Surface
Note: The biosafety cabinet is very top heavy. Use caution when lifting or moving it.
When installing the biosafety cabinet onto an existing work surface or benchtop, ensure
that the structure can safely support the combined weight of the cabinet and any related
equipment. The work surface should be at least as wide as the cabinet and 31 inches (787
mm) deep to properly support the unit.
A hole or notch may be cut in the supporting surface in the right front corner to
accommodate the optional drain valve.
Product Service 1-800-522-7658
Page 44
44
Installing the Cabinet on a Labconco Base
Width
Base Stand w/Feet Model #
4'
3401004
5’
3401005
6'
3401006
Width
Manual Lift Stand #
Electric (115V) Lift Stand
#
Electric (230V) Lift Stand
#
4'
3780201
3780101
3780104
5'
3780203
3780106
3780107
6'
3780202
3780102
3780105
Table 3-1
Table 3-2
Stand
Labconco offers accessory Base Stands in a variety of configurations to suit your
particular needs. Stands can be ordered with adjustable telescoping legs or with a
manually or electrically adjustable hydraulic lift.
Telescoping Base Stands
These stands are included with some Cabinet models, or are available separately. The
base stands for each width cabinet are listed in Table 3-1 below. An optional caster
wheel kit is available (part # 3730500).
Manual or Electric Hydraulic Lift Base Stands
These base stands offer infinitely adjustable height between 25.5 and 33.5 inches (648
to 851 mm), giving a cabinet work surface height of 28.0 to 36.0 inches. The height is
adjusted either by a manual (hand crank) or electric pump that drives hydraulic rams in
the legs of the stands. All of the hydraulic stands are equipped with fixed feet, but can
be converted to caster wheels with the addition of Caster Kit #3784000. The base
stands for each cabinet size is listed in Table 3-2 below.
Note: When installing the cabinet on the hydraulic lift base stand, ensure that the
hydraulic lines and the electrical cord are clear of any obstructions before installing the
cabinet on the stand or operating the lift system.
Product Service 1-800-522-7658
Page 45
45
SoLoTM Electric Hydraulic Lift Base Stands
115V SoLo Stand
#
230V SoLo
No. America
Plug #
230V SoLo
UK Plug #
230V SoLo
Schuko Plug
#
230V SoLo
China/Australia
Plug #
4'
3780311
3780315
3780331
3780335
3780339
5'
3780312
3780316
3780332
3780336
3780340
6'
3780313
3780317
3780333
3780337
3780341
Table 3-3
These base stands permit the Cabinet to be lowered enough to be transferred through a
standard doorway as low as 78 inches. Casters provide mobility and lock in place. The
SoLo Stands for each Purifier Cabinet series model is listed below.
Product Service 1-800-522-7658
Page 46
46
Connecting the Biosafety Cabinet to Utility
Figure 3-2
Service Lines
Note: Some models have a solenoid valve connected to the service valve on the right
side, rear position. The solenoid prevents gas from flowing to the service valve when the
unit blower is off. It is the only service valve position that can be fitted with a solenoid
valve. Connect the gas service to the solenoid valve.
The service lines (if any) should be connected to the tube fitting(s) on the outside of the
liner wall as shown in Figure 3-2 To install the tubing, follow these steps:
1. Ensure that the tubing is ¼ inch O.D., soft metal, and that the end has been
completely deburred.
2. Route the tubing from the rear of the cabinet, ensuring that it will line up with the
slot in the back of the side panel. The slot is located from 8 ¾ to 11 ¼ inches (222
to 288 mm) from the bottom of the cabinet.
Note: Make sure that the tube routing will not contact any electrical wires. DO NOT
loop service line tubing within the side panels of the cabinet.
3. Make sure that the nut on the tube fitting is loose, but do not remove it. Look inside
the fitting to make sure the tube ferrule is there.
4. Push the tube into the fitting until it is properly seated. The tube will go
approximately ¾ inch (19 mm) into the fitting.
5. Tighten the tube fitting nut hand tight and then, using a 7/16-inch wrench, tighten it
at least ¾ turn more.
6. Close the service valve in the biosafety cabinet and then slowly open the shutoff
valve on the service valve. Test all fittings for leakage. Tighten the tube nut slightly
if needed.
Tube fitting
Tube fitting nut
Product Service 1-800-522-7658
Page 47
47
Optional VentusTM Canopy Exhaust
Connection
Certain applications such as working with odorous products or volatile toxic materials
will require the connection of the biosafety cabinet to an exhaust system.
Note: The canopy connection, also referred to as a thimble or air gap connection,
allows single or multiple biohazard cabinets to be connected to an exhaust system.
During operation, the exhaust system draws all of the cabinet’s exhaust air, plus a
volume of room air (through the Inlet Relief Valve in the canopy) into the exhaust duct.
Canopy connections function as a “shock absorber” allowing the system to function
properly during changes in room air pressure.
For information on selecting a canopy connection, go to
Note: If the research involves the use of toxic compounds or volatile materials, contact
the facility’s safety officer or Labconco to ensure that the biosafety cabinet and its
exhaust system are compatible with the materials you will be working with.
Section Eight: Accessories.
Product Service 1-800-522-7658
Page 48
48
Optional Vacu-PassTM Cord & Cable Portal
Figure 3-3
Use
Note: There must be enough clearance to pass the cord or cable between the Cabinet’s
exterior dress panel and any obstruction.
Note: Some Vacu-Pass components and the cord or cable passing through it may
become contaminated during use of the cabinet. Ensure all potentially contaminated
components are surface decontaminated before handling or removal from the cabinet.
1. Remove the grommet from the liner side wall. Remove the solid sealing plug from
the body of the portal by either pressing it through from the outside, or by carefully
inserting a spatula or similar device between the sealing plug and the body of the
portal, and prying the plug out.
2. Pass the cord or cable through the body of the portal, and then through one of the
plugs that has been cut for cord or cable use, then through the grommet, as shown
in Figure 3-3.
Note: select a plug with a hole that is slightly smaller than the cord or cable, to create a
proper seal. This will also help minimize movement of the cord or cable if it is
accidentally pulled during use.
3. Position the cord or cable as it will be used in the cabinet, and then push the plug
back into the body of the portal until it seats in the portal. Reinstall the grommet.
Product Service 1-800-522-7658
Page 49
49
Drain Valve Installation
Figure 3-4
In order to prevent damage during shipping, the drain valve assembly has not been
installed. If desired, the valve should be installed after the cabinet is in its final location.
To install the valve assembly, follow these steps:
1. Lift the work surfaces out of the biosafety cabinet by lifting on the knobs at the front
of the work surface.
2. Using a putty knife, remove and discard the stainless steel cover that is sealed over
the drain mounting holes. Scrape out remaining sealant that is around the holes.
3. Apply a light coating of silicone sealant (user supplied) to the mounting surface of
the drain assembly. Attach the drain assembly under the bottom of the cabinet as
shown in Figure 3-4. Wipe off any excess sealant from the cabinet bottom. Ensure
that the center drain hole is unobstructed.
4. Make sure the drain valve is in the closed position.
5. Reinstall the work surfaces.
6. Allow the silicone sealant to cure for at least eight hours before exposing it to liquid.
NOTE: The drain valve assembly attaches to the underside of the cabinet bottom.
Apply a light coat of silicone sealant to this surface
of the connector, aligning the three holes in the
connector with the three holes in the biosafety
cabinet liner.
Product Service 1-800-522-7658
Page 50
50
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
Page 51
51
Section Four -
Figure 4-1
Initial Operation of the Cabinet
This section will take you through the steps to begin initial operation of the Cabinet, with
an explanation the controls, display and options, in order to prepare the unit for its
initial certification.
System Reset Switch
The cabinet has a system reset switch for resetting its microprocessors. The switch is
located on the front of the electronics module, on top of the cabinet, as shown in Figure
4-1. Ensure that the switch is in the “ON” (up) position before attempting to operate the
cabinet.
The System Reset
Switch
Product Service 1-800-522-7658
Page 52
52
Information Center
Figure 4-2
10:03
Figure 4-3
The Information Center is an LCD display located on the right side wall at eye level.
When the blower is started, if the Cabinet is configured to be connected to an exhaust
system, Figure 4-2 will appear for 60 seconds while the unit initiates operation.
After 60 seconds, the default display screen will appear. The display provides a clock,
the life remaining for both filters, the cabinet’s current status, inflow velocities (if
equipped with the optional airflow sensor), as shown in Figure 4-3. In the event of an
alarm, the Information Center will immediately display a context sensitive display
indicating the cause of the alarm, and possible solutions, as shown in Figures 4-4a-f.
The display will enter sleep mode, turning itself off, one minute after the blower is
turned off or the sash is closed.
Clock
Filter Life
Product Service 1-800-522-7658
Page 53
53
Alarm Screens
Figure 4-4b
Figure 4-4e
Figure 4-4a
Figure 4-4c
Figure 4-4d
Sash is too high
The sash is not open at the appropriate height.
Airflow Alerts
The airflow patterns in the cabinet have changed, resulting
in a sudden change in either motor speed. This is most likely
due to a blockage of the grille or the exhaust filter outlet. It
may also be caused by removal of the work surface(s) while
the cabinet is in operation.
Exhaust Fan Alarm
There has been a failure of the exhaust fan, or its
communication to the cabinet’s control board. DO NOT USE
THE CABINET UNTIL THE PROBLEM HAS BEEN
CORRECTED.
Exhaust System Alarm
When equipped with the Ventus Canopy, and the exhaust
system fails to move a sufficient volume of air, this display
screen is shown, and an audible alarm heard. If this alarm is
displayed, the cabinet blowers will need to be turned off,
and then back on again to reset the alarm. Frequent
Exhaust System Alarms indicate unstable or insufficient
exhaust flow, and must be corrected.
System Error
The motors and display circuit board are not
communicating properly. DO NOT USE THE CABINET
UNTIL THE PROBLEM HAS BEEN CORRECTED.
Product Service 1-800-522-7658
Page 54
54
Operating the Sliding Sash
Figure 4-5
The counterbalanced, anti-racking sash mechanism requires only a few pounds of force
to move the sash up or down. You can open or close the sash smoothly with one or two
hands positioned on either handle.
The sash position alarm and safety interlock system senses the sash position and acts
appropriately. The biosafety cabinet has been programmed to operate at a 12-inch
(305- mm) sash opening. Raising the sash above or below its operating height will
activate the audible and visual alarms. The audible alarm can be temporarily muted (for
approximately five minutes) by depressing and releasing the
the sash back to its operating position will reset the alarm and defeat the muting of the
alarm. The safety interlock system senses when the sash is closed and allows the
optional ultraviolet (UV) lamp to operate only when the sash is closed, to protect the
operator from irradiation.
OK/Mute
button. Closing
Starting the Biosafety Cabinet
1. To start the biosafety cabinet, raise the sash until its bottom edge aligns with the
proper sash height label on the left corner post, as decal is shown in Figure 4-5.
2. Press the blower button to start the unit. The unit will display a standby screen
for approximately 60 seconds to allow the cabinet to reach proper operating
conditions. If the alarm sounds, recheck the sash position. If the sash is too
high, the sash audible alarm and the LCD display will indicate the sash is too
high.
3. To turn the UV light on, the sash must be completely closed to prevent the
escape of any UV radiation. Push the UV light button to activate the UV light.
Note: The sash must be completely closed for the UV light to activate.
Sash height label
Product Service 1-800-522-7658
Page 55
55
The Cabinet Touchpad
Figure 4-6
The touchpad of the Cabinet is shown in Figure 4-6. Take a moment to get familiar with
the buttons, their locations and functions. Also familiarize yourself with the display
located on the right side wall. The display will report system functions, such as filter
capacity, timer displays, alarm or error messages, as well as icons that illuminate when
cabinet functions such as UV light and blower are operational.
Blower Button – Starts or stops the cabinet blower. When the
blower is in Smart-StartTM mode, opening the sash from the closed
position turns the blower on automatically. When in recirculating
mode with Night-SmartTM, when the sash is closed, the motor slows
to idle to maintain air cleanliness in the work area. When the sash
is reopened, the blower resumes normal operation. Pressing this
button overrides Smart-Start and Night-Smart operation
Light Button – Turns the fluorescent lamps on or off. Closing the
sash automatically turns the lights off. When the lights are in
Smart-Start mode, raising the sash turns the lights on
automatically.
Outlet Button – Turns the electrical outlets in the work area on or
off.
UV Light Button – Turns the UV lamp on or off. When the UV
lamp is in Smart-Start mode, closing the sash turns the light on.
When the sash is raised, the light turns off automatically.
Timer Button – Allows you to select either a repeating interval
timer, or an elapsed timer (stopwatch).
OK/Mute Button – Mutes all audible alarms for approximately 5
minutes, unless there is a system error alarm. When in the Menu
mode, this button is used to select an option.
Menu Button – This button toggles the display between the
display and menu modes. When in the menu mode, pressing this
button returns you to the previous menu level.
Select Buttons – Allow you to choose different options in the
menu mode.
Product Service 1-800-522-7658
Page 56
56
Navigating the Cabinet Menu Screens
MyLogicTM allows you to use the Smart-Start or Night-Smart features that activate
functions automatically when the sash is opened or closed. Night-Smart will only work if
the cabinet is not connected to an exhaust system.
If equipped, the UV lamp can be programmed to operate for a given time interval when
the sash is closed, before it shuts off.
NOTE: When you are in the menu mode, if a selection is not made within 30
seconds, the display will reset back to display mode.
Keypad operations are shown as
green italics
NOTE: Pressing the appropriate touchpad button will override Smart-Start or
Night-Smart selections.
To access the menu, press the
menu. To select from the various menu options press the ▲ or ▼ buttons until the
selected option is displayed. Press
return to the previous menu level.
.
Display Mode Menu Mode
blue bold italic
Menu
button. The display panel will show the first level
OK/Mute
Menu
. Menu screen selections are shown as
to accept that option, or press
Menu
to
Product Service 1-800-522-7658
Page 57
57
Navigating the MyLogicTM Menu Screens
The MyLogic screens will allow you to set the cabinet’s clock, and to personalize its
operation. Please note all MyLogic screens have a blue background.
Setting the Clock
Using the ▲ and ▼ buttons on the touchpad, highlight the
blue when selected. Press
Using the ▲ and ▼ buttons on the touchpad,
highlight
selected. Press
setting screen:
At this screen, select whether you want the clock
to display in a 12- or 24-Hour format.
When you have highlighted your choice, press
OK/MUTE
Use the ▲ and ▼ buttons to select the hour, and
press
Use the ▲ and ▼ buttons to select the minute,
and press
screen.
set the clock
OK/MUTE
to go to the next screen…
OK/Mute
…
OK/MUTE
OK/MUTE
-it will turn white when
to enter the first clock
to return to the first MyLogic
to enter the first MyLogic screen:
OK/Mute
MyLogic
option-it will turn
Product Service 1-800-522-7658
Page 58
58
Configuring the Cabinet
In the first MyLogic screen, use the ▲ and ▼
buttons on the touchpad to highlight
Logic for use
OK/MUTE
The first screen gives you the option of activating
the Smart-Start option for the blower; if you want
the cabinet blower to start every time you raise the
sash, select
start
is selected, then the blower must be manually
started from the keypad. When
pressed, the next configuration screen will appear.
The next screen gives you the option of activating
the Smart-Start option for the fluorescent light; if
you want the lights to turn on every time you raise
the sash, select
If
stay off
manually turned on from the keypad. When
OK/MUTE
will appear.
If you want the cabinet blower to run slowly,
maintaining reduced airflows every time you close
the sash, select
press
OK/Mute
blower will stop when the sash is closed. When
OK/MUTE
will appear.
If your Cabinet is configured for a UV light, then
you will see the next two screens; if you want the
UV lamp to turn on every time you close the sash,
select
off
when the sash is closed. When
pressed, the final configuration screen will appear.
turn on
is selected, then the UV light will not turn on
-it will turn white when selected. Press
to enter the first configuration screen:
start
, and then press
turn on
is selected, then the lights must be
is pressed, the next configuration screen
, and then press
go into NightSmart mode
. If
stop
is selected, then the
is pressed, the next configuration screen
, and then press
OK/Mute
configure my
OK/Mute
OK/MUTE
OK/Mute
and then
. If
OK/MUTE
. If
is
stay
is
not
.
Product Service 1-800-522-7658
Page 59
59
If you choose to use NightSmart option for the UV lamp,
this screen allows you to control the time the UV lamp will
remain on after the sash is closed. Use the ▲ and ▼
buttons on the touchpad to cycle through the time
intervals available, and then press
The screen will then return to the first MyLogic screen.
OK/MUTE
to select it.
Navigating the Settings Menu Screens
The Settings screens will allow an administrator to set some of the cabinet’s operational
parameters. Please note all Settings screens have a green background.
Using the ▲ and ▼ buttons on the touchpad, highlight the
green when selected. Press OK to enter the first Settings screen:
Settings
option-it will turn
OK Button
Display Options
Units of Measure
Note: The Units of Measure refers to the display of
airflow velocities if the cabinet is equipped with the
optional airflow sensor.
Using the ▲ and ▼ buttons on the touchpad,
highlight the
white when selected, and then press OK. Using the
▲ and ▼ buttons on the touchpad, highlight either
metric
when selected, and then press OK. The screen will
then return to the first Settings screen.
or
Units of Measure
imperial
units of measure-it will turn white
option-it will turn
Product Service 1-800-522-7658
Page 60
60
Startup tone
The Security Lock Is:
or to choose,
OK to select, M ENU to return
turned on
button for mor e than 5
seconds to unl ock the Logic)
turned off
(Hold the
Security Lock
Using the ▲ and ▼ buttons on the touchpad, highlight the
Startup Tone
option-it will turn white when selected, and
then press OK. Using the ▲ and ▼ buttons on the
touchpad, highlight either
Turned on
or
Turned off
option.
When turned on, an audible beep will sound during the
first 60 seconds of blower operation to caution the user
that the unit is not yet ready for use.
Security Lock
Note: The Security Lock feature “locks” the keypad to prevent unauthorized use of the
cabinet. The security lock is unlocked by holding the ▼ button for 5 seconds. The lock
deactivates after cabinet is unlocked.
From the Settings menu screen, use the ▲ and ▼ buttons
on the touchpad to highlight the
turn white when selected. Press
Security Lock screen. Using the ▲ and ▼ buttons on the
touchpad, highlight either
turned on
white when selected, press
return to the first Settings screen.
RS-232 Output Rate
Note: This selection will only work if the optional EN/RS-232 board is installed.
This menu option selects the rate that the RS-232 board outputs data. Data can be
output at a rate of once per second, once every 10 seconds, once every 30 seconds, or
once per minute.
From the Settings menu screen, use the ▲ and ▼ buttons
on the touchpad to highlight the
white when selected. Press
232 output screen. Using the ▲ and ▼ buttons on the
touchpad, highlight either the data output rate preferred.
It will turn white when selected, and then press OK. The
screen will then return to the first Settings screen.
Security Lock
OK/MUTE
or
OK/Mute
RS-232 output
OK/MUTE
option-it will
to enter the
turned off
-it will turn
. The screen will then
-it will turn
to enter the RS-
Product Service 1-800-522-7658
Page 61
61
UV Settings
For models equipped with the optional UV light the Cabinet has an integral UV light
maintenance system. It allows you to define how many hours you want the UV lamp to
operate before receiving a reminder to replace it, a way to monitor how many hours the
lamp has been on, and the means to reset the UV lamp hourmeter.
UV Lamp Hourmeter
This display only shows how many hours the UV lamp has been lit, and how many hours
remain until you will receive a warning to replace the lamp.
From the Settings menu screen, use the ▲ and ▼
buttons on the touchpad to highlight the
option-it will turn white when selected. Press
enter the UV Settings screen. Using the ▲ and ▼ buttons
on the touchpad, highlight UV Hourmeter-it will turn white
when selected, and then press
then return to the UV Hourmeter screen.
This screen displays how many hours the UV lamp has
operated, and how many hours of operation remain before
replacement is recommended. When finished with this
screen, press
screen.
MENU
to return to the first UV Settings
OK/Mute
Reset UV Lamp Hourmeter
This option lets you reset the UV hourmeter to 0 hours
whenever the lamp has been replaced.
This screen allows you to reset the UV Hourmeter to 0
hours if you press
you to the first UV Settings screen without resetting the
hourmeter.
OK/Mute
. Pressing
Change UV Lamp Life
In this screen, you can set the number of operating hours before receiving the replace
UV lamp warning. For most UV lamps, the output of UV light decreases at a constant
rate. Typically, after 6,000 hours of operation the lamp will output 80%. This option
allows you to set operational life of the UV lamp, in 100 hour increments.
From the UV Settings menu screen, use the ▲ and ▼
buttons on the touchpad to highlight the
it will turn white when selected. Press
the Set UV life screen. Use the ▲ and ▼ buttons to increase
or decrease the lamp life in 100 hour increments, until the
desired value is displayed, and then press
screen will then return to the UV Settings screen.
UV Settings
OK/MUTE
. The screen will
MENU
will return
Set UV Life
OK/MUTE
to enter
OK/Mute
to
option-
. The
Product Service 1-800-522-7658
Page 62
62
Timer Operation
NOTE: The timer button allows activation of an interval (countdown) or
stopwatch (elapsed) timer. The timers cannot be operated simultaneously.
To access the main timer menu, press the
operation. The main timer menu is shown on the LCD display. Use the ▲ and ▼ buttons
to highlight the
highlighted timer function.
Interval
or
Stopwatch
Timer
Timer. Press the
button anytime during normal
OK/MUTE
button to select the
Interval Timer Operation
1. When selected, the Interval Timer menu is displayed on the LCD. The timer
defaults to 0:00:00 (hours:minutes:seconds).
2. Press and hold the ▲ or ▼ buttons to increase or decrease the timer interval.
3. When the proper interval is entered on the display, press the
to start the timer.
4. When the timer reaches 0:00:00, an audible alarm will sound, and the timer will
reset itself and repeat the countdown.
5. Press the
6. Press the
menu.
OK/MUTE
Menu
button to clear the interval timer and return to the main timer
button to pause the timer.
OK/MUTE
button
Stopwatch Timer Operation
1. When selected, the Stopwatch Timer menu is displayed on the LCD. The timer
defaults to 0:00:00.
2. Press the
3. Press the
4. Press the
timer menu.
OK/MUTE
OK/MUTE
Menu
button to clear the stopwatch timer and return to the main
button to start the timer.
button again to zero the timer.
If An Airflow Alert Activates
The most common causes of an Airflow Alert are:
Blockage of the inlet grilles or exhaust outlet.
Removal of the work surface or grille during operation.
Resetting the Airflow Alert System
The Airflow Alert automatically resets to normal operation once the motor speed has
stabilized.
Product Service 1-800-522-7658
Page 63
63
Section 5
MAIN MENU
1. MyLogic
TM
2. Settings
3. Service
or to choo se,
OK to select, ME NU to escape
or to choose,
OK to select, ME NU to return
Current Settings
Restore Default
Diagnostics
Configuration
Calibration
Service
ATTENTION!
The following screens are used
to alter the operation of the
Logic. They should only be used
by a qualified certifier as part
of the certification process.
Calibration
OK to proceed, MENU to return
Certification Procedures for the
Cabinet
This section will outline test procedures to validate the performance of the Cabinet.
Note: These are the only Labconco-approved test procedures for validating
the performance of the Cabinet Biosafety Cabinet. Other test procedures may
yield different or inaccurate test results.
NOTE: In order to properly certify the Cabinet, you must obtain a Cabinet
Certifier Kit, Labconco P/N 3858400. Qualified certifiers can obtain this kit by
contacting Labconco Customer Service Department at 800-821-5525.
Note: The ECM motor is programmed by Labconco to deliver a constant
volume of air throughout the life of the HEPA filters. Any changes to the
blower speed control should be small (less than 5 units).
Accessing the Certifier’s Menu
Note: You will need to access this menu to do any of the following:
Adjust the blower speed
To reset the filter gauge
To calibrate the optional airflow sensor
Adjusting the Downflow, Inflow and Filter
Life Gauges
1. Press the
Menu
button.
2. Press the ▼ button until the
turn yellow).
3. Press
OK/Mute
to enter the Services menu screen.
4. Press the ▼ button until the
will turn white).
5. Press
OK/Mute
to start the calibration procedure.
6. You will see a
warning screen
alter the BSC’s settings.
7. Press
OK/Mute
to input the password.
Product Service 1-800-522-7658
Services
Calibration
option is highlighted (it will
option is highlighted (it
alerting you that you are about to
Page 64
64
PASSWORD:
Calibration
The Inflow displayed
value is: 102 FPM
Calibration
Inflow Display
or to chang e display value,
UV Light to res et to 105 FPM,
OK to select, ME NU to finish
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Supply Fan Speed
or to change motor speed,
OK to select, MENU to escape
Calibration
Supply Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
Leave Gauge unchanged
The ECM setting is: 80
The current RPM is: 1050
The average RPM is: 1020
Calibration
Exhaust Fan Speed
or to change motor speed,
OK to select, MENU to escape
Calibration
Exhaust Filter Gauge
or to change filter gauge,
OK to select, MENU to escape
Leave Gauge unchanged
8. When requested for the password press
Timer, Timer
then
OK/Mute
.
Light, UV light
9. If the password is properly entered, the first certification screen
will display the supply blower motor’s PWM setting. Press the ▲
or ▼ button to increase or decrease the blower speed as
needed. When the speed is set properly, press the
OK/Mute
button to lock the new blower speed setting, and continue to the
filter life screen.
10. If this is an initial certification or a recertification after supply
HEPA filter replacement, select
this is an annual recertification, select
Reset Filter Gauge to 100%
Leave Gauge unchanged
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
OK/Mute
.
11. The next certification screen will display the exhaust blower
motor’s PWM setting. Press the ▲ or ▼ button to increase or
decrease the blower speed as needed. When the speed is set
properly, press the
OK/Mute
button to lock the new blower
speed setting, and continue to the filter life screen.
12. If this is an initial certification or a recertification after exhaust
HEPA filter replacement, select
this is an annual recertification, select
Reset Filter Gauge to 100%
Leave Gauge unchanged
If you want to set the filter gauge at a preset value, select
Gauge to new setting
. Then press
OK/Mute
.
13. If the unit is has no airflow sensor, after the filter gauge option
is selected and you press
OK/Mute
, the Cabinet will power
down, and then restart with the new settings. If the Unit has an
airflow sensor, you will then be asked to calibrate the inflow
sensor to match the value you obtained when you measured the
inflow. After the inflow is calibrated, and you press
OK/Mute
the Cabinet will power down, and then restart with the new
settings.
Product Service 1-800-522-7658
,
. If
.
Set
. If
.
Set
,
Page 65
65
Cabinet Filter Life Gauge Operation and
Resetting for Local Conditions
The filter life gauge calculates the remaining filter life by measuring and comparing the current
motor speed to the initial speed noted at the factory during assembly, and the calculated
maximum motor speed, using the formula:
100-(100x (current speed-original speed) ) = % filter life left
max. speed-original speed
So
anything
Blocking the grille.
Raising the air temperature.
Lowering the barometric pressure.
will increase the motor’s speed, causing the Filter Life Gauge to decrease. Electronic dampening
of the gauge will limit the change in readings to approximately 1%/minute.
Cabinet Biosafety Cabinets being installed at altitudes or operating at temperatures significantly
different from those at the time of manufacture (900 +/- 500 ft above sea level, 75o +/- 5o F)
must
have their filter life gauge recalibrated for local conditions. Failure to do so will result in the
users noticing a steady drop in Percent (%) Filter Life remaining as the unit operates. Below are
the instructions on how to correct the Filter Life Gauge for local conditions.
1. Ensure to correct all measurement equipment for local conditions (temperature, absolute
2. As the elevation or the ambient temperature rises, the motor power factor will have to be
3. The Cabinet MUST be recertified using instruments corrected for local conditions.
4. During recertification the certifier MUST RESET THE FILTER LIFE GAUGE, INDICATING A
5. Only by performing Step #4 AFTER THE UNIT IS READJUSTED AND RECERTIFIED FOR
6. If you do not wish to reset the filter gauge, select the option “Filter not changed”, and
7. Either selection will finish the calibration mode, or lead to calibration of inflow and
that changes the motor’s current speed, like:
pressure). Anemometers may not have this ability and might have to be done manually;
whereas, a ShortRidgeTM instrument has a setting to correct for local conditions.
reduced to compensate. For an initial certification, the motors’ speeds should be reduced
until it equals the Cabinet’s “Initial Motor Speed”as reported on the unit’s test sheet,
plus approximately 10-15 RPM per each additional 1000 feet of elevation.
NEW FILTER HAS BEEN INSTALLED.
ITS LOCAL CONDITION, will the filter life gauge register 100% (+/- 2%) during
operation. As the Filters then load, the filter life gauges will then begin to drop as
appropriate.
press “Mute/OK”.
downflow velocities.
Product Service 1-800-522-7658
Page 66
66
HEPA Leak Test Information
HEPA Filter Leak Test Data
30242
30252
30262
Air Displacement (CFM)
904
1080
1296
Laskin Nozzles needed
2 2 2
Theoretical aerosol conc. (ug/l)1
30
25
21
Actual aerosol conc. (ug/l)2
15
13
10
All models in this manual were tested to the HEPA Filter Leak Test as described in
ANSI/NSF Standard 49:2014.
Note: ensure all internal surfaces of the cabinet have been appropriately
decontaminated before proceeding.
Figure 5-1
Note: For all models, the aerosol generator
should be placed in the center of the work
area, pointing toward the rear grille, as shown
in Figure 5-1.
If the Cabinet is Contaminated
(An upstream concentration cannot be established)
If the unit has been used with biohazardous, toxic chemicals, or radioisotopes, the
aerosol access tube cannot be used. The upstream concentration cannot be measured
directly. Testing at Labconco has shown the actual concentration varies from the
calculated value. Table 5-1 shows the actual vs. calculated concentrations for these
models.
Table 5-1
HEPA Filter Leak Test Specifications
1. The calculated concentration was established by the formula:
2. Based on Mineral oil
1. Turn on the photometer and allow it to operate for a minimum of 5 minutes.
2. Check the oil level of the generator – it must be within 1/8” of the level line
3. Establish the 100% and 0% concentration levels for the photometer.
Concentration (ug/l) = (# Laskin nozzles @ 20 PSIG x 13,500)/Volume of air displaced
Leave the valve in the “CLEAR” setting.
when the generator is sitting level.
Product Service 1-800-522-7658
Page 67
67
If the Cabinet is Uncontaminated
(Establishing an Upstream Concentration)
The Purifier utilizes a unique aerosol access tube for sampling the upstream
concentration of aerosol. If after reading these instructions, you have further questions,
please contact Labconco's Product Service Department.
Note: The access tube contains contaminated air under positive pressure. DO
NOT access this line until the cabinet has been decontaminated.
1. Remove the work surface by lifting the handles on either end. Pull the work
surface straight out of the cabinet.
Locate the access tube on right side of the rear plenum wall, behind through the towel
catch. As shown in Figure 5-2.
Figure 5-2
2. Pull the tube toward the front of the unit. Remove the access tube cover.
3. Using an appropriate photometer, connect the unit's upstream line to the access
tube.
Note: Keep the photometer sampling tube as short as possible. It should
never exceed 6 feet maximum.
4. Turn on the photometer and allow it to operate for a minimum of 5 minutes.
Leave the valve in the “CLEAR” setting.
5. Check the oil level of the generator – it must be within 1/8” of the level line
when the generator is sitting level.
Product Service 1-800-522-7658
Page 68
68
Supply HEPA Filter Test
Downflow Diffuser Removal
1. Remove the diffuser by raising the sash as high as it will go, and then removing
the two acorn nuts with a 7/16” wrench or socket, as shown in Figure 5-3.
Figure 5-3
Removing the diffuser acorn nuts (Dress
panel and lamps removed for clarity
only).
Note: The diffuser acorn nuts are secured to the studs with a removable thread locking
compound to prevent them from vibrating loose during shipment of the Cabinet. There
may be some resistance the first time the nuts are removed; this is normal. No
additional thread locking compound need be applied to these acorn nuts unless the unit
is being prepared for shipment.
2. Lower the front edge of the diffuser until clears the bottom of the sash, and then
pull the diffuser straight out of the cabinet, as shown in Figure 5-4.
Figure 5-4
3. The Cabinet is now ready for the HEPA Filter Leak Test. Set the photometer
sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum at the
sampling port of the pistol.
Product Service 1-800-522-7658
Page 69
69
4. Open 2 Laskin nozzles
5. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG.
6. Scan the downstream side of the HEPA filter by passing the sampling nozzle of
the gun in slightly overlapping strokes over the entire surface of both of the
filters, with the sampling port not more than 1 inch from the surface of the filter
media. Scan the entire periphery of the filters and the gaskets between the filter
frame and the Cabinet frame. Scanning shall be done at a traverse rate of not
more than 2 inches per second.
Note: Operation of the photometer may become erratic when testing the front edge of
the supply filter frame, due to aspiration of room air into the front of the work area. This
problem can be minimized or eliminated by placing the edge of a sheet of rigid plastic or
metal at the edge of the filter gasket when scanning this area, as shown in Figure 5-5.
Figure 5-5
Acceptance
Aerosol penetration shall not exceed 0.01%.
Reassemble the unit by compressing the exhaust filter cover while installing its tabs
back into the exhaust filter bracket slots. Reinstall the diffuser, ensuring that the holes in
the back of the diffuser frame engage the posts on the rear wall of the work area, as
shown in Figure 5-6.
Figure 5-6
Diffuser pins engaging the holes in the rear of
the diffuser.
Product Service 1-800-522-7658
Page 70
70
Exhaust HEPA Filter Test
Opening the Exhaust HEPA Filter Cover
If there is sufficient overhead clearance (18 or more inches) –
1. Loosen the two Phillips screws on the front sides of the filter cover, as shown in
Figure 5-7. Tilt the cover back access the downstream side of the filter.
Figure 5-7
Loosen these screws to tilt the
cover back.
Remove these acorn nuts to
remove the cover.
If there is insufficient overhead clearance –
1. Loosen the two Phillips screws on the front sides of the filter cover, and remove
the four acorn nuts and washers. Carefully lift the cover off of the top of the
cabinet.
Note: exercise caution when removing or installing the exhaust filter cover,
to prevent damaging the Exhaust HEPA filter.
Product Service 1-800-522-7658
Page 71
71
2. The Cabinet is now ready for the HEPA Filter Leak Test. Set the photometer
sampling valve to “DOWNSTREAM”. Ensure there is a proper vacuum at the
sampling port of the pistol.
3. Open 2 Laskin nozzles
4. Ensure the pressure gauge on the generator is reading 20 +/- 1 PSIG.
5. Scan the downstream side of the HEPA filter by passing the sampling nozzle of
the gun in slightly overlapping strokes over the entire surface of both of the
filters, with the sampling port not more than 1 inch from the surface of the filter
media. Scan the entire periphery of the filters and the gaskets between the filter
frame and the Cabinet frame. Scanning shall be done at a traverse rate of not
more than 2 inches per second.
Note: Operation of the photometer may become erratic when testing the edges of the
exhaust filter frame, due to aspiration of room air into the front of the work area. This
problem can be minimized or eliminated by placing the edge of a sheet of rigid plastic or
metal at the edge of the filter gasket when scanning this area, as shown in Figure 5-8.
Figure 5-8
Acceptance
Aerosol penetration shall not exceed 0.01%.
Reassemble the unit by compressing the exhaust filter cover.
Product Service 1-800-522-7658
Page 72
72
Cabinet Width (Feet)
4 5 6
Nominal Avg. Downflow
(FPM)
60+/-5
60+/-5
60+/-5
Downflow test grid # of
points
24
24
36
Test Grid (# rows x #
columns)
3 x 8
3 x 10
3 x 12
Test Grid Data (in
inches)
Grid distance from back & sides
6.0
6.0
6.0
Distance between rows
5.44
5.44
5.44
Distance between columns
5.21
5.39
5.50
Downflow Velocities
All Cabinet models are classified as having uniform downflow, and the average downflow
velocity for all models is 60+/-5 FPM, tested as per ANSI/NSF Standard 49:2012.
All readings should be in a plane 4 inches above the bottom edge of the sash, and the
UV Lamp, IV bar and all other accessories must be removed before performing
downflow test. The test grid dimensions are outlined in Table 5-3. When taking readings
in the back two rows, the anemometer probe should be pointing toward the nearest side
wall, as shown in figure 5-8. When reading the front row, the probe should point
outward, toward the front of the cabinet, as shown in Figure 5-9. The thermal
anemometer’s time constant should be set at 10-15 seconds for greater readout
stability.
Table 5-3
Downflow Test Specifications
Product Service 1-800-522-7658
Page 73
73
Figure 5-8
Figure 5-9
Acceptance
Average downflow shall be 60 +/-5 FPM for all models, with all test points being within
+/- 16 FPM of the overall average.
Product Service 1-800-522-7658
Page 74
74
Inflow Velocity Calculation - Primary
Width (feet)
4 5 6
Nominal Average Inflow
(FPM)
105+/-5
105+/-5
105+/-5
Sash Open Area (Sq. Ft)
4.04
5.05
6.06
Nominal Avg. Exhaust Vol.
(CFM)
424
530
636
Avg. Exhaust Vol. Range
(CFM)
404-444
505-555
606-666
Method
Note: The dress panel MUST be installed on the cabinet to obtain an accurate inflow
value.
The average inflow velocity for Cabinet models is 105 ±5 FPM. It should be determined
by converting the inflow volume to the average inflow velocity. The inflow volume is
measured directly by sealing a direct inflow measuring flow meter to the face of the
unit. When corrected for local conditions, dividing the inflow volume by the opening area
will yield the average inflow velocity.
Table 5-4
Inflow Test Specifications
Acceptance
Average inflow shall be meet the specified value.
Product Service 1-800-522-7658
Page 75
75
Inflow Velocity Calculation - Secondary
Method
If the primary method cannot be performed, the secondary inflow calculation method
should be used. The secondary method uses a hot wire thermal anemometer. In this
method, the sash is lowered, and a series of velocity readings are taken at the front of
the unit.
NOTE: You must use a Labconco Certifier Kit, Labconco P/N 3858403 to
perform this test properly. Qualified certifiers can obtain this kit by
contacting Labconco Customer Service Department at 800-821-5525.
For each model Purifier, the sash should be closed until the appropriate marked
template (4+, 5+ or 6+) contacts the sash stop and the bottom edge of the sash, as
shown below in Figure 5-10.
The thermal anemometer probe should be positioned such that the distance from the
bottom of the probe holder to the center of the sensor element equals “Sensor Distance”
as shown in Table 5-5. Use the marks on the 6-foot templates, or a scale as shown in
Figure 5-11 & 5-12 below.
Figure 5-10
Measuring the restricted access opening
height, using the appropriate template.
Ensure that the bottom of the template is
seated in the sash stop.
Product Service 1-800-522-7658
Page 76
76
Secondary Inflow Data
Sash Opening Template
1
4+
5+
6+
Sensor distance (inches)2
3.25
3.25
4
# of Test points
8
10
12
Test point location
* * *
As Measured Nominal Avg. Inflow Vel. (NAIV) (FPM)
408
530
636
Acceptable Avg. Inflow Vel. (AIV) Range (FPM)
388-427
505-556
339-372
Correction Factor (CF)
1.04
1.0
1.79
Corrected AIV (CAIV) = (AIV x CF)
404-444
505-556
606-667
Sash Open Area (Sq. Ft)
4.04
5.05
6.06
Inflow Velocity Range (CAIV / Sash open area)
100-110
100-110
100-110
The Sensor Distance, as described in Table 5-5,
using the slots cut in the 6-foot Logic template.
4.00-inch mark
3.25-inch mark
The Sensor Distance, as described in Table 5-5,
using a scale.
Figure 5-11
Figure 5-12
Secondary Inflow Test Specifications
Table 5-5
Product Service 1-800-522-7658
Page 77
77
1. Locate the single row of holes at the front of the grille. Mark the 6
the side wall and subsequent test points every 9 holes until the number of test
points marked equals the width of the cabinet in feet (for a 3-foot cabinet, for
example, mark the first 3 points). Repeat for the opposite side, as shown in
Figure 5-13.
2. Start the Purifier, and let it operate for at least 5 minutes. Establish the
necessary correction factor to the thermal anemometer to ensure compliance
with its performance in a calibrated wind tunnel. This data should be available
from the calibrator of the thermal anemometer.
3. Calculate the manufacturers recommended correction factor(s) to correct for
local conditions of temperature, humidity, barometric pressure, altitude, etc.
4. Take a series of inflow velocities by placing the probe holder so that its center
mark aligns with the marked test holes. As shown in Figure 5-14.
5. Apply the wind tunnel correction and local condition correction factors to the
thermal anemometer readings.
6. Multiply the individual readings by the correction factor shown in Table 5-5.
7. Average the corrected readings.
8. The resulting value is the inflow volume in cubic feet per minute (CFM). In order
to convert this value to the average inflow velocity of feet per minute (FPM),
divide the volume by the sash open area given in Table 5-5. The resulting value
will be the calculated average inflow velocity in FPM.
th
hole from
Figure 5-13
Marking the test point locations.
Mark the 6th hole from either end, then mark every
9th hole until the number of marked points equal
the width of the cabinet in feet.
Repeat for the other side of the grille.
Measuring the Secondary Inflow Velocity.
Note the center of the probe holder aligns with the
test points marked earlier.
Acceptance
Average inflow shall meet the specification in Table 5-5.
Figure 5-14
Product Service 1-800-522-7658
Page 78
78
Work Area Air Cleanliness Test
(optional)
If the customer wants to verify air cleanliness in the work area, use the following
procedure:
1. Mark test points at the geometric center of the work surface, and midway
between the center test point and each side wall.
2. Place a particle counter pickup on a test point, at a height of 16 inches above the
work surface, pointing into the airflow, as shown in Figure 5-15. Take three
samples of 1.0 ft3. Repeat for each test point.
3. Average the results.
Figure 5-15
Acceptance
The average count should be less than 100 particles 0.5um in size per ft3.
Product Service 1-800-522-7658
Page 79
79
Fluorescent Light Level (optional)
The fluorescent light intensity should be measured as described in ANSI/NSF Standard
49:2012, Annex F.
NOTE: The light meter should be color- and cosign corrected for accurate
readings.
1. Test points should be marked along the centerline of the work surface, starting 6
inches from the side wall, with subsequent points 12 inches apart until the center
of the work surface is reached. Repeat for the other side of the work area.
2. Take background readings at the test. It should be 15 foot-candles maximum.
3. Turn on the fluorescent lights and let them warm up for at least 5 minutes.
4. Measure the light intensities at the test points.
Acceptance
The average light level should be no less than 45 foot-candles greater than the
background level, where maximum background light levels average a maximum of
15 foot-candles.
Most common causes for insufficient light levels are:
a. Malfunctioning lamp(s)
b. Old lamp(s)
c. Dusty/dirty lamp surfaces
Noise Level (optional)
The noise level should be measured as described in ANSI/NSF Standard 49:2012.
1. Noise level should be recorded from a single point, on the centerline of the
cabinet, at a position 14 inches above the work surface, and 12 inches from the
front of the cabinet.
2. Take a background reading with the cabinet blower off at the test point. It
should be less than 55 dBA.
3. Start the cabinet blower, and take a sound reading.
Acceptance
Sound levels should be less than 67 dBA when the cabinet is new, and less than 73
dBA when the filters are loaded.
Product Service 1-800-522-7658
Page 80
80
Vibration (optional)
The vibration level should be measured as described in ANSI/NSF Standard 49:2012.
Note: The vibration meter should have a range of 20-20,000 Hz, and have an
output in displacement.
1. Vibration level should be recorded from a single point, on the geometric center
of the work surface.
2. Take a background reading with the cabinet blower off at the test point.
3. Start the cabinet blower, and take a displacement reading.
Acceptance
Vibration should be less than 0.0002 inches displacement when the cabinet is new.
UV intensity (optional)
Note: The UV radiometer should measure light at a wavelength of 254nm.
1. UV intensity should be recorded from a single point, on the geometric center of
the work surface.
2. Take a background reading with the cabinet blower off at the test point.
3. Close the sash, turn on the UV light, and let it warm up for at least 5 minutes.
Acceptance
The UV intensity should be at least 200 uW-cm2.
Most common causes for insufficient UV light levels are:
d. Malfunctioning lamp(s)
e. Old lamp(s)
f. Dusty/dirty lamp surfaces
Product Service 1-800-522-7658
Page 81
81
Ground Fault Circuit Interrupter Test
(115/100 Volt models only)
Note: The GFCI tester must be able to simulate a fault of 3mA.
1. Place the tester into any of the Cabinet’s outlets. The indicator lights of the
tester should indicate normal function, and the GFCI’s indicator LED should be lit.
2. Press the test button of the tester. The indicator lights should now indicate the
circuit is inactive, and the GFCI indicator LED should be off.
3. Reset the GFCI by pressing the RESET button on the right outlet. The tester will
again indicate normal operation, and the GFCI indicator LED will illuminate.
Figure 5-16
GFCI Reset Button
GFCI Test Button
GFCI Indicator LED
Acceptance
The GFCI trips during the simulated failure, and the indicator LED turns off. Pressing
the Reset button returns the GFCI to normal function.
Product Service 1-800-522-7658
Page 82
82
THIS PAGE INTENTIONALLY BLANK
Product Service 1-800-522-7658
Page 83
83
Section 6
Cabinet Service Operations
This section will review the tools needed, and common service operations for the
Cabinet.
Recommended Tools for Service
The tools needed for most common service operations are:
Logic+ Certifier Kit, Labconco Part # 3858403
#2 Phillips Screwdriver or long bit for cordless drill
½-inch Socket with extension and ratchet
½-inch nut driver
7/16-inch socket or nut driver
5/16-inch socket or nut driver
Optional tools that may be needed include:
Cordless screwdriver/drill
Cordless ratchet
3/8-inch nut driver or socket and ratchet
Pliers
10-24 Tap
5/16 x 18 Tap
Note: If you use a cordless drill with an adjustable torque setting, set the
torque as low as possible to properly drive the screw or bolt.
External Dress Components
Front Dress Panel Removal and Installation
Figure 6-1
1. Locate and remove the two Phillips screws that secure
the front panel as shown in Figure 6-1. They are
located on the bottom corners of the front dress panel
2. Swing the bottom of the dress panel out to clear the
fluorescent light and then lift the front dress panel
straight up and away from the cabinet.
Product Service 1-800-522-7658
Page 84
84
To reinstall the panel, reverse these
steps, ensuring that the plastic pins in
the top corners of the dress panel
properly engage the corner posts.
Figure 6-2
Side Panel Removal
Note: The side panel(s) must be taken off to remove the Cabinet from its
pallet.
1. Remove and save the two Phillips screws on the front edge of the side panel.
2. Pivot the front of the panel away from the cabinet. Lift the panel straight up and
pull the panel straight away from the cabinet to release the rear of the side panel
from its hinge.
Side Panel Installation
1. Install the side panel by inserting both back panel hooks into the side panel
slots.
2. Ensure both panel slots are completely seated on the hooks.
3. Pivot the front of the panel toward the cabinet. Secure the panel by installing
and tightening the two Phillips screws.
Product Service 1-800-522-7658
Page 85
85
Corner Post Lower Trim
The corner post lower trim pieces are secured to the corner post by a single machine
screw and lock nut. When properly positioned, the trim piece fits tightly against corner
post. See Figure 6-3.
Figure 6-3
Use a 3/8” wrench and Phillips
screwdriver to adjust the corner post
screw.
Note: DO NOT over tighten the screw;
damage to the trim piece may occur.
If the corner post lower trim pieces do not fit flush to the bottom edge of the metal
corner post, examine the front flange of the chassis. The flange should be straight. If it
is bent back, it can be straightened by bending the flange forward with an adjustable
wrench, as shown in Figure 6-4.
Figure 6-4
Front side of the Cabinet
Cabinet Chassis Flange
Using an adjustable wrench to
straighten the flange
Product Service 1-800-522-7658
Page 86
86
Sash
Operation
The Cabinet sash uses a deadweight-counterbalanced system. The system
consists of two separate weights on either side of the liner. Both weights are
synchronized by a locked axle-pulley system. Both pulleys are fixed to the axle so
that both weights must move together, preventing the sash from racking.
Adjustment
There are no adjustments for the width of the sash track. There should be
approximately 1/8-inch lateral play of the sash in its track. If there is no lateral
play, examine one or both of the corner posts to ensure that they are not bent
inward. If the sash becomes racked, or is closing unevenly, it can be aligned as
follows:
1. Close the sash completely, until the lower edge of the sash is contacting
the sash stop. If the other end of the sash is not resting on its sash stop,
CAREFULLY lift the counterweight on the “high” side of the sash. This will
allow the high side of the sash to lower to the sash stop, leveling the
sash. See Figure 6-5.
Figure 6-5
Using pliers to lift a sash
weight to level the sash.
CAUTION: Exercise
caution when lifting a
counterweight. There is
a pinch potential
between the sash cable
and pulley.
Product Service 1-800-522-7658
Page 87
87
Sash Position Switches
Two microswitches are used to indicate the sash position. The switches are the same,
Labconco part # 3832400. A photo of both switches is shown in Figure 6-6.
Figure 6-6
Sash Closure Position Switch
Sash Operating Position Switch
Sash Closure Position Switch
The sash closure position switch signals the display microprocessor that the sash
is open or closed allowing proper operation of the Blower, fluorescent or UV
lights. It is wired in the normally open configuration. If the switch does not
actuate properly when the sash is within ¼-inch of being fully closed, ensure the
switch follower is properly actuating against the weight. See Figure 6-7.
Sash Operating Position Switch
The sash operating position switch signals the display microprocessor that the
sash is open too far for proper operation, as shown in Figure 6-8. It is wired in
the normally open configuration. If the switch does not actuate properly when
the sash is within ¼-inch of its operating position, ensure the switch follower is
properly actuating against the weight.
Product Service 1-800-522-7658
Page 88
88
Sash Closure Position Switch properly
actuated against the sash weight
Sash Operating Position Switch
properly actuated against the sash
weight
Figure 6-7
Figure 6-8
Product Service 1-800-522-7658
Page 89
89
Sash Cable Retainer
The sash cable retainers are located at the top of each sash pulley, as shown in
Figure 6-9. If the retainer needs adjustment, Use a 3/8-inch wrench to loosen
the bolt securing the retainer and adjust it until it lightly touches the pulley.
Retighten the bolt.
Figure 6-9
HEPA Filter Replacement
CAUTION: The cabinet must be properly decontaminated before servicing the
supply HEPA filter. Following replacement of a HEPA filter, the cabinet must
be recertified.
CAUTION: HEPA filters can be awkward to handle and heavy. Use appropriate
lifting techniques to remove and handle it. Use two people to remove the
larger filters if possible.
To Remove the Exhaust HEPA Filter:
1. Unplug the cabinet. Remove the front dress panel as shown in Figure 6-1.
2. Loosen all of the Phillips screws on the blower chamber cover. Remove all of the
screws except two screws on the top center of the panel. This will support the panel.
3. Remove the last two screws. Gently rock the cover, slide it to the left or right, and
swing it out and away from the unit.
NOTE: During disassembly, the blower plenum cover can rest on the center sash
support, as shown in Figure 6-10, to allow repositioning of the panel or your grip on it.
Product Service 1-800-522-7658
Page 90
90
Center Sash Support
1. Loosen the four sealed exhaust filter clamp bolts on the top of the cabinet
hull, as shown in Figure 6-11. DO NOT remove the bolts; only loosen them
until the exhaust HEPA filter is free of the filter frame.
2. Pull the exhaust HEPA filter straight out of the cabinet.
Figure 6-10
Figure 6-11
Exhaust filter clamp bolts
(two in each side of the
exhaust connection)
To Install an Exhaust HEPA Filter:
1. Slide the new exhaust HEPA filter all the way into the pan.
2. Sequentially tighten the four exhaust filter sealing bolts located at each
corner of the exhaust filter tray until the exhaust filter gasket is compressed
no more than 50%.
The exhaust filter sealing bolts should only be tightened enough to ensure a
proper seal of the exhaust HEPA filter. At maximum tightness, the exhaust
filter's gasket should be compressed to 50% of its original thickness. NEVER
tighten the bolts beyond this setting.
Product Service 1-800-522-7658
Page 91
91
3. Install the exhaust HEPA filter cover, uniformly tightening the screws on the
cover until the gasket has formed a proper seal.
To Remove the Supply HEPA Filter:
1. Loosen all of the Phillips screws on the blower/supply filter chamber cover.
Remove all of the screws except two screws on the top center of the panel.
This will support the panel.
2. Remove the last two screws. Gently rock the cover, slide it to the left or
right, and swing it out and away from the unit.
NOTE: During disassembly, the blower plenum cover can rest on the center
sash support, as shown in Figure 6-12, to allow repositioning of the panel or
your grip on it.
Figure 6-12
Center Sash Support
3. Use 1/2-inch sockets or wrenches to tighten the three plenum lift bolts located as
noted in Figure 6-13. This will lift the plenum off of the supply HEPA filter.
Remove the Supply HEPA filter retainers on the front of the plenum, if present.
4. Slide the supply HEPA filter straight out the unit.
5. With the HEPA filters removed, inspect the filter shelf for damage.
Figure 6-13
1/2” Plenum Lift Bolts
Supply HEPA
filter retainers (3)
Product Service 1-800-522-7658
Page 92
92
To Install a Supply HEPA Filter:
1. Install a new supply HEPA filter by pushing it straight into the cabinet,
ensuring that it is correctly oriented, and that the filter is centered on the
filter shelf.
2. Use the 1/2-inch sockets or wrenches to sequentially loosen the three
plenum lift bolts located as noted in Figure 6-13. When properly positioned,
the plenum box will be aligned with the supply HEPA filter frame. Continue to
loosen the bolts until the plenum contacts the HEPA filter and has slightly
compressed the filter gasket.
NOTE: The lift bolts should only be tightened enough to ensure a
proper seal of the supply HEPA filter. At maximum tightness, the supply
filter's gasket should be compressed to less than 50% of its original
thickness. NEVER tighten the locking bolts beyond this setting.
3. Reinstall the supply HEPA filter retainers, and the supply filter cover,
uniformly tightening the screws on the cover until the gasket has formed a
proper seal.
Supply Motor/Blower Replacement
Caution: The cabinet must be properly decontaminated before servicing the
motor/blower.
The cabinet blower motor's bearings are sealed and require no lubrication.
DO NOT attempt to lubricate them.
To replace the Supply Motor/Blower:
1. Unplug the cabinet.
2. Remove the front dress panel as shown in Figure 6-1.
3. Loosen all of the Phillips screws on the blower chamber cover. Remove all of the
screws except two screws on the top center of the panel. This will support the
panel.
4. Remove the last two screws. Gently rock the cover, slide it to the left or right,
and swing it out and away from the unit.
NOTE: During disassembly, the blower plenum cover can rest on the sash support, as
shown in Figure 6-12, to allow for its repositioning or to change your grip on it.
5. Disconnect both motor connectors from the motor. The 5-pin power connector,
located closest to the blower, is released by pressing the locking ears on either
side of the connector. The 16-pin data connector, located furthest from the
blower, is released by pressing the single locking ear located on the inside center
surface of the connector body. The connectors are shown in Figure 6-14.
Product Service 1-800-522-7658
Page 93
93
Figure 6-14
ECM Power Connector Release Tabs
ECM Data Connector Release Tab
6. Use a Phillips screwdriver to remove the two sealing plate screws and the sealing
plate. Using a 1/2-inch wrench, remove the three blower mounting bolts, as
shown in Figure 6-15.
Figure 6-15
Blower Mounting Bolts (3)
Sealing plate screws (2)
The motor/blower assembly is heavy. Handle with care.
7. While supporting the blower assembly, pull the assembly straight out the
plenum, as shown in Figure 6-16.
Figure 6-16
Product Service 1-800-522-7658
Page 94
94
8. To replace the motor/blower assembly, reverse the above procedure.
Note: During reinstallation of the blower assembly, push the blower into
position, and loosely install the two blower mounting bolts. Press the
sealing plate against the side of the blower to ensure it is properly sealed
against the back of the blower mount. Tighten the two sealing plate
screws while continuing to press the plate against the blower. This will
ensure a tight seal. Now tighten the blower mounting bolts.
9. Continue the reassembly. Plug in the cabinet and recertify it before use.
Exhaust Motor/Blower/Plenum
Replacement
Caution: The cabinet must be properly decontaminated before servicing the
assembly.
The cabinet blower motor's bearings are sealed and require no lubrication.
DO NOT attempt to lubricate them.
To replace the Motor/Blower/Plenum:
1. Unplug the cabinet.
2. Remove the front dress panel as shown in Figure 6-1.
3. Loosen all of the Phillips screws on the exhaust chamber cover. Remove all of
the screws except two screws on the top center of the panel. This will support
the panel.
4. Remove the last two screws. Gently pull off the cover.
NOTE: During disassembly, the exhaust chamber cover can rest on the two support
posts near the bottom of the panel, to allow for repositioning of the panel or your grip
on it.
5. Using a 1/2-inch wrench or socket, loosen the four sealed filter clamp bolts, as
shown in Figure 6-17.
Figure 6-17
Exhaust filter clamp bolts
(two in each side of the
exhaust connection)
Product Service 1-800-522-7658
Page 95
95
6. Carefully remove the Exhaust HEPA filter and set it in a safe spot.
7. Disconnect the exhaust motor harness at the pass through near the top of the
chamber, as shown in Figure 6-18.
Figure 6-18
Exhaust Motor wiring harness
connectors
NOTE: It will ease plenum installation and removal by laying two 2x4 or
4x4 supports under the plenum, and over the filter chamber flange, as
shown in Figure 6-19.
Figure 6-19
8. Loosen the filter clamping bolts until the plenum assembly is released.
The motor/blower/plenum assembly is heavy. Handle with care.
9. Slide the plenum out of the cabinet on the wooden supports.
10. Disconnect the exhaust motor wiring harness from the ECM Motor, and install it
on the new motor/blower/plenum assembly.
11. Install the new assembly into the Cabinet.
12. To complete the replacement, reverse the above procedure.
13. Plug in the cabinet and recertify it before use.
Product Service 1-800-522-7658
Page 96
96
Work Surface Removal
Note: The work surface of the cabinet must be thoroughly decontaminated before
removing it.
1. Lift the front edge of the work surface straight up by grasping the knob handles at
either front corner.
2. Pull the work surface straight out, letting its rear edge rest on the center support
underneath.
3. Reinstall the work surface by resting the bottom on the center rail while pushing it
back into the cabinet. Be sure to engage the tabs on the back corners of the work
surface with the slots on the rear wall of the work area.
Grille Removal
Note: The grille must be thoroughly decontaminated before removing it.
1. Remove the work surface as described earlier.
2. At one end of the grille, grip the front of grille with one hand, and the back with
the other hand. Pivot that end of the grille upward and inward, paralleling the
angle of the sash, as shown in Figure 6-20.
3. Pull the other end of the sash up and away from the bottom edge of the cabinet.
4. Reinstall the grille by reversing the above sequence, ensuring that the grille
properly engages the bottom edge of the cabinet.
Figure 6-20
Product Service 1-800-522-7658
Page 97
97
Towel Catch Removal
Although not normally required, the towel catch can be removed for cleaning,
inspection, etc.
Note: The work surface of the cabinet and the towel catch must be thoroughly
decontaminated before removing either.
Although not normally required, the towel catch can be removed for cleaning,
inspection, etc.
Note: The work surface of the cabinet and the towel catch must be thoroughly
decontaminated before removing either.
1. Remove the work surface as described above.
2. Remove the towel catch by pivoting the bottom out toward you, as shown in Figure
6-21; it is spring loaded, and you will feel some resistance. Note the orientation of
the towel catch.
3. Surface decontaminate the towel catch before removing it.
4. Reinstall the towel catch by sliding it back into position, in the correct orientation.
Also ensure that the Sampling/Decontamination Tube (the black tube with an orange
cap) rests behind the towel catch, allowing the catch to contact the rear wall of the
cabinet.
Sampling/Decontamination
Tube
Towel Catch Retaining
Spring
Towel Catch
Note: Upper and lower
towel catch flanges point to
the front of the cabinet, and
the bottom of the towel
catch rests against the back wall.
Figure 6-21
Product Service 1-800-522-7658
Page 98
98
Diffuser Removal
Caution: The diffuser should be surface decontaminated before removal.
Note: If an IV bar is in place, it will have to be removed first.
1. Raise the sash to its fully open position.
2. Support the front edge of the diffuser while removing the two 7/16-inch acorn
nuts on the front of the diffuser, as shown in Figure 6-22.
Figure 6-22
Removing the diffuser acorn nuts (Dress
panel and lamps removed for clarity only).
Note: The diffuser acorn nuts are secured to the studs with a removable
thread locking compound to prevent them from vibrating loose during
shipment of the Cabinet. There may be some resistance the first time the nuts
are removed; this is normal. No additional thread locking compound need be
applied to these acorn nuts unless the unit is being prepared for shipment.
3. Allow the front of the diffuser to drop and pull it straight out of the cabinet, as
shown in Figure 6-23.
Figure 6-23
Product Service 1-800-522-7658
Page 99
99
4. To reinstall the diffuser, ensure that the two holes on the back edge of the
diffuser align with the diffuser support pins on the rear wall of the work area, as
shown in Figure 6-24.
Diffuser pins engaging the holes in the
rear of the diffuser.
Figure 6-24
Product Service 1-800-522-7658
Page 100
100
Preparing the Cabinet for Gaseous
Sterilization
Note: This section only reviews the steps required for preparing the Cabinet
for Gas Sterilization. Thoroughly understand the sterilization procedures and
protocols supplied by the manufacturer of the sterilizing system before
attempting this operation.
1. Unplug the Cabinet from electrical power.
2. Thoroughly surface decontaminate the working area of the cabinet.
In order to get a complete seal on the front of the cabinet, do the following:
1. Remove the work surface after it has been surface decontaminated.
2. Remove the towel catch, and locate the Sampling/Decontamination Tube, as
shown in Figure 6-32.
3. Remove the front grille.
4. Place the work surface and the grille into the work area for decontamination.
5. Remove the front dress panel.
6. Remove the sash stop bracket, located near the top of the blower plenum cover.
7. Lift the sash up until the bottom edge of the sash clears the bottom edge of the
Supply HEPA Filter shelf.
8. Using flexible plastic sheet 5-8 mil thick and duct tape seal the perimeter of the
front opening. If you wish to connect the sterilizer’s discharge tube to the
Cabinet’s Sampling/Decontamination Tube, do this now, and properly seal the
discharge tube to the plastic sheet.
9. Open the exhaust filter cover.
Note: DO NOT attempt to remove the brackets that secure the exhaust filter cover;
they are needed to maintain rigidity on the top of the chassis.
10. Using flexible plastic sheet and duct tape seal the Exhaust filter opening.
11. The Cabinet is now prepared for gaseous decontamination.
Product Service 1-800-522-7658
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.